Tecumseh AVA9532ZXNHM User Manual

46.97
47.75
26.00
29.00
31.58
4.50
46.14
7
8
"
LIQUID
1
2
"
29.40
Oil Ch.
Suction Liquid Oz.
7/8" 1/2" 54.9
Factory charge 20 psig dry air, MUST BE EVACUATED
Ambient Temperatures
T, °F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
-10 23.2 16400 3450 99 15400 3450 104 14400 3450 108 12300 3430 118 11200 3410 122
-5 27.5 18700 3730 101 17500 3730 105 16400 3740 110 14100 3730 119 12900 3720 124 0 32.1 21200 4010 102 20000 4020 107 18700 4030 111 16200 4040 121 14900 4030 125 5 37.0 24000 4290 104 22600 4310 108 21200 4320 113 18400 4350 122 17000 4350 127
10 42.4 27000 4570 105 25500 4600 110 24000 4620 114 20900 4660 124 19400 4680 128 15 48.2 30300 4860 107 28700 4890 111 27000 4920 116 23700 4980 125 21900 5010 130
20 54.5 33900 5150 109 32100 5180 113 30300 5220 118 26600 5300 127 24700 5340 131
25 61.2 37700 5430 110 35800 5480 115 33800 5520 119 29700 5620 128 27700 5680 133 30 68.4 41800 5730 112 39700 5780 116 37500 5830 121 33100 5950 130 30900 6020 134 35 76.1 46200 6020 114 43800 6080 118 41500 6140 122 36700 6280 131 34300 6360 135 40 84.4 50800 6310 116 48200 6380 120 45700 6450 124 40500 6620 133 37900 6710 137 45 93.2 55600 6610 118 52900 6690 122 50100 6770 126 44600 6960 134 41800 7060 138
115°F
AVA9532ZXNHM
90°F
95°F
100°F
Overall Dimensions, inch (mm)
Line connections
Pumpdown
Air flow
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, SubCooling 5oF
Evaporator
Gross weight
Lbs. (kg)
480 (218)
110°F
SCFM
29.4 (747)
47.75 (1213)
31.58 (802)
32.84 lbs
4200
LWH
90% @ 90oF
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AVA9532ZXNHM BOM 32L4054-2E*
Air Cooled 4 HP Application Commercial Temp Refrigerant R404A Volts-Hz-Ph 208-230/60/1
AVA9532ZXNHM_REV 1
TPC - July 22, 2015
* OPTION CODE: See reverse side for Available Options
Unit BOM 32L4054-2E Fan Motor 810S124B38
Unit MODEL AVA9532ZXNHM Replacement Fan Motor 32Lxxxx-2ER(F)ATnD
Fan Motor Qty 2 R Heated/Insulated Receiver Refrigeration Range -10°F to 45°F Fan Motor RLA 1.35 F Fixed Fan Control Design Pressure Low / High 181 / 450 Fan Blade 51529-3 A Adjustable Fan Control Volts - HZ - Ph 208-230V ~ 60HZ Fan Guard 70832 T1 Air Defrost Timer Voltage Range 187 - 253 Shroud 70611-1 T2 Electrical Defrost Timer & Defrost Min. Circuit Ampacity 40.81 Heater Contactor Max. Fuse Size 70 High Pressure switch 84095-2L D Disconnect Switch (nonfused)
Low Pressure Control 84026-2 Compressor MODEL AVA9528ZXN Dual Pressure Conrol Compressor BOM AV204ET-066-J7 Compressor LRA 132 Head Master Valve 70107-1 Solenoid Valve (supplied loose) KSVC-264 Compressor RLA 30.32 Check Valve 56627 Hail Louver Assy LLPG-301
Process Valve OverLoad internal Discharge Valve (Base) 56596 Replacement Kit - O/L Liquid Valve (Base) 56500-K08 Receiver Heater (R option) 92124-1 Relay 8200RVAM12 Liquid Valve (Receiver) 56596 Receiver Thermostat (R option) 84102-2 Replacement Kit - Relay K71-63 Suction Valve (Base) 56500-K14 Fixed Fan Control (F option) 84132-01 Run Capacitor 85PR440F90 Suction Valve (Rotolock) 31529-1 Adjustable Fan Control (A option) 14955874 Replacement Kit - Run Cap. Start Capacitor 85PS330D69 Condenser 50785-4 Defrost Timer (T1 or T2 option) 84110 Replacement Kit - Start Cap. K146-44 Receiver 51084 Defrost Heater Contactor and 91014H and Contactor 91012H Accumulator TK00042000 Auxiliary Switch (T2 opt.) 91014-AUH
Liquid Filter 52000-164D Unit Drawing DGU1920-L103 Sight Glass 70084-2S Disconnect (D option) Wiring Diagram WD21-2XT2H Suction Filter 70822-5S Wiring Diagram (A or F opt.) WD21-2AT2H CrankCase Heater
AVAILABLE ACCESSORIES
REPLACEMENT PARTS
Parts/Specifications
STANDARD
AVAILABLE OPTIONS
AVA9532ZXNHM_REV 1
TPC - July 22, 2015
Loading...