Teco MA7200 User Manual

4H358D0180009
Installation Manual
MA7200
208 to 230V 1 / 3 Phase 1 ~ 3HP 3 Phase 5 ~ 40HP 380 to 460V 3 Phase 1 ~ 75HP
SAFE OPERATION NOTES
Read this instruction manual thoroughly before installation, operation, maintenance or inspection of the inverter. Only authorized personnel should be permitted to perform maintenance, inspections or parts replacement.
In this manual, notes for safe operation are classified as: “WARNING” or “CAUTION”.
WARNING
CAUTION
: Indicates a potentially hazardous situation that, if not avoided,
could result in death or serious injury to personnel.
: Indicates a potentially hazardous situation that, if not avoided,
may result in minor or moderate injury to personnel and damage to the equipment.
“WARNING” and “CAUTION”
WARNING
y Always turn off the input power supply before wiring terminals. y After turning OFF the main circuit power supply, do not touch the circuit
components until the “CHARGE” LED is extinguished.
y Never connect power circuit output U/T1, V/T2, W/T3 to AC power supply.
CAUTION
y When mounting the MA7200 in a separate enclosure, install a fan or other cooling
o
device to keep the intake air temperature below 113
F (45oC). y Do not perform a withstand voltage test to the inverter. y All the parameters of the inverter have been preset at the factory. Do not change
the settings unnecessarily.
This inverter has been placed through demanding tests at the factory before shipment. After unpacking, check for the following:
1. Verify that part numbers on shipping carton and unit match the purchase order
sheet and/or packing list.
2. Do not install or operate any inverter that is damaged or missing parts.
3. Do not install or operate any inverter that has no QC marking.
Contact your local TECO authorized distributor or TECO representative if any of the above irregularities have been found.
Contents Page
1. MA7200 Handling Description ------------------------------------- 1-1
1.1 Inspection Procedure upon Receiving ---------------------------------------- 1-1
1.2 Installation------------------------------------------------------------------------ 1-2
1.3 Removing/Attaching of LCD Digital Operator and Front Cover---------- 1-4
1.4 Wiring between Inverter and Peripheral Devices---------------------------- 1-7
1.5 Description of Terminal Function --------------------------------------------1-11
Main Circuit Wiring Diagram -------------------------------------------------1-13
1.6
1.7 Wiring Main Circuit------------------------------------------------------------1-14
1.8 Inverter Specifications ---------------------------------------------------------1-17
1.9 Dimensions ---------------------------------------------------------------------- 1-19
1.10 Peripheral Units-----------------------------------------------------------------1-22
1.11 FUSE TYPES -------------------------------------------------------------------1-29
2. Using LCD Digital Operator----------------------------------------- 2-1
3. Parameter Setting------------------------------------------------------ 3-1
3.1 Frequency Command An- ----------------------------------------------- 3-1
3.2 Parameters That Can be Changed during Running Bn-
3.3 Control Parameters Cn-
3.4 System Parameters Sn-
3.5 Monitoring Parameters Un-
-------------------------------------------------3-12
--------------------------------------------------3-30
---------------------------------------------3-75
-------------- 3-2
4. Fault Display and Troubleshooting ------------------------------ 4-1
4.1 General---------------------------------------------------------------------------- 4-1
4.2 Error Message and Troubleshooting ------------------------------------------ 4-2
Appendix
A. PID Parameter Setting -------------------------------------------------------App-1 B. Supplementary on PID Control Block Diagram--------------------------App-3 C. Wiring for PG Feedback Use------------------------------------------------App-4 D. RS-485 Communication Interface------------------------------------------App-5 E. SINK/SOURCE Typical Connection Diagram ---------------------------App-7 F. Set-up Using the Sensorless Vector Control ------------------------------App-8 G. Notes for Circuit Protection and Environmental Ratings-------------- App-10 H. Spare Parts------------------------------------------------------------------- App-14 I. Electrical Ratings For Constant Torque and Quadratic Torque ------ App-24 J. Inverter Heat Loss ---------------------------------------------------------- App-25
No. Figure Contents Page No. Figure Contents Page
1 Air clearance for MA7200 wall mounting 1-2 27 S curv e 3-27 2 Standard connection diagram 1-9 28 ASR Integral Gain 2 3-28 3 Processing the ends of twisted-pair cables 1-15 29 Deceleration to stop 3-44
The optical-couplers connect to external
4
inductive load 5 MA7200 ground winding 1-16 31 Whole range DC Injecting Braking Stop 3-44 6 LCD digital operator dimension 1-27 32 Coast to Stop with Timer 3-45 7 Analog operator 1-28 33 Output voltage limit 3-48 8 LCD digital operator 2-1 34 Stall preventio n function during deceleration 3-48 9 Acceleration and Deceleration time 3-4 35 Zero speed braking operation selection 3-49
10 Analog input gain and bias 3-5 36 Motor overload protection curve 3-51
Adjust the auto torque boost gain Bn-11 to
11
increase the output torque
12 Block diagram for PID control in inverter 3-7 38 Operation sequence in 3-wire mode 3-53
Response of PID control for step-shape
13
(deviation) input
PID Control Block diagram (After Version
14
30.18) 15 An operation example of timer function 3-9 41 Acceleration and deceleration ramp hold 3-55 16 Time chart for energy-saving operation 3-10 42 Time chart for DC injection braking command 3-57 17 User-defined V/F curve 3-15 43 PG speed control block diagram 3-58
18 Output frequency with slip compensation. 3-16 44 19 Slip compensation limit 3-16 45 Pulse signal output 3-65 20 DC injection braking time chart 3-17 46
Upper and lower bounds of the frequency
21
command 22 Setting jump frequencies 3-18 48 PID wiring diagram App-3 23 Acceleration stall prevention function 3-20 49 Wiring of PG feedback App-4 24 Run stall prevention function 3-20 50 Wiring for MODBUS Protocol communication App-5 25 Time chart for overtorque detection 3-23 51 Wiring for PROFIBUS protocol communication App-6 26 Speed search timing chart 3-25 52 RS232-C Typical Connection Diagram App-8
No. Table Contents Page
1 Main circuit terminals 1-11 2 Control circuit terminals 1-12 3 230V/460V class applicable wire size and connector 1-14 4 Brake resistor list 1-22 5 AC reactor list 1-23 6 Noise filter on the input side 1-24 7 Key's functions 2-2 8 Setting of monitoring contents 3-6
9 LCD Digital Operator Display Unit 3-21 10 230V Class Inverter Capacity Selection 3-39 11 460V Class Inverter Capacity Selection 3-40 12 V/F curve of 1~2 HP compact size, 230V Class MA inverter 3-41 13 V/F curve of 3~20 HP, 230V Class MA inverter 3-42 14 Multi-Function Input Setting 3-52 15 Multi-function analog input function list 3-60 16 Multi-function output terminal function 3-63
1-15 30 Coast to Stop 3-44
3-5 37 3-wire mode connection diagram 3-53
3-8 39 2-wire mode connection diagram 3-53 3-9 40
Time chart for multi-step speed and jog command
Time chart of output frequency with the UP/DOWN function
The input/output signal in ‘Timer’ function application
3-54
3-59
3-66
3-18 47 PID control block diagram App-3
1. MA7200 Handling Description
1.1 Inspection Procedure upon Receiving
Before delivery, Every MA7200 inverter has been properly adjusted and passed the demanding function test. After receiving the inverter, the customer should take it out and follow the below procedure: Verify that the Type No. of the inverter you’ve received is the same as the Type No.
listed on your purchase order. (Please read the Nameplate)
Observe the condition of the shipping container and report any damage immediately to
the commercial carrier that has delivered your inverter.
