TECVALCO CWT SERIES Operator's Manual

COLD WEATHER
CWT INDIRECT HEATING BOILER
OPERATOR MANUAL | EVAPORATOR VERSION | 2016
Boiling Point of Water at various Pressures ­Gauge Pressure
(Vacuum and Positive Pressure)
20
17.5
15
12.5
10
7.5
5
2.5
0
-5
-10
-12.5
-15
-17.5
-20
-22.5
Steam Pressure (positive in PSI -negative in INHG)
-25 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280
Boiling Point of Water Temperature Deg F
Low Vacuum Range (Possible Leak)
Strong Vacuum (Healthy Unit)
To use this chart correlate the steam temperature gauge vs. the vacuum gauge reading.
For service scan the QR code, or call
(780) 875-2530
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
= Do not try to light any appliance. = Do not touch any electrical switch; do not use any phone in your building. = Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s
instructions. = If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
Page 2
PN :: HEA -EVA P-MA NUAL-016 | 20170316
CWT (Cold Weather Technologies) is an indirect-heater product line of Tecvalco Ltd. Niagara Falls, Ontario CANADA Toll Free: 1 (866) 317-0131 | www.tecvalco.com
MODEL NUMBER: ____________________________________________
SERIAL NUMBER: _____________________________________________
COLD W E ATHER
IMPORTANT NOTES:
1) The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or
CAN/CSA B149.1, Natural Gas and Propane Installation Code.
2) Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fire Boilers, ANSI/ASME CSD-1.
3) Placement of the C WT DLH unit should be such that there are no combustibles or any combustible construction within three feet (3’) of boiler, vent stack, and steam piping. Boiler unit must not be installed on combustible floors.
4) The equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, and applicable State Regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
5) The heater and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi (3.5 kPa). The heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi (3.5 kPa).
6) The heater shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service.
7) Provisions for combustion and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Clause 8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the local building codes.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
8) This heater is not connected / serviced as a common venting system.
9) Vent clearances will be for the Authority having Jurisdiction to determine the correct dimensions for their site clearances.
10) ANSI Z21.13/CSA 4.9 requires a sediment trap to be installed upstream of the fuel train. End users will need to make accommodation for a sediment trap in your piping upstream of fuel train.
11) Manual main shutoff valve location: The manual main shutoff valve is located before the Fisher HSR regulator on the fuel train.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
All wiring indicated within this manual shall be done in accordance with the NEC “National Electrical Code” for US applications.
Verify proper operation after servicing.
This manual and the instructions outlined within apply to all CWT Evaporator Models ranging from DLH-70 to DLH-4620
Page 3
FOREWORD
Foreword
Thank you for purchasing a Cold Weather Technologies (CWT) Natural Gas Indirect Heating Boiler. The following manual has been simplified to give both technical and non-technical owners and operators a detailed and thorough understanding of CWT Natural Gas Indirect Heating Boiler operation. Detailed installation diagrams and pictures can also be found inside this manual. These diagrams will serve you well as a reference for the unit and its materials.
Please note: it is essential that all wiring and piping be installed in accordance with this manual
The boiler is designed to operate on natural gas. However, please ensure that the fuel gas used in your application is the same gas that is specified on the heater model and rating plate.
Some components in the Instrumentation might have been changed or replaced due to market availability at the time when this manual was prepared. However, a changed component does not affect the overall capability of the CWT Natural Gas Indirect Heater. With proper care and regular maintenance, the heater should provide years of trouble–free service. Please take a few moments and read through the manual carefully. Keep the manual in a safe place where it can be easily located if needed.
We welcome any suggestions from customers to help improve this product line, please feel free to call Tecvalco.
The CWT boiler and its components are designed, fabricated, tested and inspected in accordance to the laws, codes, statutes and regulations for use in the Province of Alberta, Canada. The end user is responsible for ensuring that
CWT complies with all Federal, Municipal, Provincial, State and Local laws, Codes, Statutes and Regulations prior to installation of the unit, and application of permits, licenses, certificates and authorizations thereof.
Page 4
Warning: This manual must be read in its entirety before installation of this product. Installation and commissioning must be performed by a qualified technician and adhere to the safety standards. Failure to do so will result in personnel injury or property damage
PN :: HEA -EVA P-MA NUAL-016 | 20170316
TABLE OF CONTENTS
Table of Contents
Installation, operating and service manual SECTION A
Quality control documentation SECTION B
CAD drawings SECTION C
Material Safety Data Sheets SECTION D
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 5
SECTION A CONTENTS
(A) Installation, operating and service manual
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
2. Site preparation, delivery and installation . . . . . . . . . Page 10
2.1 Prior to receiving the boiler . . . . . . . . . . . . . . . . Page 10
2.2 Upon receiving the boiler . . . . . . . . . . . . . . . . Page 11
3. Installation procedures . . . . . . . . . . . . . . . . . . . Page 12
4. Components and controls overview . . . . . . . . . . . . . Page 15
4.1 Evaporator section . . . . . . . . . . . . . . . . . . . Page 15
4.1.1 Swordfish burners (burner manifold or burner tray) . . . . Page 15
4.1.2 Pilot and thermopile assembly . . . . . . . . . . . . . . Page 16
4.1.3 The fintube assembly (primary heat exchanger) . . . . . . Page 17
4.1.4 The control box . . . . . . . . . . . . . . . . . . . . . Page 18
4.1.5 Wiring diagrams . . . . . . . . . . . . . . . . . . . . Page 21
4.1.6 Flame or flash back arrestors . . . . . . . . . . . . . . Page 27
4.1.7 Robertshaw gas valve . . . . . . . . . . . . . . . . . . Page 28
4.1.8 High temperature ESD switch . . . . . . . . . . . . . . . Page 29
4.1.9 Discharge temperature . . . . . . . . . . . . . . . . . Page 30
4.1.10 Ignitor box and hand-held sparker . . . . . . . . . . . . Page 31
4.1.11 The high-pressure switch and shutdown . . . . . . . . . . Page 32
4.1.12 Temperature control (line temperature control) . . . . . . . Page 33
4.1.13 Burst disk and burst disk holder . . . . . . . . . . . . . Page 36
4.1.14 Fisher HSR regulator . . . . . . . . . . . . . . . . . . . Page 37
4.1.15 Pressure gauge WIC (inches of water column) . . . . . . . Page 38
4.1.16 Fisher 289H relief valve . . . . . . . . . . . . . . . . . Page 38
4.1.17 Fuel train drawing . . . . . . . . . . . . . . . . . . . . Page 39
4.1.18 Pressure vacuum gauge . . . . . . . . . . . . . . . . . Page 41
4.1.19 High-pressure coil gauge . . . . . . . . . . . . . . . . Page 42
4.1.20 Liquid level gauge . . . . . . . . . . . . . . . . . . . . Page 43
4.1.21 Exhaust vent . . . . . . . . . . . . . . . . . . . . . . Page 44
4.2 Condenser section (heat exchanger) . . . . . . . . . . . Page 45
4.2.1 The heat exchanger can . . . . . . . . . . . . . . . . . Page 46
4.2.2 The high-pressure process coil . . . . . . . . . . . . . . Page 47
5. Start-up procedure . . . . . . . . . . . . . . . . . . . . . . Page 49
Page 6
6. Typical operation . . . . . . . . . . . . . . . . . . . . . . . Page 50
6.1 Recommended control settings . . . . . . . . . . . . . . Page 51
6.2 Tuning the CWT boiler . . . . . . . . . . . . . . . . . . Page 52
6.3 Cycles . . . . . . . . . . . . . . . . . . . . . . . . . Page 52
PN :: HEA -EVA P-MA NUAL-016 | 20170316
7. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . Page 54
7.1 Maintenance schedule . . . . . . . . . . . . . . . . . . Page 54
7.2 Cleaning the flame arrestor . . . . . . . . . . . . . . . Page 55
7.3 Swordfish burner clean up . . . . . . . . . . . . . . . . Page 55
7.4 Inspecting and cleaning the fin tubes . . . . . . . . . . . Page 54
7.5 Glycol sample procedure . . . . . . . . . . . . . . . . Page 57
7.6 Testing the thermopiles . . . . . . . . . . . . . . . . . Page 58
7.7 Procedure for testing high-pressure shut down . . . . . . . Page 59
7.8 Procedure to find possible leaks . . . . . . . . . . . . . . Page 60
7.9 Pulling vacuum . . . . . . . . . . . . . . . . . . . . . Page 60
7.10 Replacing damaged burst disk . . . . . . . . . . . . . . Page 61
7.11 Drawing glycol into the system . . . . . . . . . . . . . . Page 62
7.12 Recommended glycol volumes . . . . . . . . . . . . . . Page 62
7.13 Glycol characteristics . . . . . . . . . . . . . . . . . . Page 62
7.14 Gas bundle removal . . . . . . . . . . . . . . . . . . . Page 63
7.15 Boiler checklist . . . . . . . . . . . . . . . . . . . . . Page 64
8. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . Page 66
8.1 Heater inspection checklist usage . . . . . . . . . . . . . Page 66
8.2 Common problems and possible solutions . . . . . . . . Page 67
8.3 Potential zero-flow application . . . . . . . . . . . . . . Page 69
SECTION A CONTENTS
9. Optional equipment and accessories . . . . . . . . . . . . Page 70
9.1 High temperature shut down . . . . . . . . . . . . . . . Page 70
9.2 High temperature shut down installation drawing . . . . . Page 71
10. Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 73
11. Spare parts list . . . . . . . . . . . . . . . . . . . . . . . . Page 77
12. Equipment warranty - repair and return procedure . . . . . Page 80
Appendix A - CWT 140 Evaporator Packing List . . . . . . . . . . . . Page 82
Appendix B - CWT 315 Evaporator Packing List . . . . . . . . . . . . Page 83
Appendix C - CWT 385 Evaporator Packing List . . . . . . . . . . . . Page 84
Appendix D - CWT 770 Evaporator Packing List. . . . . . . . . . . . Page 85
Appendix E - CWT 140 Exhaust Stack Drawing . . . . . . . . . . . . Page 86
Appendix F - CWT 315 Exhaust Stack Drawing . . . . . . . . . . . . Page 87
Appendix G - CWT 385 Exhaust Stack Drawing. . . . . . . . . . . . Page 88
Appendix H - CWT 770 Exhaust Stack Drawing . . . . . . . . . . . . Page 89
Appendix I - DLH 140 Burner Assembly and Cross-section drawings Page 90 Appendix J - DLH 315 Burner Assembly and Cross-section drawings Page 92 Appendix K - DLH 385 Burner Assembly and Cross-section drawings Page 94 Appendix L - DLH 770 Burner Assembly and Cross-section drawings Page 96
Appendix M - CWT 140 Fuel Gas Train . . . . . . . . . . . . . . . Page 98
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 7
INTRODUCTION
1. Introduction
Cold Weather Technologies (CWT), a product line of Tecvalco Ltd., has developed the Heat Driven Loop (HDL) technology for a variety of applications for the purpose of heating process fluids and gases in the oil and gas industries. Conventional line heaters utilize heat transfer from a natural draft flame arrested burner system immersed in a glycol bath. The CWT utilizes the energy released when steam changes from a vapor to a condensed state (Known as the “Latent Heat of Vaporization” shown in figure 1.1). The HDL operates with high thermal efficiency without any moving mechanical components or external power.
The HDL is comprised of three main components, the low-pressure evaporator, the condenser (heat ex­changer) and the high pressure coil. The unit is collectively known as the CWT Natural Gas Indirect Heating Boiler. In the evaporator, the mixture of water and glycol is heated to a point at which the water is separated from the glycol, creating steam. In the heat exchanger, the steam produced from the evaporator condenses on the process coils and the energy from the condensing steam is then transferred to the gas in the coils. This separation of components has two advantages. Firstly, the evaporator can be utilized for multiple coil/heat exchanger combinations, and multiple evaporators may be attached to a heat exchanger for large boilers. Secondly, because the medium being heated is physically isolated from the combustion process, long term maintenance and safety issues are effectively controlled.
Typically a vacuum is drawn on the boiler prior to shipment, removing all the excess air from the evapora­tor and heat exchanger. The vacuum is important for two main reasons. First, under vacuum the water will begin to boil at a temperature as low as 45°C/113ºF, allowing for fast heat transfer to the heat exchanger. Second, the system will have no air in it reducing corrosion and eliminating the need to “Top Up” the glycol volume during operation.
As the gas passes through the process coil the flow will accept the energy from the steam in the condenser. With increased flow more energy will be accepted and the internal pressure of the heating system will be decreased or maintained in a vacuum state. At low flow conditions the heating system will increase in pressure up to a point of which either flow is increased through the station or a safety shut down/set point is reached on the CWT boiler.
If your system is running in or near a positive state please correlate the pressure against the unit discharge temperature graph at the front of this manual. Your heating system should always return to a vacuum state when cooled down.
