Tek-DP 1620A Cone Meter is measures flow over a wide range of Reynolds numbers of gas,
steam
and liquid applications.
1.2
Certifications
ISO 5167-5 Compliance.
1.3
1.3.1
Safety Instructions from the Manufacturer
product,
Any product purchased from the manufacturer is warranted in accordance with the relevant
disclaimer,
e for any reason without prior notice, and will not be answerable in any way for the
possible consequence of such changes.
1.3.2
Product Liability and Warranty
The
manufacturer accepts no liability for the consequences of misuse by the operator. Wrong
installation or operation of the devices (systems) will cause the warranty to be void. The
s the basis for the sales contract shall also
apply.
1.3.3
Information Concerning the Documentation
To prevent any injury to the operator or damage to the device it is essential to read the
national standard safety instructions. This
operating manual contain all the information that is required in various stages, such as product
identification, incoming acceptance and storage, mounting, connection, operation and
commissioning, troubleshooting, maintenance, and disposal.
1.4
Safety Precautions
These
by
well
For additional information that are not discussed in this manual, contact the manufacturer.
Disclaimer
The manufacturer will not be held accountable for any damage that happens by using its
including, but not limited to direct, indirect, or incidental and consequential damages.
product documentation and our Terms and Conditions of Sale.
The manufacturer has the right to modify the content of this document, including the
at any tim
The operator shall bear authority for the suitability of the device for the specific application.
respective Terms and Conditions of Sale, which form
information in this document and the applicable
You must read these instructions carefully prior to installing and commissioning the device.
instructions are an important part of the product and must be kept for future reference. Only
observing these instructions, optimum protection of both personnel and the environment, as
as safe and fault-free operation of the device can be ensured.
The following safety symbol marks are used in this operation manual and on the instrument.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in
death or severe injury
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE
Indicates that operating the hardware or software in this manner may damage it
or lead to system failure.
1.5
1.5.1
Packaging, Transportation and Storage
Packaging
The original package consists of
1.
2.
Tek-DP 1620A Cone Meter
Documentation Package NDT and Materials Certificates
NOTE
Unpack and Check the contents for damages or sign of rough handling. Report
packing
list provided.
damage to the manufacturer immediately. Check the contents against the
Avoid impact shocks to the device and prevent it from getting wet during
transportation.
whenever possible.
1.5.3
Storage
precautions:
•
Store your product in the manufacturer’s original packing used for shipping.
Storage location should conform to the following requirements:
1.
3.
Free from rain and water ingress
At room temperature with minimal temperature and humidity variation
Properties of the instrument can change when stored outdoors (carbon steels).
1.5.4
Nameplate
details
and technical data.
NOTE
Check the device nameplate to ensure that the device is delivered according to your
order. Check for the correct Beta Ratio, Pipe ID, and TAG number if printed on the
nameplate. Flow Meter Coefficient of discharge
(Cd)
is shown on the materials
certification / documentation for entry into a flow computer
Verify local safety regulations, directives, and company procedures with respect to
•
hoisting, rigging, and transportation of heavy equipment.
Transport the product to the installation site using the original manufacturer’s packing
•
If this product is to be stored for a long period of time before installation, take the following
•
2.
Free from vibration and impact shock
•
The nameplate lists the order number and other important information, such as design
DP 1620A Cone Meters are manufactured and designed for measuring multiple fluid types
from gases to liquids and vapors, the meter uses differential pressure to provide accurate,
variable
transmitter in conjunction with a flow computer in certain world regions chart recorders are still
product
This operator
e Meter in
liquid, gas, and steam applications.
2.2
Usage and DP Applications
DP 1620A Cone Meters are fully capable and designed to work in both unprocessed and
processed applications, and are ideal for upstream, midstream and downstream flow
pressure
validation
detailed within the company website.
2.3
Main Meter Components
The cone meter comprises three main components, as shown in Figure 1 & Figure 2.
i.
ii.
Meter body or tube (closed conduit) with or without flanges
block
downstream with a
pressure sensing conduit for reading differential pressures at the center of the cone and
tap may be used under certain process
Tek-DP 1620A Cone Meters can be manufactured from various materials (Carbon-
iii.
All
A105/106/LF350 steels etc., stainless, or duplex stainless steel) to meet specific process
natural gas steam, air, nitrogen, ethanol, digester gas and a host of
products.
