TECSYSTEM T2612, T2612-B, T2612-C, T2612-AD Instruction Manual

http://www.tecsystem.it
T2612 T2612-B T2612-C
T2612-AD
INSTRUCTION MANUAL
TECSYSTEM S.r.l.
20094 Corsico (MI)
Fax: +39-0248600783
T2612 UNI
TECSYSTEM S.r.l ®
R. 1.3 07/09/12
2
T2612 UNI
TECSYSTEM S.r.l ®
POWER SUPPLY
Rated voltage 120 or 240 Vac 50/60 Hz
Selection through voltage jumper
Tolerance +/- 10%
Power input protected by 500 mA fast
fuse
COMMUNICATION: ONLY FOR T2612 AND T2612AD
Standard serial output RS485 Modbus® RTU
ANALOGUE OUT: ONLY FOR T2612C AND T2612AD
1 output 4-20 mA ref. 0-240°C
INPUTS
4 inputs RTD Pt100 sensors - 3 wires
4th additional input (selectable)
Removable rear terminals
Input channels protected against electri-
cal and magnetic noises and spikes
Sensors length cables compensation up
to 500 m (1mm²)
OUTPUTS
2 alarm relays (ALARM-TRIP)
Output contacts capacity of ALARM, TRIP,
FAULT relays: 5A 220Vac cosφ=1
Fan 1 and Fan 2 outputs protected by sepa­rate 10A slow fuses (max 16A)
Output contacts capacity of FAN relays: 20A 220Vac cosφ=1
TEST AND PERFORMANCES
Assembling in accordance with CE rules
Protection against electrical and mag-
netic noises CEI-EN61000-4-4
Dielectric strength: 2500 Vac for 1 min­ute from relays to sensors, relays to power supply, power supply to sensors
Accuracy: ± 1% full scale, ± 1 digit
Ambient operating temperature: -20°C to
60°C
Humidity: 90% non-condensing
Housing: painted steel panel, frontal part
in polycarbonate IP65
Burden 7VA
Data storage 10 years minimum
Digital linearity of sensors signal
Self-diagnostic circuit
Program and reading resolution: 1 digit
Opt. Protection treatment of electronic
part
DISPLAYING AND DATA MANAGEMENT
1 display 20.5 mm high with 3 digits for dis­playing temperatures
LED for displaying reference channel
LED’s indicating alarm or trip channel
LED indicating FAULT
Temperature monitoring from 0°C to 240 °C
2 alarm thresholds for channels 1-2-3
2 alarm thresholds for channel 4
2 alarm ON-OFF thresholds for fan control
Manually operated fans
Sensors diagnostic (Fcc-Foc-Fcd)
Entering the programming by frontal push
button
Automatic stop of programming cycle after 1 minute of no operation
Wrong programming automatic display
Possibility of setting automatic channel
scanning, hottest channel, manual scanning
Maximum temperatures and alarms storage
Frontal alarm reset key
Possibility of setting HOLD function for out-
put relays
DIMENSIONS
Frontal panel: 320mm x 210mm
Depth 90mm
1) TECHNICAL SPECIFICATIONS
3
T2612 UNI
TECSYSTEM S.r.l ®
2) MOUNTING
Make a hole with the dimensions of 155 x 280 mm (See cut-out diagram at page 13)
3) POWER SUPPLY
Select the power voltage (120 or 240 VAC) through the “Voltage change” jumper.
REMARK: In case of unit replacement, to grant the correct and safe operating, you must replace the sensors, relays, and power supply connecting terminals with the new terminals provided with the unit: this only if the terminal blocks are of different brand.
4) ALARMS AND FAN CONTROL ELECTRICAL CONNECTIONS
Take the removable terminal board off the unit before wiring. ALARM and TRIP relays energize only when the prefixed temperature limits are reached. The FAULT relay always energizes when the apparatus is powered and it resets when the Pt100’s are damaged or when there is no power voltage. The FAN relays can be used for fan control or else they can be included in the conditioning circuit of the transformer box.
5) THERMOMETRIC SENSORS CONNECTION
Each Pt100 sensor has three conductors : one white and two red (CEI 75.8) Fig.1 shows the disposition in the terminal board of the connection cables to the unit. Channel 2 must be always referred to the central column of the transformer. Channel 4 must be always referred to the ambient Pt100 sensor, if you want to monitor the temperature of the transformer box through the T2612 unit.
