Tecumseh Compressor Company
March 16, 2011
Indoor Condensing Units
Model: AWG4516EXNXF BoM: 2B1169-1 R-22 1 1/2 HP AIRCOOLED
Model
AWG4516EXNXF
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Evaporator T
°F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
10 32.8 6538 1106 90 5918 1081 99 5297 1087 108 4682 1103 117
15 37.7 7674 1163 91 6983 1151 101 6297 1167 110 5629 1189 119
20 43.0 9017 1220 93 8236 1221 102 7457 1246 111 6680 1275 120
25 48.7 10542 1275 96 9633 1290 104 8747 1326 113 7863 1362 122
30 54.8 12166 1330 98 11155 1360 107 10148 1405 115 9143 1448 124
35 61.4 13941 1386 100 12791 1429 109 11641 1485 117 10546 1532 126
40 68.5 15855 1440 103 14558 1497 111 13212 1563 120 11926 1618 128
45 76.0 17778 1498 106 16383 1564 114 14934 1637 122 13490 1698 130
50 84.0 19827 1553 108 18200 1634 116 16572 1715 124 15037 1779 132
55 92.6 21940 1607 111 20123 1699 119 23229 1788 126 16516 1860 134
25.0 33.5 19.5 14.7 7/8” S 3/8” S 19 lbs 1800 38.5 190
Dimensions, inches Line Connection* Pumpdown Air Oil Ch Gr. Wt.
L W H CH Suction Liquid
80F 90F 100F 110F
Return gas temp. 65F, 5F sub cooling
90 F 90%
Ambient Temperatures
SCFM Oz. Lbs.
60 Hz Performance