35.38
36.25
23.5025.50
26.08
4.24
34.62
SUCTION 7/8"
LIQUID3/8"
Oil Ch.
Suction Liquid Oz.
Factory charge 20 psig dry air, MUST BE EVACUATED
T, °F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
-10 23.2 10200 2020 90 8700 1980 100 8000 1950 105 7200 1930 109 5900 1870 119
-5 27.5 11600 2140 92 10000 2120 101 9200 2110 106 8500 2090 111 7000 2050 120
0 32.1 13100 2270 93 11400 2270 103 10600 2260 107 9800 2250 112 8200 2230 121
5 37.0 14800 2390 95 13000 2410 104 12100 2410 109 11200 2410 113 9600 2400 123
10 42.4 16600 2520 96 14700 2560 106 13700 2560 110 12800 2570 115 11000 2570 124
15 48.2 18500 2650 98 16500 2700 107 15500 2710 112 14400 2720 116 12500 2750 126
20 54.5 20600 2780 100 18400 2840 109 17300 2860 114 16200 2880 118 14100 2920 127
25 61.2 22900 2910 102 20500 2990 111 19300 3020 115 18100 3040 120 15800 3090 129
30 68.4 25300 3030 104 22700 3130 113 21400 3170 117 20100 3200 122 17600 3260 130
35 76.1 27800 3160 106 25000 3270 115 23600 3320 119 22200 3360 124 19500 3430 132
40 84.4 30400 3300 109 27400 3420 117 25900 3470 121 24500 3510 126 21500 3600 134
45 93.2 33200 3430 111 30000 3560 120 28400 3620 124 26800 3670 128 23600 3770 136
Overall Dimensions, inch (mm)
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, SubCooling 5oF
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWA9518ZXNHN
BOM 32L2133-2E*
Air Cooled 2 ¼ HP
Application Commercial Temp
Refrigerant R404A
Volts-Hz-Ph 208-230/60/1
AWA9518ZXNHN_REV3
TPC - May 20, 2014
* OPTION CODE: See reverse side for Available Options
Unit BOM 32L2133-2E Fan Motor 810F050C20
Unit MODEL AWA9518ZXNHN Replacement Fan Motor 50W230 32Lxxxx-2ER(F)ATnD
Fan Motor Qty 2 R Heated/Insulated Receiver
Refrigeration Range -10°F to 45°F Fan Motor RLA 0.7 F Fixed Fan Control
Design Pressure Low / High 181 / 450 Fan Blade 51568-1 A Adjustable Fan Control
Volts - HZ - Ph 208-230V ~ 60HZ Fan Guard 70831 T1 Air Defrost Timer
Voltage Range 187 - 253 Shroud 70648-2 T2 Electrical Defrost Timer & Defrost
Min. Circuit Ampacity 20.04 Heater Contactor
Max. Fuse Size 35 High Pressure switch 84095-2L D Disconnect Switch (nonfused)
Low Pressure Control 84026-2
Compressor MODEL AWA9514ZXN Dual Pressure Conrol
Compressor BOM AW617ET-099-P2
Compressor LRA 90 Head Master Valve 70083 Solenoid Valve (supplied loose) KSVC-264
Compressor RLA 14.74 Check Valve 56626 Hail Louver Assy LLPG-201
OverLoad internal Discharge Valve (Base) 56618
Replacement Kit - O/L Liquid Valve (Base) 56500-K06 Receiver Heater (R option) 92124-2
Relay 820ARR3J50 Liquid Valve (Receiver) attached Receiver Thermostat (R option) 84102-2
Replacement Kit - Relay K71-19 Suction Valve (Base) 56500-K14 Fixed Fan Control (F option) 84132-1
Run Capacitor 85PR370F21 Suction Valve (Rotolock) Adjustable Fan Control (A option)
Run Capacitor Rating 45 MFD, 370 V
Start Capacitor 85PS330D69 Condenser 50858-1 Defrost Timer (T1 or T2 option) 84110
Start Capacitor Rating 145-175 MFD, 330 V Receiver 51099-1L Defrost Heater Contactor and 91014B and
Contactor 91014B Accumulator TK00042000 Auxiliary Switch (T2 opt.) 91014-AUX
Liquid Filter 70139
Unit Drawing DGU1918-L103 Sight Glass 70084-S Disconnect (D option) LDSG-613
Wiring Diagram WD21-2XT2 Suction Filter 70822-5S
Wiring Diagram (A or F opt.) WD21-2AT2 CrankCase Heater 91022-1
AWA9518ZXNHN_REV3