Tecumseh AVA2510ZXTKS User Manual

AVA2510ZXTKS_Rel
AVA2510ZXTKS
Overall Dimensions, inch (mm)
Line connections
Pump down
Air flow
Oil Ch.
Gross weight
L W H
Suction
Liquid
90% @ 90oF
SCFM
Oz.
Lbs. (kg)
26.55 (674)
28.94 (735)
26.08 (662)
7/8"
1/2"
15.70 lbs
750
54.9
250 (113)
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
Ambient Temperatures
80°F
90°F
95°F
100°F
110°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-30
10.7
6800
1930
98
5800
1890
106
5300
1870
110
-25
14.0
8000
2150
101
6800
2100
109
6200
2080
113
5700
2040
117 -20
17.1
9200
2370
104
7800
2320
112
7200
2290
116
6600
2260
120
5500
2180
128
-15
19.3
10400
2600
107
8900
2550
115
8200
2520
119
7500
2490
123
6300
2420
130
-10
24.5
11600
2830
110
10000
2780
118
9200
2760
122
8400
2730
126
7100
2670
133
-5
28.8
12900
3070
114
11000
3030
122
10200
3010
126
9300
2980
129
7900
2940
136
0
33.5
14100
3310
117
12100
3280
125
11100
3260
129
10300
3250
133
8600
3220
140
5
36.5
15400
3550
121
13200
3540
129
12100
3530
133
11200
3530
136 10
43.7
16700
3800
125
14200
3810
133
13100
3810
137
12100
3810
140
Performance @ 60 Hz, Return gas 40oF, Sub Cooling 5oF
TPC March 28, 2016
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AVA2510ZXTKS BOM 32L2117-4U
Air Cooled 2 1/2 HP Application Low Temp Refrigerant R404A Volts-Hz-Ph. 200-230/60/3
AVA2510ZXTKS_Rel
Parts/Specifications
Unit BOM
32L2117-4U
Fan Motor
810F050C20
Adjustable Fan Control
----
Unit MODEL
AVA2510ZXTKS
Replacement Fan Motor
50W230
Fixed Fan Control
----
Fan Motor Qty
1
Refrigeration Range
-30°F to 10°F
Fan Motor RLA
0.7
Defrost Timer
----
Design Pressure Low / High
181 / 450
Fan Blade
51568-1
Electric Defrost Timer
LTCG-T2
Volts - HZ - Ph
200-230V 3~ 60HZ
Fan Guard
70831
Voltage Range
180 - 253
Receiver Heater
-----
Min. Circuit Ampacity
13.25
Shroud
70727-2
Receiver Heater Thermostat
-----
Max. Fuse Size
25
Condenser
50857-1
C/Case Heater
90699
Compressor MODEL
AVA2490ZXT
Receiver
51082-1K
Unit Drawing
DGU1920-L421
Compressor BOM
AV182RT-012-A2
Accumulator
----
Wiring Diagram
WD23-102
Compressor LRA
65.1
Liquid Filter
52000-084D
Compressor RLA
9.87
Sight Glass
70084-2S
Suction Filter
----
Overload
Internal
Replacement Kit - O/L
----
High Pressure Switch
84095-2L
Relay
----
Low Pressure Control
84026-2
Replacement Kit - Relay
----
Low Pressure Switch
----
Run Capacitor
----
Head Master Valve
70083
Replacement Kit Run Cap.
----
Check Valve
----
Loose Optional Items
Start Capacitor
----
Liquid Valve
31590
Disconnect Switch
LDSG-332
Replacement Kit Start Cap
----
Suction Valve (Base)
56500-K14
Liquid Solenoid
KSVC-285
Contactor
91014H
Hail Louver
----
TPC March 28, 2016
Loading...