Tecumseh AWG4530WXNLN User Manual

AWG4530WXNLN_Rel
AWG4530WXNLN
Overall Dimensions, inch (mm)
Line connections
Pump down
Air flow
Oil Ch.
Gross weight
L W H
Suction
Liquid
90% @ 90oF
SCFM
Oz.
Lbs. (kg)
26.55 (674)
36.25 (921)
26.08 (662)
7/8"
3/8"
23.26
1750
33.86
280 (127)
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
Ambient Temperatures
80°F
90°F
95°F
100°F
110°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
10
32.8
17000
2310
96
15500
2370
106
14700
2390
111
14000
2420
116
12700
2480
126
15
37.7
19000
2470
98
17400
2530
108
16600
2560
113
15800
2590
118
14300
2660
128
20
43.0
21200
2620
101
19500
2690
110
18600
2720
115
17700
2760
120
16000
2840
130
25
48.8
23500
2770
103
21700
2850
112
20700
2890
117
19800
2930
122
17900
3030
132
30
54.9
25900
2920
106
23900
3000
115
23000
3050
119
21900
3100
124
19900
3200
134
35
61.5
28400
3070
109
26400
3160
117
25300
3210
122
24200
3260
126
22000
3380
136
40
68.5
31000
3210
112
28900
3310
120
27800
3370
124
26600
3430
129
24200
3560
138
45
76.0
33700
3360
115
31600
3460
122
30400
3520
127
29200
3590
131
26600
3740
141
50
84.0
36600
3490
118
34300
3610
125
33100
3680
129
31800
3750
134
29100
3920
143
55
92.6
39600
3630
121
37200
3760
128
36000
3830
132
34600
3910
136
31700
4090
146
R22 Capacity Performance @ 60 Hz, Return Gas Temperature 65oF, --- Sub Cooling 5oF, shown above R407C Capacity performance factor: 0.87 (Multiply the R22 BTU/Hr. by 0.87 to determine the Capacity at R407C)
TPC April 12, 2016
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWG4530WXNLN BOM 32L2186-6U
Air Cooled 2 1/2 HP Application High Temp Refrigerant R22 / R407C Volts-Hz-Ph. 208-230/60/1
AWG4530WXNLN_Rel
Parts/Specifications
Unit BOM
32L2186-6U
Fan Motor
810F050C20
Adjustable Fan Control
14955874
Unit MODEL
AWG4530WXNLN
Replacement Fan Motor
50W230
Fixed Fan Control
----
Fan Motor Qty
2
Refrigeration Range
20°F to 55°F
Fan Motor RLA
0.7
Defrost Timer
LTCG-T1
Design Pressure Low / High
150 / 450
Fan Blade
51568-1
Electric Defrost Timer
----
Volts - HZ - Ph
208-230V ~ 60HZ
Fan Guard
70831
Voltage Range
187 - 253
Receiver Heater
-----
Min. Circuit Ampacity
19.61
Shroud
70648-2
Receiver Heater Thermostat
-----
Max. Fuse Size
35
Condenser
50858-1
C/Case Heater
91022-1
Compressor MODEL
AWG5530WXN
Receiver
51099-2L
Unit Drawing
DGU1918-L021
Compressor BOM
AW707HT-099-J7
Accumulator
----
Wiring Diagram
WD21-205
Compressor LRA
90
Liquid Filter
70139
Compressor RLA
14.40
Sight Glass
70084-S
Suction Filter
----
OverLoad
Internal
Replacement Kit - O/L
----
High Pressure Switch
84095-1L
Relay
8200RVAL94
Low Pressure Control
84026-2
Replacement Kit - Relay
K71-19
Low Pressure Switch
----
Run Capacitor
85PR370F21
Head Master Valve
70083-1
Replacement Kit Run Cap.
K150-18
Check Valve
----
Loose Optional Items
Start Capacitor
85PS330D17
Liquid Valve
On the Receiver
Disconnect Switch
LDSG-613
Replacement Kit Start Cap
K146-44
Suction Valve (Base)
56500-K14
Liquid Solenoid
KSVC-264
Contactor
91017H
Hail Louver
LLPG-201
TPC April 12, 2016
Loading...