TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWA9512ZXNHN
BOM 32L1451-2E*
Air Cooled 1 ¼ HP
Application Commercial Temp
Refrigerant R404A
AWA9512ZXNHN_REV1
TPC - February 11, 2014
Volts-Hz-Ph 208-230/60/1
36.25
35.38
23.5025.50
Overall Dimensions, inch (mm) Line connections Pumpdown Air flow
AWA9512ZXNHN
Factory charge 20 psig dry air,
Evaporator
T, °F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
-10 23.9 4500 1620 99 4100 1590 103 3700 1560 108 2800 1510 117 2400 1480 121
-5 27.5 5700 1660 101 5200 1630 105 4700 1610 109 3800 1560 118 3300 1540 122
0 32.1 6900 1720 103 6400 1700 107 5800 1690 111 4700 1650 120 4200 1630 124
5 37.0 8200 1810 104 7600 1800 108 7000 1780 112 5800 1760 121 5200 1740 125
10 42.4 9600 1920 106 8900 1910 110 8200 1900 114 6900 1880 122 6200 1870 126
15 48.2 11000 2030 108 10300 2020 111 9500 2020 115 8000 2010 124 7200 2010 128
20 54.5 12500 2140 109 11600 2140 113 10800 2140 117 9200 2150 125 8300 2150 129
25 61.2 14000 2240 111 13100 2250 115 12200 2260 118 10400 2280 127 9500 2290 130
30 68.4 15600 2330 113 14600 2350 116 13600 2360 120 11600 2400 128 10700 2410 132
35 76.1 17200 2390 114 16100 2420 118 15100 2440 122 12900 2490 129 11900 2520 133
40 84.4 18900 2430 116 17700 2460 119 16600 2500 123 14300 2560 131 13100 2600 134
45 93.2 20600 2420 118 19300 2470 121 18100 2510 125 15600 2600 133 14400 2640 136
Performance @ 60 Hz, Return gas 40
LWH
26.43 (671) 36.25 (921) 26.08 (662) 20.09 lbs 1500
MUST BE EVACUATED
90°F 95°F
o
F below 20oF Evaporator and 65oF above 20oF evaporator, SubCooling 5oF
* OPTION CODE: See reverse side for Available O p t ions
26.08
4.24
Suction Liquid Oz.
7/8" 3/8" 38.6
Ambient Temperatures
100°F
90% @ 90
34.62
SUCTION 7/8"
o
F
SCFM
110°F 115°F
Oil Ch.
LIQUID3/8"
Gross weight
Lbs. (kg)
320 (145)

AWA9512ZXNHN_REV1
TPC - February 11, 2014
Parts/Specifications
STANDARD AVAILABLE OPTIONS
Unit BOM 32L1451-2E Fan Motor 810F050C20
Unit MODEL AWA9512ZXNHN Replacement Fan Motor 50W230 32Lxxxx-2ER(F)ATnD
Fan Motor Qty 2 R Heated/Insulated Receiver
Refrigeration Range -10°F to 45°F Fan Motor RLA 0.7 F Fixed Fan Control
Design Pressure Low / High 181 / 450 Fan Blade 51568-1 A Adjustable Fan Control
Volts - HZ - Ph 208-230V ~ 60HZ Fan Guard 70831 T1 Air Defrost Timer
Voltage Range 187 - 253 Shroud 70648-2 T2 Electrical Defrost Timer & Defrost
Min. Circuit Ampacity 14.91 Heater Contactor
Max. Fuse Size 25 High Pressure Switch 84095-2L D Disconnect Switch (nonfused)
Low Pressure Control 84026-2
Compressor MODEL AWA9490ZXN Dual Pressure Conrol
Compressor BOM AW616ET-111-A2
Compressor LRA 52 He ad Master Valve 70083 Solenoid Valve (supplied loose) KSVC-264
Compressor RL
OverLoad Internal Discharge Valve (Base) 56618
Replacement Kit - O/L Liquid Valve (Base) 56500-K06 Receiver Heater (R option) 92124-2
Relay 820ARR3H23 Liquid Valve (Receiver) attached Receiver Thermostat (R option) 84102-2
Replacement Kit - Relay Suction Valve (Base) 56500-K14 Fixed Fan Control (F option) 84132-1
Run Capacitor 85PR370F17 Suction Valve (Rotolock) 31531-1 Adjustable Fan Control (A option)
Run Capacitor Rating 35MFD 370V
Start Capacitor 85PS330D69 Condenser 50858-1 Defrost Timer (T1 or T2 option) 84110
Start Capacitor Rating 145-175 MFD 330V Receiver 51099-2L Defrost Heater Contactor and 91014B and
Contactor 91014B Accumulator TK00042000 Auxiliary Switch (T2 opt.) 91014-AUX
Unit Drawing DGU1918-L101 Sight Glass 70084-S Disconnect (D option)
Wiring Diagram WD21-2XT2 Suction Filter 70822-5S
Wiring Diagram (A or F opt.) WD21-2AT2 CrankCase Heater 91022-1
10.64 Check Valve 56626 Hail Louver Ass
Process Valve
Liquid Filter 70139
AVAILABLE ACCESSORIES
LLPG-201
REPLACEMENT PARTS