Page 8
PN :: HEA -EVA P-MA NUAL-016 | 20170316
125 / 257
Temperature (C/F)
100 / 212
75 / 167
50 / 122
LATENT HEAT
Heat required to change
1lb (500g) of ice at -50 degrees C (-58 degrees F) to 1lb (500g) of steam at 104 degrees C (219 degrees F) at 1 atmopsheric condition
GAS
Phase changes from liquid to vapour with no change in temperature [Latent Heat of Vapourization]
Temperature rises from 0 to 100 (Celsius)
25 / 77
0 / 32
Phase changes from solid to liquid with no change in temperature [Latent Heat of Fusion}
Temperature rises from -50 to 0 (Celsius)
-25 / -13
0 / 0
-50 / -58
Energy (Joules/BTU)
21,101 / 200
42,202 / 400
63,303 / 600
84,404 / 800
105,505 / 1,000
The latent heat exchanged from the steam as it condenses into liquid water to the natural gas inside the high-pressure coil is the key to heat exchange in our HDL system. A 50/50 propylene glycol/water or ethylene glycol/water mixture is used in all HDL systems for freeze protection and corrosion inhibition along with minimum oxidation.
126,606 / 1,200
LIQUID
SOLID
147,707 / 1,400
168,808 / 1,600
(Figure 1.1)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 9
SITE PREPARATION AND DELIVERY
2. Site preparation and delivery
2.1 Prior to receiving the boiler
In preparation for the receipt of the boiler the following should be performed:
2.1.1 Tecvalco recommends that the boiler be levelled (a solid pad or base should be completed before arrival of the unit).
Note: Please follow all local jurisdictions and codes to design a proper founda­tion. In addition the equipment shall be installed in accordance with those instal­lation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
The reason for a solid base is to ensure the integrity of the HDL (Heat Driven Loop), the boiler depends on gravity for the water to return from the heat exchanger to the evaporator. If the foundation slopes the wrong way it puts undue stress on the high pressure flanges and the condensed returning water will be trapped and will “pocket” at the far end of the heater. In this situation the Heat exchange process (HDL) is disrupted as no steam can be generated and the glycol can overheat.
2.1.2 A thermowell should be installed in the gas piping downstream of the reg- ulators (depends on application) and this thermowell will receive the probe for the gas temperature control. It is the end user’s responsibility to select, and notify
Cold Weather Technologies of, the appropriate thermowells prior to shipping the heating boiler (see section 3.1 for thermowell sizings). The thermowell must
be in contact with the flow of gas to operate the system properly.
2.1.3 The CWT evaporator fuel supply operates on an inlet fuel pressure of 5 psi or less, depending on the model of the heater. Regulating and fuel supply me­tering equipment on the fuel train is the sole responsibility of the end user. It is also the end user’s responsibility to ensure that an adequate fuel supply is available.
(This fuel supply must be clean and dry pipeline quality natural gas or propane.)
Page 10
PN :: HEA -EVA P-MA NUAL-016 | 20170316
SITE PREPARATION AND DELIVERY
2.2 Upon arrival of your new CWT heating boiler at site
The CWT boiler is typically shipped completely charged with heat transfer fluid and on vacuum (depends on size of heater).
2.2.1 Check for any damage to the evaporator body and heater exchanger.
2.2.2 Unload the boiler using lift points (lugs) on the skid as shown on the lifting
diagram provided by Tecvalco and place on pad or on preferred base (Section 2.1.1). The heater should be level throughout the entire lift process.
2.2.3 Open the shipping crate to ensure all loose shipped items were sent and received in good order. (There will be a check list of parts in side the crate.) The packing list for our standard CWT models can be found in the Appendix at the end of this manual.
2.2.4 Check burner section for loose bolts, miss aligned burners, proper burner tray placement, loose gas line fittings and foreign debris from the manufacturing and shipping process.
2.2.5 Check the vacuum on the heater to make sure it is still established.
Note: If any of the above points are not satisfactory please contact Tecvalco immediately.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 11
INSTALLATION PROCEDURES
IM POR TANT: All wiring must be done in accordance with the current Canadian Electrical Code
3. Installation procedures
3.1 Place thermowells in downstream gas piping just past the meter station.
The line temperature probe is typically placed immediately after the last pressure regulation in the facility. Place thermowells as close as possible to meter station. The probe requires a thermowell with a minimum internal bore of .512 inches (13mm). Tecvalco can supply the appropriate thermowell upon request. Length will depend on pipe size and collar used on pipe. This information will be required in order to send proper length.
It is also recommended to install a temp gauge on the piping next to the Line Temp Controller to ensure the Temp Controller is always calibrated correctly (Reading the proper temperature)
NOTE: It is suggested that a barrier be created within this conduit prior to the thermowell in the high pressure line.
Use the following table to select the appropriate thermowell, and notify Tecvalco Industries of the part number.
Heater size Number of (BTU in 1000’s) thermowells
140 1 385 1 770 (single) 1 770 (2-385) 2 1155 (3-385) 3 1540 (2-770) 2 2300 (3-770) 3 3100 (4-770) 4 4600 (6-770) 6
Figure 3.1a
Note: One thermowell per evaporator.
CWT Part Numbers Description
THR-SS-.75-.5-4-.512 3/4” NPS x 1/2” x 2.5” U Length x .512 Bore THR-SS-.75-.5-5-.512 3/4” NPS x 1/2” x 3.5” U Length x .512 Bore THR-SS-.75-.5-6-.512 3/4” NPS x 1/2” x 4.5” U Length x .512 Bore THR-SS-.75-.5-8-.512 3/4” NPS x 1/2” x 6.5” U Length x .512 Bore THR-SS-.75-.5-9-.512 3/4” NPS x 1/2” x 7.5” U Length x .512 Bore THR-SS-1-.5-2-.512 1” NPS x 1/2” x 1” U Length x .512 Bore THR-SS-1-.5-4-.512 1” NPS x 1/2” x 2.5” U Length x .512 Bore THR-SS-1-.5-5-.512 1” NPS x 1/2” x 3.5” U Length x .512 Bore THR-SS-1-.5-6-.512 1” NPS x 1/2” x 4.5” U Length x .512 Bore
• It is suggested the tip of the thermowell be in the middle of the pipe, or beyond in smaller pipes.
• Please ensure that proper components and procedures are used for the pressure piping.
• It is suggested that appropriate thermally conductive heat transfer compound be used.
Page 12
Page 12
NOTE: All customers should select
components and materials based upon
applicable engineering standards.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
INSTALLATION PROCEDURES
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Figure 3.1b
Page 13
Page 13
INSTALLATION PROCEDURES
Figure 3.3
3.2 Connect the fuel supply line to the fuel train on the evaporator. Be sure to check local codes. The CWT evaporator operates on a max inlet fuel pressure of 20 psig to the Fisher HSR.
HE ATER SIZE MAXIMUM PSI MINIMUM PSI
140,000 Btu/hr Heater 5 1
385,000 Btu/hr Heater 5 3
770,000 Btu/hr Heater 5 5
Based on a Fisher HSR Regulator with a 1/2” Orifice
3.3 If supplied with a boiler having multiple evaporators, run cable from the terminal remote box (see figure 3.3) to the remote box.
3.4 To install the line temperature control switch, refer to figure 3.1.1b.
3.5 Place B-Vent exhaust stack on evaporator (see section 4.1.21 for images of
the B-Vent exhaust stack):
• Remove exhaust stack blind or cover.
• Keep stack gasket that is in place to be re-used with the B-Vent stack.
• Place rain cap on exhaust stack section (use screws).
• Place exhaust stack sections together if necessary (use screws).
• Place exhaust stack on evaporator (lifting equipment maybe needed).
• Use bolts from cover to secure the evaporator (evaporator size 140 will not require bolts).
• Install stack temperatue gauge provided in the field crate.
Page 14
Figure 3.6
3.6 Pressure gauges to be placed in valves located on coil (See figure 3.6)
3.7 When completed all parts from crate should be used
3.8 Note: Tecvalco highly recommends insulating gas piping from heater coil
outlet, up to the pipe where the downstream thermo-probe be installed.
3.9 Ready for pre-start up, start-up and run procedure. Note: Please confirm all connections are tight and sealed.
3.10 Vent installation Vent Installations shall be in accordance with “Venting of Equipment” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or “Venting Systems and Air supply for Appliances” of the Natural Gas and Propane Installation Code, CAN/B 149.1, or applicable provisions of the local building codes. Type of Vent: “B” Gas Vent. For stack assembly limitations, please look at Appendix E to H. a. Slide the vent stack assembly into the stack support bracket. Lock stack in place. b. Safely climb on a step ladder and place the stack support bracket onto the stack flange located on top of the boiler as show on pa ge 81. c. Use 1/2 inch Grade 5 bots and nuts provided to securely bolt the vent stack.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4. Components, safeties, and controls
The CWT evaporator is equipped with a number of safety systems that protect personnel and equipment. These systems function automatically without the need for constant supervision; however, some of the systems may require manual start-up after a shut down. A thorough examination of the device should be performed to determine the cause of any shut down. Activation of a safety shut down may be a signal that maintenance is needed for the device. Contact Tecvalco if the cause of the shut down is unknown.
The controls on the CWT operate on the energy provided by the thermopiles located near the continuous pilot. The power provided passes through a circuit that contains the various switches, as illustrated in the following pages.
In general, safety and control is quite simple; if any of the switches open, the circuit will be broken and the main burner will shut down; if the pressure switch or the ESD open both the main burner and the pilot will be extinguished and a manual restart will be required.
4.1 Evaporator section:
The firebox contains the burners, burner manifold, burner tray, Ignitor/thermopile assembly and the pilot and main fuel lines.
4.1.1 Swordfish burners (burner manifold or burner tray)
The burners are referred to as “swordfish burner”. Each burner is capable of a maximum firing rate of 35,000 Btu/hr, at 14 inch w.c. and #45 orifices. They sit in slots in the burner tray and can be equipped with a primary air adjuster (upon customer request).
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Figure 4.1.1a -
Page 15
COMPONENTS, SAFETIES, AND CONTROLS
The burner manifold is connected to the main fuel line and distributes the incoming fuel gas evenly to the burner.
Figure 4.1.1 -
The burner tray for 770,000 Btu’s, which contains
22 swordfish burners, one split manifold and
four thermocouples on two pilot assemblies.
Each swordfish burner generates 35,000 Btu’s per hour:
140,000 (Btu’s)= 4 swordfish burners
385,000 (Btu’s)= 11 swordfish burners
770,000 (Btu’s)= 22 swordfish burners
4.1.2 Pilot and thermopile assembly
The pilot and thermopile assembly consists of two 700 mV thermopiles, a pilot burner, and a sparker.
Page 16
(Figure 4.1.2)
NOTE: The pilot orifice should be stamped with the part number BL22N for natural
gas applications and 22LP for propane applications.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.1.3 The fintube assembly (primary heat exchanger)
The fintubes are located above the burners and span the width of the firebox. The flue gas passes through the fins and exit through the flue and stack. As the heated flue gas pass through the fintubes they heat the water-glycol mixture and cause the water to boil, generating steam.
(Figure 4.1.3)
(Figure 4.1.3a)
The photo above shows the primary heat exchanger with the side (saddle) tank open. The heat transfer fluid sits in the saddle tanks and fins as the combustion products pass upward, through the fins.
NOTE: The internal design is different for different models.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 17
COMPONENTS, SAFETIES, AND CONTROLS
4.1.4 The control box
The control box is attached to the evaporator and houses the various controls and safeties for the CWT heating unit. Included are the Robertshaw gas valve, the switches for high steam temperature (labelled “discharge temp”) and high glycol temperature (labelled “ESD”). Also included are the ignition box and a gauge to indicate main fuel line pressure downstream of the gas control valve. The gas line temperature control, while usually remote from the boiler, is also connected to the control box and system control logic.
Please refer to figures (4.1.4a and 4.1.4b) for control box instrumentation layout
Page 18
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
1 2
3
4
Components
1) Discharge temp
2) High temperature ESD
3) 4x4x2 CWT Ignitor box
4) Pilot gas line - 1/4” 304SS tubing
5) Fuel pressure gauge
6) Robertshaw type 7000 MVR gas valve
7) 3/4” tubing Portable hand held ignitor (not shown)
6
5
7
(Figure 4.1.4a) CWT standard control box 140,385 models
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 19
COMPONENTS, SAFETIES, AND CONTROLS
33
1
5 5
2
4 4
2
1
6 6
7 7
(Figure 4.1.4b) CW T standard control box
770 model
No. Components
1) Discharge temp
2) High temperature ESD
3) 4x4x2 CWT Ignitor box
4) Pilot gas line - 1/4” 304SS tubing
5) Fuel pressure gauge
6) Robertshaw type 7000 MVR gas valve
7) 3/4” tubing Portable hand held ignitor (not shown)
Page 20
PN :: HEA -EVA P-MA NUAL-016 | 20170316
4.1.5 Wiring diagrams
COMPONENTS, SAFETIES, AND CONTROLS
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Bill of material
1 Pressure switch
2 Temperature switch
3 Emergency shut-down device
4 Electronic ignition housing
5 Robertshaw millivolt gas valve
6 Temperature switch (-15 to 35C)
7 High temperature switch (0 to 100F)
8 Temperature switch (15 to 75F)
9 Temperature switch (55 to 175F)
(Figure 4.1.5a) CWT standard control box layout schematics 140,315 and 385
Page 21
COMPONENTS, SAFETIES, AND CONTROLS
Page 22
Page 22
(Figure 4.1.5b)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
PN :: HEA -EVA P-MA NUAL-016 | 20170316
(Figure 4.1.5c)
Page 23
Page 23
COMPONENTS, SAFETIES, AND CONTROLS
Page 24
Page 24
(Figure 4.1.5d)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
PN :: HEA -EVA P-MA NUAL-016 | 20170316
(Figure 4.1.5e)
Page 25
Page 25
COMPONENTS, SAFETIES, AND CONTROLS
Page 26
Page 26
(Figure 4.1.5f)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.1.6 Flame or flashback arrestors
It is a simple safety device, which quenches the flame from escaping to the outside after burner housing. Ensure you are following local codes and regulations in
the use of a flame arrestor.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
(Figure 4.1.6)
Page 27
Page 27
COMPONENTS, SAFETIES, AND CONTROLS
4.1.7 Robertshaw gas valve
The Robertshaw gas valve is the primary fuel control on the boiler. The current generated by the thermopiles in the continuous pilot powers the valve. The valve has three settings: off, pilot, and on. When the valve is in the on position it will respond to the controls in thermostats in the circuit and the unit will operate.
