Teknim TFP-40 Series, TFP-404, TFP-408 Installation & Operation Manual

2016
Conventional Fire Alarm Panel
Installation & Operation Manual
Issue Date: 26/12/2016 Rev:02
TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
1
Table of Contents
1 Introduction ........................................................................................................................................ 3
2 Warnings ............................................................................................................................................ 3
3 Technical Specifications ........................................................................................................................ 4
4 TFP-40x Series Conventional System ..................................................................................................... 5
4.1 Panel Properties ........................................................................................................................... 5
4.2 Panel User Interface ..................................................................................................................... 6
5 Installation .......................................................................................................................................... 9
5.1 Recommended Cables .................................................................................................................. 9
5.2 Mounting..................................................................................................................................... 9
5.3 Supply Input................................................................................................................................ 9
5.4 Battery Connection ....................................................................................................................... 9
5.7 Zone Lines ............................................................................................................................... 10
6 User Levels........................................................................................................................................ 11
6.1 Level 1 ..................................................................................................................................... 11
6.2 Level 2 ..................................................................................................................................... 11
6.3 Level 3 ..................................................................................................................................... 11
6.4 Level 4 ..................................................................................................................................... 11
7 Using the Panel ................................................................................................................................. 12
7.1 Disable Mode ............................................................................................................................. 12
7.2 Test Mode ................................................................................................................................. 12
7.3 Siren Resound Option ................................................................................................................. 13
7.4 System Error ............................................................................................................................. 13
7.5 Error Diagnostic ......................................................................................................................... 13
8 Maintenance ...................................................................................................................................... 14
8.1 Situations requiring Maintenance, Repair or Servicing .................................................................... 14
8.2 Routine Checks .......................................................................................................................... 14
8.2.1 Daily ..................................................................................................................................... 14
8.2.2 Weekly .................................................................................................................................. 14
8.2.3 4 Years ................................................................................................................................. 14
9 Appendices ........................................................................................................................................ 15
9.1 Appendix-Mechanical .................................................................................................................. 15
9.2 Appendeix- Electrical .................................................................................................................. 19
9.3 Appendix-Level .......................................................................................................................... 21
10 Issues to be considered ...................................................................................................................... 26
10.1 Maintenance, Repair and Cleaning to be carried out by the Consumer ............................................ 26
10.2 Information on Faulty Usage ....................................................................................................... 26
10.3 Handling and Transportation ....................................................................................................... 26
TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
2
Table 1 Main Button Functions ...................................................................................................................... 7
Table 2 Auxiliary Button Functions ................................................................................................................. 8
Table 3 Level-2 Key...................................................................................................................................... 8
Table 4 LED Indicators ................................................................................................................................. 9
Table 5 Properties of the Recommended Cables ........................................................................................... 10
Table 6 Known Errors ................................................................................................................................. 14
Figure 1 Control Panel User Interface ............................................................................................................ 7
Figure 2 Panel Front Cover Screws .............................................................................................................. 16
Figure 3 Mounting Screw Holes ................................................................................................................... 17
Figure 4 Electrical Connections .................................................................................................................... 18
Figure 5 Battery Connection ........................................................................................................................ 19
Figure 6 Siren Connection ........................................................................................................................... 20
Figure 7 Zone Connection ........................................................................................................................... 20
Figure 8 Zone Grounding Connection ........................................................................................................... 21
Figure 9 Level-3 ......................................................................................................................................... 22
1922
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi
No:1 Kat:2/32 Ümraniye, İstanbul, Turkiye
16
1922-CPD-0690
EN 54-2:1997, EN 54-2:1997/AC:1999, EN 54-2:1997/A1:2006
Control and indicating equipment for fire detection and fire alarm systems for
buildings
TFP-404, TFP-408
Provided options:
Output to C
Test Condition
EN 54-4:1997, EN 54-4:1997/AC:1999, EN 54-4:1997/A1:2002, EN 54-4:1997/A2:2006
Power supply equipment for fire detection and fire alarm systems for buildings
TFP-404, TFP-408
Other technical data: see BİLGİ-TEC-160928 held by the manufacturer.
TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
3
1 Introduction
This manual contains the installation instructions, technical properties, and panel configuration information related to TFP-40x Series Teknim Conventional Panels.
TFP-40x Teknim conventional panels may be viewed under 2 options as 4- or 8-zone devices. 32 detectors or fire alarm buttons can be connected per zone.
TFP -40x series panels compliant with EN54-2/4 standards
Before installation, the manual must be read and installation must be carried out by authorized persons in accordance with the instructions.
Before starting the installation, check that the following list is complete inside the package:
- TFP-40x panel,
- 6 pieces of 4K7 siren end-of-line resistances for TFP-404 and 10 pieces for TFP-408,
- Lock key for access level 2,
- Battery cable,
- Battery mounting lugs and 4 screws
- 4 screws and dowels for wall-mounting
- Allen key,
- Installation and Operation Manual
- Quick Installation Manual
- Warranty Certificate
2 Warnings
- The panel contains electronic card consisting of digital and analog circuits. Therefore it should not be
used before having read the entire operation manual.
