TECSYSTEM NT538 Instruction Manual

http://www.tecsystem.it
INSTRUCTION MANUAL
TECSYSTEM S.r.l.
20094 Corsico (MI)
Tel.: +39-024581861
Fax: +39-0248600783
NT538
R. 1.3 07/09/12
NT538
2
NT538
INNOVATIONS INTRODUCED WITH THE NT538
1. New hardware and software for a further improvement of immunity to disturbances.
2. Reading rate increasing, indispensable for applications where fast temperature variations must be monitored.
3. Intelligent control of alarm detecting relays which is able to exclude possible overtemperatures caused by an external disturbance without causing working prob­lems or manual reset conditions.
4. Detecting of possible corruption of data stored in the memory (Ech) and default value reset for security.
5. Storage in T. Max mode of possible alarms occurred from last reset and recording of possible sensor failures.
6. Error detecting in case of wrong programming with specific indication of the wrong value couple.
7. Possibility to return to previous programming step for a faster value modification.
8. SCAN display mode to see, in sequence, the temperature and the state of the
alarms for all channels
9. 8 channels with two programmable thresholds in an independent way.
10 Fan contact to check a cooling system.
11. More compact sizes compared with T538 version1.
12. Options with serial output to control the expansion module such as:
a) EXT 4.20-8: module with 4-20 mA outputs for each channel b) EXT RL-8: module with 2 relays (alarm and trip) for each channel c) EXT RS485 Modbus: module for connection on a Modbus network
13. Possibility to connect many expansion module on serial output in order
to have many expanding options simultaneously.
3
NT538
1) TECHNICAL SPECIFICATIONS
POWER SUPPLY
Rated values 24-240 Vac-dc
Highest tolerable values 20-270 Vac-dc
Vdc with reversible polarity Vdc
COMMUNICATION
option
INPUTS
8 inputs RTD Pt100—3 wires
Removable rear terminals
Input channels protected against electro-
magnetic noises and spikes
Sensor length cable compensation up to
500 m (1 mm² )
OUTPUTS
2 alarm relays (ALARM-TRIP)
1 alarm relay for fan control (FAN)
1 alarm for sensor fault or working anom-
aly (FAULT)
Outputs contacts capacity: 5A-250V ac resistive.
TESTS AND PERFORMANCES
Assembling in accordance with CE rules
Protection against electrical noises CEI
-EN50081-2/50082-2
Dielectric strength 2500 Vac for 1 minute from relays to sensors, relays to power supply, power supply to sensors
Accuracy ± 1% full scale value ± 1 digit
Ambient operating temperature from –20
°C to +60°C
Humidity 90% no-condensing
housing NORYL 94V0
Frontal in polycarbonate IP65
Absorption 3VA
Data storage 10 years minimum
Digital linearity of sensor signal
Self-diagnosis circuit
Option protection treatment of elec-
tronic part
Vibration test IEC 68-2-6 Amplitude ± 1 mm from 2Hz a 13.2Hz Acceleration ± 0.7G from 13.2Hz to 100Hz.
(*) Seismic test according to IEEE 344-1.987
*Cross reference T154 for constructive analogy.
DISPLAYING AND DATA MANAGEMENT
1 display 13mm high with 3 digit for dis­playing temperatures and messages
8 leds to show selected channel
4 leds to display the state of the alarms
for selected channel
Temperature monitoring from
0°C to 240°C
2 alarm thresholds (alarm/trip) for each channel
2 ON-OFF thresholds for fan control
Sensors diagnostic (Fcc-Foc)
Data storage diagnostic (Ech)
Programming access through front key
Automatic output from programming cycle
after 1 minute of no-operation
Wrong programming automatic display
Possibility of setting automatic channels
scanning, hottest channel, manual scan­ning
Maximum reached temperatures, alarm storage and sensor fault.
Frontal alarm reset push button
DIMENSIONS
100 x 100 mm-DIN43700– depth 140 mm (terminal box included)
Panel cut-out 92 x 92 mm
4
NT538
2) MOUNTING
Make a hole in the panel sheet with dimensions 92x92 mm. Firmly tighten the device with the enclosed fixing blocks.
3) POWER SUPPLY
NT538 control device has an UNIVERSAL supply, i.e. it can be indifferently fed from 24 to 240 Vac-dc, regardless of polarities in Vdc. This peculiarity is obtained using a new-concept and new-designed tested feeder, which relieves the technician of each concern for the correct supply Vac or Vdc. To terminal 41 must always be connected the ground.