The pressure regulating process of the Robertshaw gas valves are bypassed. The pressure regulating for the units is performed by the supplied Fisher HSR regulators.
WARNING: The Robertshaw gas valve is not intended for operation at higher than 14.0” W.C. (.5 psi) supply gas pressure. Exposure to higher supply pressure may cause damage and could result in fire.
Pilot tube connection
Gas valve top knob
Pilot adjustment (under cap)
Page 28
(Figure 4.1.7)
NOTE: Please refer to Technical Manual section for detailed product information.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.1.8 High temperature ESD switch
The high-temp ESD thermostat monitors and responds to the temperature of the glycol/water mixture in the evaporator. It is set at 230°F (110°C).
When the temperature of the solvent (glycol/water) rises above the dial setting, the contacts open, thereby opening the electrical contact and shutting the Robertshaw valve.
This switch acts as one of the emergency shut downs; it will shut off the gas to both the pilot and the main burner and requires an operator to reset before relighting.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
(Figure 4.1.8)
NOTE: Please refer to Technical Manual section for detailed product information.
Page 29
COMPONENTS, SAFETIES, AND CONTROLS
4.1.9 Discharge temperature switch
The discharge temperature thermostat monitors the temperature of the steam in the evaporator. It is generally set between 175°F/79.44°C and 200 °F/ 93.3 °C in natural gas applications. If the steam temperature in the evaporator exceeds this set point the switch will open the main gas valve in the Robertshaw gas valve. The pilot will remain lit. The steam chamber temperature will have to cool enough to clear the deadband of the switch before it closes and allows the evaporator to fire again. This can occur in situations where the load on the evaporator is very low. The gas temperature probe can call for heat in response to ambient, when the unit fires there is little or no flow and therefore little or no heat exchange. The evaporator will rapidly heat up and the steam temperature in the unit will reach the discharge temperature switch set point.
(Figure 4.1.9)
NOTE: Please refer to Technical Manual section for detailed product information.
Page 30
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.1.10 Ignitor box and hand-held sparker
The ignition box assembly consists of a receiver in the control panel and a separate hand-held sparker. Inside the sparker is an AA battery.
NOTE: Before lighting the evaporator, it is mandatory to test the atmosphere first for combustible gases around the unit.
Receiver
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Hand held sparker
(Figure 4.1.10)
Page 31
COMPONENTS, SAFETIES, AND CONTROLS
4.1.11 The high pressure switch and shutdown
The evaporator is equipped with a high-pressure shutdown switch. This switch will shut off the main and the pilot fuel if the pressure in the boiler reaches 5 psig. The main burner and the pilot are extinguished. Once the unit has cooled enough for the pressure to drop below 5 psig, the pilot will require to be lit manually.
Page 32
(Figure 4.1.11)
NOTE: Please refer to technical manual section for detailed product information.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.1.12 Temperature control (line temperature control)
The line temperature control monitors the temperature of the gas in the downstream gas piping.
It is generally set between 0°C (32°F) and 5°C (41°F) in natural gas applications. If the gas temperature in the downstream gas piping falls below this set point the switch will close, allowing gas to flow to the main burner, generating steam for heat transfer.
Once the heated gas passing the line temp controller has exceeded its set point. The contacts will open which stops the gas flowing to the main burners.
If low or zero gas flow situations exist we suggest installing the probe near the outlet of the high-pressure coil (refer to section 8.5).
The temperature set point must then be increased to account for the pressure drop through the gate station.
(As a general rule, a 100 Psi drop in pressure will result in drop of 7°F (-13.9°C) of temperature).
NOTE: Please refer to technical manual section for detailed product information.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 33
COMPONENTS, SAFETIES, AND CONTROLS
4.1.12a 140 / 315 / 385 heater line temperature controller (T675A switch)
As the temperature of the controlled medium falls below the set point less differential, the T675A switch makes terminals R to B and energizes a normally closed solenoid valve to provide heat. Figure 4.1.12a.1 shows the operation of the T675A. Figure 4.1.12a.2 shows the location of the adjustment dial on models with an adjustable differential.
Controller comes in F or C.
(Fi gur e 4.1.12a.1)
(Figure 4.1.12a.2)
R
B
(Figure 4.1.12a.3)
Page 34
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.1.12b 770 heater line temperature controller (T678A switch)
When the temperature at the sensing element rises above the set point of the controller, the switch on the right makes R to W. Should the temperature continue to rise through the preselected inter stage differential of the controller, the switch on the left will make R to W.
Conversely, on a temperature fall, the switch on the left makes R to B, providing first step switching. If the temperature continues to fall, the switch on the right makes R to B to provide sequencing of equipment.
The T678A temperature controller has an adjustable inter stage differential. The set point adjustment knob determines the temperature at which the right switch oper­ates. The left switch can be adjusted to operate from 3 to 10 degrees F (1.7 to 5.6 degrees C) (or 3.6 to 12 degrees F (2.0 to 6.7 degrees C) on some models) above the point of operation of the right switch. An illustration depicting the operation of the T678A is shown in figure 4.1.14b.1. The inter stage differential is adjusted by turning the star wheel with a narrow screwdriver inserted into the rectangular hole in the chassis (figure 4.1.14b.2).
Controller comes in F or C.
B
R
PN :: HEA -EVA P-MA NUAL-016 | 20170316
2
1
B
(Fi gur e 4.1.12b.1)
R
(Figure 4.1.12b.3)
(Figure 4.1.12b.2)
Page 35
COMPONENTS, SAFETIES, AND CONTROLS
4.1.13 Burst disk and burst disk holder
The CWT Heater is designed to operate below 15 psig. If the pressure in the boiler reaches 15 psig the rupture disk will fail and the pressure will be released. The rupture disk is located above the fluid level in the unit so most of what will be released will be steam. The small amount of glycol that would be carried along will be collected in the containment system.
Note: For the new graphite gaskets, a 3M High Strength 90 Spray Adhesive Clear must be used on all bonding surfaces.
There are a few different styles of rupture discs used in the past on CWT Line Heaters. The most current one is shown in figure 4.1.13a and 4.1.13b.
(Figure 4.1.13a) Burst disk.
Older style rupture discs can be changed out to the new graphite rupture disc with minor alterations to the old style discs and piping.
Page 36
(Figure 4.1.13b) Burst disk with holders.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.1.14 Fisher HSR regulator
Pressure reducing regulator is to regulate gas and dependant on the end users gas usage. Vent as per local codes. Maximum inlet supply pressure is 20 psi with the .5” orifice that are installed.
(Figure 4.1.14)
The following table is using a HSR with .5 inch orifice.
Inlet pressures and standard cubic feet per hour for each heater assembly:
BOILER SIZE INLET PRESSURE REQUIRED SCFH 140 5 psig 200 385 5 psig 480 770 (Single) 5 psig 1050 770 (2-385) 5 psig 960 1155 (3-385) 5 psig 1440
1.54 (2-770) 5 psig 2100
2.3 (3-770) 5 psig 3150
3.1 (4-770) 5 psig 4200
4.6 (6-770) 5 psig 6300
(Table 4.1.14)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 37
COMPONENTS, SAFETIES, AND CONTROLS
4.1.15 Fuel pressure gauge IWC (inches of water column)
(Figure 4.1.15)
Pressure measurements in inches of water column
1 psi = 27.68 inches of water column, so 0.45 psi would be z27.68 * 0.45 = 8.3 inches of water column
WARNING: The Robertshaw gas valve is not intended for operation at higher than 14.0” W.C. (.5 psi) supply gas pressure. Exposure to higher supply pressure may cause damage and could result in fire.
4.1.16 Fisher 289L relief valve
This valve is set to relieve excess gas pressure at .5 psi. Vent as per local codes.
Page 38
(Figure 4.1.16)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
4.1.17 Fuel train drawing
COMPONENTS, SAFETIES, AND CONTROLS
Fuel gas assembly drawings can be found in Appendix M.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
P&ID Drawing for 140 and 385 (Figure 4.1.17a)
Page 39
COMPONENTS, SAFETIES, AND CONTROLS
Page 40
P&ID Drawing for 770 (Figure 4.1.17b)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
4.1.18 Pressure vacuum gauge
COMPONENTS, SAFETIES, AND CONTROLS
The vacuum gauge indicates the strength of vacuum. When the unit has a steam temperature of less that 60 degrees Celsius, the gauge should be in the range of –20 to –28 inches HG. Note: Heat transfer efficiency will increase with high vacuum. Note: Ensure that the needle valve is fully open (during operation) or fully
closed (during maintenance), needle valves that are partially open or closed can leak and cause the unit to lose vacuum.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
(Figure 4.1.18)
Page 41
COMPONENTS, SAFETIES, AND CONTROLS
4.1.19 High pressure coil gauge
Page 42
(Figure 4.1.19)
Picture of pressure gauge above is the standard pressure gauge CWT uses on inlet and outlet of high pressure coils to determine the gas pressure. For Compressed Natural Gas (CNG) applications, the supplied gauge will have a scale to 5000 psig.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
4.1.20 Liquid level gauge
COMPONENTS, SAFETIES, AND CONTROLS
Heat transfer fluid (50/50 water glycol mix)
(Figure 4.1.20)
Pictured above is the liquid level gauge, which indicates the availability of the heat transfer fluid in the system. The level gauge is not meant to indicate proper work­ing level; it is only for indication that there is fluid in the system.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 43
COMPONENTS, SAFETIES, AND CONTROLS
4.1.21 Exhaust vent
The exhaust stack cap supplied with the CWT heater is a residential, B-Vent style stack cap. They come in six inch, eight inch, or 12 inch, depending on the evaporator model.
The six inch stack has a high-wind stack cap with bird screen, while the eight and 12 inch stacks are both equipped with the bird screen.
Stacks are to be cleaned out (blown out) periodically as part of the routine maintenance. B-vent stacks are double-walled galvalume and can dent very easily. Proper care when installing the vent stack should be taken to prevent damage.
For assembly information please refer to Appendix E, F, G, and H.
B-vent for 140,000 BTU evaporator
6 inch
Page 44
B-vent for
315,000 / 385,000 BTU
B-vent for 770,000 BTU evaporator
12 inch
evaporator
8 inch
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.2 Condenser section (heat exchanger)
The condenser or heat exchanger is the part of the CWT Heater where the steam condenses on the pressure coil that contains the cold gas. When the steam contacts the cold pipe it releases latent heat by condensing to water. The water falls back to the evaporator section by gravity. The energy released as the steam condenses to water is significant. Just as it takes a significant amount of energy to convert water to steam, a large amount of energy is released when the steam condenses back to water. The inlet and outlet of the high-pressure piping is not defined, either flow direction will result in an acceptable heat exchange.
Gas outlet/inlet
Gas inlet/outlet
(Figure 4.2)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 45
COMPONENTS, SAFETIES, AND CONTROLS
4.2 .1 The heat exchanger can
The condenser/heat exchanger can contains the pressure coil and provides the vessel in which the steam is allowed to condense on the coil.
Inside the condenser can (photo below) the receivers at the far end support the coil.
Receivers to support the coil
Steam inlet
Condensate (water) outlet
Page 46
(Figure 4.2.1)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
COMPONENTS, SAFETIES, AND CONTROLS
4.2.2 High-pressure process coil
The high-pressure coil is the device that contains the gas to be heated. It is a registered pressure device built and certified in accordance with ASME B31.3 (pressure piping). The coil is typically a serpentine device as pictured below, the cylindrical coils are helical spiral coils and adjacent to it are standard high-pressure coils.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 47
COMPONENTS, SAFETIES, AND CONTROLS
Support
Page 48
(Figure 4.2.2) Note the nubs on the end of the coil.
These provide support and grounding for the coil inside the can
NOTE: High pressure coils are rated for: -20°F to 400°F (-29°C to 240°C). For low temp applications: -50°F to 400°F (-45°C to 204°C).
PN :: HEA -EVA P-MA NUAL-016 | 20170316
START-UP PROCEDURE
5. Start-up procedure
Prior to start-up the unit combustion chamber and all gas fittings should be checked for gastightness and proper placement as shifting can occur during shipping. All connections should be checked and verified by a gas fitter prior to supplying gas to the unit. Deficiencies or issues should be recorded and noted, items requiring warranty or further investigation should be relayed back to the Tecvalco factory immediately. On start up in very cold weather the boiler coil might be quite cold. Ensure the unit is warmed up to higher than 0°C (32ºF) prior to pressuring up the coil. If the boiler is down in very cold weather and there is no gas flow passing through the unit, the boiler should be isolated and the pressure reduced.