- In case of any malfunction or in the case that the panel needs maintenance, maintenance and repairs
must be carried out by the authorized service station of the manufacturer company or the people/companies authorized by the manufacturer company.
- The cable lines for the supply line of the panel, siren line, and the detector line should be as specified in
this manual.
- When panel is energized with supply voltage, do not make any changes to the panel connections.
- The grounding connection to the panel must have been made.
- Do not apply ~230 VAC 50Hz mains voltage to the inputs-outputs of the zone line, inputs of the siren
line connections, and the inputs of the battery connections.
- Do not use batteries that have reached the end of useful life or have been damaged by falling below a
voltage level. The device does not charge batteries that are below voltage level 20.5 VDC.
Warning: Do not start mounting before having read the entire manual.
TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
4
3 Technical Specifications
Supply
Voltage
230 / 110 VAC (+%10 / -%15)
Frequency
50 / 60 Hz (±%5)
Mains Input Fuse
2A
Output Voltage
21 – 29 Vdc ± %2
Output Fuse
4A (F1)
Cable Type
3 x 1,5mm² (Phase, Neutria, Ground)
Battery
2 x 12V, 7Ah (Recommended Yuasa NP7-12, 12V7Ah)
Battery CutOff Voltage
20,5 V
Battery Internal Resistance Fault
Resistance > 1,5 ohm
Greatest Current to be drawn from the Battery
When the main power source is not connected 2A Battery Fuse
4A (F2)
Charging Voltage
27,6 Vdc @20°C, with heat compensation
Charging Current
500mA (resistance limited)
Imin
TFP-404 – 75mA, TFP-408 – 110mA
ImaxA
500 mA
ImaxB
1,5 A
Outputs
Supervised Siren Outputs
2 adet 24Vdc (15 devices / 32mA per device) (Caution : The output current of the panel should not exceed 1.4 A)
Siren Fuse
2 x 500mA (F5-F6)
Siren End-of-line Resistance
4K7 ohm, %5, 1/4W
General Error Relay
1 x NC/NO dry contact 30V, 2A
Fire Relay
1 x NC/NO dry contact, 30V, 2A
Auxiliary Output (AUX)
1 x 24Vdc/450mA(Caution : The output current of the panel should not exceed 1.4 A)
AUX Fuse
1 x 500mA (F3)
Cable Type for Outputs
2 x 1,5mm² J-Y(St)Y…Lg (Recommended)
Zone Information
Number Of Zones
4 or 8
Number of Detectors
32 pieces per zone (TFD series)
Output
24Vdc/450mA(Caution : The output current of the panel should not exceed 1.4A)
Output Fuse
1 x 500mA (F4)
Cable Resistance
40 ohm (en fazla)
Cable Length
1,5 km 1,5mm² cross-section (Maximum)
End Of Line Resistance
4K7 ohm, %5, 1/4W
Cable Type For zone
2 x 1,5mm² J-Y(St)Y…Lg (Recommended)
Environmental Conditions
Temperature
-10C ~ 55C (14F ~ 131F)
Humidity
95% RH (maximum)
IP Class
IP30
Mechanical
Color
RAL9006(Light Gray)
Dimensions (H x W x D)
340 x 300 x 100 mm
Weight
4,4kg (without battery)
The device properties may be changed without notification.
The battery recommended for the device is Yuasa NP7-12.
The greatest current that can be given to the zones and outputs is 1.4A.
TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
5
4 TFP-40x Series Conventional System
TFP-40x series conventional systems are fire detection systems, which are designed with 4 or 8-zones and in which 32 detectors or fire alarm buttons can be connected per zone. The system also provides features like 2 supervised siren outputs, 1 dry contact fault relay, 1 dry contact alarm relay, and 1 x 24 AV AUX output.
The panels satisfy the standards "EN54-2 & 4 Fire detection and fire alarm systems - Control and indicating equipment". In addition, they satisfy the following conditional provisions of EN54-2:
- EN54-2 Article 7.8. Transmission of fire alarm signals received from one zone to fire alarm devices,
- EN54-2 Article 10. Test status that allows automatic resetting for zone fire test;
The panels are supplied by 2-ampere internal power supply. Spaces have been allocated in the panels for placement of batteries as shown in "Figure 5 Battery Connection". The power supply compliant with EN54-4 has a smart battery charging system with heat compensation.
The transition between access levels 1 and 2 is facilitated with the switch at the front of the panel. For access level 3, the front cover of the panel must be removed. Access level 4 is made available with a special apparatus provided by the manufacturer.
There are 6 buttons to control the system. 3 performance these, "Alarm On/Off", "Silence" and "Reset", are designed larger and in color to direct the user.
For the calculation of how long the system can be supplied via a battery after an interruption of the main supply, the current consumptions of the panel are given in the table for uncharged and alarm statuses.
