Tecumseh AWA7515ZXDLS User Manual

AWA7515ZXDLS_Rel
AWA7515ZXDLS
Overall Dimensions, inch (mm)
Line connections
Pump down
Air flow
Oil Ch.
Gross weight
L W H
Suction
Liquid
90% @ 90oF
SCFM
Oz.
Lbs. (kg)
26.55 (674)
28.94 (735)
26.08 (662)
7/8"
3/8"
15.70
750
38.6
200 (91)
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
Ambient Temperatures
80°F
90°F
95°F
100°F
110°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
23.6
9100
1960
100
8000
1910
108
7400
1900
112
6800
1900
117
5700
1880
125
-5
27.5
10200
2100
103
8900
2070
110
8300
2060
115
7600
2070
119
6400
2070
127 0 32.1
11300
2240
106
9900
2220
113
9200
2220
117
8500
2230
121
7200
2240
130 5 37.0
12500
2380
109
10900
2370
116
10200
2380
120
9400
2400
124
8000
2420
132
10
42.4
13700
2520
113
12000
2530
118
11200
2540
122
10400
2560
126
8900
2590
134
15
48.2
15000
2670
116
13200
2690
121
12300
2710
125
11400
2740
129
9700
2780
137
20
54.5
16400
2830
119
14400
2860
124
13400
2890
128
12400
2920
131
10600
2960
139
25
61.2
17900
3000
123
15600
3040
127
14500
3070
130
13500
3110
134
11500
3160
142
30
68.4
19400
3200
126
16900
3240
130
15800
3280
133
14600
3310
137
12500
3370
145
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, Sub Cooling 5oF
TPC April 19, 2016
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWA7515ZXDLS BOM 32L3220-6U
Air Cooled 1 3/4 HP Application Medium Temp Refrigerant R404A Volts-Hz-Ph. 208-230/60/1
AWA7515ZXDLS_Rel
Parts/Specifications
Unit BOM
32L3220-6U
Fan Motor
810F050C20
Adjustable Fan Control
----
Unit MODEL
AWA7515ZXDLS
Replacement Fan Motor
50W230
Fixed Fan Control
----
Fan Motor Qty
1
Refrigeration Range
-10°F to 30°F
Fan Motor RLA
0.7
Defrost Timer
LTCG-T1
Design Pressure Low / High
181 / 450
Fan Blade
51568-1
Electric Defrost Timer
----
Volts - HZ - Ph
208-230V ~ 60HZ
Fan Guard
70831
Voltage Range
187 - 253
Receiver Heater
-----
Min. Circuit Ampacity
20.94
Shroud
70727-2
Receiver Heater Thermostat
-----
Max. Fuse Size
35
Condenser
50857-1
C/Case Heater
91022-1
Compressor MODEL
AWA7515ZXD
Receiver
51082-1K
Unit Drawing
DGU1918-L421
Compressor BOM
AW612ET-099-J7
Accumulator
----
Wiring Diagram
WD21-105
Compressor LRA
96.8
Liquid Filter
70139
Compressor RLA
16.03
Sight Glass
70084-S
Suction Filter
----
OverLoad
Internal
Replacement Kit - O/L
----
High Pressure Switch
84095-2L
Relay
8200RVAM12
Low Pressure Control
84026-2
Replacement Kit - Relay
K71-63
Low Pressure Switch
----
Run Capacitor
85PR370F17
Head Master Valve
70083
Replacement Kit Run Cap.
K150-14
Check Valve
----
Loose Optional Items
Start Capacitor
85PS330D13
Liquid Valve
31590
Disconnect Switch
LDSG-613
Replacement Kit Start Cap
K146-40
Suction Valve (Base)
56500-K14
Liquid Solenoid
KSVC-264
Contactor
91014H
Hail Louver
----
TPC April 19, 2016
Loading...