Teikoku DynaPump LE Series Instruction Manual

Instruction Manual
for: Installation, Operation, & Maintenance
DYNAPUMP
Sealless Leakproof Canned Motor Pump
LE SERIES
4/09
Table of Contents
Paragraph Page
SECTION 1. GENERAL INFORMATION
1-1. General Design and Operation ..................................................................................................... 1
1-2. Stator Assembly ............................................................................................................................ 2
1-3. Rotor Assembly ............................................................................................................................. 2
1-4. Bearings ........................................................................................................................................ 2
1-5. Thrust Washers and Shaft Sleeves .............................................................................................. 2
1-6. Cooling Flow ................................................................................................................................. 2
1-7. Automatic Thrust Balance ............................................................................................................. 2
1-8. Safety Precautions ........................................................................................................................ 2
SECTION 2. INSTALLATION
2-1. Receipt Inspection ......................................................................................................................... 4
2-1.1. Storage Note ......................................................................................................................... 4
2-2. Structural ........................................................................................................................................ 4
2-2.1. Pump Location ...................................................................................................................... 4
2-2.2. Mounting and Alignment ....................................................................................................... 4
2-2.3. Piping Data ........................................................................................................................... 5
2-3. Electrical ......................................................................................................................................... 6
2-3.1. General ................................................................................................................................. 6
2-3.2. Thermal Cut-Out ................................................................................................................... 6
2-3.3. Starting Equipment ............................................................................................................... 6
2-3.4. Bearing Wear Monitor .................................................................................................................. 7
SECTION 3. OPERATION
3-1. Procedure Before Initial Start-up ................................................................................................... 9
3-2. Priming and Venting ...................................................................................................................... 9
3-3. Rotation Check .............................................................................................................................. 9
3-4. Starting Procedure ......................................................................................................................... 9
3-5. Operation Details .......................................................................................................................... 10
3-6. Shutdown Procedure ..................................................................................................................... 10
SECTION 4. MAINTENANCE
4-1. Recommended Tools For Disassembly, Reassembly and Inspection ....................................... 11
4-1.1. Disassembly ........................................................................................................................ 11
4-2. Inspection ...................................................................................................................................... 11
4-2.1. Bearings ............................................................................................................................... 11
4-2.2. Shaft Sleeves and Thrust Collars ........................................................................................11
4-2.3. Rotor Assembly Inspection .................................................................................................. 12
4-2.4. Stator Assembly Inspection ................................................................................................. 12
4-2.5. General Inspection............................................................................................................... 12
4-3. Reassembly .................................................................................................................................. 12
i
FIGURES & TABLES
Figures
1-1 Dynapump LE Series Standard Circulation ................................................................................ 1
2-1 Dynapump LE Series Wiring Diagram 460 Volt, 3 Phase ........................................................... 7
2-2 Teikoku Rotary Guardian .......................................................................................................... 7
4-1 Dynapump LE Series Bearing Wear ........................................................................................... 13
4-2 Dynapump LE Series “g” Gap ..................................................................................................... 13
Tables
2-1 Dynapump LE Series Electrical Data .......................................................................................... 7
2-2 Trouble Shooting ......................................................................................................................... 8
4-1 Dynapump LE Series Bearing Wear Limit .................................................................................. 14
4-2 Dynapump LE Series Playing Gap of Rotor (Axial End Play) .................................................... 14
4-3 Dynapump LE Series Adjusting Value of Gap “g” ....................................................................... 14
4-4 Dynapump LE Series Tightening Torque for Impeller Bolt .......................................................... 14
APPENDIX
Trouble Analysis Sheet ........................................................................................................ ..................... A-1
Decontamination Certifi cation and Flushing Procedure (Page 1 of 2) ..................................................... A-2
Decontamination Certifi cation and Flushing Procedure (Page 2 of 2) ..................................................... A-3
Cross Section Drawing
D-65214 ............................................................................................................................................ A-4
LE Minimum Flows ................................................................................................................................... A-5
Outline Drawing
Standard - C-60538 .......................................................................................................................... A-6
With ANSI Baseplate - C60541.......................................................................................................... A-7
ii
CAUTION
Dynapump LE Series are canned motor, sealless pumps that offer a low cost, off the shelf, environmentally friendly alternative to sealed and single containment sealless pumps. Care should be exercised upon installation, start up, removal and maintenance of the pumps. Recommended safety equipment should be used at all times.
Prior to returning any Dynapump LE Series to the factory the following procedure must be followed:
1. Return Authorization must be obtained from the factory.
2. The pump must be decontaminated and cleaned.
3. The pump must be accompanied by a Decontamination Form, completely filled out and signed by a responsible individual at the customer’s facility. (Refer to copy of Decontamination Form in the Appendix of the Instruction Manual.)
It is recommend that, as a minimum, a set of bearings and gaskets be purchased for each Dynapump LE Series installed. When ordering spare parts, please reference the serial number and model designation indicated on pump nameplate. When ordering an impeller assembly, specify the diameter which can be measured across the blade tips.
Dynapump LE Series purchased for a particular application should only be used for that service. Metallurgy, bearing materials and motor size may not be compatible if used on a different application. Consult your local, authorized Teikoku USA Inc / Chempump representative or distributor, or contact the factory for confirmation.
SECTION 1. General Information
1.1 General Design and Operation
The Dynapump LE Series is a combined centrifugal pump and squirrel cage induction electric motor built together into a single hermetically sealed unit. The pump impeller is of the closed type, and is mounted on one end of the rotor shaft, which extends from the motor section into the pump casing. The rotor is sub­merged in the fluid being pumped and is, therefore, “canned” to isolate the motor rotor from contact with the fluid. The stator winding is also “canned” to iso­late it from the fluid being pumped. Bearings are submerged in system fluid and are therefore, lubri­cated by the process fluid.
The Dynapump LE has only one moving part, a com­bined rotor-impeller assembly that is driven by the induced magnetic field of an induction motor. A por­tion of the pumped fluid is allowed to re-circulate through the rotor cavity to cool the motor and lubri­cate the bearings. The stator windings are protected from contact with the re-circulating fluid by a corro­sion resistant, non-magnetic, alloy liner, which com­pletely seals or “cans” the stator winding. The re­circulating fluid is channeled into the motor section by holes drilled in the front bearing housing. A por­tion of the pumpage flows across the front bearing and returns to the rear of the impeller. The remain­der passes over the rotor, across the rear bearing, and returns to suction through a hollow shaft. See Figure 1-1.