DP 1620A Cone Meter is manufactured to meet the ISO 5167 Part 5 DP Cone Meter
geometry is
used for other cone meter types with certain exceptions such as wall taps for vertical flow
orientations and extra taps for smart metering operations.
Tek-
repeatable and low cost of ownership measurement solutions.
All Tek-DP 1620A Cone Meters read flow rates by using by a differential pressure or multi-
used which will operate with a cone meter.
The method used to connect the transmitter to the meter varies, depending on the type of
measured and available space for mounting the meter in the supporting pipework.
manual provides installation instructions and some piping diagrams for using the Con
Tek-
measurement applications that present large measurement challenges.
The Tek-DP 1620A Cone Meters is also available in many different configurations for lowcoalbed/seam methane wellhead, High /low pressure separator, wet gas with Tek DPro
systems steam and other field applications, compressor anti-surge control, and fuel gas as
Differential Pressure Cone assembly, either fabricated or machined from a monostainless/ other steel piece (not carbon) positioned in the center of the meter tube
A pair of pressure tapping’s - wall tap upstream and a sensing tap
meter body. (Note: a downstream wallmeasurement conditions.)
requirements for metering:
hydrocarbon and non-Hydrocarbon liquids from crude oil to wastewater and cryogenic
The Tek-
Standard when applied for custody transfer applications the same dimensions and
www.GlobalTestSupply.com
Fig 1: Basic components of the Tek-DP 1620A Cone Meter
The Tek-DP 1620A Cone Meter has no moving parts, and is designed to ISO 5167 Part 5 Geometries.
There are no stagnation areas at the DP meter element where trash or fluid particles can lodge
which
resides downstream of the flow.
2.4
Measuring Principle
shape
flow measurement computer with
mal
also
is
proportional to the Square Root of the DP. The pipe area is based on the internal pipe diameter
the
beta ratio (β) for DP Cone Meters this is calculated as being:
Where, D is pipe Diameter.
d is Cone Diameter.
within the measurement section during normal flowing conditions.
The meter is virtually maintenance-free due to the self-cleaning action at the cone beta edge
The Tek-DP 1620A Cone Meter generates a differential pressure across a centrally fixed cone
that can be used to calculate fluid flow rates using ISO 5167 Part 5 published equations.
A DP / MVT transmitter measures the differential pressure and outputs an integrated electronic
signal, typically via standard Modbus or a 4-20 mA output to a
cone meter equations installed, or other process control tertiary device for readout and review.
For compressible fluids (gasses), line pressure and temperature measurements are required for
accurate flow rate calculations such as custody transfer applications as well as compensation for
any adiabatic changes in the meter expansion factor also detailed in ISO 5167 Part 5. During nor
operation process fluids flow around the differential producer cone, and pressure drop occurs
according to Bernoulli principles of conservation of energy. The static line pressure (P1) is
measured via a wall tap strategically located upstream of the cone (Figure 2). Pressure is
measured via a sensing tap that is connected to the cone center using a conduit and measures
pressure at a central point immediately downstream of the cone (P2). The fluid flow-rate is
calculated using the differential pressure (DP).
The principle of the conservation of mass and energy applies to cone meters thus, a flow rate Q
and the area reduction being the annulus area at the cone beta edge. This relationship is called
The meter differential producer cone element reshapes the fluid velocity profile directly upstream
and
across the expanding element conditioning flows naturally and eliminating the need for
be
meter
and high degrees of performance are ensured even under extremely disturbed flow conditions.
2.5
Operation
DPro DP Cone Meters are fabricated and assembled using ASME approved welding
qualifications and material certification available to 3.lb and 3.lc quality
requirements with full material traceability either in standard steels or exotics.
Fig 3: TEK-DP 1620A DP Cone Meter
TEK-DPro Cone Meters are manufactured with attention to their geometry and metrology based
may
occur at certain higher fluid ReD numbers.
traditional flow conditioners or long straight lengths. Tek-DP 1620A Cone Meter can therefore
installed in shorter meter runs than those required by a conventional differential pressure
All Tektechniques. Welder
on ISO Standards. All up and downstream weld-neck seam welds are honed to provide smooth
entry & exit into and out of the cone meter measurement section.
