teko Astra-421 Operation Manual

Astra-421 Ver. RF
Wireless Optoelectronic Smoke Detector
Operation Manual
This operation manual is intended for studying principle of operation, correct use, operating conditions and maintenance of the wireless optoelectronic smoke detector «Astra-421» ver.RF (hereinafter «detector») (figure 1). The manufacturer reserves the right to make alteration regard­ing refinement of the product without prior notification. All changes will be imported into new edition of the operation manual.
1 Function
1.1 The detector is intended for
detecting fire followed by smoke spreading, forming and transmit­ting «Fire» notification to the re­ceiver «Astra-RVA» (hereinafter «receiver») of wireless intrusion/fire detection and alarming system Ob-
server-1.
1.2 The detector supports 3 operat-
ing frequencies.
1.3 Electric power is supplied by a
lithium-thionyl-chloride battery cell standard size AA, voltage 3,6 V (included in delivery set).
2 Principle of Operation
The principle of operation of the detector is based on register­ing infrared radiation (hereinafter IR) that is reflected from smoke particles in the smoke chamber by a photodetector. Fur­ther the electric signal formed by the photodetector is amplified and sent to microcontroller in order to analyze the smoke densi­ty value. The detector generates «Fire» or «Warning» notifica­tion in accordance with a specified operating algorithm.
3 Specifications
Detector`s sensitivity, dB/m ................................ from 0,05 to 0,2
Response time, sec., max ......................................................... 5
Detection area, m2, max ........................................................ 110
Installation height, m, max ....................................................... 10
Technical Parameters of Radio Channel
Operating frequency, MHz ................................................ 433,42
Emission power, mWt, max ..................................................... 10
Wireless coverage range*, m, min ......................................... 300
General Technical Parameters Current consumption:
- with transmitter turned OFF, mA, max............................... .0,05
- with transmitter turned ON, mA, max ................................... .25
Supply voltage, V ................................................. from 2,7 to 3,6
Technical readiness time, s, max…………………………….….60
Standby mode recovery time, s, max ...................................... 60
* Along the line-of-sight. Wireless coverage range is largely dependent on the design features of construction, the installation location, the in­terference situation.
Overall dimensions, mm, max
- diameter .............................................................................. 100
- height ..................................................................................... 47
Weight, kg, max .................................................................... 0,12
Battery cell average life time, years, min ................................... 3
Operating Conditions
Temperature range, °С ..................................... from - 10 to + 55
Relative air humidity, % ................................ up to 93 at + 40 °С
without moisture condensation
4 Delivery Set
Wireless optoelectronic smoke detector
«Astra-421» ver. RF ........................................................... 1 pcs
Screw 3,9х32 ...................................................................... 2 pcs
Dowel 6х30 ......................................................................... 2 pcs
Battery cell .......................................................................... 1 pcs
Operation manual ............................................................. 1 copy
5 Structure
Constructively the detector consists of a removable electronic unit and a base (figure 2).
Figure 2
Inside the electronic unit is a smoke chamber and printed circuit board (PCB) with radio elements and photodetector. Mounted on PCB is a LED for checking the detector`s operability. The design of the detector provides for its installation on the ceiling.
Note - It is not recommended to disassemble the electronic unit of the detector, as it may damage the detector’s tuning.
Figure 1
421-rkv16_1_en
2
6 Information Capacity
Table 1- Notification types
Notification
types
LED
Receiver
Standby mode
Lights up for the time of 1-20
sec, then flashes once per 1 sec. Duration is up to 60 sec.
Norm
Not lit
+
Fire
Flashes once per 1,5 as the smoke density in the secure area reaches the oper­ation threshold. Flashes as long as the smoke is there.
+
Warning
Flashes 2 times per 1 sec during 5 sec as the smoke density in the secure area reaches 75% of the activation threshold
+
Failure
Flashes 1 time per 3 sec
+
Low supply voltage
Flashes 2 times successively once per 10-15 sec, at supply voltage less than 2,9 V.
+
«+» – notification is generated, «–» – notification is not generated
Note - In case «Low supply voltage» notification is generated, it is necessary to replace battery cell within one week.
7 Operation Modes
The detector provides for «Test» and «Autotest» operating modes, intended for testing electronic circuits of the detector.
7.1 The «Test» mode is
activated when reading a coded message by LED sent from laser tester «Astra- 941» (figure 3). In 5 sec after reading the message, the detector must output the «Fire» notification
- if the detector operation is normal, or «Failure» - in case of a failure.
Figure 3
Note - Laser tester «Astra-941» is optional and delivered sepa- rately.
7.2 The «Autotest» mode is activated by the detector auto-
matically every 24 hours. At that the operation threshold is ad­justed depending on the environment and the «Test» mode is activated. Upon successful completion of the test notification is not generated. In case of failure, «Failure» notification is generated.
8 Pre-starting Procedure
8.1 After transportation in conditions differing from those of
operation, keep the detector unpacked for 4 hours in the ex­pected operating conditions.
ATTENTION! Check correspondence of frequency carrier of the detector and the receiver.
8.2 Running Detector
Attention! Lithium-thionyl-chloride batteries have an effect of
«passivation» to provide the possibility of long-term storage. To provide battery normal operation after long-term storage, hold an «activation» procedure.
Step-1
Place the detector on-the­spot. Turn the electronic module counterclockwise. Remove the electronic unit from the detector`s base.
Step-2
Install the battery cell. Switch the detector ON by in­stalling jumper on power plug.
Step-3
To replace battery:
- switch the detector OFF;
- remove the old one;
- after no less than 20 sec install the new battery. When installing into detector the battery is automatically «activated» and checked. The LED lights red (less than 20 sec.) After checking: In case the LED flashes 2 times successively with fre- quency once per 10-15 sec («Low supply voltage»), remove jumper, close the positive and negative poles of the battery for 2-3 sec with a piece of wire and repeat switching by in­stalling jumper back after at least 20 sec. In case the LED flashes with frequency once per 1 sec («Standby mode») and notification «Power failure» is not appears, the battery is considered as useful.
8.3 Registration Procedure
The detector registering in the receiver memory occurs at the moment of powering up.
Step-1
Place the detector on-the­spot. Turn the electronic module counterclockwise. Remove the electronic unit from the detector`s base.
Step-2
Switch the detector OFF by removing jumper from power plug
Loading...
+ 2 hidden pages