WARNING: Test atmosphere around the heater prior to lighting (procedure also on control box door). If an explosive mixture exists locate and shut off the source of the fuel and ensure the flame arrestor is in place and secure.
1. Open main gas ball valve on the fuel gas supply.
2. Turn Robertshaw control valve to the “PILOT” position.
3. Depress pilot button.
4. Insert hand held ignitor into the ignition box in the control cabinet and depress the button, while still depressing the pilot button. This causes a spark to jump across the pilot assembly. You should hear the sparking. Once the pilot lights you will no longer hear the spark. It may take several minutes for the natural gas to reach pilot area, due to the length of fuel gas supply line and the amount of trapped air.
5. Hold pilot button down for 30 seconds and then release.
6. Look through the site glass to confirm the pilot remained lit. If not, check that the valves on the fuel supply are open and return to step four. If this problem persists press the reset on the ESD control and try again or check fuel gas
7. With established pilot turn Robertshaw control to the “ON” position.
8. Change the setting of the line temperature switch to force heater to light. The main gas control valve should open and the heater should light. On first light you may get a slight burst of gas because of air in line. Turn to pilot for a second and then back to on. If the main burner does not light, confirm that all the dial type switches are calling for heat.
9. Once the evaporator is operating, examine the flame and note any instability.
10. Use the CWT Line Heater checklist inspection form (section 7.15) to record the initial data.
11. For 385,000 and 770,000 Btu/hr: Allow 5 minute complete shutoff before attempting to re-fire.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 49
TYPICAL OPERATION
6. Typical operation
During the first operating cycle of the heater, allow the system to run. Monitor the pressure, the discharge temperature and the level of heat transfer fluid in the sight glass. During initial start up and during normal operation the level of heat fluid will vary widely in the sight glass.
While the system is warming up, you will hear clattering and clanking inside the evaporator, which is normal and due to thermal expansion of steel inside the system and steam being percolated out of the glycol quickly. This should stop once the heater reaches a temperature range of approximately 125 deg. F to 150 deg. F.
Once the evaporator is warm (the main flame bed turns on and off to keep the gas warm) note the duration of the on and off cycles and the maximum and minimum temperatures reached. The season and gas flow will determine the cycle times; slow flow means long cycles and high flow mean short cycles. Use the attached Inspection sheet (section 7.15)
If the evaporator appears not to be warming gas sufficiently consider increasing the fuel pressure. Insufficient fuel gas will cause the unit to run constantly, and will not heat properly. If the heater cycles off and on it has sufficient energy to heat the gas.
To achieve low flow rate setting, while burner is in operation, turn the knob on the Robertshaw gas valve to reduce the input. The minimum and maximum allowable inlet pressures are indicated on the rating plate inside the control panel.
Page 50
PN :: HEA -EVA P-MA NUAL-016 | 20170316
6.1 Recommended control settings
CONTROL MINIMUM MAXIMUM RECOMMENDED
Steam (discharge) 76°C/170°F 95°C/200°F Start out at 170°F and temperature (°C/°F) increase as the process requires so that heater control is by the line temperature controller and not the discharge temperature controller. The maximum setting is 20 0 °F.
ESD shutdown (°C/°F) 110°C/230°F 110°C /230°F Operate at 110º C/ 230°F. If this trips contact CWT.
TYPICAL OPERATION
Pressure switch 5 Psi/ 5 Psi/ This switch is factory set (psig/kpa) 34.4KPa 34.4 KPa to 5 psig.
Line temperature 0°C/32°F 5°C / 41°F Depending on the (°C/°F) conditions and the nature of the gas set this as required (About 2°C/ 35°F)
OPTIONAL
Gas bundle outlet 24°C / 75°F 43°C / 110°F Depending on the temperature (°C/°F) season. Summer 24°C / (High Temp Shut Down) 75°F Winter 43°C/110°F
(Table 6.1)
Note: When multi-heating boilers are used on a heat exchanger, the line temperature switches should be rotated, so that the single boiler is not always the lead unit.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 51
TYPICAL OPERATION
6.2 Tuning the CWT Heater
The CWT Heater has a significant advantage over conventional systems in that it has a high turndown capability. A CWT evaporator can run with fuel inlet pressures varying between 3.5” WC (0.13 psi) and 14” WC (0.52 psi). This allows the operator to set the cycle time of the boiler to best fit the load. Ideally, a perfectly tuned heater would run 100 per cent of the time on the coldest day of the year. In practice, a well-tuned Evaporator will typically cycle three to four times per hour. Cycle time is determined by firing rate and load. The “on”, or firing, portion of the cycle can be controlled by the firing rate. If the firing rate is increased this will shorten the “on” part of the cycle. Flow and pressure drop through the station controls the “off” part of the cycle.
Some general rules for tuning include:
If possible, set the firing rate during high station load conditions and let the boiler stabilize (warm up) before continuing.
Fire at a high enough rate that the boiler will cycle at least three times per hour.
Fire at a high enough rate to ensure the stack temperature exceeds 130°C (266º F). Below this point incomplete combustion may occur and “raining” may occur in the stack.
Fire at a low enough rate that the stack temperature does not exceed 250°C (482º F). Above this would impair the boiler or stack.
Obtain a combustion analysis and optimize the combustion.
Observe the flame and address any lifting and/or hunting. Consult Tecvalco for advice.
6.3 Cycles
The CWT boiler normally operates with cycles on and off (figure 6.3a). The nature of the cycle depends on the firing rate and load as well as the set points on the controls primarily the gas temperature control. (See section 6.1)
When the boiler fires in response to a call for heat by the gas temperature control the evaporators begin the process of boiling the water. As the steam temperature and pressure increase more heat is delivered to the process gas. Eventually the temperature of the gas reaches the set point of the gas temperature control and the main burner shuts down. Upon shutdown, a large amount of energy remains in the evaporator and the temperature of the gas will continue to climb for some time (depending on the load). As a result the heater tends to overshoot the set point by a few degrees. Similarly when the heater is off, and the temperature is falling, when the gas line temperature control reaches the set point (plus the dead-band) it will call for heat and the evaporator will fire. It might undershoot the set point before the evaporator catches up.
Page 52
PN :: HEA -EVA P-MA NUAL-016 | 20170316
1 0 .0
G as Tem p (H eat er Off) G as Te m p (Hea ter F irin g)
Heater Off
Heater Firing
1
2
3
5
6
8
TYPICAL OPERATION
Gas Temperature Profile with CWT Line Heater (Illustrative Purposes Only)
8 . 0
7
6 . 0
4 . 0
2 . 0
Gas Temperature (°C)
0 . 0
-2 .0
4
-4 .0
-6 .0
0 1 2 3 4 5 6 7 8 9 10 1 1 1 2 1 3 14 1 5 1 6 1 7 1 8 1 9 2 0 21 22 2 3 2 4 2 5 26 27 2 8
PN :: HEA -EVA P-MA NUAL-016 | 20170316
(Approx. 8min)
(Approx. 5min)
Time
(Figure 6.3a)
Page 53
MAINTENANCE
WARNING: Inspections and tests included in this section may be regulated by local, Federal, or other jurisdictions. Please review all applicable codes and regulations prior to conducting any activities on CWT equipment.
7. Maintenance
WARNING: Never perform maintenance on the boiler when under operation or hot. Please ensure that the unit is shut and cooled down for 25 minutes, and that all fuel gas to the device has been shut off prior to performing any maintenance operation.
ALWAYS assume that there is pressure in the system.
7.1 Maintenance schedule
It is suggested that the boiler should undergo a complete inspection, maintenance and cleaning at least semi-annually (spring and fall). Use the following maintenance checklist in conjunction with the CWT inspection sheet (section 7.15). The inspec­tion can be done in connection with maintenance and can begin with a boiler that is operating; however sufficient time should be available to allow the evaporator to cool prior to the maintenance activities.
WARNING: Performing pressure tests on the system can be hazardous, and should only be performed by trained professionals. Contact Tecvalco if you have any questions.
WARNING: Keep boiler area clear and free from combustible materials, gasoline and other flammable vapors and liquids
Page 54
Service inspections a. A poor adjusted or malfunctioning appliance can deposit soot and other debris which can enter the vent system. The vent should be visually inspected at least annually for the presence of deposits of soot or debris. Blow air through the stack till no debris. b. The heater must be periodically inspected by a qualified serviceman or Tecvalco service technicians.
Inspection Checklist qTake pictures of the complete heater.
qRecord heater serial number and coil serial number. qShut heater off and let it cool down. qEnsure vacuum is between -20 inches and -26 inches. qCheck the glycol level in the sight glass. qOpen the burner box door and take pictures of burner tray and burner box. qRemove stack and take pictures of stack walls and top of fin tubes. qRemove burner tray gas line and disconnect the pilot assembly by removing the nut and drop the pilot assembly to the bottom of the combustion chamber. qWhen burner tray is removed take pictures of bottom of fin tubes. If possible, do a visual inspection. qUse an air compressor to blow off top and bottom of fin tubes. qOnce complete, do a visual inspection. If not clean, then repeat. qUse a vacuum cleaner to clean up the bottom of burner box and, if possible, the top of the fin tubes. qTake pictures of cleaned-out burner box and top of fin tubes. qClean burners from tray with air and check orifices to see if they are clean. This may require disassembly. qClean flame arrestor cell with air, or a water/soap solution until all openings are free and clear. qReassemble burner tray and install back in burner box. Hook up gas line and pilot assembly. Ensure burner tray placement is proper. If required, contact Tecvalco Ltd. personnel. qCheck wires in burner box for defects. If necessary, replace. qClose up burner box area, ensuring gaskets are properly in place. qIf heater has cooled down enough, take glycol samples. qWhen complete, relight heater using start-up procedure.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
qOnce heater is up to temperature function test each switch, for temperature controllers calibration please use a dry block. qDischarge temperature switch. 170-200°F / 76-95°C. Set at required temperature for process. qHigh temperature ESD switch. 230°F / 110°C. Will require relight. qLine temperature control switch. Set to desired temperature. qPressure switch. Set at 5 psi. qCheck millivolt readings. qCheck temperature of gas at station outlet, as well as in and out of the coil qCheck fuel pressure, in inches WC. qCheck steam and stack temperature. qPerform combustion analysis, if possible.
WARNING: Do not obstruct the flow of combustion and ventilation air.
7.2 Cleaning the flame arrestor
The flame arrestor on the evaporator should be inspected and cleaned at least semi­annually in order to ensure that it is in good working order and that enough air is provided to support proper combustion. In some cases more frequent cleaning may be required. (Locations where large amounts of dust are present or environmental factors). It is important to note that a clogged flame arrestor can fail as a safety device and result in hazardous situations. Therefore, it is very impor­tant to clean the arrestor on a regular basis.
a. Ensure the evaporator is off prior to removing the flame arrestor. b. Remove the flame arrestor and examine the cell – make sure that it is not damaged. c. Examine the gasket around the flange and ensure it is intact and in good condition. d. Use compressed air or nitrogen to blow out any dust or contaminants that might be in the weave of the cell. e. While the flame arrestor is removed inspect the burners – look specifically for signs of scale and or soot. f. Replace the flame arrestor; ensure that the cell fits tightly against the back flange.
MAINTENANCE
SEMI-ANNUAL
WARNING: Inspections and tests included in this section may be regulated by local, Federal, or other jurisdictions. Please review all applicable codes and regulations prior to conducting any activities on CWT equipment.
SEMI-ANNUAL
7.3 Swordfish burner clean-up
For detailed assembly drawings, refer to Appendix I, J, K, and L.
1. Turn gas valve to pilot, then turn off main gas. Let cool.
2. Open heater door and disconnect main gas flex from burner manifold. Unhook pilot gas line at Hylok fitting and remove burners if possible. Disconnect pilot bracket from burner tray. This will allow operator to remove the burner tray without having to disconnect the wires.
3. Remove burners from unit.
4. Check the burner venturi ports are free of foreign particles (dust, lint and debris).
5. Clean burners with bristle brush and/or vacuum cleaner. DO NOT alter burner ports or pilot location.
6. If the fin tubes need to be inspected and cleaned go to section 7.4.
7. Reinstall burners in unit. Make sure front and rear of burners are positioned correctly in burner support brackets.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
The burner tray can be difficult to remove as the combustion chamber walls can slightly warp due to heat. In this case, the walls inside may be required to be pushed get with a spreader bar to accomodate burner tray removal,
WARNING: Performing pressure tests on the system can be hazardous, and should only be performed by trained professionals. Contact Tecvalco if you have any questions.
Page 55
MAINTENANCE
WARNING: Inspections and tests included in this section may be regulated by local, Federal, or other jurisdictions. Please review all applicable codes and regulations prior to conducting any activities on CWT equipment.
7.4 Inspecting and cleaning the fin tubes
The fin tubes should be inspected and cleaned semi-annually. It is suggested that this be done before and after peak times (spring and fall, possibly).
1. Complete steps 1 to 3 of swordfish burner clean-up (7.3).
3. The stack will need to be turned to the side or removed for inspection and cleaning of the top of the fin tubes.
SEMI-ANNUAL
4. Once the burner tray and stack have been removed, take pictures of the fine tubes above and below, if possible. Note any problem areas and contact Tecvalco.
