Tecumseh VSAG511ZXTHN Performance Data Sheet

F
7
TECUMSEH HERMETIC
CONDENSING UNIT
Model VSAG511ZXTHN BOM 32L2642-2E
Air Cooled 2 ¾ HP Application Low Temp
VSAG511ZXTHN
TPC___preliminary
October 14, 2011
Refrigerant R404A
23.5025.50
35.38
36.25
SUCTION 7/8"
26.08
4.24
Dim. Enclosure(inch)* Line connections Gross weight
VSAG511ZXTHN
*) Enclosure Mounting Holes, 23.5 x 35.38 Factory charge 20 psig dry air,
Evaporator
PS IG B TU H Watts Head Con d T BT U H Watts Head Cond T BTU H Watts Head Co nd T BTU H Watts Head Con d T
T, °
-40 5.5 4700 2060 213 93 4600 2220 246 103 4600 2300 264 108 4200 2490 301 118
-35 8.0 5600 2140 217 94 5300 2300 250 104 5300 2380 267 109 4800 2570 304 118
-30 10.7 6400 2220 221 95 6100 2370 254 105 6000 2460 271 110 5400 2650 308 119
-25 14.0 7400 2290 225 97 6900 2450 257 106 6700 2540 274 111 6100 2730 311 120
-20 17.1 8400 2360 229 98 7800 2530 261 107 7600 2620 278 112 6800 2810 315 121
-15 19.3 9400 2440 233 99 8700 2610 266 108 8500 2700 282 113 7600 2890 319 122
-10 24.5 105 00 2520 238 101 9700 2690 270 110 9400 2780 287 114 8500 2970 323 123
-5 28.8 11700 2600 243 102 10800 2770 275 111 10500 2860 292 115 9500 3060 328 124 0 33.5 12900 2680 248 104 11900 2860 281 112 11500 2950 298 117 10500 3160 334 125 5 36.5 14200 2770 254 105 13100 2960 287 114 12700 3050 304 118 11600 3260 340 127
10 43 .
Pe rforma nc e @ 6 0 H z , Re turn ga s 4 0
155 00 2870 261 107 1440 0 3060 294 116 1390 0 3160 311 120 12700 336 0 347 128
LWH
26.43 36.25 26.08
MUST BE EVACUATED
85°F 95°F 100°F 110°F
o
F, SubCooling 5oF
Suction Liquid
7/8 Sweat 1/2 Sweat
Ambient Temperatures
Pumpdown Oil Ch.Air flow
90% @ 90
o
F
20.44 1525 55
SCFM Oz.
PRELIMINARY PERFORMANCE DATA
Lbs.
330
r
V
VSAG511ZXTHN
TPC___preliminary October 14, 2011
Parts/Specifications
STANDARD OPTIONAL
Unit BOM 32L2642-2E Unit MODEL
SAG511ZXTHN
Refrigeration RAN GE -40 °F to 10°F Fa n Blade 51568- 1 Desi gn Pressur e Low 181 Fan G uar d 70831 Desi gn Pressur e High 450 Shroud 70648- 2 Receiver H eater (R) LHR-22 2 Volts - HZ - Ph 200-230V 3~ 60HZ Voltage Range 180 - 253 High Pressure switch 84095-2L Solenoid Valve (S) KSVC-285 Min. Circuit Ampacity 14.11 Low Pressure Control 84026-2 M ax. Fuse Size 25 Dual Pr essure Conr ol Discon nect (D) KD SG-3 01
Co m pre ss or MOD EL VSA G49 4ZXT Conde nser 50858 Compressor BOM VS121RT-008-A4 Head Master Valve 70083 Compressor LRA 80 Check Valve 56626 Co m pre ss or RLA 10.00 Pro cess Valv e
