TECO-Westinghouse Motor GA7200 Operation Manual

4H358D0030007
M O T O R C O M P A N Y
Operation Manual
GA7200
380 to 460V 1HP~450HP 200
to 230V 1HP~100HP
The GA7200 is a high-performance/low noise general-purpose inverter. This manual describes
the operation procedures for the digital operator (JNEP--12) provided with the GA7200.
A thorough understanding of this operation manual and the GA7200 installation manual is
recommended before using the GA7200.
2
CONTENTS
Page
1. OUTLINE............................................................................................... 5
1.1 MAIN FUNCTIONS............................................................................................................................. 5
1.2 DIGITAL OPERATOR KEYPAD.......................................................................................................... 6
2. DRIVE MODE AND PROGRAM MODE................................................ 8
2.1 DISPLAY CONTENTS........................................................................................................................ 9
2.2 CONSTANT GROUPS ....................................................................................................................... 10
3. CONSTANTS SETTING AND CHANGE ............................................... 11
3.1 STANDARD FACTORY SETTING .....................................................................................................11
3.2 FREQUENCY REFERENCE SETTING AND CHANGE .................................................................. 11
3.3 CONSTANTS CHANGE AND FUNCTION SELECTION ................................................................... 12
3.4 OPERATION ERRORS “ ”................................................................................................. 13
4. WIRING................................................................................................. 14
4.1 CONNECTION DIAGRAMS ............................................................................................................... 14
4.2 TERMINAL FUNCTIONS (MAIN CIRCUIT)……………………………………………………………….16
5. DIGITAL OPERATOR PROGRAMMING............................................... 18
6. PROGRAM MODE SETTING AND CHANGE....................................... 20
6.1 V/f PATTERN SETTING ....................................................Sn-02....................................................... 23
6.2 ACCEL/DECEL TIME SETTING .......................................bn-0 I to-04 (Sn-06, Sn-15 to -18)........... 24
6.3 INPUT SIGNAL SELECTION ............................................Sn-04....................................................... 27
6.4 PROTECTIVE CHARACTERISTICS SELECTION...........Sn-10 to-14 ............................................. 28
6.5 MULTI-FUNCTION INPUT SELECTION...........................Sn-04, Sn-15 to 19, bn-09....................... 31
6.6 CONTACT OUTPUT SELECTION ....................................Sn-20....................................................... 37
6.7 FREQUENCY REFERENCE CHANGE ............................bn-05, -06................................................ 40
6.8 DC INJECTION BRAKING (DC) .......................................Cn-10 to -13 ............................................ 41
6.9 FULL-RANGE DC INJECTION BRAKING STOP
(DCB STOP).....................................................................Sn-04=10 XX, Cn-12............................... 42
6.10 UPPER/LOWER LIMIT OF
FREQUENCY REFERENCE ..........................................Cn-14, -15 ............................................... 43
6.11 PROHIBITED (SKIP) FREQUENCY ...............................Cn-16 to -19 ............................................44
6.12 DISPLAY MODE CHANGE .............................................Cn-20 ...................................................... 45
6.13 STALL PREVENTION LEVEL WHILE RUNNING...........Cn-30 (Sn-10) ......................................... 46
6.14 AUTO RESET/RESTART OPERATION AT FAULT.........Cn-36 ...................................................... 47
6.15 INITIALIZING CONSTANTS............................................Sn-03....................................................... 48
3
7. CONSTANTS/FUNCTION LIST ............................................................ 50
7.1 FREQUENCY REFERENCE ..........................................An- .................................................. 50
7.2 CONSTANT CHANGE WHILE RUNNING......................bn- .................................................. 51
7.3 SYSTEM CONSTANTS...................................................Sn- .................................................. 55
Inverter Capacity Selection ...............................................Sn-01....................................................... 62
V/f Pattern Selection .........................................................Sn-02....................................................... 66
