Tecumseh AWA9510ZXNHN Performance Data Sheet

w
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWA9510ZXNHN BOM 32L1351-2E*
Air Cooled 1 HP Application Commercial Temp Refrigerant R404A
AWA9510ZXNHN_REV1
TPC - February 11, 2014
Volts-Hz-Ph 208-230/60/1
36.25
35.38
23.5025.50
26.08
Overall Dimensions, inch (mm) Line connections
AWA9510ZXNHN
Factory charge 20 psig dry air,
Evaporator
T, °F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
-5 27.5 5700 1510 100 5300 1490 105 4800 1480 109 3700 1450 118 3100 1440 123 0 32.1 6600 1610 102 6100 1600 106 5600 1590 111 4400 1570 120 3800 1560 124 5 37.0 7600 1710 103 7100 1700 108 6500 1690 112 5200 1680 121 4500 1680 126
10 42.4 8800 1810 105 8200 1800 109 7600 1800 113 6100 1800 122 5400 1790 127 15 48.2 10000 1910 106 9400 1910 111 8700 1910 115 7200 1910 124 6300 1910 129
20 54.5 11400 2000 108 10700 2010 112 9900 2010 117 8300 2030 125 7400 2040 130
25 61.2 12900 2100 110 12100 2110 114 11300 2120 118 9500 2140 127 8600 2160 132 30 68.4 14500 2200 112 13700 2210 116 12800 2230 120 10800 2260 129 9800 2280 133 35 76.1 16300 2290 114 15300 2310 118 14300 2330 122 12200 2380 131 11100 2410 135 40 84.4 18100 2390 116 17100 2410 120 16000 2440 124 13700 2500 133 12600 2530 137 45 93.2 20100 2480 118 19000 2510 122 17800 2550 126 15300 2620 135 14100 2660 139 50 103.0 22200 2580 120 20900 2610 124 19700 2660 128 17100 2740 137 15700 2790 141
Performance @ 60 Hz, Return gas 40
L
26.43 (671) 320 (145)36.25 (921) 26.08 (662) 19.80 lbs 1750
MUST BE EVACUATED
WH
95°F 100°F
o
F below 20oF Evaporator and 65oF above 20oF evaporator, SubCooling 5oF
Suction Liquid Oz.
7/8" 3/8" 38.6
Ambient Temperatures
* OPTION CODE: See reverse side for Available Options
Pumpdown Air flo
90% @ 90oF
110°F 115°F90°F
34.62
SUCTION 7/8"
SCFM
Oil Ch.
Gross weight
LIQUID3/8"
Lbs. (kg)
r
A
y
AWA9510ZXNHN_REV1
TPC - February 11, 2014
Parts/Specifications
STANDARD AVAILABLE OPTIONS
Unit BOM 32L1351-2E Unit MODEL AWA9510ZXNHN
Refrigeration Range -5°F to 50°F Fan Motor RLA 0.7 F Fixed Fan Control Design Pressure Low / High 181 / 450 Fan Blade 51568-1 A Adjustable Fan Control Volts - HZ - Ph 208-230V ~ 60HZ Fan Guard 70831 T1 Air Defrost Timer Voltage Range 187-254 Shroud 70648-2 T2 Electrical Defrost Timer & Defrost Min. Circuit Ampacity 14.91 Heater Contactor Max. Fuse Size 25 High Pressure Switch 84095-2L D Disconnect Switch (nonfused)
Compressor MODEL AWA9490ZXN Dual Pressure Conrol Compressor BOM AW616ET-111-A2 Compressor LRA 52 Head Master Valve 70083 Solenoid Valve (supplied loose) KSVC-264 Compressor RL
OverLoad Internal Discharge Valve (Base) 56618 Replacement Kit - O/L Liquid Valve (Base) 56500-K06 Receiver Heater (R option) 92124-2 Relay 820ARR3H23 Liquid Valve (Receiver) attached Receiver Thermostat (R option) 84102-2 Replacement Kit - Relay Suction Valve (Base) 56500-K14 Fixed Fan Control (F option) 84132-01 Run Capacitor 85PR370F17 Suction Valve (Rotolock) 31531-1 Adjustable Fan Control (A option) 14955874 Run Capacitor Rating 35 MFD 370V Start Capacitor 85PS330D69 Condenser 50855-1 Defrost Timer (T1 or T2 option) 84110 Start Capacitor Rating 145-175 MFD 330V Receiver 51099-2L Defrost Heater Contactor and 91014B and Contactor 91014B Accumulator TK00042000 Auxiliary Switch (T2 opt.) 91014-AUX
Unit Drawing DGU1918-L101 Sight Glass 70084-S Disconnect (D option) Wiring Diagram WD21-2XT2 Suction Filter 70822-5S Wiring Diagram (A or F opt.) WD21-2AT2 CrankCase Heater 91022-1
10.64 Check Valve 56626 Hail Louver Ass
Fan Moto Replacement Fan Motor 50W230 Fan Motor Qty 2 R Heated/Insulated Receiver
Low Pressure Control 84026-2
Process Valve
Liquid Filter 70139
810F050C20
32Lxxxx-2ER(F)ATnD
AVAILABLE ACCESSORIES
REPLACEMENT PARTS
LLPG-201