Tecumseh AVA5542EXT Performance Data Sheet

Performance Data Sheet
AVA5542EXT
General Information
Model AVA5542EXT Refrigerant R-22 Test Condition ASHRAE Performance Test Voltage 230V 3~ 60HZ Return Gas -6.7°C (20°F) SUPERHEAT Motor Type 3PH
Performance Information
-15
-10
-5
0
5
10
15
20
Condensing Temperature (°F)
80 90 100 110 120 130 140
Btu/h 10800 8800 Watts 1770 1720 Amps 7.74 7.70
Lb/h 140 118
Btu/h 13700 11500 9650 Watts 1900 1880 1860 Amps 8.00 8.00 7.98
Lb/h 176 154 134
Btu/h 16800 14400 12400 10600 Watts 2030 2040 2050 2050 Amps 8.24 8.28 8.31 8.31
Lb/h 214 191 171 153
Btu/h 20000 17500 15300 13300 11500 Watts 2140 2180 2220 2260 2270 Amps 8.47 8.55 8.63 8.69 8.69
Lb/h 254 230 209 190 172
Btu/h 23500 20800 18400 16200 14200 Watts 2250 2320 2390 2460 2500 Amps 8.68 8.80 8.93 9.04 9.11
Lb/h 296 272 250 229 211
Btu/h 27200 24300 21700 19300 17100 15000 13000 Watts 2350 2450 2550 2650 2720 2770 2780 Amps 8.86 9.03 9.22 9.39 9.52 9.59 9.57
Lb/h 341 316 293 271 251 232 212
Btu/h 31200 28100 25300 22700 20200 17900 15600 Watts 2430 2560 2700 2820 2930 3010 3050 Amps 9.02 9.24 9.48 9.71 9.91 10.0 10.1
Lb/h 388 362 339 316 295 274 253
Btu/h 35500 32200 29200 26300 23600 21000 18500 Watts 2500 2660 2830 2990 3130 3240 3310 Amps 9.15 9.43 9.72 10.0 10.3 10.5 10.6
Lb/h 439 413 388 365 342 319 296
Btu/h 40200 36700 33400 30200 27200 24400 21600
25
30
35
40
45
50
55
Watts 2550 2750 2940 3140 3310 3460 3560 Amps 9.25 9.58 9.93 10.3 10.6 10.9 11.1
Lb/h 493 466 441 416 392 368 343
Btu/h 45300 41500 37900 34500 31200 28100 25000 Watts 2580 2810 3040 3270 3480 3650 3790 Amps 9.32 9.70 10.1 10.5 10.9 11.3 11.6
Lb/h 552 524 498 472 447 421 394
Btu/h 50700 46700 42800 39100 35600 32100 28700 Watts 2600 2860 3130 3380 3620 3840 4010 Amps 9.35 9.79 10.3 10.8 11.2 11.7 12.1
Lb/h 615 586 559 532 506 478 450
Btu/h 56600 52300 48200 44200 40300 36500 32700 Watts 2590 2890 3190 3480 3750 4000 4210 Amps 9.33 9.84 10.4 10.9 11.5 12.0 12.5
Lb/h 682 653 625 597 569 540 510
Btu/h 63000 58400 53900 49600 45400 41300 37200 Watts 2560 2890 3220 3550 3860 4140 4380 Amps 9.28 9.84 10.5 11.1 11.7 12.3 12.9
Lb/h 754 725 696 667 637 606 574
Btu/h 69900 65000 60200 55500 51000 46500 42000 Watts 2510 2870 3240 3600 3940 4260 4540 Amps 9.18 9.80 10.5 11.2 11.9 12.6 13.3
Lb/h 832 802 772 741 710 678 644
Btu/h 77300 72000 66900 61900 57000 52200 47300 Watts 2430 2830 3230 3630 4000 4350 4670 Amps 9.02 9.72 10.5 11.3 12.1 12.9 13.6
Lb/h 916 884 853 822 790 756 720
COEFFICIENTS CAPACITY POWER CURRENT MASS FLOW
C1 5.344559E+04 3.176192E+03 1.058879E+01 6.040353E+02 C2 8.658597E+02 -2.465224E+01 1.355807E-02 7.516444E+00 C3 -6.077276E+02 -4.068084E+01 -8.557885E-02 -6.803809E+00 C4 6.935925E+00 -2.563580E-01 -7.375143E-04 4.736875E-02 C5 -1.601694E+00 5.709510E-01 -6.668002E-05 2.592976E-02 C6 2.804323E+00 4.891359E-01 1.052613E-03 3.758913E-02 C7 3.999739E-02 -2.141744E-03 -4.093833E-06 4.543648E-04 C8 -2.942422E-02 7.653372E-04 4.432614E-06 -2.543590E-05 C9 -1.070291E-02 2.193041E-04 5.515137E-06 -2.234170E-04
C10 -5.440767E-03 -1.774582E-03 -3.926883E-06 -9.056742E-05
Value = C1 + C2 * Te + C4 * Te^2 + C7 * Te^3 + (C3 + C5 * Te + C8 * Te^2) * Tc + (C6 + C9 * Te) * Tc^2 + C10 * Tc^3
Te = Evaporator Temperature
Tc = Condensing Temperature
Loading...