Operation Mode Selection 1 .............................................Sn-04....................................................... 69
Operation Mode Selection 2 .............................................Sn-05....................................................... 72
Operation Mode Selection 3 .............................................Sn-06....................................................... 73
Operation Mode Selection 4 .............................................Sn-07....................................................... 76
Operation Mode Selection 5 .............................................Sn-08....................................................... 77
Operation Mode Selection 6 .............................................Sn-09....................................................... 78
Protective Characteristic Selection 1 ................................Sn-10....................................................... 89
Protective Characteristic Selection 2 ................................Sn-11....................................................... 81
Protective Characteristic Selection 3 ................................Sn-12....................................................... 82
Protective Characteristic Selection 4 ................................Sn-13…………………………………Not Used
Protective Characteristic Selection 5 ................................Sn-14....................................................... 83
7.4 MULTI-FUNCTION CONTACT INPUT SELECTION ......Sn-15 to -18 ............................................ 84
7.5 MULTI-FUNCTION ANALOG INPUT SELECTION ........Sn-19....................................................... 96
7.6 MULTI-FUNCTION CONTACT OUTPUT SELECTION ..Sn-20 to -22 ............................................ 97
7.7 CONTROL CONSTANTS................................................Cn- ................................................. 101
7.8 MONITOR DISPLAY .......................................................Un- ................................................. 117
8. FAULT DISPLAY AND TROUBLESHOOTING...................................... 119
9. GA7200 TERMINAL FUNCTIONS ........................................................ 123
10. APPENDIX (OPTIONS AND PERIPHERALS) .................................... 124
10.1 OPTION CARDS .............................................................................................................................. 124
10.2 ANALOG OPERATOR...................................................................................................................... 125
10.3 BRAKING RESISTOR AND BRAKING UNIT................................................................................... 126
10.4 AC REACTOR .................................................................................................................................. 127
10.5 NOISE FILTER ................................................................................................................................. 128
4
1.1 MAIN FUNCTIONS
1. OUTLINE
Function Description
Drive Mode
GA7200 can be operated easily with the digital operator.
Function selection and constant setting for
Program Mode
GA7200 can be performed with the digital operator.
Monitoring of output frequency, output
Monitor Function
current, output voltage or status of run / stop commands can be performed with the digital operator.
If a fault occurs, its contents order of occurrence is displayed. When the power
Fault Contents Display
supply is turned ON, maintenance inspection or troubleshooting can be performed since fault is recorded.
5
q
y
y
y
y
y
y
1.2 DIGITAL OPERATOR KEYPAD
Mode Display
Drive Mode Display Red lamp lights in DRIVE mode and goes out in PRGM mode.
Rotation Direction Display Red lamp lights in DRIVE mode and goes out in PRGM mode.
REMOTE Mode Red lamp lights when controlled by external terminal commands. SEQ: When RUN/STOP signal is selected from terminals. REF: When fre
Displa
Displays set value of each function or monitoring values such as frequency and output current. (5 digits)
uency reference is selected from terminals.
Mode Selection Ke
Depressing this key changes mode. (DRIVE or PRGM)
Display Selection Ke
Depressing this key changes the display.
Read/Write Ke
Depressing this key recalls and displays data from memory. Depressing it a second time enters display data into memory.
Numeral Change Key
Changes numeral such as set values and constant signals.
︿
: Increment key
: Decrement key
Digit Selection Ke
Selects numerical digits. Selected digit blinks. This key resets operation when fault occurs.
Run Command Ke
Run Command Key to operate by digital operator.
STOP command is input. (Motor stops in either mode.)*
Red lamp lights by depressing STOP. *
Selects FWD or REV run. Effective only in DRIVE mode.
While depressing this key, JOG speed is selected. Effective only in DRIVE mode.
6
*
RUN or STOP lamp changes in accordance with the following operations.