This honing procedure minimizes fluid jetting effects entering the meter throat/annulus that
Jetting effects occur where weld beads protrude into the flow stream and may cause
an over-
run of the flow conditioning effect provided by the meter DP element. This
effect is particularly evident on larger beta ratios, it is good practice to always
implement this operation in the manufacturing process of a cone meter
2.6 System Components
are typically required for the
condensate
pot may also be required.
2.6.1
Differential Pressure Transmitters
cone
gas,
and steam applications.
2.6.2
Shut-Off Valves
valve
NOTE
The valves must not affect the transmission of the differential pressure signal.
Install block valves next to the Tek-DP 1620A Cone Meter pressure taps. Never use a globe
valve for differential pressure transmission lines. (See: Figure 4)
Fig 4: Valve Connections
installed which does not affect the performance.
A transmitter, valve manifold, shut-off valves, and impulse tubing
operation of a Tek-DP 1620A Cone Meter. If the meter is used to measure steam, a
A differential pressure transmitter records the differential pressure signal generated by the
meter and provides an analog or serial output to a flow computer or data control system.
The transmitter(s) selected for an installation must be appropriate for operating conditions of
the process in terms of both accuracy and safety.
DP devices must be zeroed following installation. The procedure varies somewhat for liquid,
Choose a block valve that is rated for the operating pressure of the pipe in which it will be
installed. Where dangerous or corrosive fluids or gases like oxygen are likely, the block
and packing must provide ample protection.
Note: Some meters have rear gussets
2.6.3Valve Manifolds
A 3-way or 5-way valve manifold isolates the transmitter from the process lines (5-valve
manifolds are recommended). They allow the operator to calibrate the transmitter without
removing it from the impulse tubing, drain the transmitter and impulse tubing or vent it to
atmosphere. (See Figure 5)
Valve manifolds must be oriented according to manufacturer’s instructions to
prevent trapping of air or liquid in the sensing lines and tubing. This can cause an
incorrect flow measurement condition.
2.6.4
Impulse Tubing Considerations
DP 1620A Cone Meter and its transmitter,
consider the following installation advice for optimizing your system’s measurement accuracy.
vent
to the atmosphere”.
2.6.5
Tubing Size Selection.
DP 1620A Cone Meter tap holes to the transmitter have
a
and
also reduce plugging / freezing.
2.6.6
Process Tubing / Sensing Lines
must not exceed 1” (25 mm). For steam applications, the ID should
the
required
for flow signals used in process safety management. A minimum tubing ID of 5/8” (16 mm) is
in
condensing vapor service, 1” (25 mm) is preferred.
2.6.7
Tubing Lengths and Configurations
length
and tubing orientation:
•
Tubing lengths must be short enough to ensure a high degree of accuracy, and long enough
transmitters in case of maintenance and also emergency maintenance.
Before connecting impulse tubing between the Tek-
“In a well- designed installation, fluids will drain freely from the process lines and gases will
Impulse tubing that connects any Tekdiameters that change with service conditions. The bore should be no smaller than ¼” (6 mm)
minimum diameter of 3/8” (10 mm) is recommended to allow for any condensate drainage
The internal diameter (ID)
be in the range 3/8” (10 mm) to 1” (25 mm) depending on meter diameter.
The use of incorrect tubing both diameter and material selection can create a safety risk and
cost incurred to regaining a process system control can be substantial. High reliability is
recommended for these types of industrial applications were possible. For high temperatures
For best performance, please try to meet the following recommendations for tubing
to ensure proper cooling of high-temperature fluids before they reach the transmitter.
Make sure the installation permits access to impulse tubes, valves, valve manifolds, and
Limit the number of fittings and avoid long tubing sections, which can impair measurement
accuracy and increase the risk of plugging.
elevation
Temperature differences may cause a difference between the density of the fluids in the
two sensing lines, which will change the amount of differential pressure measured. Both
lines
be
bend and install
d or gas trap, as applicable. A liquid trap should be installed at the lowest point in a
service
installation.
•••
2.7
Very High Temperature Applications
and
transmitters (200°F or 92°C Max). A condensate chamber / vessel can be used to isolate
effects. Alternatively, a long tube section can be
As a general operational guideline when planning tubing lengths for temperature control, run a
tion where possible, and allow for a temperature drop of 100°F (37.8°C)
NOTE
This is a rule of thumb guideline, the operator is still responsible for verification that
including the environmental conditions during operation.
