Teknoware TKT24 series, TKT2404C, TKT2408C Nstallation And User Manual

TKT24series
Addressable 24 V Central Battery Unit
Installation and User Guide
This product may only be installed or maintained by a qualified electrician.
QUICK GUIDE: FRONT PANEL INDICATOR LEDs
Central Battery Unit is ON
Mains mode
Battery mode
Error, see Chapter 8 for details about error codes
Test(s) running
Table of Contents
1. Product Description 5
1.1 Manufacturer 5
1.2 Model 5
1.3 General Description 5
1.4 Storage 5
1.5 Technical Details 6
2. Planning the System 7
3. Installing the System 7
3.1 Connections, Parts and Layout 8
4. Commissioning 11
5. Structure of the User Interface 11
6. Main View 12
7. Main Menu 12
7.1 Circuit- and Luminaire Configurations 12
7.2 History of Tests and error log 12
7.3 Functions 13
7.4 Settings 13
7.5 Setting the Time 13
7.6 Luminaire Test Settings 13
7.7 Battery Settings 14
3
8. Warnings and Errors 16
8.1 BATTERY ERROR 16
8.2 BATTERY OVERVOLTAGE 16
8.3 DEEP DISCHARGE 16
8.4 BATTERY UNDERVOLTAGE 16
8.5 TEMPERATURE ERROR 16
8.6 MAINS NOT PRESENT 16
8.7 MOSFET BROKEN + circuit board number 16
8.8 LUMINAIRE BROKEN 17
8.9 FUSE ERROR 17
9. Mechanical Dimensions: TKT2404C 18
10. Mechanical Dimensions: TKT2408C 19
4
1. Product Description
1.1 Manufacturer
Teknoware Oy P.O. Box 19, FI-15101 Lahti Ilmarisentie 8, FI-15200 Lahti info@teknoware.com www.teknoware.com
1.2 Model
TKT24…C
1.3 General Description
TKT24 is an addressable 24 V central battery unit (CBU) for emergency lights. The CBU is supplied with 220–240 AC mains, maintaining the battery charge and supplying the emergency ligh circuits with 24 VAC. If mains is disconnected, or mains supply drops below the defined limit, the CBU switches to battery mode, and supplies the emergency ligh circuits with 24 VDC. Battery supply is maintained until the mains is restored (with user set delay), or until the battery capacity drops to deep discharge limit.
In addition to the mentioned basic functions, the CBU has the following monitoring- and reporting functions:
• Testing of addressable luminaires, and the monitoring of their operation - indicaties the address of faulty luminaire
• Tests the batteries automatically
• Tests can also be started manually
• Self-learning system: luminaires can be added or removed after commissioning
• Mode- and warning statuses can be communicated via. relay connections to building monitoring systems
• A direct data connection to Teknoware ACM system.
• All the functions of the CBU can be accessed from the LCD interface.
1.4 Storage
If the CBU and batteries are not installed directly after delivery, the following instructions must be followed:
• The CBU must be protected from humidity
• Storing temperature of the CBU and batteries: +10…+30°C.
• If the batteries are stored for an extended period of time, the batteries must be recharged every 6 months, for 12 hours at a time.
Note!
The delivery may include lead batteris, that have charge, and that may short circuit due to
inproper storage! Take this into account when storing the CBU.
5
1.5 Technical Details
Nominal Supply Voltage: 220-240 VAC, 50/60Hz, 1~
Casing / IP Class: IP20
Output Voltage: Main supply: 24 VAC, Battery supply: 24 VDC
Battery Voltage: 24 VDC
Battery Recharge Time: 12 h (80 %)
Batteries:
Max Input Power TKT2404C:
Max Input Power: 700 VA
Ambient temperature: +10...+30°C
CBU Input Fuse: 1~ Circuit breaker, 16 A, C-curve
Output Circuit Fuses: 5 x 20 mm:n glass tube fuse 4 AT
Battery Fuse: Circuit breaker32 A/250 VDC
Output connector: Max. wire 4 mm²
Mass (without batteries):
TKT2404C: 2 x 17 Ah TKT2408C: 2 x 38 Ah
400 VA
TKT2404C: 11,1 kg TKT2408C: 16,0 kg
Voltage limits
• When mains drops below 165 VAC, the CBU supplies voltage for the emergency lighting from the batteries
• When mains is disconnected, the CBU supplies voltage for the emergency lighting from the batteries.
• If the battery voltage rises above 28,5 V, the CBU gives a Battery Overvoltage warning
• If the battery voltage drops below 20,0 V:n, the CBU gives a Battery Undervoltage warning.
• During battery mode, if the battery voltage drops below 19,0 V:n, the CBU goes into deep discharge mode.
6