INVERTER OUTPUT FREQUENCY
RUN
FREQUENCY
RUN
Lamp
STOP
Lamp
: Lit : Blink
: Off
STOP
7
2. DRIVE MODE AND PRGM (PROGRAM) MODE
Selection of DRIVE mode or PRGM mode can be performed by using the key when the
PRGM
DRIVE
inverter is stopped. When function selection or a change of set value is required, switch to the PRGM mode.
Operation is enabled.
An operation can be performed by
DRIVE mode functions
PRGM mode functions
JOG
and keys.
Frequency reference value or bn constants
can be changed while running.
Program (function selection, constant setting) can be changed.
Note: Cannot be performed while running.
FWD
REV
RUN
STOP
8
g
y
y
y
2.1 DISPLAY CONTENTS
MODE SWITCHABLE ONLY AT STOPPING
PRGM
DRIVE
É
-
Display of faults which occurred before power supply was turned OFF
É
É
É
­Frequency reference
value displa
-
Output frequency
-
monitor displa
Output current monitor displa
Display of faults which occurred before power supply was turned OFF
If a fault occurs, the contents are displayed. Fault occurrence order and display are provided by
Fault reset
or keys.
RESET
Un- monitor É display
É
An- reading/setting
É
bn- readin
/setting
The constant group to be displayed is changed each time display selection key DSPL is depressed.
ÉFor details of constants ( An- , bn- , Cn- , Sn- , Un- , refer to Section 7, “CONSTANTS/FUNCTION LIST.”
9
2.2 CONSTANT GROUPS
Constants of GA7200 are classified as follows:
Constant Group Contents
An-
bn-
Cn-
Sn-
Frequency reference setting
Constant group able to be changed while running
Constant, among control constant groups, related to operation change characteristics
Constant, among system constant groups, to be used for function selection
The ability to set or read the different groups of constants is
determined by Sn-03 as shown below.
DRIVE Mode PRGM Mode
Sn-03
Setting Reading Setting Reading
0000
0101 An bn, Sn, Cn An bn, Sn, Cn *
An, bn Sn, Cn An, bn, Sn, Cn Factory set
Remarks
* It is recommended that Sn-03 be set to 0101 and reading mode entered after test run adjustment.
Note: To read the Sn or Cn constants while in the DRIVE mode, depress the
key depressed.
RESET
DSPL
key with
10
3. CONSTANTS SETTING AND CHANGE
3.1 STANDARD FACTORY SETTING
Contents Set Value
Frequency Reference Input Can be set by digital operator.
Run Command Input
V/f Pattern 60Hz, constant torque characteristics (Standard motor)
Acceleration Time 10 seconds
Motor Protection Electronic overload thermal protection (Standard motor)
Can be set by digital operator.
(RUN/STOP/FWD/REV/JOG)
Note: For more details, refer to Section 7 “CONSTANTS/FUNCTION LIST.”
3.2 FREQUENCY REFERENCE SETTING AND CHANGE
(Example) Frequency reference value is set to 15Hz.
Description Keypad Operation Digital Operator Display Remarks
Frequency reference value
is displayed.
Set or change reference
value. (Input “1”).
DSPL
Blinking
Select digit.
Set or change reference
value. (Input “5”.)
Write-in constant.
RESET
ENTER
DATA
11
Stops blinking for 2 seconds.
3.3 CONSTANTS CHANGE AND FUNCTION SELECTION
All constants are changed and functions are selected in the same manner.
When changing Cn- and Sn- constants, program mode must be selected.
(Example) Jog frequency (An-09) set value is changed from 6Hz to 10Hz.
Description Keypad Operation Digital Operator Display Remarks
Constant group to be set
or changed is displayed.
Select constant No. to be
set or changed.
Constant set value is
displayed.
Constant is set or
changed.
Set value is written in.
DSPL
DATA
ENTER
DATA
ENTER
-
-
(“End” is displayed for 0.5
second).
Confirm “End” displayed for
each constant.