When the control device is directly fed from secondary winding of the transformer to be protected, it can be damaged by high-intensity over voltages. These problems occur if the main switch is connected without load. Above mentioned problems are much more evident when the voltage is 220 Vac is directly taken from the transformer secondary bars and there is a fixed capacitor battery to phase the transformer itself.
REMARK: in case of unit replacement, to grant the correct and safe oper ating, you must replace the sensors, relays, and power supply connecting ter minals with the new terminals provided with the unit: this only if the termi nal blocks are of different brand.
4) ELECTRICAL CONNECTIONS FOR ALARMS AND FAN Carry out the electrical connections on the removable rear terminals, after having removed
them from the device. ALARM and TRIP relays switch only when the set temperature limits are reached. FAULT relay (Fault) switches when the meter is fed, while gets de-energised when a fault occurs to Pt100 sensors, data memory fault (Ech) or when supply voltage is lacking. FAN contact can be used to check the cooling fans or it can be inserted in a transformer room conditioning circuit.
5) TEMPERATURE SENSOR CONNECTION
Each temperature sensor Pt100 has a white wire and two red wires (CEI 75.8 standards). Fig. 1 shows the position inside the terminal box of monitoring unit connection cables. Each channel can be independently programmed with two alarm thresholds (alarm and trip).
To protect the control device from line over voltages, we suggest to use the elec­tronic discharger PT73-220, designed by TECSYSTEM S.r.l. for this specific pur­pose. As alternative we suggest to use supply voltages from 24 Vac or, much better, 24 Vdc.
5
NT538
6) MEASURING SIGNAL TRANSFER
All the measuring signal transfer cables for Pt100 must absolutely:
be separated from the power ones
be made with shielded cable and twisted conductors
have at least 0,5 mm² section
be twisted if there is no shield
be firmly fixed inside the terminal boxes
have tinned or silvered conductors
All “NT” series control devices have the sensor signal linearization, with a maximum error
of 1% of full scale value.
7) TEMPERATURE SENSOR DIAGNOSTIC
In case of breaking of a temperature sensor mounted on the machine to be protected, FAULT relay immediately switches with the relevant indication of defective sensor on the corresponding channel.
Fcc for short-circuited sensor.
Foc for interrupted sensor
To eliminate the message and reset Fault switching, it is necessary to verify Pt100 con­nections and, in case, replace the defective sensor.
8) PROGRAMMED DATA DIAGNOSTIC
In case of breaking of the internal storage or corruption of programmed data, just after switching on, it appears Ech indication with the relevant reporting of the Fault contact. In this case, for safety reasons, the default parameters: NCH=8, Alarm Ch1-2-3-4-5-6-7­8= 90°C, Trip Ch1-2-3-4-5-6-7-8= 119°C, Fan= YES, Fan-on= 70°, Fan-off= 60°, HFn= 000 are automatically loaded. Eliminate Ech indication by pressing RESET and run programming to insert desired val­ues. Finally turn off and turn on again the unit to verify the correct memory working; in case it is damaged and Ech still appears, please return the monitoring unit to TECSYSTEM for repair.
9) TEMPERATURE DIAGNOSTIC
If one of the temperature sensor detects a temperature higher than 1°C compared t o set value as alarm limit, after approximately 5 seconds ALARM relay switches together with turning on of channel reference LED ALARM (CHn). When the release temperature limit is passed, TRIP relay switches together with turning on of channel reference LED TRIP (CHn). As soon as taken temperature returns to equal or lower values than set limit for ALARM and TRIP relays switching, they de-energise with consequent turning off of relevant LED’s.
TECSYSTEM S.r.l. has designed an own special cable to transfer the measur­ing signals, according to CEI standards, with all the protection requirements provided for : mod. CT-ES
6
NT538
10) COOLING FAN CONTROL
NT538 monitoring unit, if opportunely programmed, can control ON-OFF of transformer fans, according to set temperatures. Fans on machine are driven using the temperatures taken from enabled channels.
11) FAN TEST
It is possible, through programming (hFn), to lay down that fans are activated for 5 minutes each “xxx” hours, regardless of column or room temperature values (ex.: with hfn=001 fans are activated for 5 minutes each hour). This function has the aim to periodically verify the working of the fans and their control ap­paratus during long idle periods. Loading 000 value, this function is inhibited.