Inverter nameplate:
Model:MA7200-2002-N1 HP:2 KVA:2.7 AC Input: 1PH/3PH 200-230V 50/60Hz
AC Output: 3PH 0-230V Amps: 6.4A
LISTED
MOTOR COMPANY
(IND. CONT. EQ.)
848F
INVERTER MODEL
INPUT SPECIFICATION
OUTPUT SPECIFICATION
Inverter model number :
MA7200 -2002 -N1
MA7200 Series
N1: NEMA1 N4: NEMA4
Max. Applicable Motor
Rated Voltage
2: 200~230V 4: 380~460V
Capacity (HP)
0001 : 1HP
0075 : 75HP NEMA4 for 1~20HP only
1-1
1.2 Installation
When installing the inverter, always provide the following space to allow normal heat dissipation.
50 mm min.
120 mm
min.
AIR
ambient
temperature
-10 ~ + 40
50 mm
min.
30 mm
min.
30 mm
min.
120 mm
min.
AIR
(a) Space in Side (b) Space in Top/bottom
Fig. 1-a. Air clearance for MA7200 wall mounting
1-2
L3
L2(N)
220-240V 380-480V
L3
L1(L)
Single/ThreePhases
T1
3Phases IM
T3T2
L2(N)L1(L)
220-240V 380-480V
Single/ThreePhases
T1 T2 T3
3Phases IM
(a) NEMA4 Frame1 (b) NEMA4 Frame2
Fig. 1-b. MA7200 NEMA4 Installation
CAUTION
Location of equipment is important to achieve proper performance and normal operating life. The MA7200 inverter should be installed in area where the following conditions exist.
y Ambient temperature: +14 to 104 y Install the MA7200 in a location protected from rain, moisture and direct sunlight. y Install the MA7200 in a location free from harmful mists, gases, liquids, airborne
dusts and metallic particles.
y Install the MA7200 in a location free from vibration and electromagnetic noise.
(i.e. welding machines, power units, etc…)
o
F, (-10 to 40oC).
y When mounting multiple units in a common enclosure, install a cooling fan or some
other means to cool the air entering the inverter to at least 113
1-3
o
F (+45oC) or below.
1.3 Removing/Attaching the Digital Operator and Front cover
b
CAUTION
Please disassemble Front Cover before you connect wires to terminals on MA7200
models.
230V 1~25HP & 460V 1~30HP models: Plastic instructions, so please disconnect
LCD Digital Operator before you disassem wiring connection, assemble Front Cover first then reinstall LCD Digital Operator.
230V 30HP40HP & 460V 40~75HP: Iron instructions, you can disassemble Front
Cover for wiring connection without disconnect LCD Digital Operator. Then reinstall Front Cover back after you finished wiring connection.
MA7200 disassembly / Assembly procedures will be depended on different model as follows:
le Front Cover. After you finished the
(A) For 230V : 1-2HP, 460V : 1-2HP
y MA7200-2001-N1 y MA7200-4001-N1 y MA7200-2002-N1 y MA7200-4002-N1
Removing the digital operator :
Take off the two screws on the front cover in the place a and b. Remove the front cover and take off the screws in the place c and d. Disconnect the RS-232 cable connector on the backside of
LCD Digital
Operator
d
c
RS-232
Cable
Connector
the LCD digital operator. Lift and remove digital operator.
Attaching the front cover and digital operator:
Connect the RS-232 cable connector on the back of the LCD digital operator.
Front Cov er
a
b
Attach the digital operator and tighten the screws in the place c and d. Insert the tabs of the upper part of front cover into the groove of the inverter and tighten the screws in the place a and b.
1-4
(B) For 230V : 3-10HP, 460V : 3-10HP
b
y MA7200-2003-N1 y MA7200-4003-N1 y MA7200-2005-N1 y MA7200-4005-N1 y MA7200-2007-N1 y MA7200-4007-N1 y MA7200-2010-N1 y MA7200-4010-N1
Removing the digital operator
Take off the screws in the place a. and b. Press the lever on the side of the digital operator
in the direction of arrow 1 to unlock the digital operator.
Disconnect the RS-232 cable connector on the back side of the LCD digital operator. Lift the digital operator in the direction of arrow 2 to remove the digital operator.
Removing the front cover
Press the left and right sides of the front cover in the directions of arrow 1 and lift the bottom of the cover in the direction of arrow 2 to remove the front cover.
Mounting the front cover and digital operator
Front Cover
Front
Cover
1
c
LCD Digital Operator
2
2
1
a
1
b
RS-232
Cable
Connector
Insert the tab of the upper part of front cover into the groove of the inverter and press the lower part of the front cover onto the inverter until the front cover snaps shut.
Connecting the RS-232 cable connector on the
ack side of the LCD digital operator and hook the digital operator at a on the front cover in the direction of arrow 1.
Press the digital operator in the direction of arrow 2 until it snaps in the place b and then tighten the screws in the place c and d. (on the front cover)
1-5
Digital
Operator
Front
Cover
e
c
a
b
2
1
d
RS-232
Cable
Connector
(C) For 230V 15,20HP and 460V 15,20HP Series
y MA7200-2015-N1 y MA7200-4015-N1 y MA7200-2020-N1 y MA7200-4020-N1
Removing the digital operator :
Take off the screws in the place a. and b. Disconnect the RS-232 cable connector on the back side of the LCD digital operator and then lift the digital operator upwards.
Removing the front cover :
Loosen the two screws of the front cover in the place c and d. And lift the bottom of the front cover to remove the front cover.
Mounting the front cover and digital operator :
Insert the tab of the upper part of front cover into the groove of the inverter and tighten the screws in the place c and d. Connect the RS-232 cable connector on the back of the LCD digital operator. Attach the digital operator and tighten the screws in the place a and b.
a
LCD Digital
b
Front
Cover
d
c
Ope ra tor
RS-232 Cable
Connector
(D) For 230V 30~40HP and 460V 40~75HP Series
Removing the front cover: Loosen the two screws
of the front cover in the place a. and b. Then loosen the two screws c and d
, lift the front cover
upwards. (Don’t removing the digital operator.)
Mounting the front cover: Press the front cover
and then tighten the screws in the place a, b, c and d.
Front cover
1-6
1.4 Wiring between Inverter and Peripheral devices and notice
CAUTION
1. After turning OFF the main circuit power supply, do not touch the circuit
components or change any circuit components before the “CHARGE” lamps extinguished. (It indicates that there is still some charge in the capacitor).
2. Never do wiring work or take apart the connectors in the inverter while the power
is still on.
3. Never connect the inverter output U/T1, V/T2, W/T3 to the AC source.
4. Always connect the ground lead E to ground.
5. Never apply high voltage test directly to the components within the inverter. (The
semiconductor devices are vulnerable to high voltage shock.)
6. The CMOS IC on the control board is vulnerable to ESD. Do not try to touch the
control board.
7. If Sn-03 is 7,9,11 (2-wire mode) or is 8, 10, 12 (3-wire mode), except parameter
settings of Sn-01 and Sn-02, the other parameter settings will return to their initial settings at factory. If the inverter is initially operated in 3-wire mode (Sn-03= 8, 10, 12), the motor will rotate in CCW sense after setting changed to 2-wire mode. (Sn-03= 7, 9, 11). Be sure that the terminals 1 and 2 are OPEN so as not to harmful to personal or cause any potential damage to machines.