12
3.4 OPERATION ERRORS “ “
The constant setting fault is checked when power is applied or PRGM is changed to DRIVE mode. Digital operator displays faults if the is detected. The fault contact output of the inverter is not executed. If the following “conditions” occur at power ON or changing PRGM into DRIVE , it becomes .
Display Fault Conditions Example
kVA Constant
Setting Fault (Sn-01)
Constant Setting
Range Fault
Multi-function Input Setting Fault (Sn-15 to-18)
V/f Data Set Fault (Cn-02 to-08)
When 460V class constant is set for 230V class inverter or 230V
class constant is set for 460V.
When “out of setting range” constant is set.
When multi-function inputs Sn-15 to -18 are set as follows:
Set values are not arranged in numerical order. (including equal
values)
Both search references “61” and “62” are set.
Up command (set value = 10) and DOWN command (set value =
11) cannot be set simultaneously.
Up command (set value = 10), DOWN command (set value = 11)
and accel prohibit command (set value = 0A) are set together.
More than two set values except FF are set.
When Cn-02 to 08 do not satisfy the following conditions.
F
max.≧FA>FB≧FMIN.
(Cn-02) (Cn-04) (Cn-05) (Cn-07)
V
V
max.
(Cn-03)
V
C.
(Cn-06)
V
min.
(Cn-08)
F
(Cn-07)
min.
F
(Cn-05)
Sn-15 = 3
Sn-16 = 4
Sn-17 = 6
Sn-18 = 5
Cn-02 = 50
Cn-04 = 60
Cn-05 = 3
Cn-07 = 1.5
F
F
A
B
(Cn-04)
max.
(Cn-02)
F
Constant Set Fault
Constant Write-in
Fault
When any following set fault:
Carrier frequency upper limit (Cn-23) > 5kHz and Carrier frequency
lower limit (Cn-24) 5kHz.
Carrier frequency proportional Gain
(Cn-25) > 6 and (Cn-23) < (Cn-24)
The constant is not written in correctly to NV-RAM.
(Only at initialization)
13
Cn-23 = 6kHz
Cn-24 = 5kHz
/
/
/
/
/
/
4. WIRING
GA7200 has been programmed to operate from the digital operator when shipped from the factory. Therefore, just connecting the main circuit power enables drive operation.
Note: When external signals or external devices and digital operator are used, refer to Section 7, “CONSTANTS/FUNCTION LIST”, in this manual.
4.1 CONNECTION DIAGRAM
230V Class
10 HP (7.5kW, 13.7kVA) or smaller
B1/
3-PHASE
POWER
SUPPLY
R
S
T
15/20 HP (11/15kW, 20.6/27.4kVA)
3-PHASE
POWER
SUPPLY
R
/L1
S
/L2
T
/L3
r
s
25 HP (18.5kW, 34kVA) or larger
/L1
GA7200
/L2
/L3
JNEP--12
B1/ 2
GA7200
JNEP--12
B2
B2
T3/W
T1
T2
T3
T1/U
T2/V
PE
PE
U
V
W
IM
IM
3-PHASE
POWER
SUPPLY
R
/L1
/L2
S
/L3
T
r
s
14
GA7200
JNEP--12
T1
T2
T3
PE
U
V
W
IM
/
/
/
/
/
/
/
/
/
460V Class
10 HP (7.5kW, 13.7kVA) or smaller
3-PHASE
POWER
SUPPLY
15/20 HP (11/15kW, 20.6/27.4kVA)
3-PHASE
POWER
SUPPLY
25 HP (18.5kW, 34kVA) or larger
3-PHASE
POWER
SUPPLY
/L1
R
/L2
S
/L3
T
/L1
R
/L2
S
/L3
T
R
/L1
/L2
S
/L3
T
r
S400
B1/
GA7200
B1/
GA7200
JNEP--12
GA7200
JNEP--12
B2
JNEP--12
U
T1
T2
V
T3
W
PE
2
B2
U
T1
T2
V
T3
W
PE
U
T1
T2
V
T3
W
PE
IM
IM
IM
15
4.2 TERMINAL FUNCTIONS
MAIN CIRCUIT
VOLTAGE 230V CLASS 460V CLASS
Rating
Terminal
R(L1)
S(L2)
T(L3)
U(T1)
V(T2)
W(T3)
B1/○+
B2
-
+1, ○+
+2
+3
s
r
s400
PE ( ) Grounding
1~10HP 15~20HP 25~30HP 40~100HP 1~10HP 15~20HP 25~60HP 75~450HP
Circuit input power supply
Inverter output
B1/○+,B2:
braking resistor
