Tecumseh VSC9518XXTLN User Manual

Page 1
VSC9518XXTLN_Rel
Refrigerant
Overall Dimensions, inch (mm)
Line
connections
Pump down
(lbs.)
90% @ 90oF
Air flow
Oil
Ch.
Gross
weight
L W H
Suction
Liquid
SCFM
Oz.
Lbs. (kg)
R404A/R507
26.55 (674)
36.25 (921)
26.08 (662)
7/8"
1/2"
20.39
1500
36
410 (186)
R22
23.50
R134a
23.84
R407A
22.47
R407F
21.92
Units are factory charged with 20 psig dry air, MUST BE EVACUATED
TPC May 25, 2016
TECUMSEH OUTDOOR
CONDENSING UNIT
Model VSC9518XXTLN BOM 32L2166-6U
Air Cooled 2 HP Application Commercial Temp Refrigerant R404A/R507/R22/R134a/R407A/R407F Volts-Hz-Ph. 200-230/60/3
Page 2
VSC9518XXTLN R404A / R507 Performance
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, Sub Cooling 5oF
Evaporator
Ambient Temperatures
90°F
95°F
100°F
110°F
115°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
24.8
5300
2050
97
4900
2180
102
4500
2320
106
3800
2600
116
3500
2740
120
-5
29.1
7500
2060
98
7100
2200
103
6600
2350
107
5800
2630
117
5400
2780
121 0 33.9
9700
2080
99
9200
2230
104
8700
2370
109
7800
2670
118
7300
2820
123 5 39.0
11900
2100
101
11300
2250
105
10700
2400
110
9700
2700
119
9100
2850
124
10
44.5
14000
2120
102
13300
2270
107
12700
2430
111
11500
2740
121
10900
2890
125
15
50.4
16000
2140
104
15300
2300
108
14600
2460
113
13300
2770
122
12600
2930
127
20
56.8
18000
2170
105
17300
2330
110
16500
2490
114
15000
2810
124
14200
2970
128
25
63.6
20000
2210
107
19200
2380
112
18300
2540
116
16700
2860
125
15800
3020
129
30
70.9
21900
2260
109
21000
2430
113
20100
2590
118
18300
2910
127
17300
3080
131
35
78.8
23800
2320
111
22800
2490
115
21800
2650
120
19800
2980
128
18800
3140
132
40
87.1
25600
2400
113
24500
2560
117
23500
2720
121
21300
3050
130
20200
3210
134
45
96.0
27400
2480
115
26200
2650
119
25100
2810
123
22700
3130
131
21500
3290
135
VSC9518XXTLN R22 Performance
Performance @ 60 Hz, Suction Super Heat (MAX.) 20oF, Sub Cooling 5oF Preliminary Data
Evaporator
Ambient Temperatures
90°F
95°F
100°F
110°F
115°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
16.7 -5
20.3 0
24.2
9700
1710
101
9200
1770
105
8700
1840
110 5 28.5
10800
1750
102
10300
1820
107
9800
1900
111
9000
2050
120 10
33.0
12000
1800
103
11600
1870
108
11100
1950
112
10300
2110
121
9900
2190
126
15
38.0
13500
1850
105
13000
1920
109
12600
2000
114
11700
2170
123
11300
2260
127
20
43.3
15100
1900
107
14700
1980
111
14200
2060
115
13300
2230
124
12900
2320
129
25
49.0
17000
1950
108
16500
2030
113
16000
2110
117
15100
2290
126
14600
2390
130
30
55.2
19000
2000
110
18500
2090
115
18000
2170
119
17000
2350
128
16500
2450
132
35
61.7
21100
2060
113
20600
2140
117
20100
2230
121
19100
2420
130
18500
2520
134
40
68.8
23500
2120
115
23000
2200
119
22400
2290
123
21200
2480
132
20600
2580
136
45
76.3
26000
2180
117
25500
2260
121
24800
2350
126
23600
2540
134
22900
2640
138
VSC9518XXTLN R134a Performance
Performance @ 60 Hz, Suction Super Heat (MAX.) 20oF, Sub Cooling 5oF Preliminary Data
Evaporator
Ambient Temperatures
90°F
95°F
100°F
110°F
115°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
10
12.1
8300
1290
100
8000
1340
105
7800
1400
110
7200
1510
119
6900
1570
124
15
15.2
9400
1310
102
9200
1370
106
8900
1420
111
8300
1540
120
8000
1610
125
20
18.6
10700
1340
103
10400
1400
108
10100
1450
112
9400
1580
122
9100
1640
126
25
22.3
12100
1370
104
11700
1430
109
11400
1480
114
10700
1610
123
10300
1680
127
30
26.3
13500
1400
106
13200
1460
111
12800
1520
115
12000
1640
124
11600
1710
129
35
30.6
15100
1430
108
14700
1490
112
14300
1550
117
13500
1680