CAUTION
1. Determine the wire size for the main circuit so that the line voltage drop is within
2% of the rated voltage. If there is the possibility of excessive voltage drop due to wire length, use a larger wire (larger diameter) suitable to the required length
-3
10current(A)length(m) wire/km)(resistance wire3drop(V) voltageLine ×××Ω×=
2. If the length of the cable wire between the inverter and the motor exceeds 30m,
use a lower carrier frequency for PWM (adjust the parameter Cn-34). Refer to Page 3-21
1-7
Example of connection between the MA7200 and typical peripheral devices are shown as below.
b
MCCB (Molded-Case Circuit Breaker)
Power supply
y Choose the Molded Case Circuit Breaker (MCCB) of
proper current rating. Please refer to the selection guide
Power supply switch(NFB) and earth leakage breaker
“1.10 Peripheral Units” on Page 1-22.
y Do not use a circuit breaker for start/stop operation. y When a ground fault interrupter is used, select the one with
no influence for high frequency. Setting current should be 200mA or above and the operating time at 0.1 second or longer to avoid false triggering.
MC (Magnetic Contactor)
Electromagnetic contactor
y It is not always necessary to have a Magnetic Contactor on
the input side. However, an input Magnetic Contactor can
e used to prevent an automatic restart after recovery from
an external power loss during remote control operation.
y Do not use the Magnetic Contactor for start/stop operation.
AC Reactor
AC reactor
y To improve power factor or to reduce surge current, install
an AC Reactor on the input side of the MA7200.
Input Noise Filter
Input noise filter
y When used with TECO specified Input Noise Filter, the
MA7200 will comply with EN55011 class A regulation.
y Please refer to the selection guide “1.10 Peripheral Units”
on page 1-22.
MA7200 Inverter
MA 7200 inverter
y The input power supply can be connected to any terminal
R/L1, S/L2, T/L3 on the terminal block.
y Please connect the ground terminal E to the site ground
securely.
Output Noise Filter (Zero Phase Core)
Zero phase core
y Install an Output Noise Filter between the MA7200 and the
Induction Motor to eliminate noise transmitted between the power line and the inverter.
y Please refer to the selection guide “1.10 Peripheral
Devices” on page 1-22.
Induction Motor
Induction motor
y When multiple motors are driven in parallel with an
inverter, the inverter rated current should be at least 1.1 times the total motor rated current.
y The inverter and the motor must be separately grounded.
1-8
Standard Connection Diagram
The standard connection diagram of MA7200 is shown in Fig. 2. The sign
indicates the main circuit terminal and the sign indicates control circuit terminal. The terminal function and arrangement are summarized in Table 1 and Table 2. There are three types of control board, the terminal arrangement is shown as below.
(A) For Compact Size Type 230V : 1-2HP, 460V : 1-2HP (NEMA4 are the same)
MA7200-2001/2-N1 MA7200-4001/2-N1
Braki ng Resi stor
B1/P B2
MC
Main Ckt
Power Supply
NFB
R/L1 S/L2 T/L3
U/T1 V/T2
W/T3
IM
FWD/ST OP
REV/STOP
External Fault
Fault RESET
Multi- Step Speed Ref.1
Multi-Step Speed R ed.2
Jogging
Fact ory Preset
Acc. & Dec. Switch
2k 1/2W
COMMAND
EXTERNAL FREQUENCY
(*4)Pulse Input Frequency Command
(*1)
0 ~ +10V
Ω
4 ~ 20 mA
0 ~ +10V
0V
EXTERNAL PG DC VOLTAGE
PG INPUT (A PHASE)
Shield
P
Wire
(*2) The terminal arrangement
(*3) The control board code No. : 4P101C0040001
(*4) The CN2 wire code No. : 4H339D0250001
P
P
(*1)
CN2
IP12
IG12
A(+)
A(-)
P
Twisted Wire
1
2
3
4
5
6
7
8
SC (DG)
E
+12V Power Supply for Speed Ref.
VIN Master Speed Ref.
AIN Master Speed Ref.
AUX Multi-Funtion Analog Input
(*4)
1
2
3
4
("C lose":F WD)
FWD
REV ("Close":REV)
Eb
RESET
Multi-Function Contact Input
Digital signal Common
Shield Sheath
GND Analog signal Common
TP1
Shielded
SC
13
E
24
OPEN
PULL UP
57
Analog
Output 1
(+12V, 20 mA)
Ω
0 ~ 10V, (20k
4 ~ 20 mA, (250
0 ~ 10V, (20k
IP12
68
)
Ω
)
Ω
)
VIN AIN AUX DO 1 DO 2 DO G
+12V
GND AO1 AO2
GND
Analog
Output 2
E
AO1
AO2
GND
RA
RB
RC
DO1
DO2
DOG
S(-)
Grounding Lead (<100
Multi-Function Contact Output 250V AC, <1A 30V DC, <1A
S(+)
S(-)
ES(+)
RA RB RC
Ω
)
Analog Monitor 1 , 2 (DC 0 ~ 10 V)
Multi-Function Output 1, 2 (Open Collector 48V, 50mA)
RS-485 Port
Fig. 2-a Standard connection diagram
1-9
(B) 230V : 3-40HP, 460V : 3-75HP (NEMA4 to 20HP)
Ω
(
)
(*2)
yp
y MA7200-2003-N1 y MA7200-4003-N1 through through MA7200-2040-N1 MA7200-4075-N1
Braking Resistor
B1/P B2
Main Ckt
Power Supply
FW D/STOP
REV/STOP External Fault Fault RESET
Multi-Step
Speed Ref.1
Factory Preset
Multi-Step
Speed Red.2
Jogging Acc. & Dec.
Switch
2k
1/2W
COMMAND
EXTERNAL FREQUENCY
(*4)Pulse Input Frequency Command
Ω
4 ~ 20 mA
0 ~ +10V
EXTERNAL PG
DC VOLTAGE
PG INPUT
(A PHASE)
-10V ~ +10V P
0V
P
MC NFB
R/L1
S/L2
T/L3
FW D ("Close":FWD)
1
2
REV ("Close":REV)
3
Eb
4
RESET
5 6
7 8
+12V or -12V Power Supply Speed Ref.
for
VIN Master Speed Ref. 0 ~ 10V & -10V~10V
AIN Master Speed Ref.
AUX Multi-Function Analog Input
P
(*1) IP12
IG12
A(+)
A(-)
Multi-Function Contact Input
24VG
(Sink Common)
24V
(Source Common)
E
Shield Sheath
SINK
(20 KΩ)
GND Analog signal Common
TP1
OPEN
PULL UP
Analog
Output 1
(* 2)
TP2 :
TP2 :
SOURCE
SINK
(±12V, 20 mA)
, (20kΩ) 4 ~ 20 mA, (250Ω)
0 ~ 10V, (20k
IP12
Output 2
)
Analog
U/T1
V/T2
W/T3
AO1
AO2
GND
R1A
R1B
R1C
R2A
R2C
DO1
DOG
E
Grounding Lead
(<100 Ω )
Multi-Function Contact Output 250V AC, <1A
30V DC, <1A
Multi-Function Output 1
Open Collector 48V, 50mA
S(+)
S(-)
IM
Analog Monitor 1, 2 (DC 0 ~ 10 V)
RS-485 Port
(*1)
( * 1)
input, the short jumper of TP2 must be set to SINK position, and set to SOURCE position for source type input.
