Tecumseh AWG4530EXTHN Performance Data Sheet

TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWG4530EXTHN BOM 32L2107-2E*
Air Cooled 2 ½ HP Application High Temp Refrigerant R22
AWG4530EXTHN_REV2
TPC - February 14, 2014
Volts-Hz-Ph 200-230/60/3
36.25
35.38
23.5025.50
26.08
34.62
SUCTION 7/8"
Overall Dimensions, inch (mm) Line connections
AWG4530EXTHN
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
T, °F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
10 32.8 17000 2310 96 15500 2370 106 14700 2390 111 14000 2420 116 12700 2480 126 15 37.7 19000 2470 98 17400 2530 108 16600 2560 113 15800 2590 118 14300 2660 128 20 43.0 21200 2620 101 19500 2690 110 18600 2720 115 17700 2760 120 16000 2840 130 25 48.8 23500 2770 103 21700 2850 112 20700 2890 117 19800 2930 122 17900 3030 132 30 54.9 25900 2920 106 23900 3000 115 23000 3050 119 21900 3100 124 19900 3200 134 35 61.5 28400 3070 109 26400 3160 117 25300 3210 122 24200 3260 126 22000 3380 136 40 68.5 31000 3210 112 28900 3310 120 27800 3370 124 26600 3430 129 24200 3560 138
45 76.0 33700 3360 115 31600 3460 122 30400 3520 127 29200 3590 131 26600 3740 141
50 84.0 36600 3490 118 34300 3610 125 33100 3680 129 31800 3750 134 29100 3920 143 55 92.6 39600 3630 121 37200 3760 128 36000 3830 132 34600 3910 136 31700 4090 146
Performance @ 60 Hz, Return Gas Temperature 65
LW H
26.43 (671) 36.25 (921) 26.08 (662) 23.26 lbs 1500
80°F 90°F 95°F
o
F, --- SubCooling 5oF
Suction Liquid Oz.
7/8" 3/8" 38.6
Ambient Temperatures
* OPTION CODE: See reverse side for Available Options
Pumpdown Air flow
90% @ 90
o
SCFM
F
100°F 110°F
Oil Ch.
Gross weight
Lbs. (kg)
300 (136)
LIQUID3/8"
A
y
AWG4530EXTHN_REV2
TPC - February 14, 2014
Parts/Specifications
STANDARD AVAILABLE OPTIONS
Unit BOM 32L2107-2E Unit MODEL AWG4530EXTHN
Refrigeration Range 10°F to 55°F Fan Motor RLA 0.7 F Fixed Fan Control Design Pressure Low / High 150 / 450 Fan Blade 51568-1 A Adjustable Fan Control Volts - HZ - Ph 208-230V 3~ 60HZ Fan Guard 70831 T1 Air Defrost Timer Voltage Range 180-254 Shroud 70648-2 T2 Electrical Defrost Timer & Defrost Min. Circuit Ampacity 12.64 Heater Contactor Max. Fuse Size 20 High Pressure Switch 84095-1L D Disconnect Switch (nonfused)
Compressor MODEL AWG5530EXT Dual Pressure Conrol Compressor BOM AW707RT-120-A2 Compressor LRA 63.40 Head Master Valve 70083-1 Solenoid Valve (supplied loose) KSVC-264 Compressor RL
OverLoad Internal Discharge Valve (Base) 56618 Replacement Kit - O/L Liquid Valve (Base) 56500-K06 Receiver Heater (R option) 92124-2 Relay Liquid Valve (Receiver) attached Receiver Thermostat (R option) 84102-2 Replacement Kit - Relay Suction Valve (Base) 56500-K14 Fixed Fan Control (F option) 84132-01 Run Capacitor Suction Valve (Rotolock) Adjustable Fan Control (A option) 14955874 Run Capacitor Rating Start Capacitor Condenser 50858-1 Defrost Timer (T1 or T2 option) 84110 Start Capacitor Rating Receiver 51099-2L Defrost Heater Contactor and 91014B and Contactor 91014B Accumulator TK00042000 Auxiliary Switch (T2 opt.) 91014-AUX
Unit Drawing DGU1918-L303 Sight Glass 70084-S Disconnect (D option) LDSG-332 Wiring Diagram WD23-2XT2 Suction Filter 70822-5S Wiring Diagram (A or F opt.) WD23-2AT2 CrankCase Heater 91022-1
8.65 Check Valve 56626 Hail Louver Ass
Fan Motor 810F050C20 Replacement Fan Motor 50W230 Fan Motor Qty 2 R Heated/Insulated Receiver
Low Pressure Control 84026-2
Process Valve 31583-1
Liquid Filter 70139
32Lxxxx-2ER(F)ATnD
AVAILABLE ACCESSORIES
REPLACEMENT PARTS
LLPG-201