The Dynapump LE offers true positive secondary containment as a standard design feature. In the event of a failure of the primary containment can, the stator assembly in conjunction with the leak proof terminal post assembly provides the secondary con-
tainment. This design prevents any release of the process fluid out to the atmosphere.
A standard feature of the Dynapump LE is the pat­ented Teikoku Rotary Guardian (TRG). The TRG is an electrical meter that continuously monitors the condition of the bearings. For more information on the TRG refer to 2-3.4 Bearing Wear Monitor, Page 7.
The Dynapump LE sealless pump is a precision­built unit that, with proper care, will give years of trouble-free, leakproof service. The entire unit is mounted on a fabricated steel base cradle. Opera­tion is unaffected by the mounting or operating posi­tion, eliminating the need for any costly alignment procedures. This manual, containing basic instruc­tions for installation, operation and maintenance of the Dynapump LE Series, is designed to assist you in obtaining this service.
It is important that the persons responsible for the installation, operation, and maintenance of the pump, read and understand the manual thoroughly. Trouble-free Dynapump LE performance begins with proper pump selection and application. If the se­lected pump does not have the required performance characteristics, or if the materials of construction are not properly specified for the fluid being handled, unsatisfactory operation may result. No amount of maintenance can compensate for this.
If you are in doubt about proper Dynapump LE selec­tion or application, write or call your Dynapump LE engineering representative or the factory for assis­tance. Additional copies of this manual are available from the Dynapump LE field representative, the fac-
tory or on our website: www.dynapump.com.
Figure 1-1. Dynapump LE Series Standard Circulation
Page 1
1-2. Stator Assembly
1-5. Thrust Collars and Shaft Sleeves
The stator assembly consists of a set of three-phase windings connected in a one-circuit wye arrange­ment. Stator laminations are of low-silicon grade steel. Laminations and windings are mounted in­side the cylindrical stator band. End bells, welded to the stator band, close off the ends of the stator as­sembly. The stator liner is, in effect, a cylindrical “can” placed in the stator bore and welded to the rear end bell and front end bell to hermetically seal off the windings from contact with the liquid being pumped. Terminal leads from the windings are brought into an oversized electrical terminal box. Motor lead wires are isolated from the users’ conduit line by a leak­proof terminal post assembly mounted inside the terminal box. The design of the stator assembly in conjunction with the leakproof terminal post assem­bly provides a true positive secondary containment.
1-3. Rotor Assembly
The rotor assembly is a squirrel cage induction rotor constructed and machined for use in the Dynapump LE. It consists of a machined corrosion resistant hollow shaft, laminated core with cast aluminum bars and end rings, corrosion resistant end covers, and a corrosion resistant can. The impeller is keyed to the shaft and held in place with a bolt and lockwasher.
All Dynapump LE models are equipped with thrust collars providing a replaceable surface against which axial loads can be carried during process upset con­ditions. The shaft is also fitted with replaceable shaft sleeves. Both the thrust collars and shaft sleeves are constructed of 316SS with a hard chrome wear surface for long life. These parts are pinned or keyed to prevent rotation.
1-6. Cooling Flow
Cooling for stator, rotor, and bearings, as well as bearing lubrication, is provided by circulation of the pumped fluid. A portion of the process fluid enters the motor section through ports in the front bearing housing. The fluid flows across the front bearing and returns to the rear of the impeller. The remain­der passes over the rotor, across the rear bearing, and returns to suction through the hollow shaft. See Figure 1-1, Page 1.
1-7. Automatic Thrust Balance
Based on hydraulic principles, Dynapump LE’s au­tomatic thrust balance is accomplished by the pres­sure of the pumped fluid itself, operating in a bal­ance chamber at the front and rear of the impeller.
The rotor end covers are welded to the shaft and also to the rotor can which surrounds the outside of the rotor, thus hermetically sealing off the rotor core from contact with the liquid being pumped.
The shaft is fitted with replaceable shaft sleeves and thrust collars. These parts are pinned or keyed to prevent rotation. Axial movement is restricted by the thrust collars contacting the face of the front and rear bearings.
1-4. Bearings
The bearings for the Dynapump LE Series are car­bon graphite as standard (silicon carbide is avail­able as an option) and are machined with special helix grooves through the bore to assure adequate fluid circulation at the journal area. Each bearing is manufactured to close tolerances for a high degree of concentricity and is held in a bearing housing by a retaining screw. Bearings are easily replaced by re­moving the retaining screw and sliding the bearing from its housing.
When a change in load shifts the position of the im­peller away from the balance condition, there is an equalizing change of hydraulic pressure in the bal­ance chamber, which immediately returns the im­peller-rotor assembly to the balanced position.
1-8. Safety Precautions.
1. Do not run pump dry. If the pump is allowed to run dry the bearing sleeves and other compo­nents will be damaged and serious overheating of the motor windings will occur.
2. Avoid rapid temperature changes. Rapid changes in temperature can cause leaks to oc­cur in the gasket areas of the pump.
3. Pump may be hot. Motor section of the pump can be very hot, even when pumping cool liq­uids. Motor windings are rated to 356o F.
4. If the motor trips due to the thermal cutouts, do not restart before determining the cause.
Page 2
Restarting the motor before ascertaining the cause can result in excessive heat leading to premature failure.
5. Do not remove internal bolts in the terminal box without taking the necessary precautions. The electrical junction box is a pressure-containing component of the pump. It is possible the fluid you are pumping may be present in the motor cavity in the event of a stator liner rupture.
6. Do not remove any bolts on the pump, motor or drain plug without taking the necessary precau­tions. The pump may be under pressure. Always loosen the drain plug slowly to relieve any inter-
nal pressure before attempting to disassemble the pump. Adequate precautions must be taken if the liquid in the pump could be hazardous to personnel or the environment.
7. Always assume that there is liquid left in the pump. There is always the possibility that re­sidual liquid could remain in the pump and motor, even after thorough decontamination. Pay particular attention to the clearances between the shaft and the impeller, bearings, sleeves, bearing housings, and gaskets. Adequate pre­cautions must be taken if the liquid in the pump could be hazardous to personnel or the environ­ment.
Page 3
SECTION 2. Installation
2-1. Receipt Inspection
1. Visually inspect the shipping container for evi­dence of damage during shipment.
2. Check unit to see that suction, discharge and any other connections are sealed.
3. Inspect the suction and discharge gasket seat­ing surface to be certain that they are clean of foreign matter and free from nicks, gouges and scratches.