5. Use an air compressor or compressed air to blow out the fin tubes from the top down and then from the bottom up. Clean up any particles from bottom of the heater and any scale still on the top of the fin tubes. If needed, use a mirror to help in the inspection.
6. When cleaning is complete take pictures to note improvements.
7. Replace the stack and burner tray.
WARNING: Performing pressure tests on the system can be hazardous, and should only be performed by trained professionals. Contact Tecvalco if you have any questions.
Page 56
PN :: HEA -EVA P-MA NUAL-016 | 20170316
MAINTENANCE
7.5 Glycol sample procedure
Most CWT heaters are equipped with a double valve system, which will allow you to take a glycol sample without losing an appreciable amount of vacuum.
The procedure is as follows:
1. Take the sample when the heater is cold, in summer if possible. During operation the water and glycol separate and a sample will have an unrepresentatively high amount of glycol.
2. Open the top valve and wait for 30 seconds.
3. Close the top valve and open the bottom to obtain the sample, close the bottom valve
4. Repeat steps (2) and (3) at least two times. Such process would purge and remove the fluid standing in the low spot and to get a sample.
5. Open the top valve.
6. Open the bottom valve for 3 seconds only. This allows the system to pour back and bring fluid into the sample leg. Close both valves
7. Repeat steps 2 and 3 and obtain the required sample.
8. Note the vacuum pressure when complete.
9. For older Series II 140s with a temperature probe in the sample port, sample times will be much greater.
10. NOTE: Glycol samples are acceptable if they meet the customers’ minimum freezing points.
SEMI-ANNUAL
Top valve
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Bottom valve
(Figure 7.5)
Page 57
MAINTENANCE
NOTE: If through age or failure the thermopiles can no longer generate the power to operate the gas valve they can be replaced quite simply. In this case all the thermostats, controls and safeties would shutdown.
SEMI-ANNUAL
7.6 Testing the powerpiles
Test the powerpile assembly using the following procedure:
NOTE: Use a voltmeter set at 1000 mV
(Figure 7.6)
Test 1 – Complete system
Connect to terminals 2 and 3. Ensure the thermostats are calling for heat (turn them up). Power should be >100 mV. The main burner should fire. If the voltage >100 mV but the valve does not open replace the valve. If the power is <100 mV proceed to test 2.
Test 2 – Thermopile output
Connect to terminals 1 and 2. The thermostats should not be calling for heat (turn them down). The main burner is off the voltage should be > 325 mV. If it is less replace the thermopiles.
Test 3 – System resistance
Connect to terminals 1 and 3. The thermostats should be calling for heat. The main burner should be on. The reading should be < 80mV. If the reading is more, clean the contacts and cycle the thermostats (to clean contacts).
Test 4 – Pilot dropout
Connect to terminals 1 and 2. Hold the pilot until the power level stabilizes. Shut the pilot off and note at which point the magnet drops (should be between 120 and 30 mV (falling). If the dropout does not occur or occurs outside these points replace the gas valve.
Page 58
PN :: HEA -EVA P-MA NUAL-016 | 20170316
MAINTENANCE
7.7 Procedure for testing high-pressure shutdown
1. Testing pressure switch (shutdown setting check).
2. Turn Robertshaw gas valve to off position. Give heater .5 hour to cool.
3. Close bottom valve (3) completely.
4. Remove plug from top valve (2), (releasing vacuum from the just switch section, not all of unit).
5. Will require a pump or other to pressure test switch.
6. Unplug wire from terminal 1 on Robertshaw gas valve and wire from high temperature ESD leading to pressure switch and connect multimeter to wires (set meter at continuity). Add pressure and note where contact closes.
7. Switch should cut out at set point of 2.5 psig- 5 psig (if settings correct, reconnect the wires, replace plug, open valves turn boiler back on. Valves must be ither opened all the way, or closed all the way - otherwise the packing can leak.
SEMI-ANNUAL
WARNING: Inspections and tests included in this section may be regulated by local, Federal, or other jurisdictions. Please review all applicable codes and regulations prior to conducting any activities on CWT equipment.
Top Valve (2)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
WARNING: Performing pressure tests on the system can be hazardous, and should only be performed by trained professionals. Contact Tecvalco if you have any questions.
Bottom Valve (3)
(Figure 7.7)
Page 59
MAINTENANCE
WARNING: Inspections and tests included in this section may be regulated by local, Federal, or other jurisdictions. Please review all applicable codes and regulations prior to conducting any activities on CWT equipment.
WARNING: Performing pressure tests on the system can be hazardous, and should only be performed by trained professionals. Contact Tecvalco if you have any questions.
7.8 Procedure to find possible leak
When required, the following checklist can be used to track down possible leaks.
qTurn heater off and let cool for one hour. This needs to be done or steam will leave the system). qRemove vacuum from system. qDrain the gylcol from the system. Barrels will be required for this, so be sure to check the size of system for the amount needed. qUsing an air compressor, pressure system up to 10 psi MAX. qSoap all fittings and areas that might be affected, including pressure relief system. qInspect areas for bubbles. Testing may require up to an hour. qFix problem areas. qRe-pull vacuum to -24 to -30 inches. qPull in proper amount of glycol. Note, new glycol may be required, as old fluid may have lost its water. qRestart heater using start-up procedure.
7.9 Pulling vacuum (when required)
1. When pulling vacuum the unit must be empty. Sucking gylcol through the vacuum pump can wreck the pump seals, etc.
2. Drain heater completely or make sure heater is drained.
3. Ensure that the system is cool and that neither the main burner nor the pilot is running.
4. Connect the vacuum compressor (suction side) to the evaporator vacuum valve.
5. Turn on the compressor, and then open the valve.
6. Continue evacuation of air until the vacuum gauge reaches –26”Hg. (The higher the vacuum that is achieved in the system, the more efficiently the system will operate).
7. Once sufficient vacuum is achieved, close the vacuum valve and shut down the compressor. Remove the compressor connections and re-install vacuum valve cap.
8. Record the pressure and temperature reading on the evaporator.
9. Allow unit to stand for 30 minutes.
10. Check to see if the pressure or temperature has dropped or varied in any way.
11. If the pressure has increased with no change in temperature, there is a leak in the system. If neither of the settings has changed, proceed to the trouble shooting section. NOTE: If there has been a vacuum leak on the heater you should assume
that much of the water in the fluid has been lost – in these cases it is prudent to drain and replace the fluid.
Page 60
PN :: HEA -EVA P-MA NUAL-016 | 20170316
MAINTENANCE
7.10 Replacing damaged burst disk
When required, the following can be performed to replace a damaged burst disk.
1. Remove ABS pipe off burst disk holder and containment, then remove ruptured disk by taking out all studs and nuts on holder.
2. Make sure sealing surfaces on both parts of holder are clean and free of scaring, grooves, or debris. (If needed use steel wool to clean).
3. When reinstalling disk make sure holders are evenly spaced all the way around, and hand tighten studs equally.
4. All graphite rupture discs should be torqued as per the following sequence: a. First Pass: 5ft lbs b. Second Pass: 10ft lbs c. Third Pass: 15ft lbs d. Fourt Pass (repeat three times): 22ft lbs (NOTE: For HPX 90 style rupture disc and holder (SS): When tightening use torque wrench, first pass should be 20ft lbs using cross pattern, second pass use 65ft lbs making sure spacing is equal all the way around for units installed with rupture disc holder.
5. Reinstall ABS pipe to disk holder and containment.
WARNING: Inspections and tests included in this section may be regulated by local, Federal, or other jurisdictions. Please review all applicable codes and regulations prior to conducting any activities on CWT equipment.
WARNING: Performing pressure tests on the system can be hazardous, and should only be performed by trained professionals. Contact Tecvalco if you have any questions.
(Note: For HPX 90 syle rupture discd holder (SS) (Note: For older style painted rupture disc holders use a torque setting of 30ft lbs on first pass and 40ft lbs on second pass)
Burst disk holder containing burst disk
Containment system
ABS pipe
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 61
MAINTENANCE
7.11 Drawing glycol into system
New water-glycol mixture should be used when adding fluid to a system, or for new installs.
1. Remove the cap from the vacuum fitting.
2. Attach a vacuum hose to the fitting on the valve.
3. Insert the free end of the hose into the container of fluid mixture.
4. Open the valve to draw in fluid.
5. Close valve when the proper volume of fluid is drawn.
NOTE: Do not allow air to enter the system.
7.12 Recommended glycol volumes
The recommended glycol-water volumes for the CWT boiler are as follows. In every case, when the evaporator is operating there should be fluid in the site glass. If not please contact Tecvalco.
Heater Style Recommended fill volume 50/50 in Litres in Gallons
140 Integral 40 10.5 315 MK5 68 17. 9 385 MK6 95 25.09 770 160 42.2
( Ta b l e 7.11)
NOTE: Glycol volumes may change according to evaporator size
7.13 Glycol characteristics
The glycol in the CWT heating system is designed for freeze protection only. An easy on-site check periodically can identify if the glycol needs to be changed. The two main properties to look at are:
1) Freeze protection: ensure the glycol has adequate freeze protection for the lowest anticipated ambient temperature for your installation region.
Page 62
Page 62
2) PH: a pH higher than 11.5 can start to corrode internals in the CWT system. Any pH higher than 11.5 constitutes a glycol change-out.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
7.14 The gas bundle removal
When required by local jurisdictions and codes, the high-pressure coil should be removed and inspected (this period might also vary depending on company policy). Prior to removing the coil, contact Tecvalco for a replacement gasket and recommended bolt torque values.
1. Ensure the heater is off and cooled. Pilot extinguished, Robertshaw gas valve to off and main gas valve shut and locked out.
2. Carefully remove the insulation around the coil flange.
3. Ensure that no pressure exists in the unit.
3. Remove the coil from the heater.
4. Visually inspect the coil and the can interior for signs of corrosion or damage.
5. Inspect coil as per appropriate codes (ASME, local corporate and other).
6. Install new gasket.
7. Install studs and nuts, torque to appropriate specifications (call Tecvalco) and establish vacuum.
MAINTENANCE
PN :: HEA -EVA P-MA NUAL-016 | 20170316
(Figure 7.12)
Page 63
Page 63
MAINTENANCE
7.15 Boiler checklist
CWT Heater Inspection Sheet
Company ______________________________________ Technician _________________________________________ Location _______________________________________ Date ______________________________________________ Model _________________________________________ Coil Serial Number _________________________________ Serial Number __________________________________ Coil CRN __________________________________________ Heater Status on arrival (running, on pilot, off, cold, etc.) _________________________________________________ Steam temp. (C when firing and warm) Steam pressure (°Hg when firing and warm) Gas in temp. (C when firing and warm) Gas out temp. (C when firing and warm) Stack temp. (C when firing and warm) Station outlet temp. (C when firing and warm) Glycol fluid level (trace, ¼, ½, ¾, Full) Glycol appearance (take small sample) Fuel pressure (inches WC) Orifice size Photos taken (burners, fin tubes) Blow out cell and fin tubes
Millivolt Reading Control Settings
Side 1 Side 2
1 ________ ________ Discharge Temp. _____ °F 2 ________ ________ ESD Temp _____ °F 3 ________ ________ Line Temp. _____ °C 4 ________ ________ Pressure Switch _____ Psi High Temp ____ _ °F Combustion Analysis O2 (%) _________________________ CO2 (%) ______________________________ CO (ppm) _______________________ Efficiency ______________________________ Excess Air (%) ____________________ Stack temperature (degrees F) ____________ Boiler firing rate (BTR/hr) ______________________________________________________________________________ Note condition of insulation, any scale or sign of moisture _________________________________________________ Note condition of B-vent to steel transition piece__________________________________________________________ Comments, please note any work done or adjustments made: _____________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________
Page 64
Page 64
PN :: HEA -EVA P-MA NUAL-016 | 20170316
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 65
Page 65
TROUBLESHOOTING
WARNING: Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under wa ter.
8. Troubleshooting
The following is a list of common problems associated with the operation of the CWT heater. This list is by no means all-inclusive. Please, feel free to contact Tecvalco to assist with any problems that occur.
8.1 Heater inspection checklist Please ensure that you completely fill out a copy of the CWT Heater Inspection Checklist, found in section 7.15, as part of your troubleshooting efforts.
Page 66
PN :: HEA -EVA P-MA NUAL-016 | 20170316
8.2 Common problems and possible solutions
SYMPTOM
COMMON CAUSES
TROUBLESHOOTING
POSSIBLE CORRECTIONS
If pilot is out
If main burner will not fire
Loss of fuel gas supply
Excessive pressure in system caused pressure switch to activate
High temperature ESD switch issue
System has exceeded allowable pressure, and the relief has failed, allowing water to escape.
Pressure switch issue
Unsteady or fluctuating flame
Weak powerpile voltage
Robertshaw gas valve magnet not holding
Line temperature control switch not wired correctly
System not requiring heat
Check fuel gas supply.
Review pressure shown on gauge. If excessive, diagnose cause and fix.
Check high temperature ESD, and test functionality.
Inspect pressure relief and barrel for exited water. Diagnose cause of over-pressure and fix. Replace or repair pressure relief system.
Check pressure switch, and test functionality as per s e cti o n 7.7.