6) PT100 EXTENSION CABLE: TECHNICAL SPECIFICATIONS
Cable 20xAWG 20/19 Cu/Sn Section 0.55 mm² Flame retardant Insulation PVC105 In accordance with CEI 20.35 IEC 332.1 Max working temperature: 90°C Conformation : 4 terns of twisted and coloured conductors Shield Cu/Sn PVC flame retardant protection covering External diameter 12.0 mm Skeins of 100 m
In order to protect the electronic apparatus, we recommend the application of the insulation transformer 240VAC/240VAC or 120VAC/120VAC.
4
T2612 UNI
TECSYSTEM S.r.l ®
7) MEASURE SIGNALS TRANSPORT
All the transport cables of the Pt100 measure signals must absolutely:
be divided from the power ones
be realized with shielded cable with twisted conductors
have a section of min 0.5 mm²
be twisted if you have no shield
be firmly fixed in the terminal board
have tinned or silvered conductors
All the “T” series units have the sensors linearization with a max error of 1% v.f.s..
8) THERMOMETRIC SENSORS DIAGNOSTIC
In the event one of the thermometric sensors installed on the machine to protect is dam­aged, the FAULT relay energizes immediately, the ALARM and TRIP LED’s of the dam- aged channel lighten and the FAULT LED is lightening. The screen will automatically display a message showing the fault condition:
Fcc sensor is short circuited
Foc sensor is open
9) FCD FUNCTION - DEFECTIVE SENSORS
During the unit normal operation, if the Fcd-YES function has been selected, the display will show Fcd indicating that a sensor is damaged and the LED corresponding to the affected channel will lighten. The FAULT relay will energize giving a signal to the operator. After the replacement of the damaged sensor, you can reset the alarm pushing RESET until the display shows the message rSt.
10) TEMPERATURES DIAGNOSTIC
When one of the thermometric sensors surveys a temperature exceeding by 1°C the alarm limit, after 4 seconds the ALARM relay will energize and the ALARM LED of the affected channel will switch on. The same occurs when the TRIP temperature limit is detected: the TRIP relay energizes and the TRIP LED corresponding to the affected channel is lightening. When the surveyed temperature declines of 1°C below the prefixed limit for the ALARM and TRIP switching , the relays de-energize and the respective LED’s switch off.
TECSYSTEM srl has realised a special cable for the measure signal transport with all the protection requirements according to CEI Norms: mod. CT-ES
5
T2612 UNI
TECSYSTEM S.r.l ®
11) COOLING-FAN CONTROL
The T2612 unit, if suitably programmed, can control the ON/OFF of the transformer fans according to the set temperature values. The fans of the machine can be controlled in two different ways:
using the temperatures surveyed by the sensors on the three columns
CHF 1 2 3 - CH4 excluded
ALARM and TRIP LED 1.2.3 illuminated (e.g. F1: ON at 80°C - OFF at 70°C)
(e.g. F2: ON at 90°C - OFF at 79°C)
by an additional sensor (CH4-YES) for the ambient temperature inside the transformer
box.
CHF 4 ALARM e TRIP LED Ch4 illuminated (e.g. F1: ON at 40°C - OFF at 30°C)
(e.g. F2: ON at 45°C - OFF at 35°C)
Press
and key to select this function.
It is possible to operate the fans manually by pushing the AUTO/ON key.
12) FAN TEST
It is possible, through programming (HFn), to lay down that fans are activated for 5 minutes each “xxx” hours, regardless of column or room temperature values (ex.: with HFn=001 fans are activated for 5 minutes each hour; Maximum value: 240). This function has the aim to periodically verify the working of the fans and their control ap­paratus during long idle periods. Loading 000 value, this function is inhibited.
13) HOLD FUNCTION
To select the hold function choose the program option HLD-Yes. With hold function en­abled, when temperature exceeds the alarm set point value, the alarm relays will energize and the alarm LED’s will illuminate until you reset the relay contacts in manual reset mode. Reset is only possible when temperature falls below the set point value. To exclude the hold function select the program option HLD-no.
14) DISPLAY MODE
By pressing DISPLAY MODE you can select one of the three display modes:
HOT : the display shows automatically the temperature of the hottest channel
MAN : each channel may be viewed manually by pressing the
or key.
T.MAX: the unit shows the max. temperature recorded by the sensors and any alarm recorded after the last reset. To check the channels press
or key.
SCAN : channels cyclically change every 2 seconds
Loading...
+ 11 hidden pages