Tecumseh VSC9534ZNAHM User Manual

Oil Ch.
Suction Liquid Oz.
Factory charge 20 psig dry air, MUST BE EVACUATED
Ambient Temperatures
T, °F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
-10 23.2 19100 3790 91 17900 4280 101 17200 4500 105 16300 4720 110 13400 5330 125
-5 27.5 21000 3840 92 19600 4340 102 18800 4570 107 17900 4790 111 14700 5430 126 0 32.1 23500 3910 93 21900 4410 103 21000 4650 108 20000 4880 113 16600 5540 127 5 37.0 26600 4000 94 24700 4510 104 23700 4750 109 22500 4980 114 18900 5660 128
10 42.4 30100 4100 96 28000 4610 105 26800 4860 110 25500 5090 115 21500 5790 130 15 48.2 34000 4210 97 31500 4730 107 30200 4970 112 28800 5210 116 24400 5920 131
20 54.5 38200 4330 99 35300 4850 108 33800 5090 113 32200 5330 118 27500 6050 132
25 61.2 42500 4460 100 39300 4970 110 37600 5210 114 35900 5450 119 30600 6170 133 30 68.4 47000 4590 102 43400 5090 111 41500 5330 116 39500 5570 121 33700 6290 135 35 76.1 51500 4720 104 47400 5210 113 45300 5450 118 43200 5680 122 36800 6400 136
40 84.4 55900 4840 106 51400 5320 115 49000 5550 119 46700 5790 124 39700 6500 137
Gross weight
Lbs. (kg)
480 (218)
H
90% @ 90oF
115°F
80°F
4500
L
W
Overall Dimensions, inch (mm)
Line connections
Pumpdown
Air flow
33.44
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, SubCooling 5oF
Evaporator
VSC9534ZNAHM
90°F
95°F
100°F
SCFM
29.40 (747)
47.75 (1213)
31.58 (802)
TECUMSEH OUTDOOR
CONDENSING UNIT
Model VSC9534ZNAHM BOM 32L4097-2E*
Air Cooled 4 HP Application Commercial Temp Refrigerant R404A Volts-Hz-Ph 208-230/60/1
VSC9534ZNAHM_Rev.1
TPC - May 11, 2015
* OPTION CODE: See reverse side for Available Options
Unit BOM 32L4097-2E Fan Motor 810S186B40
Unit MODEL VSC9534ZNAHM Replacement Fan Motor 32Lxxxx-2ER(F)ATnD
Fan Motor Qty 2 R Heated/Insulated Receiver Refrigeration Range -10°F to 40°F Fan Motor RLA 1.9 F Fixed Fan Control Design Pressure Low / High 181 / 450 Fan Blade 51528-3 A Adjustable Fan Control Volts - HZ - Ph 208-230/60/1 Fan Guard 70832 T1 Air Defrost Timer Voltage Range 187 - 253 Shroud 70611-1 T2 Electrical Defrost Timer & Defrost Min. Circuit Ampacity 34.51 Heater Contactor Max. Fuse Size 60 High Pressure Switch 84095-2L D Disconnect Switch (nonfused)
Low Pressure Control 84026-2 Compressor MODEL VSC9530ZNA Dual Pressure Conrol Compressor BOM VS224ET-104-J7 Compressor LRA 150 Head Master Valve 70107-1 Solenoid Valve (supplied loose) KSVC-264 Compressor RLA 24.40 Check Valve 56627 Hail Louver Assy LLPG-301
Process Valve OverLoad Internal Discharge Valve 31590 Replacement Kit - O/L Liquid Valve (Base) 56500-K08 Receiver Heater (R option) 92124-2 Relay Liquid Valve (Receiver) 56596 Receiver Thermostat (R option) 84102-2 Replacement Kit - Relay Suction Valve (Base) 315-10016 Fixed Fan Control (F option) Run Capacitor 85PR370F29 Suction Valve (Rotolock) 31529-2 Adjustable Fan Control (A option) Replacement Kit - Run Cap. Start Capacitor Condenser 50785-4 Defrost Timer (T1 or T2 option) 84110 Replacement Kit - St. Cap. Receiver 51084 Defrost Heater Contactor and 91014H Contactor 91012H Accumulator TK00046000 Auxiliary Switch (T2 opt.) 91014-AUH
Liquid Filter 52000-164D Unit Drawing DGU1950-L136 Sight Glass 70084-2S Disconnect (D option) Wiring Diagram WD21-2XT2C Suction Filter 70822-5S Wiring Diagram (A or F opt.) CrankCase Heater 92124-4
AVAILABLE ACCESSORIES
REPLACEMENT PARTS
Parts/Specifications
STANDARD
AVAILABLE OPTIONS
VSC9534ZNAHM_Rev.1
TPC - May 11, 2015