2.8
Very Cold Temperatures
During cold temperature installations, thermal insulation and/or “heat tracing” of process lines
drop out in
sensing
prevent
vapors from producing unwanted condensation
dual phase conditions. Fastening process lines together is highly recommended to help keep
controlled
environmental conditions for the transmitter also helps to ensure accurate metering in locations
artic
circle regions).
Avoid changes in tubing elevation and fluid temperature if possible. Differences in
will cause differences in hydrostatic pressure of liquid columns in process/sensing lines.
can result in inaccurate differential pressure measurements. Fasten both process
together, if possible, to alleviate this type of issue.
Install process lines so that they slope in only one direction (up or down). If piping must
installed to slope in more than one direction, do not allow more than one
a liqui
gas service installation. A gas trap should be installed at the highest point in a liquid
Steam vapor can reach 1500°F (815°C), which exceeds the temperature rating of standard DP
pressure
the transmitter from extreme temperature
installed to allow the fluid to cool sufficiently before it reaches the transmitter.
horizontal tubing orienta
per foot (305 mm) of tubing.
the temperature at the transmitter does not exceed the transmitter’s thermal rating
may be necessary this is required where liquids are present or the possibility of liquid
a gas stream that sustains a freeze temperature to cause the liquid to solidify and block the
line. The amount of heat used to prevent these issues must be calculated carefully to also
liquids from vaporizing and prevent condensable
process lines approximately at the same temperature. Providing temperature-
where extreme temperature swings are likely (i.e., offshore platforms, desert installations or
www.GlobalTestSupply.com
2.9
Best Practices for Installing the Tek-DPro Cone Meter
WARNING
Read the best practice recommendations below in their entirety before installation of
the Tek-DPro Cone Meter.
The basic steps for installing a Tek-DPro DP Cone Meter system are described as follows.
1.
2.
3.
Install the meter in the meter run in accordance with the flow run requirements below.
Zero the transmitter.
4.
5.
2.10
Flow Run Requirements
2.11
Meter Orientation and Transmitter Position
horizontal or vertical position. The location of the
being
DPro Cone
of the
differential pressure tap.
2.12
Pressure Tap Location
through the pipeline (liquid, gas, or steam) and the orientation of the meter (vertical or horizontal).
2.13
For horizontal installations, the following installation guidelines apply:
•
For measuring liquid, differential pressure taps should be located in the bottom half of the
pipeline.
For wet gas, taps should be located between the 10 o’clock and 2 o’clock positions to allow
For steam, differential pressure taps should be located in the side of the pipeline.
••Illustrations of typical piping configurations for liquid, gas, and steam are provided in figure 6.
Secure the manifold to the meter taps.
Connect the differential pressure transmitter to the manifold, observing the
recommended guidelines below for pressure measuring tubes.
Connect the transmitter to the flow computer according to instructions in the
transmitter user manual.
The Tek-DPro Cone Meter should be installed with zero to five pipe diameters of straight run
upstream of the meter and zero to three pipe diameters downstream. The meter can be used in
pipelines that are slightly larger than the meter tube; however, if the meter tube is larger than
the pipeline, operators should contact for installation requirements. This is usually
determined before supply according to application and the degree of accuracy and performance
required.
The Tek-DPro Cone Meter can be installed in a
transmitter with respect to the meter should be based on the properties of the fluid or gas
measured (gas, steam, liquid, etc.) and the direction of flow through the pipeline.
The direction of flow is clearly labeled on nameplate affixed to the body of every TekMeter shipped. The meter must be installed so that the static pressure is always upstream
Location of the static pressure and differential pressure taps will vary with the product flowing
pipeline, between 4 o’clock and 5 o’clock positions, or between 7 o’clock and 8 o’clock
positions.
For measuring gas, differential pressure taps should be located in the top half of the
For additional installation information, refer to ISO 5167 various parts (part 5 cone meters)
Fig 6. Standard Port Location for Horizontal Installation
2.14 Points to check for the Transmitter / Meter Installation
properly by reviewing the following checkpoints:
a.
c.
Is the transmitter full scale range correct?
pressure port
negative flow may show if incorrectly
mounted?
d.
g.
2.15 Liquid Service Meter Installation
2.15.1
Meter Orientation
a
prevent gas from being trapped in liquid differential pressure lines.
