Tecumseh AKA9464ZXDHS User Manual

23.50
27.94
28.94
27.35
26.08
2.96
25.50
SUCTION
"
LIQUID
"
26.55
Oil Ch.
Suction Liquid Oz.
1/2" 3/8" 17.3
Factory charge 20 psig dry air, MUST BE EVACUATED
Ambient Temperatures
T, °F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
-10 23.2 3100 980 96 3100 970 98 2800 980 101 2500 980 106 2000 970 118
-5 27.5 3600 1040 97 3500 1030 99 3300 1040 103 3000 1040 108 2400 1040 119 0 32.1 4100 1090 98 4100 1090 100 3800 1100 104 3500 1110 109 2900 1120 120 5 37.0 4700 1150 100 4700 1150 101 4400 1160 105 4100 1170 110 3400 1190 121
10 42.4 5300 1210 101 5300 1210 102 5000 1220 106 4700 1240 111 3900 1260 123 15 48.2 6000 1270 102 6000 1270 104 5700 1280 108 5300 1300 113 4500 1330 124
20 54.5 6800 1320 104 6700 1330 105 6400 1350 109 6000 1370 114 5100 1410 125
25 61.2 7700 1380 105 7500 1390 107 7200 1410 110 6800 1430 115 5700 1480 127 30 68.4 8600 1440 107 8400 1450 108 8000 1470 112 7500 1490 117 6400 1550 128 35 76.1 9500 1500 108 9300 1510 110 8900 1530 113 8400 1560 119 7100 1620 130
40 84.4 10600 1550 110 10300 1570 111 9800 1590 115 9200 1620 120 7900 1690 132
750
LWH
90% @ 90oF
95°F
Overall Dimensions, inch (mm)
Line connections
Pumpdown
Air flow
SCFM
26.55 (674)
28.94 (735)
26.08 (662)
15.70 lbs
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, SubCooling 5oF
Evaporator
Gross weight
Lbs. (kg)
190 (91)
100°F
110°F
AKA9464ZXDHS
80°F
90°F
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AKA9464ZXDHS BOM 32L751-2E*
Air Cooled 3/4 HP Application Commercial Temp Refrigerant R404A Volts-Hz-Ph 208-230/60/1
AKA9464ZXDHS_Rev 3
TPC - March 16, 2016
* OPTION CODE: See reverse side for Available Options
Unit BOM 32L751-2E Fan Motor 810F050C20
Unit MODEL AKA9464ZXDHS Replacement Fan Motor 810F050C20(C) 32Lxxxx-2ER(F)ATnD
Fan Motor Qty 1 R Heated/Insulated Receiver Refrigeration Range -10°F to 40°F Fan Motor RLA 0.7 F Fixed Fan Control Design Pressure Low / High 181 / 450 Fan Blade 51568-1 A Adjustable Fan Control Volts - HZ - Ph 208-230V ~ 60HZ Fan Guard 70831 T1 Air Defrost Timer Voltage Range 187 - 253 Shroud 70727-2 T2 Electrical Defrost Timer & Defrost Min. Circuit Ampacity 8.16 Heater Contactor Max. Fuse Size 15 High Pressure switch 84095-2L D Disconnect Switch (nonfused)
Low Pressure Control 84026-2 Compressor MODEL AKA9455ZXD Dual Pressure Conrol Compressor BOM AK171ET-038-J7 Compressor LRA 31 Head Master Valve 70083 Solenoid Valve (supplied loose) KSVC-264 Compressor RLA 5.83 Check Valve 56626 Hail Louver Assy LLPG-101
Process Valve OverLoad 8300MRAG29 Discharge Valve (Base) 56618 Replacement Kit - O/L K90-20 Liquid Valve (Base) 56500-K06 Receiver Heater (R option) 92124-2 Relay 8200RVAM01 Liquid Valve (Receiver) 31590 Receiver Thermostat (R option) 84102-2 Replacement Kit - Relay K71-17 Suction Valve (Base) 56500-K08 Fixed Fan Control (F option) Run Capacitor 85PR370E36 Suction Valve (Rotolock) 31582-3K Adjustable Fan Control (A option) Replacement Kit Run Cap. K150-03 Start Capacitor 85685 Condenser 50857-1 Defrost Timer (T1 or T2 option) 84110 Replacement Kit Start Cap K146-02 Receiver 51082-1K Defrost Heater Contactor and 91014H and Contactor 91014H Accumulator TK00013000 Auxiliary Switch (T2 opt.) 91014-AUH
Liquid Filter 70139 Unit Drawing DGU1909-L111 Sight Glass 70084-S Disconnect (D option) LDSG-301 Wiring Diagram WD21-1T2 Suction Filter 704-20001 Wiring Diagram (A or F opt.) CrankCase Heater 92123-1
AVAILABLE ACCESSORIES
REPLACEMENT PARTS
Parts/Specifications
STANDARD
AVAILABLE OPTIONS
AKA9464ZXDHS_Rev 3
TPC - March 16, 2016
Loading...