4. Check all nameplate data against shipping pa­pers.
2-1.1. Storage Note
In situations where a Dynapump LE Series is to be stored for a period of time prior to installation and where the climate experiences wide temperature changes and high humidity, the terminal box, suc­tion and discharge flange, and any other openings must be sealed to prevent moisture from entering the internals of the pump.
suction lift are possible but not recommended. Location of the pump and arrangement of the sys­tem should be such that sufficient NPSH (Net Posi­tive Suction Head) is provided over vapor pressure of the fluid at the pump inlet. NPSH requirements at the design point are stated on the pump order data sheet. For additional design points, refer to the cor­responding performance curves located in the Ap­pendix of this manual.
NOTE Experience has proven that most pump troubles result from poor suction condi­tions including insufficient NPSH. The suc­tion line must have as few pressure drops as possible and available NPSH MUST be greater than required NPSH.
Depending on job conditions, available NPSH can sometimes be increased to meet the NPSH required by the pump for satisfactory operation. NPSH can be “tailored” by changes in the piping, in liquid supply level, by pressurizing the suction vessel and by sev­eral other methods. Refer to Table 2-2, Page 8, Trouble Shooting.
2-2. Structural
The pump design and construction eliminates the necessity of aligning the pump and motor. The pump should be supported from the mountings provided. It should be mounted in such a way as to have its weight properly supported. Suction and discharge piping must be properly supported and aligned so that no strain is placed on the pump casing.
General
1. Remove burrs and sharp edges from flanges when making up joints.
2. When connecting flanged joints, be sure inside diameters match within 1/16" so as not to im­pose a strain on the pump casing.
3. Use pipe hangers or supports at intervals as necessary.
2-2.1. Pump Location
Locate the pump as close as possible to the fluid supply with a positive suction head. Installations with
2-2.2. Mounting and Alignment
The Dynapump LE Series combines a pump and motor in a single hermetically sealed unit. No te­dious coupling alignment is required because the pump has no external coupling between pump and motor. All models can be mounted in any position. For mounting with discharge on the side or in any other position other than top discharge, please con­tact the factory. Modifications must be made to the standard internal venting arrangement and hydrau­lic thrust balance system.
Base cradles are offered on all models. Simply set the pump on a foundation strong enough to support its weight. There is no need to bolt down or grout in a Dynapump LE Series. All Dynapump LE Series mod­els are provided with a specially made base de­signed to mount on a standard ANSI base plate to facilitate inspection and repair.
Be sure that the suction and discharge piping is prop­erly aligned so that no strain is placed on the pump casing by out-of-line piping.
Page 4
2-2.3. Piping Data
Observe the standards of the Hydraulic Institute when sizing and making up suction and discharge piping. Follow these procedures:
It is extremely important to design and size the suction system to minimize pressure losses and to be sure that the pump will not be “starved” for fluid during operation. NPSH problems are a result of improper suction systems.
1. Remove burrs and sharp edges when making up joints.
2. When using flanged joints, be sure inside diam­eters match properly. When gasketing flanged joints, DO NOT cut flow hole smaller than flange opening.
3. Use pipe hangers or supports at necessary in­tervals.
4. Provide for pipe expansion when required by fluid temperature.
5. When welding joints, avoid possibility of welding shot entering the suction or discharge line, and thereby entering the pump. Do not weld pipe
while connected to pump.
6. When starting up a new system, it is recom­mended to place a temporary 3/16" mesh screen at or near suction port of pump to catch welding shot, scale or other foreign matter. Refer to Sec­tion 3-1, Page 9.
7. Do not spring piping when making up any con­nections.
8. Make suction piping as straight as possible, avoiding unnecessary elbows. Where necessary, use 45 degree or long-sweep 90 degree fittings.
9. Make suction piping short, direct, and never smaller in diameter than suction opening of pump. Suction piping should be equal to or larger than pump suction port, depending on pipe length.
10. Insure that all joints in suction piping are airtight.
11. When installing valves and other fittings, posi­tion them to avoid formation of air pockets.
12. Permanently mounted suction filters are not rec­ommended.
If suction pipe length is short, pipe diameter can be the same size as the pump suction port diameter. If suction piping is long, the size should be one or two sizes larger than pump suction port, depending on piping length. Use the largest pipe size practical on suction piping and keep piping short and free from elbows, tees or other sources of pressure drop.
If elbows, tees or valves must be used, locate them from 10 to 15 pipe diameters upstream from suc­tion. When reducing to pump suction port diameter, use eccentric reducers with eccentric side down to avoid air pockets.
When operating under conditions where pump prime can be lost during off cycles, a foot valve should be provided in the suction line to avoid the necessity of priming each time the pump is started. This valve should be of the flapper type rather than the multiple spring type and of ample size to avoid undue friction loss in the suction line.
When foot valves are used, or when there are other possibilities of fluid hammer, it is important to close the discharge valve before shutting down the pump.
When it is necessary to connect two or more pumps to the same suction line, provide gate valves so that any pump can be isolated from the line. Install gate valves with stems horizontal to avoid air pockets. Globe valves should be avoided, particularly where NPSH is critical.
If discharge pipe length is normal, pipe diameter can be the same size as the pump discharge port diameter. If discharge piping is of considerable length, use larger diameter pipe (one or two sizes larger).
If the pump is to discharge into a closed system or an elevated tank, place a gate valve or check valve in the discharge line close to the pump. The pump can then be opened for inspection without fluid loss or damage to the immediate area.
Page 5
RECOMMENDED Install properly sized pressure gauges in suction and discharge lines near the pump ports so that operation of the pump and system can be easily observed. Should cavi­tation, vapor binding, or unstable operation occur, widely fluctuating discharge pres­sures will be observed.
Such gauges provide a positive means of determin­ing actual system conditions and can be used to
great advantage in evaluating system problems.
2-3. Electrical
2-3.1. General
Except where indicated, all Dynapump LE Series are started with full line voltage. Refer to Paragraph 3-3, Page 9, for checking direction of rotation. Also see Wiring Diagram Figure 2-1, Page 7 for proper wiring connections.
WARNING The thermal cutout switch does not provide protection against fast heat build-up result­ing from locked rotor conditions, single phasing or heavy overloads. The current overload relay heaters in the magnetic starter must provide for this protection. The rating of the heaters should be high enough to avoid nuisance cut outs under running loads, but must not be oversized. Refer to Table 2-1, Page 7, for starting and running electrical characteristics. It is recom­mended that “quick trip” (Class 10) heat­ers be used because of the more rapid re­sponse time.
2-3.3. Starting Equipment
Motor starters (normally not supplied with Dynapump LE Series) should be sized to handle the load re­quired. Full Load HP, Full Load Amps and Start KVA Data is listed in Table 2-1, Page 7.