Examine the flame. Is it steady or fluctuating? Is it lifting off the burners? If so, the combustion may need tuning. Contact CWT for advice.
Test the voltage to each powerpile. See section 7.6.
Use test 4 (pilot dropout) in section 7.6
Check wiring diagrams (found in section 4.1.5).
Check line temperature control switch to see if it is turning on and off at desired temperature. Set to appropriate temperature.
Problem with line temperature switch
Steam temperature exceeds setting of discharge temperature switch
Loss of fuel gas supply
Weak powerpile voltage
Robertshaw gas valve magnet not holding
Heater has lost
Malfunctioning vacuum gauge
vacuum * Always assume unit is under pressure until
Evaporator is hot with high steam pressure due to operation
proven otherwise
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Test functionality of switch. Repair or replace if necessary.
Review steam temperature settings. May need re­view with CWT. Possible low- or zero-flow situation.
Check fuel gas supply.
Test the voltage to each powerpile. See section 7.6.
Use test 4 (pilot dropout) in section 7.6
Ensure that vacuum is lost and that vacuum gauge is accurate.
Record steam pressure and steam temperature from heater. Using these values, review table 10.19.
Page 67
TROUBLESHOOTING
SYMPTOM
Heater has lost vacuum (con’t.)
Failure or release of pressure relief system
Gas is not being heated to proper temperature
COMMON CAUSES
System has exceeded internal pressure and relief has failed.
Possible leakage of fittings, burst disc, switches, etc.
Possible leakage in pressure relief system
System has exceeded allowable internal pressure setting of relief system
Line temperature switch settings
Fuel gas pressure
Line temperature switch location
Gas piping insulation
POSSIBLE CORRECTIONS
Inspect pressure relief barrel for exited fluid. If present, diagnose overpressure cause. Fix and replace pressure relief system and all fluid.
Test system for leakages using procedure 7.8 and
7.10 .
Test system for leakages using procedure 7.8 and
7.10 .
Diagnose overpressure cause. Repair or replace relief system and replace all fluids.
Check switch settings. Function test switches. Set­tings can be found on page 51. Check local codes.
Check fuel gas pressure. It may need to be turned up or down, depending on requirements.
Check line temperature switch for proper location. Is the switch placed just past the final pressure cut?
It is recommended that the piping be insulated. If it is not, then the switch in the gas piping may pick up ambient temperature.
Page 68
Page 68
Gas flow
Safety switch operation
Lost water/fluid
Check gas flow through coil. Potential zero- or low­flow through coil. See section 8.3.
Inspect switches in system to ensure no settings have been exceeded.
Inspect glycol site glass for fluid level. Find cause and fix.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
8.3 Potential zero-flow application
The CWT Heater’s application is typically designed to sense the temperature of the gas as it exits the gate station after the last pressure cut. If a zero-flow situation exists (where no, or very little gas is flowing through the system) the probe that is downstream from the facility can be subjected to ambient temperatures below the set point of the control.
As there is minimal or zero flow, the now-heated gas will not flow past the probe, and will not signal the heater to stop its firing sequence. With the external insulation on the evaporators being very efficient, the heat being generated cannot escape and the overall temperature and pressure within the evaporator and heat exchanger will increase.
As this occurs certain safety devices will begin to operate:
1. The steam temperature will increase beyond the acceptable temperature of the discharge temperature switch, causing the safety device to open the circuit and stop the main flame from firing. a) If the unit can release enough heat to the surroundings, the temperature will drop and the discharge temperature switch will automatically reset, allowing the heater to resume firing as directed by the still cold downstream temperature probe.
2. If the heat can not be released then the pressure within the evaporator and condenser will continue to increase, ultimately surpassing the 3 to 5 psi range of the pressure switch. This will open the electrical circuit, stopping the gas to the pilot and the main burners, keeping the unit from firing. This removes all electrical power from the evaporator and will not allow the system to resume firing until it is visited by a field technician to investigate the problem and physically relight the system.
NOTE: In earlier models the pilot light would have remained lit, allowing it to re-fire once the pressure had dropped below the 3-5 psi set point.
3. Finally, as the unit continues to release the heat and generates steam (even without a flame but potentially from the heat stored in the steel of the housing etc.) the pressure may build to 15 psi at which time the burst disk will rupture.
4. If there is still enough residual heat in the system after the burst disk has failed, the glycol will continuing to increase its temperature and its temperature may rise to a point in excess of the ESD setting, causing the ESD to shut down. This will kill the pilot the main gas and then “pop” the ESD button.
TROUBLESHOOTING
NOTE:
If the line temperature probe is installed at the outlet of the high-pressure coil “the set temperature” must be set accordingly.
A general rule is that for every 100 psi of pressure drop 7°F/-
13.9°C temperature drop. For example, if a 500 psi pressure drop is to occur the outlet temperature of the coil should be initially set 35°F above the temperature required after the last pressure drop i.e if a temperature at 35°F/1.67°C is required after the last pressure drop, the line temperature control should initially be set to 70°F/3.34°C.
The boiler should then be monitored for proper operation.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 69
Page 69
OPTIONAL EQUIPMENT AND ACCESSORIES
9. Optional equipment and accessories
9.1 High-temperature shut down
There are three options.
Page 70
Page 70
(Figure 10.1)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
9.2 High-temperature shut down installation drawing
OPTIONAL EQUIPMENT AND ACCESSORIES
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 71
Page 71
OPTIONAL EQUIPMENT AND ACCESSORIES
THIS PAGE LEFT
INTENTIONALLY BLANK
Page 72
Page 72
PN :: HEA -EVA P-MA NUAL-016 | 20170316
10. Glossary
10.1 Low-pressure evaporator
An evaporator is a closed vessel in which water or other fluid is heated to a gaseous state for heating applications. In the CWT evaporator the pressure produced is less than 15 psi, hence it’s a low-pressure evaporator.
10.2 Inches of mercury: In Hg or “Hg is a measuring unit for pressure”. It is defined as the pressure exerted by a column of mercury of 1 inch in height at 32°F (0°C) at the standard acceleration of gravity. 1 in Hg = 3,386.389 pascals at 0°C. In English units: 1 in Hg = .491098 psi, or 2.036254 in Hg = 1 psi.
GLOSSARY
10.3 Pascal (pa): It is a measure of force per unit area i.e. equivalent to one newton per square meter or one joule per cubic meter.
10.4. Pressure (P): Is the force per unit area applied to an object in a direction perpendicular to the surface.
10.5 Gauge pressure: Is the pressure relative to the local atmospheric or ambient pressure.
10.6 Inches water column: Instead of using pressure as units of measurement, inches of water are commonly used in airflow applications in HVAC (Heat, Ventilating and Air Conditioning) because the pressure measurements are very minute.
10.7 British Thermal Unit (BTU): The British Thermal Unit (BTU or Btu) is a unit of energy used in the power, steam generation, heating and air conditioning industries. The term “BTU” is used to describe the heat value (energy content) of fuels, and also to describe the power of heating and cooling systems. One BTU is approximately 1,054 - 1,060 joules (J).
10.8 MBTU: One thousand BTU
10.9 MMBTU: One million BTU
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 73
Page 73
GLOSSARY
10.10 Latent heat: is the amount of energy released or absorbed by a chemical substance during a change of state (i.e. solid, liquid, or gas), or a phase transition
10 .11 Vacuum: A vacuum reference can be thought of as the opposite of a gage reference. Vacuum references are notated with “V”, for example PSIV or “HgV”
10.12 Differential: Differential pressure measurement is the difference between two unknown pressures. Output is zero when the two pressures are the same, regardless of magnitude. Differential pressures are notated as “D” (PSID).
10.13 Absolute: As previously described, the zero point of an absolute reference is the absence of all matter. There is no pressure at absolute zero. All absolute pressure measurements made are therefore positive. Absolute pressure measurements are abbreviated with an “A”. For example, 0 PSIA o6 6”HgA.
10.14 Gage: To ignore the effects of changing weather, altitude or depth, a “Gage” pressure reference is sometimes useful. This reference measures pressure relative to the local atmosphere. Changes in local atmospheric pressure occur due to weather, or if the instrument is moving because of changes in altitude and/or depth. Gage pressure is denoted as “G” or PSIG.
10.15 Heat required to raise the temperature of a material:
Page 74
Page 74
Q1 = Heat required to raise temperature W = Pounds of material CP = Specific heat of material (Btu/lb-ºF) T = Temperature rise of material (TFinal - TInitial) ºF
PN :: HEA -EVA P-MA NUAL-016 | 20170316
10.16 SCFH: Standard Cubic Feet per Hour
10.17 Common PSI Conversions
1 PSI = 27.68”WC (inches of water column) 1 PSI = 2.036”Hg (inches of mercury) 1 PSI = 51.715 mmHg or Torr 1 PSI = 0.068947 Bar 1 PSI = 0.06804 Atmospheres (Note that 1 Bar is not exactly 1 atmosphere) 1 PSI = 6.8947 Kilo Pascals or KPa 1 PSI = 0.0703 Kg/cm2 1 PSI = 2.307 feet of water
GLOSSARY
10.18 Peak load: Measurement of the maximum amount of energy delivered at a point of time
10.19 Flue gas: Combustion gases that are vented to the atmosphere. The equation below providesanapproximationofthepressuredifference,ΔP,(betweenthe bottom and the top of the flue gas stack) that is created by the draft.
ΔP = Available pressure difference, in Pa C = 0.0342 a = Atmospheric pressure, in Pa h = Height of the flue gas stack, in m To = Absolute outside air temperature, in K Ti = Absolute average temperature of the flue gas inside the stack, in K
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 75
Page 75
GLOSSARY
10.19 CWT pressure and temperature chart
This chart can also be used as a diagnostic tool as the pressure and temperature of the CWT boiler steam chamber should fall on this line. If the steam temperature and pressure do not meet the line, there might be a problem, which requires further investigation.
Boiling Point of Water at various Pressures - Gauge Pressure
(Vacuum and Positive Pressure)
20
17.5
15
12.5
10
7.5
5
2.5
0
120/49
-2.5
-5
S te am Pre ss ur e
-7.5
-10
-12.5
(po si tive i n PS I - nega tive i n I NH G)
-15
-17.5
-20
-22.5
-25
130/54
140/60
150/66
160/71
170/77
180/82
190/88
200/93
210/100
220/104
B oi ling P oi nt of Wa te r Temper at ure D eg F / Deg C
230/110
240/116
250/121
260/127
270/132
280/138
Page 76
Page 76
The CWT boiler typically operates with negative pressure (vacuum), and is usually in the range of –20 to –26 In Vacuum Hg or below 0 psig. If a CWT heating Evaporator is operating at close to 0 psig and close to 100°C (212°F) it may be the result of very low process load or an indication of a loss of vacuum. In every case, the most important indicator of the condition of a CWT boiler is the pressure and temperature in the evaporator.