2.15.2
2.15.3
Wall Taps
the
pressure sensing port connected to the cone meter can become plugged with ice for such
measure
manufacturing
and selected as an option before supply).
or contact etc.
Before putting the Tek-DPro Cone Meter into service, verify that the transmitter is installed
b.
Has the transmitter zero been checked and/or adjusted (dead weight tested)?
Has the transmitter and flow computer been set to the correct operating mode “linear or
square root”?
Have the sensing lines to the transmitter been purged cleaned / blown with nitrogen?
Are there any leaks in the sensing lines?
e.
Is the manifold calibration cross valve closed?
f.
Is the Tek-DPro Cone Meter high pressure port located upstream of the lowand connected the correct way to the transmitter –
Tek-DPro Cone Meters can be installed both in a horizontal or vertical position.
Horizontal Installations are is the standard orientation, however where space is very limited,
vertical position may prove to be the best option.
Pipe Orientation
The orientation of piping is dictated by the position of the meter, the type of product being
measured, and for vertical meter installations, the direction of flow. When a vertical piping
system is used, the operator must give special consideration to the piping configuration to
In extremely cold environments where there is a risk of product freezing in the process lines,
lowinstallations, a downstream wall tap may be installed in the meter and should be used
the downstream differential pressure value. (Note this has to be installed during
www.GlobalTestSupply.com
This option will allow ice /hydrate blockage to be removed without removing the meter from
the meter run, but the meter run must be isolated and depressurized before attempting to
clean
out the blockage refer to earlier sections regarding this aspect.
2.15.4
Condensate Chamber or Drip Pot
avoid
impulse
tubing between the cone meter and the DP transmitter.
2.15.5
Horizontal Installation for Liquids
horizontal
centerline (4 o'clock to 5 o'clock or 7 o'clock to 8 o'clock). Taps at the bottom of the pipe may
also become plugged with solids from the liquid; taps above the centerline can accumulate air
nsing gases. For liquid service, the connecting sensing lines from the meter
to the transmitter shall slope downward towards the transmitter with no U bends or
in a liquid service, even if the liquid is water. As a result, the piping configuration must be
should be extended
-
foot angle to the top of the manifold block. The manifold block should be mounted
slopes
downward also.
Condensate chamber (drip pot) is a collection vessel recommended in certain standards to
gas bubbles in liquid instrument tubing. It should be mounted at the highest point in the
For horizontal installations, pressure taps must be positioned at 30° to 60° below the
locks or non-conde
opportunities for pockets. The minimum recommended slope for self-venting is 1 inch per
In most process applications, the operator should assume that some level of gas or vapor
designed to allow gas to rise back into the flow stream. The process piping
horizontally a very short distance from the downstream tap and then sloped at a nominal 1
inch-perhorizontally below the upstream tap so that piping from the upstream tap to the manifold
When a flowing condition is stopped, particulates may fall into the low-pressure port.
It is advisable to flush the low-pressure port with an
inert fluid before starting the
be used
pressure
configurations that use the standard upstream
due
to the risk of trapping gas. For such applications, consider the use of a vertically
oriented meter with two wall taps (Fig 2.0)
Fig 8: Installation suggestion for upward flowing condition - Cone Meter with Vertical Orientation
2.15.7
Horizontal Meter Installation for Wet Gas
centerline
and the top of the pipe (3 o'clock to 12 o'clock or 9 o'clock to 12 o'clock). If the fluid is a "wet
a
If
the connecting tubing extending from the cone meter to the transmitter is not installed in a
vertical position, it should slope upward (at least 1 inch per foot) to ensure proper drainage.
Fig 9: 12 o’ clock position (preferred)
Fig 10: 3 o’ clock position
meter, unless a wall tap design is being used. A wall tap design should always
on applications where trash may have a propensity to fall into the central lowport (Fig 1.0). Downward flow piping
and downstream pressure ports are also not recommended for liquid applications
Fig 1.0
Fig 2.0
The pressure taps on the Tek-DPro DP Cone Meter should be between the horizontal
gas" (i.e., a gas containing small quantities of liquids). The pressure taps should be situated in
vertical position (12 o’clock) to allow all liquids to drain away from the transmitter (Figure 9).
Short lengths preferred
to assist in reduction
of Gauge Line Error
The most difficult application for a differential pressure measurement is steam or hot gasses.
This
are
transmitter and may not be single phase due to
temperature change at the tubing due to various factors (Insulation failure, Joules Thompson
temperature
orientated
review
of the intended install.