2-3.2. Thermal Cutouts
All Dynapump LE Series are fitted with a thermal cutout. The cutout is a heat-sensitive bimetallic switch mounted in intimate contact with the stator windings. The TCO wiring diagram is shown in Fig­ure 2-1, Page 7. Maximum holding coil currents is
3.1 AMPS for 115 volts.
WARNING Do not connect TCO in series with main power lead. Excessive heat build up in the winding area opens the normally closed thermal switch, which, in turn, opens the holding coil circuit, shutting off power to the pump. Be sure to connect the thermal cutout as required.
Thermal cutouts in Class H insulated motors are set to open at 356
o
F (180o C). If the motor cuts out because of TCO action, there will be a time delay before the motor can be restarted. The motor must be restarted manually.
DO NOT RESTART UNTIL YOU DETERMINE THE CAUSE OF THE OVERHEATING.
Heaters in the starters should be sized for the am­perage shown on the Dynapump LE Series name­plate. DO NOT size heaters in excess of 10% of full load amp rating. In order to provide complete protec­tion for Dynapump LE Series motors under all con­ditions, it is recommended that “quick trip” (Class
10) type heaters be used in the starters where avail­able. Standard heaters provide adequate protection for Dynapump LE Series motors under starting or normal running conditions, but require a greater length of time than “quick trip” type heaters to cut out if the motor is subject to locked rotor or overload conditions.
CASE I - 460 Volt, 3-Phase Dynapump LE Series (See Figure 2-1, Page 7).
Typical 3-phase across-the-line magnetic starter with start-stop push button station shown.
Thermo switch (thermal cutout inside Dynapump LE Series motor) is wired as shown in Figure 2-1, Page
7.
Be sure to size heaters properly. Motor data can be found on the pump nameplate.
Page 6
Figure 2-1. Dynapump LE Series 460-Volt, 3-Phase
2-3.4. Bearing Wear Monitor
The TRG METER is color coded for easy recogni­tion:
- Green = Normal operation.
- Yellow = Pump should be scheduled for maintenance.
- Red = Pump should be shut down and
removed for maintenance.
There is no requirement for resetting of the TRG af­ter replacement of worn components. Once the worn components are replaced and the pump is re­turned to service, the TRG meter will return to the Green position.
The TRG has been designed to accommodate a va­riety of output options and can be configured to match existing or future plant instrumentation without sig­nificant modification.
The Dynapump LE Series patented Teikoku Rotary Guardian (TRG) takes the mystery out of pump reli­ability by continuously monitoring the critical running clearances between the rotating and stationary com­ponents. The TRG is mounted on the electrical junc­tion box as standard.
The TRG meter operates on the principle of induced voltage. Electric coils are embedded in the stator windings and an electric current is produced with the rotation of the rotor assembly. When the rotor is perfectly centered in the stator between the coils the electric currents are balanced and no voltage is de­tected. When bearing wear occurs the rotor moves toward one coil and away from the other producing a low voltage that is indicated by the TRG meter. As this gap becomes larger the voltage increases. The TRG should be monitored frequently to determine the condition of the pump.
Figure 2-2. Dynapump LE Series TRG
Table 2-1. Dynapump LE Series Electrical Data
MOTOR INSUL VOLT PHASE HERTZ RPM FULL FULL FULL START STARTING LOCKED OPER
SIZE CLASS LOAD LOAD LOAD KVA AMPS ROTOR TEMP
AMPS KW HP CODE CODE
3111 H 460 3 60 3450 3.1 1.4 1.8 8.3 10.4 E T3A 3115 H 460 3 60 3450 5.5 2.5 3.3 15.4 19.4 E T3A 3211 H 460 3 60 3450 8.0 4.0 5.3 22.7 28.5 D T3A 3215 H 460 3 60 3450 14.5 7.5 10.0 41.3 51.8 D T3A 3311 H 460 3 60 3450 17.0 8.8 11.7 49.6 62.3 D T3A 3315 H 460 3 60 3450 24.0 12.4 16.6 76.1 95.5 E T3A
Page 7
Table 2-2. Trouble Shooting
Trouble
I. Failure to Deliver
Required Capacity
II. Insufficient Pressure
Cause
a. Pump not primed. b. Air leaks in suction piping. c. Motor not energized. d. Motor windings burnt out or
grounded.
e. Low suction head.
f. Discharge head too high.
g. Discharge valve closed or
partially opened. h. Impeller clogged. i. Wrong direction of rotation.
j. Damaged impeller.
a. Pump not primed. b. Air leaks in suction piping. c. Motor not energized. d. Motor windings burnt out or
grounded.
e. Low suction head.
f. Discharge valve open too wide.
g. Impeller clogged. h. Wrong direction of rotation. i. Damaged impeller.
Remedy
a. Re-prime pump in accordance with Paragraph 3-2. b. Locate leaks and eliminate. c. Check motor wiring. See Paragraph 2-3. d. Check electrical continuity of windings and if
negative response, stator assembly needs to be replaced.
e. Correct suction side of system to insure availability
of design NPSH.
f. Correct discharge side of system to insure proper
operating conditions.
g. Open discharge valve until rated discharge pressure
is obtained. h. Remove obstructions in the impeller. i . Reverse any two motor leads and check with phase
sequence meter. See Paragraph 3-3. j. Impeller must be repaired or replaced.
a. Re-prime pump in accordance with Paragraph 3-2. b. Locate leaks and eliminate. c. Check motor wiring. See Paragraph 2-3. d. Check electrical continuity of windings and if
negative response, stator assembly needs to be
replaced. e. Correct suction side of system to insure availability
of design NPSH. f. Close down discharge valve until rated discharge
pressure is obtained. g. Remove obstructions in the impeller. h. Reverse any two motor leads. i. Impeller must be repaired or replaced.