( * 2) The terminal
(*3) The terminal arrangement
Shield
Wire
1
and
8
P
j
The terminal can be set as SINK or SOURCE type input interface, when setting as sink t
Shield Wire
c
must be set to SINK posit
VIN Ref. can be set in two input methods as 0~10V or -10~+10V
(*4) The control board code No. : 4P101C0060002
(
*3)
( * 4)
The terminal A(+), A(-) can be the output terminal of Pulse Input Frequency Command, and the jumper of TP1 must be set to OPEN position. Pulse Input Frequency Command: 0~32KHz, 3~12V High torsion, input resistor 2.7KΩ
( * 5) The terminal arrangement ( * 6) The control board code No. 4P101C0130001
Shielded
P
Twisted W ire
~
Shield e Twisted
can be set
ion, and set to SOURCE position for source type input.
24VG
Wire
as SINK or
S OURCE
24VG
1 3 5 7 AUXVIN AIN24V DO1 DOG IP12 A(+) A(-)
E
2 4 6 8 +12VGND AO1 AO2 E IG12 S(+) S(-)GND R2A R2C R1A R1B R1C
1 3 5
E
2
4
Fig. 2-b Standard connection diagram
type input interface, when setting
7 VIN AIN
24V DOG
6 8
+12V-12V
AUX DO1
GND
c
AO1 AO2 E
1 8
~
as sink type input, the short jumper of TP2
~
j
A(+)
A(
S(+)
-) S(-)
R2A R2C R1A R1B R1C
IP12
IG12
Fig. 2-b Standard connection diagram
1-10
e
1.5 Description of terminal function
/
/
/
Table 1 Main circuit terminals
Terminal 230V:1~20HP, 460V:1~20HP 230V:25~40HP, 460V:25~75HP
R/L1
S/L2
T/L3 B1/P
B2
Θ
B2/R U/T1 V/T2
W/T3
E
Terminal block configuration
˙230V : 1 ~ 2HP ˙ 460V : 1 ~ 2HP
Main circuit input power supply (For single phase power supply, please use R/L1, S/L2 as input terminal)
B1/P, B2: External braking resistor B1/P, Θ: DC power supply input
- \ : DC power supply or
-
braking unit
Unused -
Inverter output
Grounding lead (3rd type grounding)
-
L1 S/L2 T/L3
R/
B1/P
T1 V/T2
B2
U/
W
T3
J4
B1/P
J2
B2
R/L1S/
L2 T/L3
T1 V/T2
U/
W
˙230V : 3~5HP
U
R
S
E
/L1
/L2
Power In
T
/L3
B1/P B1/R B2
Dynamic Brake
/T1V/T2
To M ot or
CHARGE
W
/T3
˙460V : 3~5HP
U
/T1
V
R
/L1
S
/L2
Power In
T
/L3
B1/P B2
Dynamic Brake
To Motor
CHARGE
/T2
W
/T3
˙230V/460V : 7.5~10HP
R
/L1
S
/L2
T
E
Power In
/L3
B1/P B1/R B2
Dynamic Brake
U
/T1V/T2W/T3
To Motor
CHARGE
E
˙230V/460V : 15~20HP ˙ 230V : 25~40HP, 460V : 25~75HP
T3
R/L1
S/
T/
L2
L3
B1/P B2
U/
W
V/
T1
T2
T3
R/L1 S/L2 T/L3 U/T1
W
V/
T2
/T3
1-11
Table 2 Control circuit terminals
Terminal Functions
1(DI1) Forward Operation – Stop Signal 2(DI2) Reverse Operation – Stop Signal 3(DI3) External Fault Input 4(DI4) Fault Reset 5(DI5) 6(DI6) 7(DI7) 8(DI8)
SC(DG)
(24VG)
24V Source Common Point (Locate the short jumper of TP2 in SOURCE position)
E Connection to Shield Signal Lead (Frame Ground)
+15V(+12V) DC voltage for External Device
-12V Only support by the board 4P101C01301 VIN Master speed Voltage Reference (0~10V) (4P101C01301 support –10V~10V input) AIN Master speed Current Reference (4~20mA)
AUX
GND Analog Signal Common
IP12 IG12 A(+)
A(-)
AO1
AO2
GND Common Lead for Analog Port RA(R1A) Relay Contact Output A RB(R1B) Relay Contact Output B RC(R1C) Relay Contact Common
Multifunction Input Terminal: 3-Wire Operation, Load/Remote Control, Multi-Speed Select, FWD/REV Select, ACC/DEC Choice, ACC/DEC Halting, Base Block, Overheat Warn, PID Control, DC Braking, Speed Search, Up/Down Function, PG Feedback Control, External Fault, Timer function, Multifunction Analog Input Setting
Digital Signal Ground Sink Common Point (Locate the short jumper of TP2 in SINK position)
Auxiliary Analog Input: Auxiliary frequency Command, Frequency Gain, Frequency Bias, Overtorque Detection, Output Voltage Bias, ACC/DEC Ramp, DC-Brake Current, Stall Prevention Current Level during Running Mode, PID Control, Lower-Bound of Frequency Command, Frequency-Jump-4, etc
External Power Source For PG Feedback Use
Signal Input of PG (also can be the input terminal of Pulse Input Frequency Command)
Analog Multifunction Output Port: Frequency Commend, Output Frequency, Output Current, Output Voltage, DC Voltage, PID Controlled Value, Analog Command Input of VIN, AIN or AUX.(Below 2mA)
Same function as terminal DO1, DO2
DO1
DO2
R2A R2B
DOG Common Terminal (of Open Collector Transistor)
S(+)
S(-)
Digital Multi-Function (Open Collector) Output “1”, “2” Terminals: During-Running, Zero-speed, Agreed-frequency, Agree-frequency-setting, Frequency-Output, Inverter-Operation-Ready, Undervoltage-Detection, Base-Block Output, Run Source, Frequency command, Overtorque Detection, Frequency Command Invalid, Fault, Undervoltage, Overheat, Motor Overload, Inverter Overload, During-Retry, Communication-Fault, Timer-Function-Output
RS-485 Port
Caution
Use the control circuit terminals VIN, AIN according the setting of Sn-24.
The MAX. Output current at terminal (+15V or +12V) is 20mA.
The multi-function analog output terminals AO1, AO2 is a dedicated output for a frequency meter, ammeter,
etc. Do not use these 2 analog outputs for feedback control or any other control purpose.
1-12
1.6 Main Circuit Wiring Diagram
Main Circuit Wiring Diagram of MA7200:
1. 230V/460V : 1~20HP
2. 230V : 25HP 460V : 25~30HP
3. 230V : 30~40HP 460V : 40~75HP DC Reactor built-in
1-13
1.7 Wiring main circuit and notice
Main circuit wiring
The non-fusible-breaker (NFB) should be installed between the AC source and the R/L1-S/L2-T/L3 input terminal of MA7200 inverter. The user can make his own decision of installing electromagnetic contactor block (MCB) or not. To protect against the false triggering of leakage-current, the user should install a leakage current breaker with amperage sensitivity200mA and operation time0.1 sec.