2.16.1
Orientation
the
be
the best option taking into consideration the previous suggestions in earlier paragraphs.
2.16.2
Sensing /Impulse Tubing Orientation
meter,
installations,
the flow direction is also a factor. When a vertical meter run is to be used, operators/ system
liquid
from being trapped and thus cause incorrect measurement readings.
2.16.3
Condensate Chambers
prevent
heated steam from entering a differential pressure transmitter and causing overheating
diameter tee is only required to collect the liquid.
chamber
reservoir will be needed to prevent heat issues. Modern DP / smart transmitters have smaller
diaphragm movements and do not need large condensate chamber volumes.
2.16.4
Horizontal Service Applications – Steam / Hot Gases
The meter shall be installed so that the pressure taps shall be situated above the horizontal
centerline (9 o'clock to 3 o'clock only) of the meter. Condensing hot vapors from steam, cause
prevent
hot process fluid from damaging the transmitter in this operating condition. The
impulse/sensing tubing should slope upwards from the cone meter to the condensate pots. As
in
as
shown in Figure 12. In either case, condensate pots should be situated at the same location /
enable differential pressure readings that are accurate. A line from the bottom of the
tee to the transmitter mounted below the tee should be filled to the point where any excess
the
fluid must be protected from freezing as mentioned in an earlier section. The fluid fill
methodology requires a careful application with heat tracing and insulation to keep it in the
installation requires careful consideration regarding the transmitter tubing. Steam /Hot Gases
usually at a temperature which can damage a DP
effects, Phase envelope etc.) Liquid or gaseous phases can ensue depending on both
and pressure /environmental conditions. Differential pressure impulse tubing must be
in such a manner that it can operate with a gas or liquid present which requires some initial
All Tek-DPro Cone Meters can be installed in a horizontal or vertical position. Horizontal is
standard orientation, however where space is very limited, a vertical position may prove to
The installation /position of the DP impulse tubing is determined by the orientation of the
also the type and quality of the Steam/Hot Gas to be measured. For vertical meter
designers should give special consideration to the impulse tubing configuration to prevent
Condensate chambers are installed to provide a liquid reservoir / buffer that helps to
superof the electronics. In most cases, a largeHowever, if the DP is being read by using a chart recorder, a larger volume condensate
liquid fluids to form in impulse lines. The use of a condensate chamber is mandatory to
mentioned, a condensate pot can be a tubing tee (Modern DP / smart transmitters) as shown
Figure 11 or large size condensate chambers (for higher volume devices like chart recorders)
level to
fluid can drain back into the meter to help prevent build up.
In many cases, water (condensed steam) is used for this fluid fill. However, in cold weather,
www.GlobalTestSupply.com
liquid phase and to keep both the high-pressure and low-pressure legs of the tubing at the same
temperature (maintaining the liquid fill at the same density).
A liquid leg fill fluid other than base water should be used if practical. Methanol is a possible
s
immiscible with water and remains liquid throughout a broader range of temperatures than
some other fill components (i.e., -31 to 645oF)
Fig 11: Horizontal Application DP Transmitter
Fig 12: Horizontal Application
(Chart Recorder Typical Application)
2.17
Specifications
Accuracy
±0.5% with Calibration
Repeatability
±0.1 % or better
Flow Ranges
10:1 and greater
0.45 through 0.85
Special betas available
as per ISO S167-5. Typically, 0-3D upstream and 0-2D
downstream is required
Inconel
Other materials available on request
Line Sizes
2” to 48”
Flanged
Others on request
Performance Verification Testing
ISO 5167-5
substitute, but di-butyl phthalate is recommended by various users as a fill fluid because it i
Standard Beta Ratios
Instillation Piping Requirements
Material
Large Condensate Chambers
(Steam)
Duplex
304 or 316 Stainless Steel
Hastelloy C-276
Carbon Steels
When removing the instrument from hazardous processes, avoid direct
electrical code.
•
3.1
General Instructions
3.1.1 Before installing a Tek-DP 1620A Cone Meter, review the following installation tips:
•
Make sure the piping, tubing, or manifold installed between the Tek-DP 1620A Cone Meters
WARNING
•
•
Never use a rod to clean out process lines in high-pressure applications or where high
meter
run should be isolated and completely depressurized before inserting any cleaning / test
rod into an impulse tube line. Check for ice/hydrate build ups in tapping points as it can
false impression and become a projectile during a warmup
from freezing temperatures, do not look directly into the taps in this condition.
