AWA9514ZXNLN
Overall Dimensions, inch (mm)
Line connections
Pump down
Air flow
Oil Ch.
Gross weight
L W H
Suction
Liquid
90% @ 90oF
SCFM
Oz.
Lbs. (kg)
26.43 (671)
36.25 (921)
26.08 (662)
7/8"
3/8"
19.80 lbs.
1750
38.6
320 (145)
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
Ambient Temperatures
80°F
90°F
95°F
100°F
110°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
23.9
7600
1640
92
6400
1620
101
5900
1600
105
5400
1580
110
4600
1540
119
-5
27.5
8700
1750
93
7400
1740
102
6800
1720
107
6200
1700
111
5400
1670
121 0 32.1
9800
1860
95
8500
1850
104
7800
1840
108
7200
1830
113
6200
1810
122 5 37.0
11200
1960
97
9700
1970
106
9000
1970
110
8300
1960
115
7200
1950
123
10
42.4
12600
2070
99
11000
2090
107
10300
2090
112
9500
2090
116
8200
2090
125
15
48.2
14200
2180
101
12500
2210
109
11600
2220
114
10800
2220
118
9300
2230
127
20
54.5
15900
2290
103
14000
2330
111
13100
2340
116
12200
2350
120
10500
2370
128
25
61.2
17700
2390
105
15700
2450
113
14700
2470
118
13700
2480
122
11900
2510
130
30
68.4
19600
2500
107
17500
2570
115
16400
2590
120
15300
2620
124
13300
2660
132
35
76.1
21700
2610
109
19400
2690
117
18200
2720
122
17000
2750
126
14800
2800
134
40
84.4
23800
2720
111
21400
2810
120
20100
2850
124
18900
2880
128
16400
2940
136
45
93.2
26100
2830
114
23500
2930
122
22200
2980
126
20800
3010
130
18100
3090
138
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, Sub Cooling 5oF
TPC January 26, 2016
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWA9514ZXNLN BOM 32L3238-6U
Air Cooled 1 3/4 HP Application Commercial Temp Refrigerant R404A Volts-Hz-Ph. 208-230/60/1
AWA9514ZXNLN_Rel
Parts/Specifications
Unit BOM
32L3238-6U
Fan Motor
810F050C20
Adjustable Fan Control
14955874
Unit MODEL
AWA9514ZXNLN
Replacement Fan Motor
50W230
Fixed Fan Control
----
Fan Motor Qty
2
Refrigeration Range
-10°F to 45°F
Fan Motor RLA
0.7
Defrost Timer
LTCG-T1
Design Pressure Low / High
181 / 450
Fan Blade
51568-1
Electric Defrost Timer
----
Volts - HZ - Ph
208-230V ~ 60HZ
Fan Guard
70831
Voltage Range
187 - 253
Receiver Heater
-----
Min. Circuit Ampacity
17.15
Shroud
70648-2
Receiver Heater Thermostat
-----
Max. Fuse Size
30
Condenser
50855-1
C/Case Heater
91022-1
Compressor MODEL
AWA9512ZXN
Receiver
51099-2L
Unit Drawing
DGU1918-L021
Compressor BOM
AW611FT-099-A2
Accumulator
----
Wiring Diagram
WD21-205
Compressor LRA
60
Liquid Filter
70139
Compressor RLA
12.44
Sight Glass
70084-S
Suction Filter
----
OverLoad
Internal
Replacement Kit - O/L
----
High Pressure Switch
84095-2L
Relay
8200RVAL94
Low Pressure Control
84026-2
Replacement Kit - Relay
K71-19
Low Pressure Switch
----
Run Capacitor
85PR370F17
Head Master Valve
70083
Replacement Kit Run Cap.
K150-14
Check Valve
----
Loose Optional Items
Start Capacitor
85PS330D16
Liquid Valve
On the Receiver
Disconnect Switch
LDSG-311
Replacement Kit Start Cap
K146-43
Suction Valve (Base)
56500-K14
Liquid Solenoid
KSVC-285
Contactor
91017H
Hail Louver
LLPG-201
TPC January 26, 2016