Model
Idle Status
Alarm Status
TFP-404
75 mA
140 mA
TFP-408
115 mA
180 mA
4.1 Panel Properties
4 or 8 zones controlled against incorrect connections with end-of-line resistances,
Capability to connect 32 detectors or fire alarm buttons per zone,
"Fire and Fault/Disable/Test" LEDs for the zones,
LEDs for general error, system error, supply error, battery error , earth error , siren status, energy, system
on , test, disable , access level, communication, general alarm,
Capability to disable desired zones; capability to see the disabled zones with the dedicated disable LED on
the panel.
Easily conducted zone test,
Smart charging system that prolongs the battery life; where there is no main supply and the system is
supplied through battery, when the battery voltage drops below 20.5 VDC, the device shuts itself down automatically to preserve the batteries and not to cause false alarms.
2 siren outputs controlled against incorrect connections with end-of-line resistances,
1 NC/NO fire relay (button alarm, detector alarm, etc.)
1 NC/NO fault relay (Energy error , zone error , battery error , etc.)
1 output with Aux 24VDC 500 mA automatic fuse
Switch system determining intervention authorization level
Easy-to-understand front panel,
Switched power supply (with 27.75 Vdc SMPS 2A automatic fuse)
Metal housing
Used with 2 x 12V 7Ah batteries. The battery recommended for the device is Yuasa NP7-12
TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
6
4.2 Panel User Interface
This chapter describes the indicators and buttons on the panel.
Figure 1 Control Panel User Interface
The buttons C, D, and E shown in Figure 1 Control Panel User Interface are main buttons and have single functions. They are designed larger than other buttons and in color for user convenience. The functions of the buttons are defined in Table-1.
Table 1 Main Button Functions
Label
Task
[C]
ALARM On / Off
Shall be used in Level-2 and Level-3. Starts the evacuation procedure, activates sirens. Mutes sirens in alarm status or resounds the muted sirens.
[D]
MUTE
Mutes Buzzer in cases of fault or alarm.
[E]
RESET
Shall be used in Level-2 and Level-3. Used to restore the panel in alarm or fault status to normal operating status.
The buttons F, G, and H shown in Figure 1 Control Panel User Interface have multiple functions. These functions vary depending on the access level and the time of button presses.
The functions of the buttons are defined in Table-2.
Long press: Keeping the button pressed for more than 3 seconds
Short press: Pressing and releasing the button in a period under 3 seconds
TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
7
Table 1 Auxiliary Buttons Functions
Label
Task
Short press
Long press
[F]
DISABLE (<)
It is used to change the processed zone when test or disable process is active in Level-2. It shows the disable zones for 3 seconds when Level-1 and test or disable process are deactivated.
It is used to turn on and off the deactivation process in Level-2. In this case, the fault statuses of the zones or the siren are not shown. Only the disable zones are shown.
[G]
ENTER
It is confirmed to carry out disable or test processes at the selected zone/siren when disable or test processes are carried out.
It is used to show the details of the fault statuses in Level-1.
[H]
TEST (>)
It is used to test the buzzer and the LEDs in Level-1. It is used to change the processed zone or siren when disable process is active in Level-2. Also, it is used to show the tested zones and siren for 3 seconds when test and disable processes are deactivated.
It is used to show the zones and siren being tested for 3 seconds in Level-1. It is used to turn on and off the test process in Level-2. In this case, it show the zones and siren being tested.
Level 1 and 2 checks are carried out with a special key provided by the manufacturer company. It is not possible to remove the key in Level 2.
Table 3 Level - 2 Key
Label
Task
[Y]
LEVEL-2
Key in vertical position; Keylock off; Level-1 Key in horizontal position; Keylock on; Level-2
Panel fault and alarm statuses are provided with LED indicators. An internal buzzer is available to provide audible warning. LEDs and buzzer can be tested without transiting to any level.
TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
8
Table 4 LED Indicators
Label
LED name
Fixed LED
Blinking LED
Color
[V]
FIRE
NONE
Shows that the panel is in alarm status (250 ms)
Red
[I]
General Error
Shows a system error
Shows there is a fault in the system
Yellow
[J]
System Error
Shows a system error
NONE
Yellow
[K]
Supply Error
NONE
Shows there is a fault in the power source or charging circuit
Yellow
[L]
Battery Error
NONE
Shows there is a fault in the battery
Yellow
[M]
Earth Error
NONE
Shows there is a fault in the earth connection
Yellow
[N]
Siren Status
Shows that the siren is disabled
Shows there is a fault in the siren
Yellow
[O]
Energy
Shows that the system is supplied from any source
NONE
Green
[P]
System Activated
Shows that there no problems that can affect the full operation of the system
NONE
Green
[R]
Test
Shows that one or more zones are in test status
NONE
Yellow
[S]
Disable
Shows that the zones or the siren are disabled
NONE
Yellow
[T]
Access Level
Level 3 active
Level 2 active
Yellow
[U]
Communication
NONE
Show that the system is communicating with the computer
Yellow
[A]
Zone fire
NONE
Shows that the zone is in fire status
Red
[B]
Zone Fault/Disable /Test
Shows that the zone is disabled or in test status
Shows there is a fault in the zone
Yellow
Loading...
+ 18 hidden pages