OverLoad INTERNAL Suction Valve 31529-2 Relay E Enclosure Run Capacitor Receiver 51099-2L R Receiver Heater Run Capacitor Rating Receiver Qty 1 A Adjustable fan control Start Capacitor Accumulator TK00042000 F Fixed fan Control Start C apacitor Rating Liqu id Filter 52000-0 84D T1 Defrost timer option Contactor 91014B Sight Glass 70084-2 T2 Defrost timer & Defro s t Heaters Con tact or
Unit Drawing DGU1950-L301 S Solenoid liquid Valve (supplied loose) Wiring no Fan controls WD23-2XT2L CrankCase Heater 14947869
Fan Mo to
810F050C20 Adjustable Fan Ctrl (A) LAFC-001 Fan Mo tor Qty 2 Fan Motor RLA 0.7 Defrost Timer (Tn) LTCG-T2
BOM INDEX DESCRIPTION
Liquid Valve
32xYYYY- 2E RA(F)TnDS
Suction Filter 70822-5S D Discon nect
POWER SUPPLY
208-230 / 60 / 3
COMPRESSOR
TERMINAL
DEFROST HEATERS
CONTACTOR COIL
SOLENOID
LIQUID INJECTION
COMPRESSOR
CONTACTOR COIL
see note A
L3L2T3
L1 T1
GRD
C
S R
T2
4
3
1
2
COMPRESSOR CONTACTOR
NC AUXILIARY SWITCH
COMPRESSOR CONTACTOR
NO AUXILIARY SWITCH
HP LP
RECEIVER
HEATER
CRANK CASE
HEATER
BLACK
RED
YELLOW
X
N
THERMOSTAT
COMPRESSOR
CONTACTOR
DEFROST CONTROL RANCO 8145-xx PRECISION 6145-xx
DT
TERMINAL
BOARD
T1L1T2
IMPORTANT:
COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR. ALLOW TIME FOR RESET. USE COPPER CONDUCTORS ONLY. (EMPLOYER DES CONDUCTEUERS DE CUIVER SEULEMENT.)
FAN 1
FAN 2
L2
P1
L1
L3 T3T1 F1 F2
L2
L3
T3
DEFROST HEATERS
CONTACTOR
L3
T1L1T2L2T3
NOTES
FIELD WIRING NOTES
1. ALL FIELD WIRING MUST BE DONE IN COMPLIANCE WITH ALL APPLICABLE LOCAL AND NATION AL CODES.
2. CONNECT INCOMING POWER LEADS FROM POWER SUPPLY TO L1, L2, AND L3 IN COMPRESSOR CONTACTOR OR TO L1, L2 AND L3 IN DISCONNECT SWITCH (IF PROVIDED). USE COOPER CONDUCTORS ONLY. (EMPLOYER DES CONDUC TEURS DE CUIVER SEULEMENT.) PROVIDE EQUIPMENT GROUNDING CONDUCTOR. USE 75°C (MIN.) WIRING
3. DEFROST HEATERS LOADS SHOULD NOT BE HIGHER THEN THE MAXIMUM HEATERS LOAD INDICATED ON THE UNIT LABEL. DEFROST HEATERS TO BE CONTROLLED WITH A CONTACTOR AS SHOWN ON THE DIAGRAM.
GENERAL NOTES:
A. CONTACTOR COIL CIRCU IT IS FACTORY CONNECTED TO 230 V SO URCE IN PANEL AS SHOWN B. COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR. ALLOW TIME FOR RESET.
FC
FAN CONTROL
LP
LOW PRESSURE CONTROL
HP
HIGH PRESSURE SWITCH
DT
DISCHARGE LINE THERMOSTAT
FACTORY COMPONENTS
OPTIONAL FACTORY COMPONENTS
OPTIONAL FIELD COMPONENTS
CONDENSING UNIT WIRING, 230V 60Hz 3 Ph,
Liquid Injection Solenoid, Fan control, T1 & T2 defrost options
REL
REVISION
WD23-2XT2L
MAR. 11, 2011
Loading...