B1/○+,○-: DC power supply
-
- -
B2: braking resistor
+
2:optional DCL
DC power supply
-
B1/○+,
B1/○+,
B1/○+,○-:
- - - -
+1,
+2,○+
+, ○- : DC power supply or Braking Unit
-
r-s: cooling fan power supply
- : DC
power supply or Braking Unit
3: DCL
r-s: cooling fan power supply
B1/○+,B2: braking
resistor
DC power
B1/○+,○-:
supply
-
B1/○+,B2:
braking resistor
B1/○+,○+ 2:optional DCL
B1/○+,○-: DC power supply
-
-
- : DC
power supply or Braking Unit
3: DCL
r-s: cooling fan power supply
+1,
+2,○+
+, ○-: DC power supply or Braking Unit
r-s: cooling fan power supply
16
CONTROL CIRCUIT
Classifi-
cation
Sequence Output Signal
Analog Input Signal
Sequence Output Signal
Output
Signal
Terminal Signal Function Description Signal Level
Forward operation-stop
1
signal
Reverse operation-stop
2
signal
3 External fault input Fault at closed, normal state at open
4 Fault reset input Reset at closed
Master/Aux.
5
Multi-step speed ref. 1
6 Multi-step speed ref. 2 Effective at “closed”
7 Jog command Jog run at “closed”
8 External coast to stop
11 Sequence common -
Power supply terminal for
15
speed reference
13 0 to +10V/100% freq. 0 to +10V (20kΩ)
Master speed frequency reference
14
16 Aux. frequency reference 0-10V/100%
Common terminal for control
17
circuit
12 Shield connection - -
9
During running (NO) Run at “closed”
10
25 Zero speed detection
26 Speed agreed detection
27 Open collector output common -
18
Fault contact output
19
common (NO, NC)
20
21 Frequency meter output Analog
22 Common
Forward run at closed, stop at open
Reverse run at closed, stop at open
Auxiliary freq. ref. at “closed”
Inv. output stop at “closed”
Speed reference power supply
4 to 20mA/100% freq. 4 to 20mA (250Ω)
0 -
Occurs at minimum freq. (Cn-07) or less
Occurs when the frequency reaches 1% of set freq.
Fault at closed between terminals 18 and 20 Fault at open between terminals 19 and 20
0 to 10V/100% freq.
Multi-function contact input: the following signals are available to select. Forward/reverse select, run mode select, multi-speed select, jog frequency select, accel/decel time select, external fault, external base clock stop, hold command, aux. input effective, speed search, energy-saving operation.
Multi-function contact input: one of the following signals are available to select. Speed command, speed gain, speed bias, over torque, over voltage bias, rate of accel/decel, DB current.
Multi-function contact input: one of the following signals available to output. Output during running, zero speed, synchronized speed, arbitrary speed agreed, frequency detection, overtorque,
±
undervoltage, run mode, coast to stop, braking resistor overheat..
Ammeter/voltmeter/wattmeter output selection available
Photo-coupler insulation input +24V DC 8mA
+15V (Allowable current 20mA max.)
0 to +10V (10k)
Dry contact Contact capacity:
250V AC 1A or less 30VDC 1A or less
Open collector output +48V 50mA or less
Dry contact Contact capacity:
250VAC 1A or less 30VDC 1A or less
0 to11V max. 2mA or less
17
,
supply
5. DIGITAL OPERATOR PROGRAMMING
The following is an operation example for the digital operator keypad.