Table 3 230V and 460V class ap plicab le wire size and connector
MA7200 model Wire size (mm2)
Power
supply
230V
1Φ
3Φ
230V
3 Φ
460V
3Φ
Applicable
Power Rating
(HP)*1
1HP 2 4.8 2HP 2.7 6.4 3HP 4 9.6
5.4HP 7.5 17.5 5.5 5.5
7.5HP 10.1 24 8 10HP 13.7 32 8 15HP 20.6 48 14 8 20HP 27.4 64 22 8 25HP 34 80 22 14 30HP 41 96 38 14 40HP 54 130 60 22
1HP 2.2 2.6 2HP 3.4 4 3HP 4.1 4.8
5.4HP 7.5 8.7
7.5HP 10.3 12 10HP 12.3 15 5.5 5.5 15HP 20.6 24 8 8 20HP 27.4 32 8 8 25HP 34 40 8 8 30HP 41 48 14 8 40HP 54 64 22 8 50HP 68 80 22 14 60HP 82 96 38 14 75HP 110 128 60 22
Rated
KVA
*1 : It is assumed constant torque load.
Rated
current
(A)
Main
circuit
25.5 25.5 0.52 25.5 3.55.5 0.52
3.55.5 3.55.5 0.52
25.5 25.5 0.52 25.5 3.55.5 0.52 25.5 3.55.5 0.52 25.5 3.55.5 0.52 35.5 3.55.5 0.52
Ground
connection
*2
wire E (G)
5.58 0.52
5.58 0.52
Control
*3
wire
0.52
0.52
0.52
0.52
0.52
0.52
0.52
0.52
0.52
0.52
0.52
0.52
0.52
0.52
0.5~2
*4
MCB*4
NFB
TO-50EC(15A) CN-11 TO-50EC(20A) CN-11 TO-50EC(20A) CN-11 TO-50EC(30A) CN-16
TO-100S(50A) CN-18
TO-100S(60A) CN-25 TO-100S(100A) CN-50 TO-100S(100A) CN-65 TO-225S(150A) CN-80 TO-225S(175A) CN-100 TO-225S(175A) CN-125
TO-50EC(15A) CN-11 TO-50EC(15A) CN-11 TO-50EC(15A) CN-11 TO-50EC(15A) CN-18 TO-50EC(20A) CN-18 TO-50EC(30A) CN-25 TO-50EC(30A) CN-25
TO-100S(50A) CN-35
TO-100S(75A) CN-50 TO-100S(100A) CN-50 TO-100S(100A) CN-65 TO-125S(125A) CN-80 TO-225S(175A) CN-100 TO-225S(175A) CN-125
*2 : The main circuit has terminals of R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, B1/P, B2/R, B2,Θ.
*3 : The control wire is the wire led to the pin terminals of control board.
*4 : In Table 3, the specified Part No. of NFB and MC are the item No. of the products of TECO. The
customer can use the same rating of similar products from other sources. To decrease the noise interference, be sure to add R-C surge suppressor (R: 10Ω/5W, C: 0.1μF/1000VDC) at the 2
terminals of coils of electromagnetic contactor.
1-14
External circuit wiring precaution:
(A) Control circuit wiring:
(1) Separate the control circuit wiring from main circuit wiring (R/L1, S/L2, T/L3, U/T1,
V/T2, W/T3) and other high-power lines to avoid noise interruption.
(2) Separate the wiring for control circuit terminals RA-RB-RC (R1A-R2B-R2C) (contact
output) from wiring for terminals c~j, A01, A02, GND, DO1, DO2 , DOG 15V(or +12V, -12V), VIN, AIN, AUX, GND, IP12, IG12, A (+), A (-), S(+) and S(-).
(3) Use the twisted-pair or shielded twisted-pair cables for control circuits to prevent
operating faults. Process the cable ends as shown in Fig. 3. The max. wiring distance should not exceed 50 meter.
Shield sheath
Connect to shield
sheath terminal E
Insulated with tape
Armor
Do not
connect here
Fig. 3. Processing the ends of twisted-pair cables
When the digital multi-function output terminals connect serially to an external relay, an
anti-parallel freewheeling diode should be applied at both ends of relay, as shown below.
50 mA max.
48V max.
free-wheeling diode
(100V, >100mA)
7200MA
MA7200
external wiring circuit
Fig. 4. The Optical-couplers connect to external inductive load
(B) Wiring the main circuit terminals:
(1) Input power supply can be connected to any terminal R/L1, S/L2 or T/L3 on the
terminal block. The phase sequence of input power supply is irrelevant to the phase sequence.
(2) Never connect the AC power source to the output terminals U/T1, V/T2 and. W/T3. (3) Connect the output terminals U/T1, V/T2, W/T3 to motor lead wires U/T1, V/T2, and
W/T3, respectively.
(4) Check that the motor rotates forward with the forward run source. Switch over any 2
of the output terminals to each other and reconnect if the motor rotates in reverse with the forward run source.
(5) Never connect a phase advancing capacitor or LC/RC noise filter to an output circuit.
1-15
(C) GROUNDING :
(1) Always use the ground terminal (E) with a ground resistance of less than 100Ω. (2) Do not share the ground wire with other devices, such as welding machines or
power tools.
(3) Always use a ground wire that complies with the technical standards on electrical
equipment and minimize the length of ground wire.
(4) When using more than one inverter, be careful not to loop the ground wire, as
shown below.
(a) OK (b) OK (c) NO
Fig. 5. MA7200 ground winding
Determine the wire size for the main circuit so that the line voltage drop is within
2% of the rated voltage. (If there is the possibility of excessive voltage drop, use a larger wire suitable to the required length)
Installing an AC reactor
If the inverter is connected to a large-capacity power source (600kVA or more), install an optional AC reactor on the input side of the inverter. This also improves the power factor on the power supply side.
If the cable between the inverter and the motor is long, the high-frequency
leakage current will increase, causing the inverter output current to increase as well. This may affect peripheral devices. To prevent this, adjust the carrier frequency, as shown below:
Cable length < 100ft. 100-165ft. 166-328ft.
Carrier frequency
15kHz max
10kHz max
5kHz max
>
329ft.
