TECUMSEH HERMETIC
CONDENSING UNIT
Model VSAG515ZXTHM
BOM 32L3642-2E
Air Cooled 3 ¾ HP
Application Low Temp
VSAG515ZXTHM
TPC___preliminary
October 14, 2011
SUCTION 7/8"
31.58
4.50
LIQUID 1/2"
Refrigerant R404A
47.75
46.97
26.0029.00
Dim. Enclosure(inch)* Line connections
VSAG515ZXTHM
*) Enclosure Mounting Holes, 26.25 x 58.5
Factory charge 20 psig dry air,
Evaporator
PSIG BTUHWatts Head Cond TBTUHWatts Head Cond T BTUHWatts Head Cond TBTUHWatts Head Cond
T, °
-40 5.5 7000 2880 212 93 69 00 3090 243 102 680 0 322 0 261 107 6300 3520 299 117
-35 8.0 8100 2990 216 94 78 00 3190 248 103 770 0 332 0 265 108 7000 3620 304 118
-30 10.7 9300 3090 220 95 8900 3290 252 105 8700 3420 269 109 7900 3710 308 119
-25 14.0 10700 3190 224 96 10100 3390 256 106 9800 3520 273 110 8900 3810 312 120
-20 17.1 121 00 3290 228 98 11300 3490 259 107 1100 0 3610 277 11 1 100 00 390 0 316 121
-15 19.3 136 00 3390 232 99 12700 3600 263 108 1230 0 3720 281 11 2 111 00 400 0 319 122
-10 24.5 15200 3500 236 100 14100 3700 268 109 13600 3820 285 113 12300 4100 323 123
-5 28.8 16700 3620 240 101 15500 3820 272 110 15000 3930 289 115 13500 4210 327 124
0 33.5 18300 3740 245 103 16900 3940 277 111 16300 4060 294 116 14800 4330 331 125
5 36.5 19900 3870 251 104 18400 4070 282 113 17700 4190 299 117 16000 4460 336 126
10 43.7 21400 4020 256 106 19700 4210 28
Performance @ 60 Hz, Return gas 40
LWH
29.40 47.75 31.58
MUST BE EVACUATED
85°F 95°F 100°F 110°F
o
F, SubCooling 5oF
Suction Liquid
7/8 Sweat 1/2 Sweat
Ambient Tempera tures
114 19000 4330 304 118 17200 4590 341 12
Pumpdown
90% @ 90
o
F
33.44 4200
Air flow Oil Ch.
SCFM
Oz.
55
Gross weight
Lbs.
550
PRELIMINARY PERFORMANCE DATA
VSAG515ZXTHM
TPC___preliminary
October 14, 2011
Parts/Specifications
STANDARD OPTIONAL
Unit BOM 32L3642-2E
Unit MODEL
SAG515ZXTHM
Re fr ige r ation RANGE -40°F t o 10° F Fan Blad e 51528-3
De sign Pressure Low 181 Fan G uard 70832
De sign Pressure H i gh 450 S hroud 70611-1 Re ceiv er H eat er ( R) LHR- 223
Volts - HZ - Ph 200-230V 3~ 60HZ
Volta ge Ra nge 180 - 253 Hig h Pressure sw itch 84095- 2L Solenoi d Va lve (S) KSVC-285
Min. Circuit Ampacity 16.49 Low Pressure Control 84026-2
M ax. Fuse Size 25 Dua l Pressure Conr ol Disc onne c t (D ) KD SG- 301
Co m pre ssor MOD EL VSAG513ZXT Condense r 50785-4
Compressor BOM VS123RT-008-A4 Head Master Valve 70083
Compressor LRA 80 Check Valve 56626
Compressor RL
9.98 Process Valve
Ov erLoad INTERNAL Suct ion Valve 31529-2