Operation Pattern
Typical Operation
INPUT VOLTAGE SETTING
POWER ON
FWD SELECTION
Description Keypad Operation Digital Operator Display Remarks
PRECAUTION
Before Power ON
For the 460V class, 25HP (18.5kW, 34kVA) or larger inverter,
change the supply voltage selection tap of control transformer to the same tap as input voltage. Refer to Installation Manual.
Before Operation
Be sure to set input voltage in control constant Cn-01.
The initial value is 220 for 230V class
FWD 60Hz
FWD 15Hz
RUN FWD JOG
FREQUENCY SETTING
SET VALUE CHANGE
REV SELECTION
440 for 460V class.
REV 60Hz
t
Frequency reference
1
Turn on
power supply
Set input
2
voltage power
Cont’d
value is displayed.
Select PRGM mode.
Select control constant
(Cn- )
(ex: 220V)
Display Cn-01 data.
Set 220V as input
voltage.
PRGM
DRIVE
DSPL
DATA
ENTER
RESET
DATA
ENTER
Depress three times.
18
-
-
LED DRIVE OFF
Displayed for 0.5 second.
Confirm the display.
g
3
4
Cont’d
FWD JOG
Frequency
Settin
Description Keypad Operation Digital Operator Display Remarks
15Hz
Select DRIVE mode.
Select output frequency
monitor display.
Select rotating direction.
(FWD is default at power
ON.)
Jog operation.
Frequency reference
value display is selected.
Change reference value.
Set value is written in.
Select output frequency
monitor display.
PRGM
DRIVE
DSPL
JOG
DSPL
RESET
DATA
ENTER
DSPL
Depress Six times.
LED DRIVE lights.
LED FWD lights.
Stops blinking for two seconds.
5
FWD RUN
6
frequency
7
REV RUN
8
Change
reference
value
60Hz
STOP
Running operation.
Select frequency
reference value display.
Change reference value.
Set value is written in.
Select output frequency
monitor value.
Switch to reverse run.
Decelerate to a stop.
RUN
DSPL
RESET
DATA
ENTER
DSPL
FWD
REV
STOP
LED lights.
RUN
Stops blinking for two
seconds.
LED REV lights.
STOP
LED lights.
blinks
RUN
while decelerating
19
pag
6. PROGRAM MODE SETTING AND CHANGE
The following shows an example of main functions and characteristics.
6.1 V/f PATTERN SETTING
Sn-02
16 types of V/f patterns are available according to motor type, load characteristics and operating conditions.
To select V/f pattern, set the inverter input voltage to Cn-01.
For details on the different V/f patterns, refer to Par. 7.3
SYSTEM CONSTANTS “V/f PATTERN SELECTION” on
e 67.
PRECAUTION
■■ FIXED V/f PATTERN SELECTION
(Example) Change to variable torque characteristics (Set “7”.)
Description Keypad Operation Digital Operator Display Remarks
Select PRGM mode.
Select Sn-02.
Constant display
value is displayed.
Set or change
constant.
Constant value is
written in.
PRGM
DRIVE
DSPL
DATA
ENTER
RESET
DATA
ENTER
Depress twice.
-
-
LED DRIVE OFF
Displayed for 0.5 second. Confirm the display for each constant.
20
INPUT VOLTAGE SETTING
(Example) Set input voltage to 220V.
Description Keypad Operation Digital Operator Display Remarks
Select PRGM mode.
Select Cn-01.
Constant set value
is displayed.
Set or change
constant.
Constant value is
written in.
PRGM
DRIVE
Depress three times.
DSPL
DATA
DATA
ENTER
RESET
ENTER
-
-
LED DRIVE OFF
Displayed for 0.5 second. Confirm the display for each constant.