III. Pump Loses Prime After
Starting
IV. Pump Takes Too Much
Power
V. Pump Vibrates
VI. Motor Running Hot
a. Pump not properly primed at
starting. b. Air leaks in suction piping. c. Air or gas in fluid. d. Low suction head.
a. Shaft bent.
b. Rotating element binds.
c. Electrical short.
d. Wrong direction of rotation.
a. Foundation not sufficiently rigid.
b. Impeller partially clogged. c. Shaft bent.
d. Worn bearings. e. Rotating element rubbing stator
liner.
a. Motor operating at overload
condition. b. Pump is operating below
minimum flow. c. Pump is running dry.
a. Reprime pump in accordance with Paragraph 3-2.
b. Locate leaks and eliminate. c. Locate source of gas or air entrainment and correct. d. Correct suction side of system to insure availability
of design NPSH.
a. Replace rotor assembly or straighten shaft if bend is
not too great.
b. Replace bearings (See Paragraph 4-1) as a result
of excessive wear, or check for presence of foreign material in rotor chamber.
c. Check electrical continuity of all phases of the motor
winding and replace stator assembly if necessary.
d. Reverse any two motor leads.
a. Tighten all bolts on with the pump base and base
supporting structure. b. Remove obstructions in the impeller. c. Replace rotor assembly or straighten shaft if bend is
not too great. d. Replace bearings (See Paragraph 4-1). e. Replace bearings (See Paragraph 4-1) as a result
of excessive wear or check for presence of foreign
material in rotor chamber.
a. Make sure pump is operating at design point and
conditions specified when purchased. b. Increase the flow thru the pump.
c. Check suction line for obstructions and closed valves.
Page 8
SECTION 3. Operation
3-1. Procedure Before Initial Start
Before starting the pump for the first time, make sure suction and discharge piping are free of tools, nuts, bolts, or other foreign matter. Save time and money by checking before start-up.
RECOMMENDED Install a temporary 3/16" mesh screen near the suction port to trap scale and other for­eign particles. The screen can be installed for 24 hours of operation, but watch closely that the pump does not become starved for fluid because of a clogged screen. RE­MOVE SCREEN AFTER 24 HOURS OF RUN­NING.
3-2. Priming and Venting
The pump must be primed before operating. Prim­ing requires the filling of the pump casing and motor chamber with liquid.
When there is a positive suction head on the pump, priming can be accomplished by opening the valves in the suction and discharge line, and allowing the pump casing and motor chamber to fill. The Dynapump LE Series is centerline discharge and is self-venting when installed in the horizontal position.
3-3. Rotation Check
Centrifugal pump impellers must rotate in the proper direction to deliver rated head and capacity. The im­peller must rotate in the same direction as the arrow cast on the pump casing.
A. A hand-held direction of rotation indicator is
available from Teikoku USA Inc and the Chempump Division. This portable device can be used to confirm the rotation of any motor.
B. Use a phase sequence meter on the electri-
cal connections.
C. After the Dynapump LE is properly primed
and vented, open suction valve 100% and start the unit with the discharge valve 20% open. Note the discharge pressure at a pres­sure gauge, which should be installed be­tween the pump casing and discharge valve. Reverse any two of the three power leads and read the pressure gauge again. The higher pressure is the correct direction of rotation. It is recommended that the unit be run as little as possible with a closed dis­charge valve in order to prevent excessive overheating of the fluid circulating within the unit.
NOTE If a discharge valve is not available an al­ternate method is to use a flow meter and determine higher flow rate. Wrong direc­tion of rotation is indicated by a low dis­charge pressure or flow rate. At shut-off, head is about 2/3 of the head produced by correct rotation. Continued operation in re­verse can result in damage to the pump. If reverse rotation has occurred, it is wise to shut down the unit and tighten the impeller bolt before restarting.
The correct direction of rotation can be checked as follows:
Wire Dynapump LE Series motor for correct voltage.
1. With main power leads connected, check direc­tion of impeller rotation. If the unit is not installed in the system, rotation can be observed by “bump­ing” the motor and looking into the suction flange. NEVER LOOK INTO THE DISCHARGE FLANGE. If direction of impeller rotation is incorrect, change two power leads.
2. If the pump is installed and primed, the direction of rotation can be checked by the following meth­ods:
Once you have determined correct rotation, tag cor­rectly connected main power leads, in accordance with motor lead markings.
3-4. Starting Procedure
After priming, venting, and checking the direction of rotation, put the pump in operation as follows:
1. Fully open the valve in the suction line.
2. Set the valve in the discharge line to 20% open.
3. Start the pump. Pump should operate with very low noise and vibrations. Excessive or abnor-
Page 9
mal noise or vibrations should be corrected im­mediately.
4. When the pump is running at full speed, slowly open the valve in the discharge line to the de­sired setting.
5. Once pump is operational, check the reading of the TRG meter. If the meter is in the green, pump is operating normally. If the meter is in the yellow or red, stop the pump and check for possible causes of the incorrect reading. Record initial reading for comparison to future readings.
corded, then the color coding system shown in sec­tion 2-3.4, Page 7 may be used to determine bearing changing intervals. If the TRGi was recorded, then the following formulas can be used. If the reading exceeds TRGi +0.3, then the pump should be sched­uled for maintenance. If the reading exceeds TRGi +0.4, then the pump should be shut down and re­moved for maintenance.
Discharge pressure should be checked frequently during operation. Pressure should be stable in a non-variable closed loop although the discharge pressure gauge needle may show small fluctuations.
CAUTION The pump should not be allowed to run for more than one minute with the discharge valve fully closed.
NOTES:
1. If the suction and discharge lines are completely filled with system fluid and adequate suction head is available, the pump can be started without clos­ing the discharge valve. During any start up se­quence, caution must be exercised not to exceed full load ampere rating indicated on the name­plate.
2. If the unit has not been run for a period of two weeks or more, the following inspections should precede its operation:
A . Check terminal box for moisture.
B. Upon starting, check for excessive noise, vi-
bration, erratic speeds or excessive amp draw.
In some cases, the fluid supply may contain an ex­cessive amount of air or gas, which will tend to sepa­rate from the fluid and remain in the passages of the pump. This results in the pump losing its prime and becoming air bound with a marked reduction in ca­pacity. The discharge pressure gauge will show large
fluctuations if this occurs.
3-6. Shutdown Procedure
Shutdown as follows:
1. Close the valve in the discharge line.
CAUTION The pump should not be allowed to run for more than one minute with the discharge valve fully closed.
2. Stop the pump (De-energize the motor).
3. Close suction valves if pump is to be removed from service.
CAUTION If the pump appears to be air bound as a result of the unit not being properly primed, do not continue operation. Locate and cor­rect the conditions that prevent proper prim­ing before attempting to start the unit.
3-5. Operation Details
TRG meter should be checked periodically during operation. If the initial reading (TRGi) was not re-
CAUTION If the pump is to be shut down for a long period of time or if there is danger of freez­ing, after stopping the pump, shut all suc­tion and discharge valves, and drain the en­tire pump and connected piping.
NOTE To assist in determining remedies for vari­ous problems, see Table 2-2, Page 8 Trouble Shooting.
Page 10
SECTION 4. Maintenance
4-1. Recommended tools for Disassembly Reassembly and Inspection.