Relay E Enclosure
Run Capacitor Receiver 51084 R Receiver Heater
Run Capacitor Rating Receiver Qty 1 A Adjustable fan control
St ar t C apacito r Accumulator TK00042 000 F Fixed fan C ontrol
St ar t Capacitor Rating Liquid Filt er 52000-164 D T1 Defrost timer optio n
Contactor 91014B Sight Glass 70084-2 T2 Defrost timer & Defrost Heaters Contactor
Unit Drawing DGU1950-L303 S Solenoid liquid Valve (supplied loose)
Wiring no Fan controls WD23-2XT2L CrankCase Heater 14947869
Fan Motor 810S186B40 Adjustable Fan Ctrl (A) LAFC-001
Fan M otor Qt y 2
Fan Motor RLA 1.9 Defrost Timer (Tn) LTCG-T2
BOM INDEX DESCRIPTION
Liquid V alve
32xYYYY - 2ERA(F)Tn DS
Suction Filter 70822-5S D Disconnect
POWER SUPPLY
208-230 / 60 / 3
COMPRESSOR
TERMINAL
DEFROST
HEATERS
CONTACTOR COIL
SOLENOID
LIQUID INJECTION
COMPRESSOR
CONTACTOR COIL
see note A
L3L2T3
L1 T1
GRD
C
S
T2
R
4
3
1
2
COMPRESSOR CONTACTOR
NC AUXILIARY SWITCH
COMPRESSOR CONTACTOR
NO AUXILIARY SWITCH
HP LP
RECEIVER
HEATER
CRANK CASE
HEATER
BLACK
RED
YELLOW
X
N
THERMOSTAT
COMPRESSOR
CONTACTOR
DEFROST CONTROL
RANCO 8145-xx
PRECISION 6145-xx
DT
TERMINAL
BOARD
T1L1T2
IMPORTANT:
COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD
PROTECTOR. ALLOW TIME FOR RESET.
USE COPPER CONDUCTORS ONLY.
(EMPLOYER DES CONDUCTEUERS DE CUIVER
SEULEMENT.)
FAN 1
FAN 2
L2
P1
L1
L3 T3T1 F1 F2
L2
L3
T3
DEFROST
HEATERS
CONTACTOR
L3
T1L1T2L2T3
NOTES
FIELD WIRING NOTES
1. ALL FIELD WIRING MUST BE DONE IN COMPLIANCE WITH ALL
APPLICABLE LOCAL AND NATIONAL CODES.
2. CONNECT INCOMING POWER LEADS FROM POWER SUPPLY
TO L1, L2, AND L3 IN COMPRESSOR CONTACTOR OR TO L1, L2 AND L3 IN
DISCONNECT SWITCH (IF PROVIDED). USE COOPER CONDUCTORS
ONLY. (EMPLOYER DES CONDUCTEURS DE CUIVER SEULEMENT.)
PROVIDE EQUIPMENT GROUNDING CONDUCTOR.
USE 75°C (MIN.) WIRING
3. DEFROST HEATERS LOADS SHOULD NOT BE HIGHER THEN THE
MAXIMUM HEATERS LOAD INDICATED ON THE UNIT LABEL.
DEFROST HEATERS TO BE CONTROLLED WITH A CONTACTOR AS SHOWN
ON THE DIAGRAM.
GENERAL NOTES:
A. CONTACTOR COIL CIRCUIT IS FACTORY CONNECTED TO 230 V SOURCE IN
PANEL AS SHOWN
B. COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR.
ALLOW TIME FOR RESET.
FC
FAN CONTROL
LP
LOW PRESSURE CONTROL
HP
HIGH PRESSURE SWITCH
DT
DISCHARGE LINE THERMOSTAT
FACTORY COMPONENTS
OPTIONAL FACTORY COMPONENTS
OPTIONAL FIELD COMPONENTS
CONDENSING UNIT WIRING, 230V 60Hz 3 Ph,
Liquid Injection Solenoid,
Fan control,
T1 & T2 defrost options
REL
REVISION
WD23-2XT2L
MAR. 11, 2011