Tecumseh AWA2490ZXDUN User Manual

AWA2490ZXDUN_Rel
AWA2490ZXDUN
Overall Dimensions, inch (mm)
Line connections
Pump down
Air flow
Oil Ch.
Gross weight
L W H
Suction
Liquid
90% @ 90oF
SCFM
Oz.
Lbs. (kg)
26.43 (671)
36.25 (921)
26.08 (662)
7/8"
3/8"
19.80 lbs.
1750
38.6
320 (145)
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
Ambient Temperatures
80°F
90°F
95°F
100°F
110°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-30
10.7
4600
1510
91
4200
1500
97
3900
1480
101
3500
1470
105 -25
14.0
5700
1660
93
5300
1650
98
4800
1640
102
4300
1620
107
3600
1560
117
-20
17.1
6900
1820
94
6400
1800
98
5900
1800
103
5300
1780
108
4400
1720
118
-15
19.3
8200
1970
96
7500
1960
100
7000
1950
104
6300
1940
110
5200
1890
119
-10
24.5
9500
2120
98
8800
2110
102
8100
2110
106
7400
2100
112
6100
2060
121
-5
28.8
10800
2270
100
10000
2270
104
9300
2270
108
8600
2260
114
7100
2230
122
0
33.5
12100
2410
102
11300
2420
106
10600
2430
111
9800
2430
116
8200
2410
124
5
36.5
13500
2560
104
12700
2580
108
11900
2590
113
11100
2590
118
9300
2590
125
10
43.7
14900
2710
105
14100
2730
110
13300
2750
114
12400
2760
119
10500
2770
127
Performance @ 60 Hz, Return gas 40oF , Sub Cooling 5oF
TPC January 26, 2016
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AWA2490ZXDUN BOM 32L2111-6C
Air Cooled 2 1/4 HP Application Low Temp Refrigerant R404A Volts-Hz-Ph. 208-230/60/1
AWA2490ZXDUN_Rel
Parts/Specifications
Unit BOM
32L2111-6C
Fan Motor
810F050C20
Adjustable Fan Control
14955874
Unit MODEL
AWA2490ZXDUN
Replacement Fan Motor
50W230
Fixed Fan Control
----
Fan Motor Qty
2
Refrigeration Range
-40°F to 10°F
Fan Motor RLA
0.7
Defrost Timer
----
Design Pressure Low / High
181 / 450
Fan Blade
51568-1
Electric Defrost Timer
LTCG-T2
Volts - HZ - Ph
208-230V ~ 60HZ
Fan Guard
70831
Voltage Range
187 - 253
Receiver Heater
92124-2
Min. Circuit Ampacity
17.32
Shroud
70648-2
Receiver Heater Thermostat
84102-2
Max. Fuse Size
30
Condenser
50855-1
C/Case Heater
91022-1
Compressor MODEL
AWA2460ZXD
Receiver
51099-2L
Unit Drawing
DGU1918-L011
Compressor BOM
AW613ET-099-A4
Accumulator
TK00042000
Wiring Diagram
WD21-204
Compressor LRA
86
Liquid Filter
52000-084D
Compressor RLA
12.56
Sight Glass
70084-2S
Suction Filter
70822-5S
OverLoad
Internal
Replacement Kit - O/L
----
High Pressure Switch
84095-2L
Relay
8200RVAL94
Low Pressure Control
84026-2
Replacement Kit - Relay
K71-19
Low Pressure Switch
----
Run Capacitor
85PR370F21
Head Master Valve
70083
Replacement Kit Run Cap.
K150-18
Check Valve
56626
Loose Optional Items
Start Capacitor
85PS330D17
Liquid Valve
On the Receiver
Disconnect Switch
LDSG-311
Replacement Kit Start Cap
K146-44
Suction Valve (Base)
56500-K14
Liquid Solenoid
KSVC-285
Contactor
91014H
Hail Louver
LLPG-201
TPC January 26, 2016
Loading...