12) DISPLAY MODE
Pressing MODE key, display mode is loaded:
SCAN: control device displays in scansion all activated channels (each 2 seconds)
AUTO: control device automatically displays the hottest channel
MAN: channel temperature manual reading of channel through cursor keys
T.MAX: monitoring unit displays the highest temperature reached by the sensors and
possible alarm or fault situations occurred after last reset.
Select channels with
S and T, delete values with RESET.
13) WORKING PROGRAM CONTROL
To check the programmed temperature values, shortly press PRG key. VIS indication ap­pears for 2 seconds, confirming entering in program vision mode. By repeatedly pressing PRG key, all the previously loaded values are rolled in sequence. After 1 minute of keyboard no-operation, display-programming procedure will be automati­cally left. To end display, press ENT key.
14) LAMP TEST
We suggest to regularly carry out monitoring unit LED test. For this operation, shortly press TEST key; all displays turn on for 2 seconds.
If one of the LED’s should not work, we kindly ask you to return the monitoring unit to TECSYSTEM (Led RS is not available on monitoring units without optional module)
7
NT538
15) ALARM RELAY TEST
This function allows to carry out a test on relays working without having to use further de­vices. To start test procedure you have to keep pressed TEST key for about 5 seconds; TST indication appears for 2 seconds, confirming entering in Relays Test mode. Blinking led shows the relay to test; using the cursors you can select the desired one. Press SET and RESET keys to energise and de-energise the relay to test; display will show ON-OFF. After 1 minute keyboard no-operation, RELAYS TEST procedure will be automatically left. To end RELAYS TEST procedure, press TEST key.
16) ALARM RELAY EXCLUSION
If you want to exclude the ALARM signal press RESET key: relay de-energises itself and LED ALARM, which was fixed, will start to blink. Exclusion system is automatically disconnected when the temperature goes under the ALARM threshold.
17) IMPORTANT NOTICE
Before carrying out the insulation test on the switchboard w here the monitoring unit is mounted, you have to disconnect it from the mains in order to avoid seri ous dam­ages.
18) FRONT PANEL
Alarm selected channel
Display mode
Selected channel
Message and tem-
perature display
Prg/RelaysTest mode
Keyboard
Data transmission (option)
8
NT538
19) PROGRAMMING NOTE: LED PRG-ON OFF:PROGRAM DISPLAY . LED PRG-ON ON: PROGRAM MODIFICATION
1) It is possible to return to previous step by pressing MODE key.
2) if pressing ENT it appears “ERR”, it means that one of the following mistakes has been made: ALARM TRIP or FAN-OFF FAN-ON. Press PRG to return to step 1 and correct the data.
3) After 1 minute of keyboard no-operation, programming is left without data storage.
PRESS EFFECT NOTES
1 PRG/SET
Keep pressed PRG key until PRG-ON led
turns on. After PRG indication, it appears
NCH indication (number of channels)
If NOP appears please see
“Programming block” paragraph
2 Load number of desired channels
Refer to channel leds
(from 1 to 8)
3 PRG/SET It appears ALARM threshold for CH 1 4 Load desired threshold 5 PRG/SET It appears TRIP threshold for CH 1
Follow the same procedure for the number of channels chosen at step 2
6 PRG/SET Fan led blinks 7 Set: YES or NO
NO: disabled fan
YES: enabled fan
8 PRG/SET Display shows ON FAN turning on
9 PRG/SET It appears ON threshold for FAN 10 Load desired threshold 11 PRG/SET Display shows OFF FAN turning off
13 Load desired threshold 14 PRG/SET Display shows HFN
Fan cyclic test for 5 minutes
each “n” hours
15 Load desired number of hours 000= disabled function
22 PRG/SET Display shows END Programming end 23 ENT Loaded data storage and programming exit
Err
(2)
: wrong programming for
values indicated by leds
24 PRG/SET Return to step 1
16 PRG/SET
Display shows n.o./ n.c.
and Alarm led blinks
Alarm relay working logic
19 Set n.o. or n.c.
n.o.: normally open
n.c.: normally closed
17 Set n.o. or n.c.
n.o.: normally open
n.c.: normally closed
18 PRG/SET
Display shows n.o./n.c.
and Trip led blinks
Trip relay working logic
20 PRG/SET Display shows FCD <> “threshold”
Fault for fast temperature
increase (°C/sec)
21
Load desired threshold
(see page 10)
From “no” up to 30 °C/sec
(no: disabled function)
12 PRG/SET It appears OFF threshold for FAN
Loading...
+ 18 hidden pages