2.5kHz
(Cn-34)
(Cn-34=6)
(Cn-34=4)
1-16
(Cn-34=2)
(Cn-34=1)
1.8 Inverter Specifications
A
A
Basic Specifications
(a) 230V Series
Inverter (HP) 1 2 3 5 7.5 10 15 20 25 30 40
Max. Applicable Motor
Output HP
Capacity (KVA)
Max. Output Voltage
Output Characteristics
Frequency (Hz)
Allowable Voltage
llowable Frequency
Power Supply
*1
(KW)
Rated Output
Rated Output
Current (A)
(V)
Max. Output
Rated Voltage,
Frequency
Fluctuation
Fluctuation
1
(0.75)
2 2.7 4 7.5 10.1 13.7 20.6 27.4 34 41 54
4.8 6.4 9.6 17.5 24 32 48 64 80 96 130
1PH/3PH 200V~230V,
(b) 460V Series
Inverter (HP)
Max. Applicable Motor
Output HP
Capacity (KVA)
Max. Output Voltage
Output Characteristics
Frequency (Hz)
Allowable Voltage
llowable Frequency
Power Supply
*1
(KW)
Rated Output
Rated Output
Current (A)
(V)
Max. Output
Rated Voltage,
Frequency
Fluctuation
Fluctuation
1 2 3 5 7.5 10 15 20 25 30 40 50 60 75
1
(0.75)
2.2 3.4 4.1 7.5 10.3 12.3 20.6 27.4 34 41 54 68 82 110
2.6 4 4.8 8.7 12 15 24 32 40 48 64 80 96 128
*1. Based on 4 pole motor
2
(1.5)
50/60Hz
2
(1.5) 3 (2.2)
3
(2.2)
5.4 (4)
Through Parameter Setting 0.1~400.0 Hz
5.4
7.5
(4)
(5.5)
Through Parameter Setting 0.1~400.0 Hz
7.5
(5.5)
3-Phases, 200V~230V
10
(7.5)
3-Phases, 380V~460V
3-Phases, 380V ~ 460V
10
(7.5)
3-Phases, 200V~230V, 50/60Hz
-15% ~ +10%
±5%
15
(11)
-15% ~ +10%
20
(15)
±5%
15
(11)
(18.5)
20
(15)
25
30
(22)
50/60Hz
25
(18.5)
40
(30)
50
(37)
30
(22)
(45)
60
40
(30)
75
(55)
*2. The spec. of NEMA4 are the same
1-17
General Specifications
Operation Mode
Control Mode Sinusoidal PWM Frequency Control Range 0.1Hz ~ 400Hz Frequency Accuracy
(varied with temperature) Speed Control Accuracy
Frequency Command Resolution Frequency Output Resolution Overload Resistibility 150% Rated Current for 1 Min
Frequency Setting Signal
Acc./Dec. Time 0.0~6000.0 sec ( Accel/Decel Time Can Be Set Independently) Voltage–Frequency Characteristics
Control Characteristics
Regeneration Torque Approx. 20%
Basic Control Function
Extra Function
Stall Prevention
Instantaneous Overcurrent Motor Overload Protection Electronic Overload Curve Protection Inverter Overload Protection Overvoltage Stop if VDC410V (230 Class) or VDC820V (460 Class) Undervoltage Stop if VDC200V (230 Class) or VDC400V (460 Class) Momentary Power Loss Ride-Through time
Protection Function
Overheat Protection Protected by Thermistor Grounding Protection Protection by DC Current Sensor Charge Indication (LED) Lit when the DC Bus Voltage Above 50V Input Phase Loss (IPL) Motor coasts to stop at Input Phase Loss Output Phase Loss (OPL) Motor coasts to stop at Output Phase Loss Application Site Indoor (No Corrosive Gas And Dust Present)
Ambient Temperature -10ºC ~ +40ºC (Not Frozen) Storage Temperature -20ºC ~ +60ºC Ambient Humidity Below 90%RH (Non-Condensing)
Condition
Environmental
Height, Vibration Below 1000M, 5.9m/S2 (0.6G), (JISC0911 Standard)
Communication Function RS-485 Installed (MODBUS Protocol)
Encoder Feedback Interface
EMI Meet EN 61800-3 With Specified EMI Filter EMS Compatibility Meet EN 61800-3 Option PROFIBUS Card
Graphic LCD Panel (English and Chinese) with parameters copying (LED: option)
Digital Command: ±0.01% (-10 ~ +40ºC), Analog Command: ±0.1% (25ºC±10ºC), ±0.1(V/F with PG feedback), ±0.5(Sensorless Vector Control)
Digital Command: 0.01Hz Analog Command: 0.06Hz/60Hz
0.01Hz
DC 0~+10V / 4~20 mA, DC-10V~+10V and Pulse Input Frequency Command (Above 230V/460V 3HP)
V/F Curve Can Be Set Through Parameter Setting
Restart After Momentary Power Loss, PID Control, Auto Torque Boost, Slip Compensation, RS_485 Communication, Speed Feedback Control, Simple PLC function, 2 Analog Output Port Cumulative Power on & Operation Hour memory, Energy Saving, Up/Down Operation, 4 Different sets of Fault Status Record (Including Latest one), MODBUS Communication, Multiple-Pulse Output Ports, Select Local/Remote, Customer Application Software Environment (C.A.S.E), SINK/SOURCE Interface. During Acceleration/Deceleration and constant Speed Running (Current Level Can Be Selected During Acceleration and Constant Speed Running. During Deceleration, Stall Prevention Can Be Enabled or Disabled)
Stopped if above 200% Rated Current
Stopped if above 150% Rated Current for 1 Min.
15ms, stop otherwise
Built-in PG Feedback Interface and set to Open-collector Interface Drive or Complementary Interface Drive
1-18
1.9 Dimensions
Open Chassis Type (IP00)
W H D W1 H1 d
269 553 277 210 530 M10
269 553 277 210 530 M10 30 269 647 277 210 530 M10 31
308 653 282 250 630 M10 46 308 747 282 250 630 M10 47
Voltage
230V
1/3Φ
230V
3Φ
460V
3Φ
Inverter
Capacity(HP)
1 2 3 5 140 279.5 176.5 126 226 M6 4.3
7.5 10 15 20 25 30 30 31
40
1 2 3 5
7.5 10 15 20 25 30 40 50 60 75
(mm)
Weight
(kg)
-
-
31
-
Enclosed Type (NEMA1) (mm)
W H D W1 H1 d
Weight
(kg)
ACL/DCL
Reference
Figure
132 217 143.5 122 207 M5 2.3 (a)
140 279.5 176.5 126 226 M6 4.3
External
211.2 300 215 192 286 M6 5.7
265 360 225 245 340 M6
12
ACL
(option)
(b)
13
DCL
269 647 277 210 530 M10
32
Built-in
(Standard)
(c)
132 217 143.5 122 207 M5 2.3 (a)
140 279.5 176.5 126 226 M6 4.3
External
211.2 300 215 192 286 M6 5.7
ACL
(option)
(b)
12
265 360 225 245 340 M6
13
DCL
Built-in
(c)
(Standard)
(a) 230V / 460V : 1~2HP
W1
W
d
H
H
1
H
2
D
1-19
(b) 230V : 3HP~25HP
460V : 3HP~30HP
(c) 230V : 30HP~40HP
460V : 40HP~75HP
W W1
1
1
W
W1
D
D
H1
H
H1
H
d
d
Open Chassis Type-IP00 Enclosed, Wall-mounted Type-NEMA1
1-20
(d) NEMA4 Type : 1HP~20HP
Voltage
230V
1/3Φ
230V
3Φ
460V
3Φ
Inverter
Capacity(HP)
1 2 3 5 198 335 217 115 315 M6 7.5
7.5 10 15 20
1 2 3 5
7.5 10 15 20
W H D W1 H1 d
198 335 217 115 315 M6
223 460 245 140 440 M6 16
198 335 217 115 315 M6
223 460 245 140 440 M6 16
NEMA4 (mm)
Weight
(kg)
6.3
7.5
6.3
7.5
1-21
1.10 Peripheral Units
Braking resistors
MA7200 230V/460V 1~20HP model have built-in braking transistor, and can be connected external braking resistor between B1/P and B2 when lack of braking ability. Above 25HP models, need to connect braking unit (on - \ of inverter) and braking resistors (on B-P0 of braking unit).