Another very important measure is the temperature of the process gas in and out of the evaporator. There should be a significant increase in the temperature of the high-pressure gas as it passes through the evaporator.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
SPARE PARTS LIST
11. Spare parts list
Associated Evaporator Model Part Number Description
140, 315, 385, 770 BAR-PLA-30 30 Gal Plastic Barrel c/w Lid 140, 315, 385, 770 BOL-LYNCHPIN-.188 3/16” Lynch Pin 140, 315, 385, 770 BUR-B-.438-27 7/16” Spud Orifice Brass 140, 315, 385, 770 CTR-CCS-646GZE1-7011 Pressure Switch w/SST Diaphragm 140, 315, 385, 770 COS-DOW-340 Heat Transfer Compound 140, 315, 385, 770 CTR-PADTHERM Pilot Assembly Double Thermopile 140, 385, 770 CTR-SP-289L-41 Fisher 289L Relief Valve 140, 385, 770 CTR-SP-HSR-CHCBMYY Fisher HSR Regulator w/1/2” Orifice 140, 315, 385, 770 CTR-SS-700-C506 Robertshaw Gas Valve 140, 315, 385 CTR-L4008E-1263 High Temp Discharge Controller w/ESD 140, 315, 385, 770 GAU-2.5-.25B-M30-30P-L Vacuum Gauge 140, 315, 385, 770 GAU-4-.5B-2000P 4” x 1/2” 0-2000 Psi BM Gauge (Inlet/Discharge) 140, 315, 385, 770 GAU-INCH-2.5-.25-0-15 2-1/2” x 1/4” 0-15 Inch Gauge 140, 315, 385, 770 HEA-EVAP-MANUAL Evaporator Instruction Manual 140, 315, 385, 770 HEA-IGNBOX-ASSY 4” x 4” x 2” CWT Ignition Box 140, 315, 385, 770 HEA-IGNHH-ASSY CWT Portable Hand Held Ignitor 140, 315, 385, 770 HOS-GFAH-.75-18 3/4” x 18” F x F Flex hose 140, 315, 385, 770 VAV-NDL-MXF-.25 1/4” CS MxF Needle Valve 140, 315, 385, 770 VAV-NDL-MXF-.5 1/2” CS MxF Needle Valve 140, 315, 385, 770 WIR-SHCAB-1P-18G 18 Ga x 1 Pair Shielded Cable 140, 315, 385, 770 WIR-SPW-7MM-HD 7mm HD Spark Plug Wire 140, 315, 385, 770 CTR-BPLT-2 2” Burst Plate (Old Style) 140, 315, 385, 770 HEA-BDISK-PAI-ASSY Burst Plate Paint Assembly (Old Style) 140, 385, 770 CTR-BPLT-2-HPX-90 2” Burst Plate (Old Style) 140, 385, 770 CTR-BPLT-2-HPX-90HOLDER SS Burst Plate Holder (SS Old Style) 140, 385, 770 CTR-GRAPHITE-RUP-DISC-2 2” Graphite Rupture Disc 140, 315, 770 BUR-SFB-098044-000 Swordfish Burner Orifice Cover 140, 770 BUR-SFB-098047-000 Swordfish Burner B&G 315, 385 BUR-SFB-81F94 Swordfish Burner Lennox 140, 315, 385 CTR-SS-T675A-1102 Discharge Temp Controller 140, 315, 385 CTR-SS-T675A-2084 Line Temp Controller 140, 315, 385 GAU-3-6-50-500-S 3” x 6” 50-500 Deg Gauge (Stack Temp) 140, 315, 385 THR-SS-.75-.5-4-.250 3/4” x 1/2” x 4” x .250 SS THR 140, 315, 385 HEA-4-SGLASS-PAI-ASSY 4” Sight Glass Paint Assembly 140, 385 THR-S304-1-.5-U16.5-.755 -.550 1” x .5” x 16.5”U x .755R x .550B 140, 770 THR-SS-.75-.5-12-.250 3/4” x 1/2” x 12” x.250 SS THR 315, 385 FIR-BVENT-8-3 8” x 3’ B-Vent Section 315, 385 FIR-BVENT-8-5 8” x 5’ B-Vent Section 315, 385 FIR-BVENT-RAINCAP-8 8” B-Vent Rain Cap 315, 385 GSK-NA1001-RD-12.5-8.625-8 12.5 “Od x 8.625”id 8 hole gasket 315, 385 HEA-BVENT-SUPPORT-8 8” Bvent Stack Support
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 77
Page 77
SPARE PARTS LIST
315, 385 GSK-304SS-FLEX-150-3 3” 150# 304SS Flex Gasket 315, 385 THR-SS-.75-.5-4-.512 3/4” x 1/2” x 4” x .512 SS THR 315, 770 THR-S304-.75-.5-U7.5-.755 -.550 3/4” x 1/2” x 7.5”U x .755R x .550B 770 HEA-6-SGLASS-PAI-ASSY 6” Sight Glass Paint Assembly 140 FIR-BVENT-6-5 6” x 5’ B-Vent Section 140 FIR-BVENT-HWCAP-6 6” Hi-Wind Cap 140 FLA-FAFBC-15-4C 15” Flame Arr. Flash Back Cell 140 FLA-FAFP-15 15” Flame Arrestor Face Plate 140 GAU-3-12-50-500-S 3” x 12” 50-500 Deg Gauge (Heater Temp) 140 GAU-3-4-M40-160-S 3” x 4” 40-160 Deg Gauge (Gas Coil Temp) 140 GSK-NA1001-RD-14.75-13.25 CWT Ring gasket 140 HEA-140-2-1100 Stack Support Arm, 140 Heater 140 GSK-GR-RD-20.5-14.125-26 20.5 ODx14.125ID 26H Graphite 140,770 THR-SS-1-.5-12-.512 1” x 1/2” x 12” x .512 THR 315 FLA-FAFBC-16-4C 16” Flame Arr. Flash Back Cell 315 GSK-NA1001-RD-15.875-14.5 MK5 Flame Cell seal gasket 315 GSK-NA1001-MK5-DOOR MARK 5 DOOR GASKET 385 FLA-FAFBC-18-IC 18” FA Flash Back Cell w/InCou 385 GSK-NA1001-RD-17.875-16.625 Flame Cell Seal Gasket, MK6 385 GSK-NA1001-MK6-DOOR MK6 DOOR GASKET 770 GSK-NA1001-RT-47/43-24/20 770 RECTANGULAR DOOR GASKET 770 CTR-SS-T678A-1361 Discharge Temp Controller 770 CTR-SS-T678A-1163 Line Temp Controller 770 FIR-BVENT-12-3 12” x 3’ B-Vent Section 770 FIR-BVENT-RAINCAP-12 12” B-Vent Rain Cap 770 GSK-NA1001-RD-16-12.625-12 16”OD X 12.625”ID 12 HOLE GASKET 770 FLA-FAFBC-20-4C 20” Flame Arr Flash Back Cell 770 GSK-304SS-FLEX-150-4 4” 150# 304SS Flex Gasket 770 GSK-NA1001-RD-20-18.625 20”ODx18.625”ID Gasket 770 HEA-770-2C-800A Stack Adapter Assembly 770 GAU-3-9-50-500-S 3” x 9” 50-500 Deg Gauge 770 THR-SS-.75-.5-9-.250 3/4” x 1/2” x 9” x .250 SS THR
Page 78
Page 78
PN :: HEA -EVA P-MA NUAL-016 | 20170316
SPARE PARTS LIST
Options
140,315,385 CTR-COIL-HTSD-1F High Temp Shut-down, Ferenheit 770 CTR-COIL-HTSD-2F High Temp Shut-down, Ferenheit 140,315,385 CTR-COIL--HTSD-1C High Temp Shut-down, Celsius 140,315,385,770 CTR-SS-93560 6 cfm vacuum pump 140,315,385,770 CTR-SS-19310 3/8 inch vacuum pump hose 140,315,385,770 COS-OIL-4383-01 Oil for vacuum pump, 4 litre container 140,315,385,770 CTR-SP-T14399T0012 HSR spring, 6” wc to 8” wc (Yellow) 140,315,385,770 CTR-SP-T14405T0012 HSR spring, 8” wc to 10” wc (Black) 140,315,385,770 CTR-SP-T14400T0012 HSR spring, 10” wc to 12.5” wc (Silver) 140,315,385,770 CTR-SPT14401T0012 HSR spring, 12.5” wc to 20” wc (Gray)
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 79
Page 79
WARRANTY
12. Equipment warranty -
repair and return procedure
This warranty shall apply to items manufactured by Tecvalco, and supplied to Buyer for use within a Tecvalco authorized distribution territory. Items manufactured by Tecvalco and supplied to the Buyer for use in locations within Canada or the United States are subject to the equipment warranty as applicable.
Warranty During the warranty period subject to the limitations herein, Tecvalco warrants that the product manufactured by any Tecvalco company and supplied to Buyer by Tecvalco or through an authorized Tecvalco distributor shall be free from defects in materials and workmanship and will conform to applicable specifications and drawings. This warranty extends only to the original end use customer and is not transferable. Tecvalco’s liability herein, whether based upon breach of warranty or contract or negligence in manufacture, shall be limited to replacement, repair or refund of a prorated purchase price paid by Buyer at Tecvalco’s election of all such defective or nonconforming items, provided that this warranty shall apply only where Buyer has given Tecvalco written notice of such defects or nonconformity within the applicable warranty period after delivery by Tecvalco of such items to the Buyer. In no event shall Tecvalco’s total liability hereunder exceed the price paid by Buyer to Tecvalco for such item. Tecvalco shall have the right prior to return to inspect at Buyer’s facility any items claimed to be defective or nonconforming.
Warranty Period The warranty period for Tecvalco manufactured products commences from the date of invoice to the Buyer and except as noted below, continues for a period of 18 months (the Warranty Period). Exceptions to this warranty period are as follows: items not manufactured by Tecvalco will carry the remaining warranty and related terms and conditions of the original manufacturer, where enforceable.
The foregoing constitutes the sole and exclusive remedy of the Buyer and exclu­sive liability of Tecvalco and is in lieu of any and all other warranties expressed or implied or statutory as to merchant liability, fitness for purpose sold, description, quality, productiveness or any other matter. Without limiting the foregoing, in no event shall Tecvalco or its suppliers be liable to Buyer for any incidental, special, punitive, exemplary or consequential damages experienced by either Buyer or a third party (including, but not limited to loss of profits or loss of use). Tecvalco is not liable for damages for any cause whatsoever (whether based in contract, tort, or otherwise) in excess of the amount paid for the item.
Page 80
Page 80
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Returns Repair of all defective or malfunctioning products by Tecvalco will be made at a location determined solely by Tecvalco. Return authorization must be obtained in writing from Tecvalco including those for repair, Buyer’s rights to repair or replacement are governed by this warranty.
Shipping The Buyer shall pay the cost of shipping the products from the Buyer’s facility to a Tecvalco designated repair location. Tecvalco will return repaired or replaced equipment at Buyer’s cost to the Buyer’s facility. Buyer shall be responsible for payment of customs duties, importation fees, VAT or other like charges.
Repair Charges In-warranty period repairs will be made at no charge to Buyer provided that failure is not due to misuse, mishandling, or act of God. An in-warranty product that is returned for repair and found not to be defective or malfunctioning or for which failure is caused by misuse, mishandling, or act of God, shall be subject to Tecvalco’s actual costs for testing and handling.
WARRANTY
The costs of out-of-warranty repairs including return shipment are subject to charges as quoted by Tecvalco. Buyer’s acceptance of these charges is necessary before repairs will be made. Return shipping shall use the most economical shipment means available. Upon request of the Buyer, Tecvalco will use other means of shipment, in which case Buyer shall pay the cost of shipping directly.
Repair Warranty Repair work performed on in-warranty products is warranted for the remainder of the original warranty period or six (6) months, whichever is greater. Repair work performed on out-of-warranty equipment is warranted for six (6) months from the date of shipment of the repaired unit from Tecvalco. This six (6) month period covers only the actual repair(s) made to the product and is exclusive of potential non-related faults that may occur during the six (6) month period.
Alteration to Equipment Purchased Modification or alteration to purchased products by anyone, other than that specifically authorized by Tecvalco, shall void and nullify, in its entirety, all warranty provisions set forth in the preceding.
Engineering Changes Tecvalco reserves the right to upgrade and modify product items ordered without prior approval or modification to Buyer and without incurring any obligation or liability to make the same or similar changes in items previously manufactured.
Post-Sale Support Please contact your authorized Tecvalco distributor or call Tecvalco Technical Support at 1-877-879-4748.