21
ARBITRARY V/f SETTING (Sn-02, Cn-02 to -08)
(Example) Change to “F
= 120Hz, V
max
= 18V”.
min
Description Keypad Operation Digital Operator Display Remarks
Select PRGM mode.
Select Sn-02.
Constant set value
is displayed.
Set or change
constant. Set to “F”.
Constant is written
in.
Select Cn-02.
Constant set value
is displayed.
Set or change
constant.
Constant value is
written in.
Select Cn-02.
Select Cn-08
Constant set value
is displayed.
Set or change
constant.
Constant value is
written in.
PRGM
DRIVE
DSPL
DATA
ENTER
RESET
DATA
ENTER
DSPL
DATA
ENTER
RESET
DATA
ENTER
DSPL
DSPL
DATA
ENTER
RESET
DATA
ENTER
Depress twice.
-
-
-
-
-
LED DRIVE OFF
Refer to the
next page
Displayed for 0.5 second. Confirm the display for each constant.
22
Set Sn-02 to F.
(18V) (Cn-08)
V
V
max.
(Cn-03)
V
C.
(Cn-06)
V
min.
F (Cn-07)
min.
(Cn-05)
F
B
F
A
(Cn-04)
F
max.
(Cn-02) (120Hz)
F
If F
MAX.
F
FB≧F
A
is not satisfied, a setting error occurs.
MIN.
When V/f pattern is selected to be linear, set the same value for Cn-07 and
Cn-05. (Cn-06 setting is disregarded). Refer to pages 67, 68 and 69 for V/f
pattern selection.
23
(
6.2 ACCEL/DECEL TIME SETTING
bn-01 to -04 (Sn-06, Sn-15 to -18)
Accel/decel time can be changed in DRIVE mode during running.
Acceleration and deceleration time each has two set values. When “ accel/decel time change” is selected (7 is set in Sn-15, Sn-16, Sn-17 or Sn-18) as a multi-function terminal function, the values set in bn-03 and-04 become effective.
S-curve characteristics of soft start can be selected in the 1-and 2-digits of Sn-06.
(Example) When S-curve not used, accel and decel times are set with
bn-01 through bn-04.
bn- Set Value
Accel Time 1 (bn-01) 5 seconds
Decel Time 1 (bn-02) 8 seconds
Accel Time 2 (bn-03) 3 seconds
Decel Time 2 (bn-04) 3 seconds
Factory setting (S-curve characteristics: provided) bn-01 to 04: 10 seconds
Fref.
bn-01, 03
bn-02, 04
0
t
Setting change (S-curve characteristics: not provided)
Fref.
bn-01
5 sec.)
bn-03
bn-02 (8 sec.)
bn-04
t
24
Description Keypad Operation Digital Operator Display Remarks
Select PRGM mode.
Select bn-01.
Constant set value
is displayed.
PRGM
DRIVE
DSPL
DATA
ENTER
-
-
LED DRIVE OFF
Set or change
constant.
Constant value is
written in.
Select bn-02.
Select Sn-06.
Constant set value
is displayed.
Set or change
constant.
Constant value is
written in.
Select Sn-18.
RESET
DATA
ENTER
DSPL
DSPL
DATA
ENTER
RESET
DATA
ENTER
DSPL
-
-
-
Displayed for 0.5 second. Confirm the display for each constant.
Refer to the next page
Displayed for 0.5 second. Confirm the display for each constant.
Constant set value
is displayed.
Set or change
constant.
Constant value is
written in.
DATA
ENTER
RESET
DATA
ENTER
25
Displayed for 0.5 second. Confirm the display for each constant.
6.2 ACCEL/DECEL TIME SETTING
Input signal selection
Sn-06 Operation mode selection 3
4 3 2 1
DIGIT
Machine requires soft start at acceleration and soft stop at deceleration.
bn-01 to -04 (Sn-06, Sn-15 to -18)
Soft start S-curve characteristics
00 S-curve 0.2 sec.
10 S-curve 0.5 sec.
11 S-curve 1.0 sec.
Master speed frequency reference
0 Normal characteristics
1 Reverse characteristics
Processing when frequency reference is missing
0 Stop by reference input
1 Operation to continue with 80% of frequency reference
Application Example
(Cont’d)
26
6.3 INPUT SIGNAL SELECTION
Sn-04
(Example) Change from operator control to terminal control of run/stop and frequency reference.