3.2
Installation for Gases
3.2.1 Horizontal Installation Gases
•
The pressure taps on the primary device should be between the center of the horizontal line
The recommended slope for self-draining is a minimum of 30°.
•
•
•
CDE
Certified Drawing E
MRB
Manufacturing Record Book
DFT
Dry Film Thickness - Custom Paint Spec
CPC
Custom Product Code
lectronic (As Built)
This section covers instructions on installation and commissioning. Installation of the device
be carried out by qualified trained, specialists authorized to perform such works.
contact with the fluid and the meter.
All installations must comply with local installation requirements and local
and the transmitter complies with national and local standards, regulations, and codes of
practice to ensure safe containment of fluid.
A hydrostatic test may be required for piping systems to prove the integrity of the pressurecontaining components.
In installations that are prone to plugging, a rod or other device may be used to remove
materials blocking the impulse tubing note caution below:
temperatures (i.e., steam) or any dangerous /corrosive fluids being measured. The
block the pressure and give a
and the pipe (3 o’clock to 12 o’clock or 9 o’clock to 12 o’clock) shown in figure 6.
The taps should be vertical to allow the liquids to drain away from the secondary device if
the fluid is a “wet gas,” i.e., a gas containing small quantities of liquids.
For gases, the connecting lines from the primary device to the secondary device should be
slope upwards.
The pressure taps should be between the center of the horizontal line and 60° below the
centerline (3 o’clock to 5 o’clock or 7 o’clock to 9 o’clock) shown in figure 6.
and
The taps should be more than 60° to the horizontal plane in any case.
•
•
Fig 30: Horizontal Installation for Liquids
3.3.2
Vertical Installations Liquids
•
In most process applications, the presumption should be made that there may be gas or
transmitter and the transmitter should be below both taps.
•
•
*Note: Wall taps must be used for dirty liquids. Standard taps should only be used on clean liquids.
Taps at the bottom-dead-center may accumulate solids if they are present in the liquid
taps above the centerline will accumulate air or non-condensing gases.
vapor associated with a liquid, even though the liquid is water.
The piping must then allow gas to rise back into the flowing medium.
The DP piping should be carried out horizontally for a short distance and then down to the
Steam applications require careful consideration during installation.
the
lines
There is a concern that before the lines fill with condensed liquid and cool, the secondary
up. In this case, it is wise to
se line to allow the liquid (water for steam service) to be
primary
considerable.
•••••
Fig 32: Horizontal Installation for Steam
3.4.2
Vertical Installation for Steam
•
Wall Taps are mostly recommended for condensing vapors, preventing condensation from
The impulse lines are shut down horizontally to a “T” at a minimum distance of 18” for
saturated and superheated steam to reduce the temperature to below the saturation
the DP cell.
•
•
Steam at a very high temperature can damage the transmitter. Additionally, it can be in the
liquid or gaseous phase, depending on temperature and pressure. Therefore, the DP
pipework must be positioned in such a way that it can operate with a gas or liquid present.
The pressure taps should be on the center of the horizontal line (3 o’clock or 9 o’clock ) of
primary device. In condensing hot vapor service, such as steam, the fluid in the impulse
is liquid condensed from the vapor. In this case, the pressure taps should be horizontal with
the impulse lines and positioned to the DP transmitter, as shown in figure 31.
system will become exposed to the vapor temperature at starthave a plugged tee fit in the impul
filled with the impulse line and secondary unit before starting up (see Figure 32).
Cryogenic (very low temperature) systems may require special designs, which are not
considered here.
The liquids in the lines will isolate the secondary device from the temperatures of the
flowing fluid.
Over a short distance of 100 mm (4”) to 200 mm (8”), the temperature difference can be
the buildup in the cone or evaporating and changing the DP.
temperature.
The “T” enables a plug to be installed at the top for the liquid filling to avoid overheating of
www.GlobalTestSupply.com
•
The manifold block will be placed directly below at a distance to maintain the DP transmitter
at a safe operating temperature.
Fig 33: Vertical Installation for Steam
3.5
Installation for Upstream and Downstream
•
In most of the flow elements, the proper operation and performance depend on unrestricted
can
be installed with O to 5D and O to 3D downstream.