Size Description
17 mm Socket wrench for pump cas-
ing, rear bearing housing bolts, rear shaft sleeve re­taining bolt, and impeller retaining bolt M10.
19 mm Socket wrench for impeller
retaining bolt M12.
3 mm Hex wrench for bearing re-
taining screws.
5 mm Hex wrench for front bearing
housing retaining bolts.
.200" Travel Dial Indicator to
measure endplay.
Dial calipers To measure bearing wear.
Feeler Gauges To measure “g” gap.
7. Measure and record the “g” gap before further disassembly. See Figure 4-2, on Page 13.
8. To remove impeller, extend tabs of lock washer and remove impeller bolt. Be careful of small parts that can be lost.
9. Remove socket head cap screws and remove Front Bearing Housing from Stator Assembly. Exercise care while removing this housing be­cause of liquids which may be contained in the stator assembly.
10. Remove Rear Bearing Housing Bolts and remove Rear Bearing Housing from Stator Assembly. Exercise caution while removing this housing because of liquids which may be contained in the Stator Assembly.
11. Remove Rotor Assembly. Place on a clean cloth to avoid damage. During the removal of the rotor take care in handling the rotor to prevent dam­age to the rotor or stator because the rotor will drop once the armature clears the stator assem­bly and the rotor shaft may hit the stator liner if not properly supported.
Torque Wrench To measure bolt tightness.
4-1.1. Disassembly
1. Fully close valves in discharge, suction and util­ity piping.
2. Disconnect the power cables from the connec­tion box prior to disassembly.
WARNING SAFETY HAZARD TO PERSONNEL WILL EXIST IF THIS STEP IS NOT FOLLOWED.
3. Remove drain plug or open drain valve to drain liquid in the pump.
4. Since piping loads may exist, insert bracing un­der casing.
5. Remove casing bolts. Be careful not to spill any remaining fluid that may be trapped in casing.
6. Remove anchor bolting in order to slide pump out of casing. Casing will remain attached to pip­ing.
12. Remove front shaft sleeve and front thrust collar.
13. To remove rear Shaft Sleeve and thrust collar, bend tabs up on lock washer and unscrew bolt.
This bolt has left hand threads.
14. To remove bearing, remove set screw and slide out bearing.
4-2. Inspection
4-2.1. Bearings
Check the following points:
A. Thrust face for scratches and chips. Refer
to Table 4-1(L), Page 14 for excess wear on thrust surface. (Check this dimension after bearing has been removed.)
B. Wear inside of bearing bore. Refer to Table
4-1 (A – B), on Page 14.
4-2.2. Shaft Sleeves and Thrust Collars
The rotor assembly shaft sleeves and thrust surfaces should also be visually inspected at the bearing con-
Page 11
tact area for general appearance and uniform wear. Excessive undercutting, pitting, or scoring is cause for replacement.
Check the following points:
A. Corrosion
B. Contact marks and wear.
3. Slide on Rear Thrust Collar, verifying that the Thrust Collar is installed correctly. Slide on the Rear Shaft Sleeve insuring that the Shaft Sleeve is tight against the Thrust Collar and is engaged in the anti-rotational key or pin. Install the Flat Washer, Lock Washer, and Lock Bolt insuring that the Lock Washer tab is engaged in the slot in the Shaft Sleeve. Torque Lock Bolt per Table 4-4, Page 14. This bolt has left hand threads.
4-2.3. Rotor Assembly Inspection
The complete rotor assembly should be visually in­spected for cracks, breaks, pitting, or corrosion which might destroy the effectiveness of the hermetically
sealed rotor end covers and sleeve.
4-2.4. Stator Assembly Inspection
The complete stator assembly should be visually in­spected for cracks, breaks, pitting, or corrosion of the stator liner which may destroy the effectiveness of the barrier. Inspect the inside of the electrical junction
box for corrosion and moisture.
4-2.5. General Inspection
1. Inspect the impeller bolt threads on the rotor shaft to ensure they are not damaged. LE Series Dynapumps have right hand threads.
2. Be sure that all mating faces are free of nicks and burrs so that they will have a smooth face ensuring a good seal. Clean off any trace of old gasket material.
3. Make sure all parts are clean. Inaccessible area may be cleaned with a small brush or pointed tool.
4. Slide on Front Thrust Collar, verifying that the Thrust Collar is installed correctly. Slide on the Front Shaft Sleeve insuring that the Shaft Sleeve is tight against the Thrust Collar and is engaged in the anti-rotational key or pin. Slide assembled Rotor into Stator with rear end of Rotor extending out of the Stator.
5. Install the Rear Stator Gasket. Slide the Rear Bearing Housing onto the Rotor and slide the Rear Bearing Housing and Rotor into the Stator. Take care to tighten bolting evenly. Torque Bolts per Table 4-5, Page 14.
6. Slide Front Bearing Housing onto Rotor and into Stator. Take care to tighten bolting evenly. Insure that the Shaft Sleeve is tight against the Thrust Collar and is engaged in the anti-rotational key or pin.
7. Slide Adjusting Washers onto Rotor Shaft. Slide Impeller onto Rotor Shaft, install the Flat Washer, Lock Washer and Lock Bolt insuring that the Lock Washer tab is engaged in the Impeller key slot. Check Rotor Assembly endplay. End play should be within the range indicated in Table 4-2, Page
7. If the rotor assembly does not fall within this range, discard the old bearings and change to new bearings.
4. The impeller face should be inspected for wear. If excessive grooving or scoring of the wear rings is evident, the impeller must be repaired or replaced.
4-3. Reassembly
1. Clean and dry all parts. Reassemble in the re­verse manner of disassembly.
2. Insert bearing with flat washer into front and rear bearing housings. Position flat washer side of bearing in line with set screw hole. While hold­ing bearing down tighten set screw.
NOTE The front bearing has only spiral grooves, the rear bearing has spiral and straight grooves.
8. Adjusting the “g-gap” using Figure 4-2, Page 13 and Table 4-3, Page 14. Pull impeller forward and with adjusting washers, installed behind im­peller in place, Gap “g” should be within indi­cated ranges using Table 4-3, Page 14. If gap is not within specified range, use adjusting wash­ers behind impeller to make adjustments.
9. Make sure impeller bolt is tight (use Table 4-4, Page 14. for correct torque values) and lock washer locking tabs are bent over.
10. Assembled pump should rotate freely by hand with no metal to metal contact.
11. Install Pump Case Gasket. Slide pump back into casing and tighten all bolts. Add new Teflon tape to plugs where needed. Torque Bolts per Table 4-5, Page 14.