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 81
APPENDIX A:
CWT 140,000 BTU/HR EVAPORATOR PACKING LIST
ITEM PART NUMBER PART TITLE PART DESCRIPTION QTY
1 CTR-SP-289H-41 289 BP FISHER REGULATOR 1” NPT, 1-4.5p 1
2 CTR-SP-HSR-CHCBMYY HSR REGULATOR HSR-1/2” ORIFICE, 10”-12.5” w.c. 1
3 FIC-CLMA1216-S316 90 DEG ELBOW 3/4”T x 1”NPT SST ELBOW 90 1
4 FIT-SST-BUSH-1-.25 BUSHING 1” x 1/4” SCH40 SST BUSHING 1
5 FIT-SST-NIP-1-2 NIPPLE 1” x 2” SCH40 SST NIPPLE 2
6 FIT-SST-NIP-1-4 NIPPLE 1” x 4” SCH40 SST NIPPLE 1
7 FIT-SST-NIP-1-6 NIPPLE 1” x 6” SCH40 SST NIPPLE 1
8 FIT-SST-TEE-150-1 TEE 1” 150#NPT 316 TEE 2
9 GAU-INCH-2.5-.25-0-15 GAUGE 2-1/2” x 1/4” 0-15 INCH GAUGE 1
10 VAV-SS-B-1-2000-T-FP BALL VALVE 1” 2000# SS FP BALL VALVE 1
11 CLA-GEAR-10 GEAR CLAMP 10” CLAMP 1
12 FIR-BVENT-6-3 EXHAUST STACK 6” x 3’ B-VENT SECTION 1
13 FIR-BVENT-6-5 EXHAUST STACK 6” x 5’ B-VENT SECTION 1
14 FIR-BVENT-HWCAP-6 EXHAUST STACK 6” HI-WIND CAP 1
15 HE A-140-2-1100 EXHAUST STACK STACK SUPPORT ARM, 140 HEATER 1
16 BOL-GR5-.5-1.5 BOLT NC, GR ADE 5, 1/2” x 1-1/2” 14
17 WAS -GR5-F-.5 WASHER 1/2” GRADE 5 FLAT WASHER 4
18 WAS -GR5-L-.5 LOCK WASHER 1/2” GRADE 5 LOCK WASHER 2
19 CTR-HIGH-TEMP-SHUT-DOWN ASSEMBLY HI-TEMPERATURE SHUT DOWN ASSEMBLY AS REQUIRED
20 CTR-SS-T675A-2084 REMOTE TEMP CONTROL T675A-2084 Honeywell Ins.Thm. 1
21 ELE-A10P8 ELECTRICAL PANEL PANEL, 8” x 6” 1
22 ELE-BOX-A1086CHQRFG ELECTRICAL BOX HOFFMAN 10x8x6 FIB JB 1
23 FIE-5232 CONDUIT C16104 STR LIQ TIGHT CON 1/2” 2
24 FIE-AL-NIP-.5-C NIPPLE 1/2” x CLOSE ALUMINUM NIPPLE 1
25 FIE-CSA050-30 FLEX CONDUIT 1/2” LIQUID TITE FLEX CONDUIT 5.25 m
26 FIE-GK50N ENCLOSURE 1/2” GK50N ENCLOSURE 35/85 GSK 1
27 FIE-K50A BACK PLATE 1/2” ALUM K50A BLANK BACKPLATE 1
28 FIE-LB50A ALUMINUM CONDUIT 1/2” LB50A ALUMINUM COND BODY 1
29 FIE-ST-050-464 CONNECTOR 1/2” STO50-464 STAR TECK CONN 2
30 FIE-UNY50NRA UNION 1/2” XP ALUM. UNION UNY50NRA 1
31 GAU-4-.5B-2000P GAUGE 4” x 1/2” 0-2000 PSI BM GAUGE 2
32 HEA-EVAP-MANUAL-006 MANUAL EVAP MANUAL REVISED, REV 6 1
33 HEA-QA-MANUAL MANUAL QUALITY ASSURANCE MANUAL 3
34 NUT-GR5-.5 NC NUT 1/2” GR ADE 5 NC NUT 2
35 NUT-LOCK-.75 LOCK NUT 3/4” LOCK NUT 3
36 THR-THERMOWELL TBD BY SALES
37 WIR-SHCAP-1P-18G CABLE 18 GAUGE x 1 PAIR SHIELDED CABLE 31 m
Page 82
PN :: HEA -EVA P-MA NUAL-016 | 20170316
APPENDIX B:
CWT 315,000 BTU/HR EVAPORATOR PACKING LIST
ITEM PART NUMBER PART TITLE PART DESCRIPTION QTY
1 CTR-SP-289H-41 289 BP FISHER REGULATOR 1” NPT, 1-4.5p 1
2 CTR-SP-HSR-CHCBMYY HSR REGULATOR HSR-1/2” ORIFICE, 10”-12.5” w.c. 1
3 FIC-CMC1216N-S316 CONNECTOR 3/4” T x 1” MNPT SS CONNECTOR 1
4 FIT-SST-BUSH-1-.25 BUSHING 1” x 1/4” SCH40 SST BUSHING 1
5 FIT-SST-NIP-1-2 NIPPLE 1” x 2” SCH40 SST NIPPLE 2
6 FIT-SST-TEE-150-1 TEE 1” 150#NPT 316 TEE 2
7 GAU-INCH-2.5-.25-0-15 GAUGE 2-1/2” x 1/4” 0-15 INCH GAUGE 1
8 VAV-SS-B-1-2000-T-FP BALL VALVE 1” 2000# SS FP BALL VALVE 1
9 FIR-BVENT-8-3 EXHAUST STACK 8” x 3’ B-VENT SECTION 1
10 FIR-BVENT-8-5 EXHAUST STACK 8” x 5’ B-VENT SECTION 1
11 FIR-BVENT-RAINCAP-8 EXHAUST STACK 8” B-VENT R AIN CAP 1
12 HE A-BVENT-SUPPORT-8 EXHAUST STACK 8” BVENT STACK SUPPORT 1
13 BOL-GR5-.5-1.5 BOLT NC, GR ADE 5, 1/2” x 1-1/2” 12
14 NUT-GR2-.5 NC NUT 1/2” GR ADE 2 NC NUT 12
15 WAS -GR5-F-.5 WASHER 1/2” GRADE 5 FLAT WASHER 24
16 CTR-HIGH-TEMP-SHUT-DOWN ASSEMBLY HI-TEMPERATURE SHUT DOWN ASSEMBLY AS REQUIRED
17 GAU-3-6-50-500-S GAUGE 3” x 6” 50-500 DEG GUAGE 1
18 CTR-SS-T675A-2084 REMOTE TEMP CONTROL T675A-2084 Honeywell Ins.Thm. 1
19 ELE-A10P8 ELECTRICAL PANEL PANEL, 8” x 6” 1
20 ELE-BOX-A1086CHQRFG ELECTRICAL BOX HOFFMAN 10x8x6 FIB JB 1
21 FIE-5232 CONDUIT C16104 STR LIQ TIGHT CON 1/2” 2
22 FIE-AL-NIP-.5-C NIPPLE 1/2” x CLOSE ALUMINUM NIPPLE 1
23 FIE-CSA050-30 FLEX CONDUIT 1/2” LIQUID TITE FLEX CONDUIT 5.25 m
24 FIE-GK50N ENCLOSURE 1/2” GK50N ENCLOSURE 35/85 GSK 1
25 FIE-K50A BACK PLATE 1/2” ALUM K50A BLANK BACKPLATE 1
26 FIE-LB50A ALUMINUM CONDUIT 1/2” LB50A ALUMINUM COND BODY 1
27 FIE-ST-050-464 CONNECTOR 1/2” STO50-464 STAR TECK CONN 2
28 FIE-UNY50NRA UNION 1/2” XP ALUM. UNION UNY50NRA 1
29 GAU-4-.5B-2000P GAUGE 4” x 1/2” 0-2000 PSI BM GAUGE 2
30 HEA-EVAP-MANUAL-006 MANUAL EVAP MANUAL REVISED, REV 6 3
31 HEA-QA-MANUAL MANUAL QUALITY ASSURANCE MANUAL 1
32 THR-THERMOWELL TBD BY SALES
33 WIR-SHCAP-1P-18G CABLE 18 GAUGE x 1 PAIR SHIELDED CABLE 31 m
FUEL GAS HEADER ASSEMBLY - P103-315
EXHUAST STACK ASSEMBLY
HI TEMP SHUT DOWN ASSEMBLY
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 83
APPENDIX C:
CWT 385,000 BTU/HR EVAPORATOR PACKING LIST
ITEM PART NUMBER PART TITLE PART DESCRIPTION QTY
1 HEA-GAS-HEADER-ASSM GAS TR AIN JOB SPECIFIC GAS HEADER ASSEMBLY 1
2 FIC-CLMA1216-S316 90 DEG ELBOW 3/4” T x 1” NPT SST ELBOW 90 1
3 FIR-BVENT-8-3 EXHAUST STACK 8” x 3’ B-VENT SECTION 1
4 FIR-BVENT-8-5 EXHAUST STACK 8” x 5’ B-VENT SECTION 1
5 FIR-BVENT-RAINCAP-8 EXHAUST STACK 8” B-VENT RAIN CAP 1
6 HEA-BVENT-SUPPORT-8 EXHAUST STACK 8” BVENT STACK SUPPORT 1
7 BOL-GR5-.5-1.5 BOLT NC, GR ADE 5, 1/2” x 1-1/2” 12
8 NUT-GR2-.5 NC NUT 1/2” GR ADE 2 NC NUT 12
9 WAS -GR5-L-.5 LOCK WASHER 1/2” GRADE 5 LOCK WASHER 24
10 CTR-HIGH-TEMP-SHUT-DOWN ASSEMBLY HI-TEMPERATURE SHUT DOWN ASSEMBLY AS
REQUIRED
11 GAU-3-6-50-500-S GAUGE 3” x 6” 50-500 DEG GUAGE 1
12 CTR-SS-T675A-2084 REMOTE TEMP CONTROL T675A-2084 Honey well Ins.Thm. 1
13 ELE-A10P8 ELECTRICAL PANEL PANEL, 8” x 6” 1
14 ELE-BOX-A1086CHQRFG ELECTRICAL BOX HOFFM AN 10x8x6 FIB JB 1
15 FIE-5232 CONDUIT C16104 STR LIQ TIGHT CON 1/2” 2
16 FIE-AL-NIP-.5-C NIPPLE 1/2” x CLOSE ALUMINUM NIPPLE 1
17 FIE-CSA050-30 FLEX CONDUIT 1/2” LIQUID TITE FLEX CONDUIT 5.25 m
18 FIE-GK50N ENCLOSURE 1/2” GK50N ENCLOSURE 35/85 GSK 1
19 FIE-K50A BACK PLATE 1/2” ALUM K50A BLANK BACKPLATE 1
20 FIE-LB50A ALUMINUM CONDUIT 1/2” LB50A ALUMINUM COND BODY 1
21 FIE-ST-050-464 CONNECTOR 1/2” STO50-464 STAR TECK CONN 2
22 FIE-UNY50NRA UNION 1/2” XP ALUM. UNION UNY50NRA 1
23 GAU-4-.5B-2000P GAUGE 4” x 1/2” 0-2000 PSI BM GAUGE 2
24 HEA-EVAP-MANUAL-006 MANUAL EVAP MANUAL REVISED, REV 6 3
25 HEA-QA-MANUAL MANUAL QUALITY ASSURANCE MANUAL 3
26 THR-THER MOWELL TBD BY SALES
27 WIR-SHCAP-1P-18G CABLE 18 GAUGE x 1 PAIR SHIELDED CABLE 31 m
FUEL GAS HEADER ASSEMBLY - P103-385
EXHUAST STACK ASSEMBLY
HI TEMP SHUT DOWN ASSEMBLY
Page 84
PN :: HEA -EVA P-MA NUAL-016 | 20170316
APPENDIX D:
CWT 770,000 BTU/HR EVAPORATOR PACKING LIST
ITEM PART NUMBER PART TITLE PART DESCRIPTION QTY
1 HEA-GAS-HEADER-ASSM GAS TRAIN JOB SPECIFIC GAS HEADER ASSEMBLY 1
2 FIR-BVENT-12-3 EXHAUST STACK 12” x 3’ B-VENT SECTION 3
3 FIR-BVENT-R AINCAP-12 EXHAUST STACK 12” B-VENT RAIN CAP 1
4 HEA-770-2-800 EXHAUST STACK 770 BOILER/EVAP STACK SUPPORT 1
5 BOL-GR5-.5-1.5 BOLT NC, GRADE 5, 1/2” x 1-1/2” 12
6 NUT-GR2-.5 NC NUT 1/2” GRADE 2 NC NUT 12
7 WAS-GR5-L-.5 LOCK WASHER 1/2” GRADE 5 LOCK WASHER 24
8 CTR-HIGH-TEMP-SHUT-DOWN ASSEMBLY HI-TEMPERATURE SHUT DOWN ASSEMBLY AS REQUIRED
9 GAU-3-12-50-500-S GAUGE 3” x 12” 50-500 DEG GUAGE 1
10 CTR-SS-T678A-1163 REMOTE TEMP CONTROL T678A-1163 Honeywell Temp. Con. 1
11 ELE-A10P8 ELECTRICAL PANEL PANEL, 8” x 6” 1
12 ELE-BOX-A1086CHQRFG ELECTRICAL BOX HOFFMAN 10x8x6 FIB JB 1
13 FIE-5232 CONDUIT C16104 STR LIQ TIGHT CON 1/2” 2
14 FIE-AL-NIP-.5-C NIPPLE 1/2” x CLOSE ALUMINUM NIPPLE 1
15 FIE-CSA050-30 FLEX CONDUIT 1/2” LIQUID TITE FLEX CONDUIT 5.5 m
16 FIE-GK50N ENCLOSURE 1/2” GK50N ENCLOSURE 35/85 GSK 1
17 FIE-K50A BACK PLATE 1/2” ALUM K50A BLANK BACKPLATE 1
18 FIE-LB50A ALUMINUM CONDUIT 1/2” LB50A ALUMINUM COND BODY 1
19 FIE-ST-050-465 CONNECTOR 1/2” STO50-465 STAR TECK CONN 2
20 FIE-UNY50NRA UNION 1/2” XP ALUM. UNION UNY50NRA 1
21 GAU-4-.5B-2000P GAUGE 4” x 1/2” 0-2000 PSI BM GAUGE 2
22 HEA-EVAP-MANUAL-006 MANUAL EVAP MANUAL REVISED, REV 6 3
23 HEA-QA-MANUAL MANUAL QUALITY ASSURANCE MANUAL 1
24 THR-THERMOWELL TBD BY SALES
25 WIR-SHCAP-2P-18G CABLE 18 GAUGE x 2 PAIR SHIELDED CABLE 35 m
FUEL GAS HEADER ASSEMBLY - P103-770
EXHUAST STACK ASSEMBLY
HI TEMP SHUT DOWN ASSEMBLY
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 85
APPENDIX E:
CWT 140 Exhaust Stack Assembly
Page 86
PN :: HEA -EVA P-MA NUAL-016 | 20170316
APPENDIX F:
CWT 315 Exhaust Stack Assembly
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 87
APPENDIX G:
CWT 385 Exhaust Stack Assembly
Page 88
PN :: HEA -EVA P-MA NUAL-016 | 20170316
APPENDIX H:
CWT 770 Exhaust Stack Assembly
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 89
APPENDIX I:
DLH 140 Burner Assembly and Cross-Section Drawings
Page 90
PN :: HEA -EVA P-MA NUAL-016 | 20170316
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 91
APPENDIX J:
DLH 315 Burner Assembly and Cross-Section Drawings
Page 92
PN :: HEA -EVA P-MA NUAL-016 | 20170316
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 93
APPENDIX K:
DLH 385 Burner Assembly and Cross-Section Drawings
Page 94
PN :: HEA -EVA P-MA NUAL-016 | 20170316
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 95
APPENDIX L:
DLH 770 Burner Assembly and Cross-Section Drawings
Page 96
PN :: HEA -EVA P-MA NUAL-016 | 20170316
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Page 97
APPENDIX M:
CWT 140 Fuel Gas Train
Page 98
PN :: HEA -EVA P-MA NUAL-016 | 20170316
Loading...