Tecumseh AKA9440ZXDUS User Manual

AKA9440ZXDUS_Rel
AKA9440ZXDUS
Overall Dimensions, inch (mm)
Line connections
Pump down
Air flow
Oil Ch.
Gross weight
L W H
Suction
Liquid
90% @ 90oF
SCFM
Oz.
Lbs. (kg)
26.55 (674)
28.94 (735)
26.08 (662)
1/2"
3/8"
15.70 lbs
750
38.6
200 (91)
Factory charge 20 psig dry air, MUST BE EVACUATED
Evaporator
Ambient Temperatures
80°F
90°F
95°F
100°F
110°F
T, °F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
23.2
3500
750
89
2400
690
97
2000
650
101
1500
610
105 -5
27.5
3600
780
89
2600
740
97
2200
710
102
1800
680
106
1100
600
114 0 32.1
3800
810
90
3000
780
98
2600
770
102
2200
750
107
1500
680
115 5 37.0
4200
840
91
3400
820
99
3000
820
103
2700
800
108
2100
760
117
10
42.4
4700
860
92
3900
860
100
3600
860
105
3200
850
109
2600
830
118
15
48.2
5200
890
93
4500
900
101
4200
900
106
3900
900
110
3200
890
119
20
54.5
5900
920
94
5200
930
103
4800
940
107
4500
940
112
3900
950
120
25
61.2
6600
950
96
5900
960
104
5500
970
109
5200
980
113
4500
1000
122
30
68.4
7400
980
98
6600
990
106
6300
1010
110
5900
1020
115
5100
1040
123
35
76.1
8300
1010
100
7400
1030
108
7000
1040
112
6600
1060
116
5700
1080
125
40
84.4
9100
1050
102
8200
1060
110
7800
1070
114
7300
1090
118
6300
1120
127
Performance @ 60 Hz, Return gas 40oF below 20oF Evaporator and 65oF above 20oF evaporator, Sub Cooling 5oF
PRELIMINARY DATA
TPC January 26, 2016
TECUMSEH OUTDOOR
CONDENSING UNIT
Model AKA9440ZXDUS BOM 32L292-6C
Air Cooled 1/2 HP Application Commercial Temp Refrigerant R404A Volts-Hz-Ph. 208-230/60/1
AKA9440ZXDUS_Rel
Parts/Specifications
Unit BOM
32L292-6C
Fan Motor
810F050C20
Adjustable Fan Control
----
Unit MODEL
AKA9440ZXDUS
Replacement Fan Motor
50W230
Fixed Fan Control
----
Fan Motor Qty
1
Refrigeration Range
-10°F to 45°F
Fan Motor RLA
0.7
Defrost Timer
----
Design Pressure Low / High
181 / 450
Fan Blade
51568-1
Electric Defrost Timer
----
Volts - HZ - Ph
208-230V ~ 60HZ
Fan Guard
70831
Voltage Range
187 - 253
Receiver Heater
92124-2
Min. Circuit Ampacity
6.25
Shroud
70727-2
Receiver Heater Thermostat
84102-2
Max. Fuse Size
15
Condenser
50857-1
C/Case Heater
92123-2
Compressor MODEL
AKA9438ZXD
Receiver
51082-1K
Unit Drawing
DGU1909-L411
Compressor BOM
AK175ET-037-P2
Accumulator
TK00013000
Wiring Diagram
WD21-103
Compressor LRA
31
Liquid Filter
70139
Compressor RLA
4.30
Sight Glass
70084-S
Suction Filter
704-20001
OverLoad
8300MRTG57
Replacement Kit - O/L
High Pressure Switch
84095-2L
Relay
8200RVAM01
Low Pressure Control
84026-2
Replacement Kit - Relay
K71-17
Low Pressure Switch
----
Run Capacitor
85PR370E36
Head Master Valve
70083
Replacement Kit Run Cap.
K150-03
Check Valve
56626
Loose Optional Items
Start Capacitor
85685
Liquid Valve
31590
Disconnect Switch
LDSG-311
Replacement Kit Start Cap
K146-02
Suction Valve (Base)
56500-K08
Liquid Solenoid
KSVC-285
Contactor
91014H
Hail Louver
----
TPC January 26, 2016
Loading...