Page 12
Figure 4-1. Bearing Wear
Figure 4-2. “g” Gap
Page 13
TABLE 4-1. Bearing Wear Limit
Note: 15A = Front Bearing, and 15B = Rear Bearing
Motor Frame Number * A-B L
3111, 3115(15B) 0.3mm (0.012 in.) 44.2mm (1.746 in.)
3115(15A), 3211, 3215(15B) 0.4mm (0.016 in.) 49.2mm (1.937 in.)
3215(15A)3311, 3315(15B) 0.4mm (0.016 in.) 59.2mm (2.331 in.)
3315(15A) 0.4mm (0.016 in.) 69.2mm (2.724 in.)
TABLE 4-2. Playing Gap of Rotor (Axial End Play)
Motor Frame Number * New Bearing
3111 0.7~1.9mm (0.028~0.075 in.) 3115, 3211 0.7~2.1mm (0.028~0.083 in.) 3215, 3311 0.7~2.1mm (0.028~0.083 in.)
3315 0.9~2.5mm (0.035~0.098 in.)
TABLE 4-3. Adjusting Value of Gap “g”
Note: “g” Gap has a +/-0.1mm adjustment range or +/-0.004 in. tolerance
Motor Frame Number * Impeller Size “g” Adjusted
3111 SG, SF 4mm (0.158 in.)
3115, 3211
3215, 3311
SG, SF, TG 4mm (0.158 in.)
TF 4.2mm (0.165 in.)
SG, SF, TG 4mm (0.158 in.)
TF 4.2mm (0.165 in.)
3315 TF 4.5mm (0.177 in.)
TABLE 4-4. Tightening Torque for Impeller and Rotor Bolts
Note: Rotor Bolts have left hand threads.
Motor Size Bolt Type Bolt Size Value of Torque
3111 Impeller M8 8 3115, 3211 Impeller M10 13 3215, 3311 Impeller M12 22
3315 Impeller M 14 34 3111, 3115 Rotor M8 8 3211, 3215 Rotor M10 13 3311, 3315 Rotor M12 34
TABLE 4-5. Tightening Torque for Pump Casing and Rear Bearing Housing Bolts
Note: Number follows M represents nominal threads OD in mm.
Motor Size Bolt Type Bolt
3111, 3115, 3211,
& 3215(SG, SF)
3215(TG, TF),
3311, & 3315
All Rear Bearing
Pump Casing M10 26
Pump Casing M12 44
Housing
(ft. lb .)
Value of Torque
Size
M10 26
(ft. lb.)
Page 14
APPENDIX
TROUBLE ANALYSIS SHEET
CUSTOMER: ____________________________________ DATE: _______________________________
ADDRESS: ____________________________________ PHONE: ______________________________
____________________________________ FAX: ________________________________
CONTACT: _____________________________________ S/N #: ______________________________
E-MAIL: _____________________________________
Proper analysis of the trouble you have been experiencing requires an accurate description
of operating conditions and the system in which the pump is installed.
DATE INSTALLED:________________ DATE REMOVED:________________ HOURS USED: _______________
1.) LIQUID OR SOLUTION HANDLED (Include impurities or % if mixture):____________________________
___________________________________________________________________________________________
IS DISSOLVED GAS PRESENT?_________________________________________________________________
ARE SOLIDS IN SUSPENSION PRESENT?_________________________________________________________
IF SO, STATE NATURE:________________________________________________________________________
2.) ACTUAL OPERATING CONDITIONS: TRANSFER CIRCULATION
FLOW: _____________________________________GPM SUCTION PRESSURE: _____________________PSIG
DISCHARGE PRESSURE: _______________________PSIG DIFFERENTIAL: ________________________PSI/FT
PUMPING TEMPERATURE: _______________________F SP. GR. @ P.T.: _________________________
VISCOSITY AT: VAPOR PRESSURE AT:
PUMPING TEMPERATURE: _____________________CPS PUMPING TEMPERATURE:___________PSIA/MMHG
AMBIENT: __________________________________CPS AMBIENT: ________________________PSIA/MMHG
3.) PLEASE SEND A SKETCH OF YOUR SYSTEM. GIVE A BRIEF DESCRIPTION, INCLUDING A ROUGH FLOW SHEET. INDICATE WHAT CHEMICAL OR PHYSICAL ACTION OCCURS BEFORE THE PUMP. SHOW COOLING OR HEATING SERVICES ON LINES DIRECTLY AFFECTING THE PUMP. SHOW WHAT CONTROLS ARE USED AND WHAT THEY OPERATE. IF MORE THAN ONE PUMP OPERATES ON A COMMON SUCTION, SHOW HOW THEY ARE BALANCED.
YOUR ATTENTION TO THIS REPORT IS GREATLY APPRECIATED. UPON RECEIPT AT CHEMPUMP, WE WILL
EVALUATE THE FACTS SHOWN AND RETURN OUR RECOMMENDATIONS TO YOU.
RETURN COMPLETED FORM TO:
CHEMPUMP FACTORY SERVICE CENTER 959 MEARNS ROAD, WARMINSTER, PA 18974 PHONE: (215) 343-6000 FAX: (267) 486-1037
Page A-1
DECONTAMINATION CERTIFICATION
AND FLUSHING PROCEDURE
CUSTOMER ______________________________________ DATE: _______________________________
ADDRESS: ____________________________________ PHONE: ______________________________
____________________________________ FAX: ________________________________
CONTACT: ____________________________________ RMA #: ______________________________
Please complete the items below. Providing this information will allow us to work as quickly and safely as possible.
PUMP MODEL: ___________________________________ SERIAL NUMBER: _______________________
PART NUMBER:___________________________________ DATE INSTALLED:_______________________
DATE PURCHASED: _______________________________ INDOOR / OUTDOOR:____________________
REASON FOR RETURN: WARRANTY REQUEST FACTORY SERVICE
FAILURE INFORMATION:
Failure To Deliver Required Capacity Vibration Motor Burnout
Loses Prime After Starting Bearing Failure Other: ______________________
Axial Wear Due To Thrust Insufficient Pressure
BRIEF DESCRIPTION OF PUMP FAILURE: ____________________________________________________________ ____________________________________________________________________________________________
____________________________________________________________________________________________
DECONTAMINATION INFORMATION
All pumps/parts must be completely decontaminated and all information in this section must be completed prior to shipment to our factory or service center. Shipments received without this documentation will not be accepted and will be returned to the point of shipment.