•
•
*Note UL= Upstream
0 = NR
Side View Front View
upstream and downstream piping length requirements.
The fully developed symmetrical flow profile is achieved with relatively short upstream and
downstream lengths.
Therefore, it needs minimal upstream and downstream straight pipe runs. The Cone meter
There should be no need for periodic maintenance or re-calibration if the meter is installed
instructions.
•
•
DL 0 0 0 1D 1D
UL 1D 1D 1D 2D 2D
DL 1D 1D 1D 2D 2D
UL 1D 1D 1D 2D 2D
DL 1D 1D 1D 2D 2D
UL 0 0 0 1D 1D
DL 0 0 0 1D 1D
UL 3D 3D 3D 4D 4D
DL 0 0 0 1D 1D
UL 3D 3D 3D 4D 4D
DL 3D 3D 3D 4D 4D
correctly.
In extreme process conditions, periodically inspect the Tek-DP 1620A DP Cone Meter for any
significant physical damage.
Calibrate and maintain secondary and tertiary instrumentation according to the manufacturer’s
This section provides troubleshooting techniques for most common operating problems shown
in
table 1.
Table 1: Troubleshooting Techniques
Symptoms
Area
Possible Problem or Solution
•No Power to transmitter.
•Check continuity on wiring or loose connection.
Negative Signal (<0mA)
Transmitter
•Transmitter wires are reversed.
•Cone Meter is installed backwards, with gauge
sensing
4mA.
•Gauge lines are reversed. Transmitter shows more
•Check “H” and “L” marks on DP Cone Meter.
•Meter has been damaged.
no flow.
Manifold / gauge lines closed or blocked.
verify pressure in the gauge lines.
coefficient.
•Foreign material trapped in gauge lines. Dirt and
valve for several minutes under high DP. Close the
No Signal (0mA) Transmitter
Tek-DP 1620A
Low signal
(<4mA)
Gauge Line
Tek-DP 1620A
Zero Signal (4mA)
Manifold
•Transmitter not wired correctly.
lines attached as marked.
•In this case, th
a lower pressure than the low pressure tap.
•This negative DP w
pressure on lower side than higher side.
•Remove meter and visually inspect.
•No flow in pipeline.
•Check other system locations to verify flow
through the meter.
•The meter cou
•
•Ensure valves and lines are open.
•If fluid is safe
e high-pressure tap would be
ould force the signal below
ld be under pressure but still have
, open vent valves on transmitter to
•Process conditions do not match actual
conditions.
•Contact your sales representative to recalculate
using the correct process conditions.
Tek-DP 1620A
Wrong Signal High or Low
Gauge Lines
•Wrong meter.
•Verify serial numbers on meters to ensure correct
specifications.
•Sometimes two meters are interchanged.
Remember each DP Cone Meter has a unique flow
sediment can settle into the gauge lines. If the
fluid is safe, vent the gauge lines and inspect for
spurts of solids, gasses, or liquids (whichever
should not be there).
•If the fluid is not safe, open the center manifold
•In a horizontal,
with the taps on the sides of the pipe (3 or 9
o’clock) For a ho
•Use loop calibrator and apply 4, 12, and 20mA to
computer / system.
•Each of these points should be correlate with the
DP Cone Meter sizing information.
•Current output signal is read incorrectly.
•Apply a known current to the loop and read the
raw signal in the computer.
•Most computers
•
•Periods with a partially full pipe will cause wrong
•
•This will increase the restriction of the meter and
raise the DP.
liquid application, install the meter
rizontal, gas application, install at
allow the user to see the mA
Signal very High Tek-DP 1620A
•If any arrow is not visible and the meter is large
than 2”, the flow direction can be determined by
the location of the pressure taps.
•The pressure taps will be closer to the upstream
side.
•On meters less than 2”, the gauge lines will need
to be removed. Look at the base of both pressure
taps. One tap will be smooth at the base, the
other will be mostly weld material.
•The smooth tap is on the upstream side.
•Flow is going in the opposite direction from what
was expected. The assumption of flow direction is
sometimes wrong.
•Verify with other system readings.
•With a meter measuring backward flow, the DP
signal will be approximately 30% high.
•Partially full pipe (liquids only). A partially full
pipe will cause the meter to read very high. This
can happen even in pressurized systems.