Inverter Braking Unit Braking Resistor
Voltage HP
1 4.8 - - JNBR-150W200 150W/200 1 119%, 10%ED
230V
1/3Φ
230V
2 6.4 - - JNBR-150W100 150W/100 1 119%, 10%ED
3 9.6 - - JNBR-260W70 260W/70 1 115%, 10%ED
5 17.5 - - JNBR-390W40 390W/40 1 119%, 10%ED
7.5 24 - - JNBR-520W30 520W/30 1 108%, 10%ED
10 32 - - JNBR-780W20 780W/20 1 119%, 10%ED
15 48 - - JNBR-2R4KW13R6 2400W/13.6 1 117%, 10%ED
3Φ
20 64 - - JNBR-3KW10 3000W/10 1 119%, 10%ED
25 80 JNTBU-230 1 JNBR-4R8KW8 4800W/8 1 119%, 10%ED
30 96 JNTBU-230 1 JNBR-4R8KW6R8 4800W/6.8 1 117%, 10%ED
40 130 JNTBU-230 2 JNBR-3KW10 3000W/10 2 119%, 10%ED
1 2.6 - - JNBR-150W750 150W/750 1 126%, 10%ED
2 4 - - JNBR-150W400 150W/400 1 119%, 10%ED
3 4.8 - - JNBR-260W250 260W/250 1 126%, 10%ED
Rated
current (A)
Model
Table 4 Braking resistor list
Number
used
Code NO. Specs.
Number
used
Braking Torque (%)
5 8.7 - - JNBR-400W150 400W/150 1 126%, 10%ED
7.5 12 - - JNBR-600W130 600W/130 1 102%, 10%ED
10 15 - - JNBR-800W100 800W/100 1 99%, 10%ED
460V
*Note 1: Another choices are listed as below.
*Note 2: JUVPHV-0060 no UL certification
15 24 - - JNBR-1R6KW50 1600W/50 1 126%, 10%ED
3Φ
20 32 - - JNBR-1R5KW50 1500W/40 1 119%, 10%ED
25 40 JNTBU-430 1 JNBR-4R8KW32 4800W/32 1 119%, 10%ED
30 48 JNTBU-430 1 JNBR-4R8KW27R2 4800W/27.2 1 117%, 10%ED
40 64 JNTBU-430 1 JNBR-6KW20 6000W/20 1 119%, 10%ED
50 80 JNTBU-430 2
60 96 JNTBU-430 2
75 128 JNTBU-430 2 JNBR-6KW20 6000W/20 2 126%, 10%ED
440V 50HP(JUVPHV-0060+JNBR-9R6KW16) x 1
440V 60HP(JUVPHV-0060+JNBR-9R6KW13R6) x 1
JNBR-4R8KW32 4800W/32 2
JNBR-4R8KW27R2 4800W/27.2 2
1-22
119%, 10%ED
117%, 10%ED
AC reactor
An AC reactor can be added on the power supply side if the inverter is connected to a
much larger capacity power supply system, or the inverter is within short distance (<10m) from power supply systems, or to increase the power factor on the power supply side.
Choose the proper AC reactor according to the below list.
Table 5 AC reactor list
Inverter Model AC reactor
V HP
230V
1Φ/3Φ
230V
3Φ
Rated
current
Code No.
Specification
(mH/A)
1 4.8A 3M200D1610021 2.1mH/5A 2 6.5A 3M200D1610030 1.1mH/10A 3 9.6A 3M200D1610048 0.71mH/15A
5.4 17.5A 3M200D1610056 0.53mH/20A
7.5 24A 3M200D1610064 0.35mH/30A 10 32A 3M200D1610072 0.265mH/40A
15 48A 3M200D1610081 0.18mH/60A 20 64A 3M200D1610099 0.13mH/80A
25 80A
30 96A
40 130A
3M200D1610102
3M200D1610111
3M200D1610269
0.12mH/90A
0.09mH/120A
0.07mH/160A
1 2.6A 3M200D1610137 8.4mH/3A 2 4A 3M200D1610145 4.2mH/5A 3 4.8A 3M200D1610153 3.6mH/7.5A
5.4 8.7A 3M200D1610161 2.2mH/10A
7.5 12A 3M200D1610170 1.42mH/15A
10 15A 3M200D1610188 1.06mH/20A
460V
3Φ
15 24A 3M200D1610196 0.7mH/30A
20 32A 3M200D1610200 0.53mH/40A
25 40A
30 48A
40 64A
50 80A
60 96A
75 128A
3M200D1610218
3M200D1610226
3M200D1610234
3M200D1610242
3M200D1610251
3M200D1610315
0.42mH/50A
0.36mH/60A
0.26mH/80A
0.24mH/90A
0.18mH/120A
0.15mH/150A
Note: The AC reactors are applied only to input side. Do not apply it to output side.
1-23
Noise filter A. INPUT SIDE NOISE FILTER
Installing a noise filter on power supply side to eliminate noise transmitted between
the power line and the inverter
MA7200 has its specified noise filter to meet the EN61800-3 class A specification
Table 6 Noise filter on the input side
Inverter Noise Filter
V HP
Current (A)
1 4.8A
Rated
1Φ
3Φ
Code Specifications Current Dimensions
4H300D1750003 JUNF12015S-MA 15 A Fig. (a)
4H300D1710001 JUNF32012S-MA 12 A Fig. (a)
230V 1/3Φ
230V
3Φ
2 6.5A
1Φ
3Φ
1Φ
3 9.6A
3Φ
5.4 17.5A 4H300D1610007 JUNF32024S-MA 24 A Fig. (a)
7.5 24A 4H300D1620002 JUNF32048S-MA 48 A
10 32A 4H300D1620002 JUNF32048S-MA 48 A Fig. (b)
15 48A 4H300D1730002 JUNF32070S-MA 70 A Fig. (b)
20 64A 4H300D1730002 JUNF32070S-MA 70 A Fig. (b)
1 2.6A 4H300D1720007 JUNF34008S-MA 8 A Fig. (a)
2 4A 4H300D1720007 JUNF34008S-MA 8 A Fig. (a)
3 4.8A 4H300D1630008 JUNF34012S-MA 12 A Fig. (a)
5.4 8.7A 4H300D1630008 JUNF34012S-MA 12 A Fig. (a)
7.5 12A 4H300D1640003 JUNF34024S-MA 24 A Fig. (b)
10 15A 4H300D1640003 JUNF34024S-MA 24 A Fig. (b)
4H300D1750003 JUNF12015S-MA 15 A Fig. (a)
4H300D1710001 JUNF32012S-MA 12 A Fig. (a)
4H300D1600001 JUNF12020S-MA 20 A Fig. (a)
4H300D1610007 JUNF32024S-MA 24 A Fig. (a)
Fig. (b)
460V
3Φ
15 24A 4H300D1740008 JUNF34048S-MA 48 A Fig. (b)
20 32A 4H300D1740008 JUNF34048S-MA 48 A Fig. (b)
25 40A 4H000D1770008 KMF370A 70A Fig. (c)
30 48A 4H000D1790009 KMF370A 70A Fig. (c)
40 64A 4H000D1790009 KMF3100A 100A Fig. (c)
50 80A 4H000D1800004 KMF3100A 100A Fig. (c)
60 96A 4H000D1800004 KMF3150A 150A Fig. (c)
75 128A 4H000D1820005 KMF3180A 180A Fig. (c)
1-24
Dimension : (unit : mm)
2
φ
φ
(a) (b)
80
(c)
40
140
125
6.5
100
LINE
L1 L2 L3
PE
LOAD
L1 L2 L3
PE
60
50
250
225
LINE
L1 L2 L3
PE
LOAD
6.5
4 −
L1 L2 L3
PE
70
Model
W W1 H H1 D d M
KMF370A 93 79 312 298 190 7 M6
KMF3100A 93 79 312 298 190 7 M6
KMF3150A 126 112 334 298 224 7 M6
Dimension (mm)
KMF3180A 126 112 334 298 224 7 M6
1-25
B. EMI SUPPRESSION ZERO PHASE CORE
)
Model : JUNFOC046S ------- Code No. : 4H000D0250001 According to the required power rating and wire size, select the matched ferrite core to
suppress EMI noise.