126
13000
1750
130
40
35.2
16700
1460
109
16300
1520
114
15900
1580
118
15000
1720
127
14500
1790
132
45
40.2
18500
1500
111
18000
1560
116
17500
1620
120
16600
1760
129
16100
1830
133
50
45.6
20300
1540
113
19800
1600
118
19300
1660
122
18300
1800
131
17700
1870
135
VSC9518XXTLN_Rel
TPC May 25, 2016
Page 3
VSC9518XXTLN_Rel
VSC9518XXTLN R407A Performance
Performance @ 60 Hz, Suction Super Heat (MAX.) 18oF, Sub Cooling 5oF Preliminary Data
Evaporator
Ambient Temperatures
90°F
95°F
100°F
110°F
115°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
23.4 -5
27.7
8000
1870
105
7600
1950
109 0
32.4
9300
1920
106
8900
2000
110 5
37.5
10600
1970
108
10200
2060
112
9700
2150
116
8800
2340
125 10
43.0
12000
2020
109
11600
2110
113
11100
2200
118
10100
2400
126 15
48.9
13600
2070
111
13100
2160
115
12500
2260
119
11500
2460
127
11000
2570
131
20
55.3
15200
2110
113
14700
2210
117
14100
2310
121
13000
2520
129
12400
2640
133
25
62.2
17000
2160
114
16400
2260
118
15800
2370
122
14600
2580
130
14000
2700
134
30
69.5
18800
2210
116
18200
2320
120
17600
2420
124
16300
2640
132
15600
2760
136
35
77.4
20800
2270
118
20200
2370
122
19500
2480
126
18100
2700
133 40
85.8
23000
2330
120
22200
2430
124
21500
2540
128
20000
2770
135 45
94.8
25200
2390
122
24400
2490
126
23600
2600
130
22100
2830
137
VSC9518XXTLN R407F Performance
Performance @ 60 Hz, Suction Super Heat (MAX.) 18oF, Sub Cooling 5oF Preliminary Data
Evaporator
Ambient Temperatures
90°F
95°F
100°F
110°F
115°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
25.3 -5
29.8 0
34.7
10500
1960
102 5 40.0
11900
2000
103
11500
2090
108
11000
2190
112
10
45.8
13500
2040
105
13000
2140
109
12500
2250
114
11500
2460
122 15
52.0
15200
2090
106
14700
2190
111
14100
2300
115
13000
2520
124
12500
2640
128
20
58.7
17000
2130
108
16500
2240
112
15900
2350
117
14700
2580
125
14100
2700
129
25
65.8
19000
2180
110
18300
2290
114
17700
2400
118
16400
2640
127 30
73.5
21000
2230
112
20400
2340
116
19700
2450
120
18300
2700
128 35
81.7
23200
2280
114
22500
2390
118
21800
2510
122
20300
2760
130 40
90.5
25600
2330
116
24800
2450
120
24000
2560
124
45
99.9
28000
2400
118
27200
2510
122
26400
2630
126
TPC May 25, 2016
Page 4
VSC9518XXTLN_Rel
Parts/Specifications
Unit BOM
32L2166-6U
Fan Motor
810F050C20
Adjustable Fan Control
14955874
Unit MODEL
VSC9518XXTLN
Replacement Fan Motor
50W230
Fixed Fan Control
----
Fan Motor Qty
2
Refrigeration Range
-10°F to 45°F
Fan Motor RLA
0.7
Defrost Timer
LTCG-T1
Design Pressure Low / High
181 / 450
Fan Blade
51568-1
Electric Defrost Timer
----
Volts - HZ - Ph
200-230V 3~ 60HZ
Fan Guard
70831
Voltage Range
180 - 253
Receiver Heater
-----
Min. Circuit Ampacity
13.24
Shroud
70648-2
Receiver Heater Thermostat
-----
Max. Fuse Size
20
Condenser
50858-1
C/Case Heater
92124-3
Compressor MODEL
VSC9515XXT
Receiver
51099-2L
Unit Drawing
DGU1950-L022
Compressor BOM
VS220RT-103-J7
Accumulator
----
Wiring Diagram
WD23-205A
Compressor LRA
60
Liquid Filter
52000-084D
Compressor RLA
9.30
Sight Glass
70084-2S
Suction Filter
----
OverLoad
Internal
Replacement Kit - O/L
----
High Pressure Switch
84095-2L
Relay
----
Low Pressure Control
84026-2
Replacement Kit - Relay
----
Low Pressure Switch
----
Run Capacitor
----
Head Master Valve
70083
Replacement Kit Run Cap.
----
Check Valve
----
Loose Optional Items
Start Capacitor
----
Liquid Valve
On the Receiver
Disconnect Switch
LDSG-332
Replacement Kit Start Cap
----
Suction Valve (Base)
56500-K14
Liquid Solenoid
KSVC-285
Contactor
91014H
Hail Louver
LLPG-201
TPC May 25, 2016