Overall Dimensions, inch (mm)
Line connections
Pump down
Air flow
Oil Ch.
Gross weight
L W H
Suction
Liquid
90% @ 90oF
SCFM
Oz.
Lbs. (kg)
26.55 (674)
28.94 (735)
26.08 (662)
7/8"
3/8"
15.70 lbs
750
38.6
200 (91)
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
Ambient Temperatures
80°F
90°F
95°F
100°F
110°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
23.2
6800
1500
96
6000
1500
104
5600
1490
108
5200
1470
113
4000
1410
121
-5
27.5
7800
1600
98
6900
1610
106
6400
1600
110
5900
1590
115
4600
1540
123
0
32.1
8800
1710
101
7800
1720
108
7200
1720
113
6700
1710
117
5300
1670
125
5
37.0
10000
1820
103
8700
1830
110
8100
1830
115
7500
1830
119
6000
1800
127
10
42.4
11100
1930
106
9700
1950
113
9000
1950
117
8300
1950
122
6800
1930
130
15
48.2
12400
2040
109
10800
2070
115
10000
2080
120
9300
2080
124
7700
2070
132
20
54.5
13700
2150
112
11900
2190
118
11000
2200
122
10200
2210
127
8500
2210
134
25
61.2
15000
2270
115
13000
2310
121
12100
2330
125
11300
2340
129
9500
2350
137
30
68.4
16400
2380
119
14300
2430
124
13300
2450
128
12400
2470
132
10500
2490
139
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, Sub Cooling 5oF
TPC January 26, 2016
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWA7512ZXDUS BOM 32L3217-6C
Air Cooled 1 1/2 HP Application Medium Temp Refrigerant R404A Volts-Hz-Ph. 208-230/60/1
AWA7512ZXDUS_Rel
Parts/Specifications
Unit BOM
32L3217-6C
Fan Motor
810F050C20
Adjustable Fan Control
----
Unit MODEL
AWA7512ZXDUS
Replacement Fan Motor
50W230
Fixed Fan Control
----
Fan Motor Qty
1
Refrigeration Range
-10°F to 30°F
Fan Motor RLA
0.7
Defrost Timer
----
Design Pressure Low / High
181 / 450
Fan Blade
51568-1
Electric Defrost Timer
----
Volts - HZ - Ph
208-230V ~ 60HZ
Fan Guard
70831
Voltage Range
187 - 253
Receiver Heater
92124-2
Min. Circuit Ampacity
16.94
Shroud
70727-2
Receiver Heater Thermostat
84102-2
Max. Fuse Size
30
Condenser
50857-1
C/Case Heater
91022-1
Compressor MODEL
AWA7512ZXD
Receiver
51082-1K
Unit Drawing
DGU1918-L411
Compressor BOM
AW611ET-099-A4
Accumulator
TK00042000
Wiring Diagram
WD21-103
Compressor LRA
73
Liquid Filter
70139
Compressor RLA
12.82
Sight Glass
70084-S
Suction Filter
70822-5S
Overload
Internal
Replacement Kit - O/L
----
High Pressure Switch
84095-2L
Relay
8200RVAL95
Low Pressure Control
84026-2
Replacement Kit - Relay
Low Pressure Switch
----
Run Capacitor
85PR370F17
Head Master Valve
70083
Replacement Kit Run Cap.
K150-14
Check Valve
56626
Loose Optional Items
Start Capacitor
85PS330D16
Liquid Valve
31590
Disconnect Switch
LDSG-311
Replacement Kit Start Cap
K146-43
Suction Valve (Base)
56500-K14
Liquid Solenoid
KSVC-285
Contactor
91014H
Hail Louver
----
TPC January 26, 2016