Teknim TFD 1430, TFD 1450 Installation And User Manual

TD-1/11-102
TFD 1430
4 Wire Optical Smoke Detector
TFD 1450
Installation and User Manual
Publish Date: 15/4/2011
IMPORTANT WARNINGS
GENERAL
Before using the device read this manual carefully. Keep it
just in case of necessity.
Abide all the rules and precautions stated in the manual.
Follow all the instructions one by one.
Keep the devices away from water and moisture.
CONDITIONS
Do not energise the device above or below the given limits
of extreme hot or cold conditions. Temperature: Between 0°C and +55°C Relative Moisture: %95 at +40°C
Air flow limit: Below 600 meters/min
SERVICE
Do not try to fix the device on your own, Removal of cover may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical interventions has to be done by technicians of service company.
MALFUNCTIONS FOR TECHNICAL SERVICE
In case of any malfunction or below conditions contact with your authorized service.
When Mains cable or the plug is harmed, Contact of device with a fluid, Exposure of rain and water, Fell down of device or harmed outer cover, Serious performance fall on the device, Depending on the instructions stated in manual, if your
device not working properly, further usage or possible wrong usage may cause other malfunctions . Contact with your authorized service in such terms.
SPARE PART
If the repair will be done by spare parts, to avoid fire, electricity shock or any other hazardous conditions, Make sure your service is using original parts or parts compatible with your equipment.
SAFETY CHECK
To make sure if your device working properly and in safe conditions or not demand service from your dealer to check devicefunctionality.
INSTALLATION AND CONNECTION
1. Remove the head of the detector attached to base by turning it counter clock wise until you reach the short line on the base(1),then pull it off(2).
2. Use at least 2 opposite ones from 4 of the screw holes on the base to fasten it.
3. Do the wiring according to schematic shown below. The order of cables do not make any difference. There is no (+/-).
4. Place the detector head back. Make sure the short line on head fits with long one on the base.
5. Energise the detector. If there is no alarm condition the LED on detector flashes once every 10 secs to show it is working at that moment. .
TEST
TD-1/11-102
This test process captures both heat and smoke sensor inside.To make a correct test, you need stable air flow at 70°C or visible smoke flow. (TFD 1450 only).
Visible smoke flow is enough for testing TFD1430.
1. If your panel has the test function ability. Start the test function.
2. Start the hot air flow and control the temperature continuosly.
3. Let the air flow directly to the top of detector head which covers thermistor. Detector will switch to alarm mode 30 seconds at most.
4. Reset detector from the panel.
5. For smoke test, allow smoke from a cotton wick or a test smoke aerosol to enter the detector-sensing chamber for at least 10 seconds.When sufficient smoke enters the chamber, the detector will start the alarm.
6. After the alarm is active remove the source. Check if the red LED on detector is active. Then reset the detector from panel.
7. If the detector is not responding in 30secs and not going in alarm mode,you must send it to service .
8. After the test is complete, system can be activated.
IMPORTANT NOTES ABOUT DETECTOR USAGE
Multisensor Works as combination of both heat and
smoke detector. At least one of them going alarm mode is enough for it to warn (TFD1450 only).
To make sure both heat and smoke is working,
complete all steps on the test.
The recommended minimum requirement for the
detector maintenance consists of an annual cleaning of dust from the detector head by using a vacuum cleaner cleaning program should be agreed to the individual environment in conformance with EN 54-7:2000 and EN 54-5:2000 standard
PROPERTIES
Model
Alarm
conditions
2 / 4 wire
Power
Supply
Contact
ratings
Operating
temperature
(°C)
Startup time
(max ,seconds)
Dimensions
(mm) Body material
TFD 1430 NC
54°C
And/or
Visible smoke
4
9 - 15
VDC
15mA
NC
30V 50mA
max.
-10 ~ 50 60 Ø110, h50
Cream color UL 94
Fireproof ABS
plastic
TFD 1450 NC
54°C
MANUFACTURER
WARNING !
DO NOT TRY TO REMOVE THE DETECTOR FROM
THE PLASTIC COVER. THIS ASSEMBLY IS SEALED
FOR YOUR SAFETY. USERS MUST AVOID
INTERVENTION. OPENING THE DETECTOR HEAD
WILL REMOVE WARRANTY.