CHECK ONE OF THE FOLLOWING:
The pump has been flushed by following steps A through Both the complete pump and the stator assembly have A3 of the Chempump Flushing Procedure on page 2 of been flushed by following steps A through B3 of the this form. No liner rupture is suspected. Chempump Flushing Procedure on page 2 of this form.
The motor must be rewound.
FLUID PUMPED: __________________________ WHAT FLUID DID YOU FLUSH WITH: ______________
Attach completed material safety data sheets (MSDS) for these fluids. If either fluid is proprietary, please attach a description of any characteristics that will assist Chempump in safe handling. Without detailed and complete information on the pumped fluid, we will not be able to process your order.
PROTECTION EQUIPMENT RECOMMENDED FOR SAFE HANDLING OF THE PROCESS FLUID:
____________
_____________________________________________________________________________
DECONTAMINATION CERTIFIED BY: _____________________________ DATE:_______________________
TITLE: ______________________________________________________ PHONE: _____________________
RETURN COMPLETED FORM AND PUMP/PART TO:
CHEMPUMP FACTORY SERVICE CENTER 959 MEARNS ROAD WARMINSTER, PA 18974 PHONE: (215) 343-6000 FAX: (267) 486-1037
CHEMPUMP MIDWEST SERVICE CENTER STATE ROUTE 2 BELMONT, WV 26134 PHONE: (304) 684-2459 FAX: (304) 684-7593
Page A-2
TEXAS PROCESS EQUIPMENT 5880 BINGLE ROAD HOUSTON, TX 77092 PHONE: (713) 460-5555 FAX: (713) 460-4807
DECONTAMINATION CERTIFICATION
AND FLUSHING PROCEDURE
FLUSHING PROCEDURES FOR CHEMPUMP PRODUCTS
THE FOLLOWING FLUSHING PROCEDURES ARE REQUIRED TO ALLOW FOR MAXIMUM REMOVAL OF PROCESS FLUIDS.
A. COMPLETE PUMP
A1 ) WITH THE SUCTION FLANGE DOWN, INTRODUCE AN APPROPRIATE NEUTRALIZING FLUID
THROUGH THE DISCHARGE FLANGE. FLUSH THE PUMP IN THIS MANNER FOR A SUFFICIENT TIME TO ALLOW FOR THE REMOVAL OF ALL PROCESS FLUID.
A2) AGAIN, WITH THE SUCTION FLANGE DOWN, REMOVE THE CIRCULATION LINE (AND FITTING IF
NECESSARY) AND INTRODUCE AN APPROPRIATE NEUTRALIZING FLUID TO THE REAR OF THE PUMP. FLUSH THE PUMP IN THIS MANNER FOR A SUFFICIENT TIME TO ALLOW FOR THE REMOVAL OF ALL PROCESS FLUID. ALSO FLUSH THE CIRCULATION LINE AND/OR HEAT EXCHANGER TUBING, AS REQUIRED.
A3) AFTER FLUSHING AS SPECIFIED ABOVE, REMOVE AS MUCH OF THE NEUTRALIZING FLUID AS
POSSIBLE USING COMPRESSED AIR OR INERT GAS.
B. G and J-SERIES STATOR ASSEMBLY (if equipped with a relief valve ): IF A STATOR LINER RUPTURE IS
SUSPECTED, FOLLOW THIS SECTION TO FLUSH THE STATOR CAVITY. CAUTION: IF THIS STEP IS
FOLLOWED, THE MOTOR MUST BE REWOUND.
B1) REMOVE THE RELIEF VALVE. INSERT A SCREWDRIVER INTO THE RELIEF VALVE ADAPTER
AND PRY THE LISK FILTER TO ONE SIDE. REMOVE THE CONNECTION BOX FROM THE LEAD NIPPLE AND CHIP AWAY THE POTTING COMPOUND FROM THE LEAD NIPPLE.
B2) POSITION THE STATOR ASSEMBLY WITH THE LEAD NIPPLE DOWN AND INTRODUCE AN
APPROPRIATE NEUTRALIZING FLUID TO THE RELIEF VALVE ADAPTER. THE FLUID WILL EXIT THROUGH THE LEAD NIPPLE. FLUSH THE STATOR CAVITY IN THIS MANNER FOR A SUFFI­CIENT TIME TO ALLOW FOR THE REMOVAL OF ALL PROCESS FLUID AND STATOR OIL.
B3) REMOVE AS MUCH OF THE NEUTRALIZING FLUID AS POSSIBLE BY PURGING THE STATOR
CAVITY WITH COMPRESSED AIR OR INERT GAS FOR 3 - 5 MINUTES.
C. NC and LE-SERIES STATOR ASSEMBLY (no relief valve): IF A STATOR LINER RUPTURE IS
SUSPECTED, FOLLOW THIS SECTION TO FLUSH THE STATOR CAVITY. CAUTION: IF THIS STEP IS
FOLLOWED, THE MOTOR MUST BE REWOUND.
C1) DRILL A HOLE THROUGH BASE CRADLE MOUNTING HOLE LOCATED IN REAR END BELL, DRILL
THIS HOLE JUST DEEP ENOUGH TO BREAK THROUGH END BELL. DRILL A SECOND HOLE THROUGH STATOR LINER ON OPPOSITE END OF STATOR.
C2) POSITION THE STATOR ASSEMBLY WITH REAR END BELL UP AND INTRODUCE AN APPROPRI-
ATE NEUTRALIZING FLUID THROUGH DRILLED HOLE IN REAR END BELL. THE FLUID WILL EXIT THROUGH THE DRILLED HOLE ON OPPOSITE SIDE. FLUSH THE STATOR CAVITY FOR A SUFFICIENT TIME TO ALLOW FOR THE REMOVAL OF ALL PROCESS FLUID.
C3) REMOVE AS MUCH OF THE NEUTRALIZING FLUID AS POSSIBLE BY PURGING THE STATOR
CAVITY WITH COMPRESSED AIR OR INERT GAS FOR 3 - 5 MINUTES.
Page A-3
A-4
A-5
A-6
A-7
Teikoku USA: 7010 Empire Central Drive, Houston, TX 77040-3214 Phone: (713) 983-9901 Fax: (713) 983-9919 Website: www.teikoku-usa.com E-mail: info@teikoku-usa.com Chempump: 959 Mearns Road, Warminster, PA 18974 Phone: (215) 343-6000 Fax: (267) 486-1037 Website: www.chempump.com E-mail: chempump@chempump.com Midwest Service Center: State Route 2 North, Belmont, WV 26134 Phone: (304) 684-2459 Fax: (304) 684-7593
Loading...