Description Keypad Operation Digital Operator Display Remarks
Select PRGM mode.
Select Sn-04.
Constant display
value is displayed.
Set or change
constant.
Constant value is
written in.
PRGM
DRIVE
DSPL
DATA
ENTER
RESET
DATA
ENTER
-
-
LED DRIVE OFF
Refer to the diagram shown below.
Displayed for 0.5 second. Confirm the display for each constant.
Input signal selection Sn-04
Sn-04 Operation mode selection
4 3 2 1
DIGIT
Frequency reference input
0 Control circuit terminal 13-14
1 Digital operator An-01
Running operation
0 Control circuit terminal
1 Digital operator
Stopping method selection
00 RAMP to stop
01 Coast to stop
10 Full-range DC injection braking stop
Coast to stop
11
(With a timer function)
27
6.4 PROTECTIVE CHARACTERISTICS SELECTION
Sn-10 to -14
Protective characteristics can be selected by Sn-10, Sn-11, Sn-12 and Sn-14.
(Example) Operation is continued after recovery from momentary power loss and the electronic thermal
protection is turned OFF.
Description Keypad Operation Digital Operator Display Remarks
Select PRGM mode.
Select Sn-11.
Constant set value is
displayed.
Set or change
constant.
Constant value is
written in.
Constant set value is
displayed.
Set or change
constant.
Constant value is
written in.
DRIVE
PRGM
DSPL
DATA
ENTER
RESET
DATA
ENTER
DSPL
DATA
ENTER
RESET
DATA
ENTER
-
-
-
LED DRIVE OFF
Refer to pages 29
and 30.
Displayed for 0.5 second. Confirm the display for each constant.
Displayed for 0.5 second. Confirm the display for each constant.
28
─ ─
Protective characteristics
Sn-10 Protective characteristic 1 (stall prevention)
Decel time during stall prevention
0 bn-02
1 bn-04
Stall prevention during running
0 Effective
1 Ineffective
4 3 2 1
DIGIT
0 Effective
1 Ineffective
0 Effective
1 Ineffective
Stall prevention during acceleration
Stall prevention during deceleration
Sn-11 Protective characteristic 2 (Momentary power loss ride-thru)
4 3 2 1
Operation at momentary power loss
0 Operation to stop
1 Operation to continue
Not used
DIGIT
0 Ineffective
1 Effective
0 Open
1 Close
Protection for internal braking resistor
Fault contact during auto rest/restart operation
Sn-12 Protective characteristic 3 (External fault terminal 3)
4 3 2 1
Processing at external fault detection
00 Ramp to stop by bn-02
01 Coast to stop
10 Ramp to stop by bn-04
11 Operation to continue
DIGIT
External fault
0 NO contact input
1 NC contact input
External fault
0 Always detected
1 Detected during running
29
6.4 PROTECTIVE CHARACTERISTICS SELECTION
Sn-13 Protective characteristic 4 (Fan fault protection)
4 3 2 1
DIGIT
Not used
Process at fan fault detection
00 Ramp to stop by bn-02
01 Coast to stop
10 Ramp to stop by bn-04
11 Operation to continue
Sn-10 to -14
(Cont’d)
Sn-14 Protective characteristic 5 (Motor protection)
4 3 2 1
DIGIT
Electronic thermal motor protection
0 Effective
1 Ineffective
Electronic thermal characteristics
0 For standard motor
1 For constant torque motor
Electronic thermal time constant For standard motor and
0
constant torque motor For motor other than listed in
1
0 above. (Short time rating)
Not used
30
Loading...
+ 104 hidden pages