The ferrite core can attenuate the frequency response at high frequency range (from
100KHz to 50MHz, as shown below). It should be able to attenuate the RFI from inverter to outside.
The zero-sequence noise ferrite core can be installed either on the input side or on the
output side. The wire around the core for each phase should be winded by following the same convention and one direction. The more winding turns the better attenuation effect. (Without saturation). If the wire size is too big to be winded, all the wire can be grouped and go through these several cores together in one direction.
Frequency attenuation characteristics (10 windings case)
0
-10
-20
-30
atteuatoin value (dB)
-40
1
10
2
10
10
Interference Frequency (kHz
3
Example: EMI suppression zero phase core application example
DRIVE FWD REV REMOTE
DIGITAL OPERATOR JNEP-31
PRGM
DSPL
DRIVE
EDIT
JOG
ENTER
FWD
RESET
REV
RUN STOP
10
4
10
Note: All the line wire of U/T1, V/T2, W/T3 phase must pass through the same
zero-phase core in the same winding sense.
1-26
LCD operator with extension wire
When used for remote control purpose, the LCD operator can have different
extension wires based upon the applications. Some extension wires are listed below.
MA7200
L
Cable Length Extension Cable Set *1 Extension Cable *2 Blank Cover *3
1m 4H332D0010000 4H314C0010003
2m 4H332D0030001 4H314C0030004
3m 4H332D0020005 4H314C0020009
4H300D1120000
5m 4H332D0040006 4H314C0040000
10m 4H332D0130005 4H314C0060001
*1 : Including special cable for LCD digital operator, blank cover, fixed use screws and
installation manual.
*2
: One special cable for LCD digital operator.
*3
: A blank cover to protect against external dusts, metallic powder, etc.
The physical dimension of LCD digital operator is drawn below.
REMOT
FWDDRIVEREV
E
REF
SEQ
DIGITAL OPERATOR JNEP-3
PRG DRIVE
JOG
FWD
REV
1
M
DSP
L
EDI
T
ENTER
RESET
STO
RUN
P
Fig. 6. LCD Digital Operator Dimension
1-27
Analog operator
All MA7200 have the digital LCD digital operator. Moreover, an analog operator as
JNEP-16 (shown in fig. 7) is also available and can be connected through wire as a
portable operator. The wiring diagram is shown below.
R/L1 S/L2 T/L3
Master Freq. Ref. 976
2k
BREAKER
FWD RUN
STOP
, 1/4 W
0 ~ 10V
FM
for Speed Ref
Analog Operator
B1/P
R/L1 S/L2 T/L3
1
SC
(+15V, 20 mA)
15V Power Supply
VIN Master Speed
GND 0V
A01
GND
MA7200
ANALOG OUTPUT
B2
U/T1 V/T2
W/T3
RA
RB
RC
DO1
During
Running
DO2
.
Speed
DOG
IM
Multi-Function Contact Output 250V AC, max. 1A 30V DC, max. 1A
Multi-Function Output 1, 2
Agree
(Open Collector 48V/50mA)
Fig. 7. Analog Operator
PROFIBUS Communication Card
Code No. : 4H300D0290009 Please refer to the appendix D and “MA7200 PROFIBUS-DP Communication
Application manual” for communication interface.
1-28
1.11 FUSE TYPES 230V class
MODEL HP KVA
100% CONT.
Output AMPS
JNTMBG□□0001JK 1 2 4.8 6 12 15 JNTMBG□□0002JK 2 2.7 6.4 8 15 20 JNTMBG□□0003JK 3 4 9.6 12 20 25 JNTMBG□□0005JK 5 7.5 17.5 21 30 x JNTMBG□□7R50JK 7.5 10.1 24 29 50 JNTMBG□□0010JK 10 13.7 32 38 60 JNTMBG□□0015JK 15 20.6 48 58 100 JNTMBG□□0020JK 20 27.4 64 77 125 JNTMBG□□0025JK 25 34 80 88 125 JNTMBG□□0030JK 30 41 96 106 150 JNTMBG□□0040JK 40 54 130 143 200
Rated Input
AMPS
3Φ FUSE
Rating
1Φ FUSE
Rating
x
x
x
x
x
x
x
460V class
MODEL HP KVA
100% CONT.
Output AMPS
Rated Input
AMPS
FUSE
Rating
JNTMBG□□0001AZ 1 2.2 2.6 3 6 JNTMBG□□0002AZ
JNTMBG□□0003AZ JNTMBG□□0005AZ JNTMBG□□7R50AZ JNTMBG□□0010AZ JNTMBG□□0015AZ JNTMBG□□0020AZ JNTMBG□□0025AZ JNTMBG□□0030AZ JNTMBG□□0040AZ JNTMBG□□0050AZ JNTMBG□□0060AZ JNTMBG□□0075AZ
Fuse Type UL designated SEMICONDUCTOR PROTECTION FUSES
Class CC,J,T,RK1 or RK5
2 3.4 4 5 10
3 4.1 4.8 6 10
5 7.5 8.7 10 20
7.5 10.3 12 14 25
10 12.3 15 18 30
15 20.6 24 29 50
20 27.4 32 38 60
25 34 40 48 70
30 41 48 53 80
40 54 64 70 100
50 68 80 88 125
60 82 96 106 150
75 110 128 141 200
Voltage Range: 300V for drives with 230V class VFD
500V for drives with 460V class VFD
1-29
2. Using LCD Digital Operator
t
r
r
Functions of LCD digital operator
JNEP-36 LCD digital operator has 2 modes: DRIVE mode and PRGM mode. When the inverter is stopped, DRIVE mode or PRGM mode can be selected by pressing the key
PRGM
DRIVE
mode, the parameter settings for operation can be changed but the operation is not enabled. The component names and function are shown as below:
. In DRIVE mode, the operation is enabled. Instead, in the PRGM
DRIVE FWD REV REMOTE
SEQ
REF
operation mode indicators DRIVE : lit when in DRIVE mode FWD : lit when there is a forward run command inpu REV : lit when there is a reverse run command input SEQ : lit when the run command is enabled from the
DIGITAL OPERATOR JNEP-36
control circuit terminal or RS-485 port (REMOTE mode) REF : lit when the frequency reference from the control
REMOTE/LOCAL
circuit terminals (VIN or AIN) or RS-485 port is
enabled (REMOTE mode)
PRGM DRIVE
DSPL
LCD Display
JOG
EDIT
ENTER
Chinese Display : 2-line by 8-characte English Display : 2-line by 20-characte
FWD
REV
RESET
Keys (Key functions are defined in Table 7)RUN STOP
Fig. 8. LCD Digital operator
Remote/Local switch function:
• Local mode – RUN command input from LCD Digital Operator (SEQ LED off) – Frequency command input from LCD Digital Operator (REF LED
off)
• Remote mode –RUN command input from control circuit (when Sn-04=1) or
RS-485 comm. port (when Sn-04=2) (SEQ LED lit)
–Frequency command input from control circuit (when Sn-05=1) or
RS-485 comm. port (when Sn-05=2) (REF LED lit)
• Press and both to switch Local/Remote mode. (Switching action of
JOG
RESET
Local/Remote only can be done while Inverter stop.)
2-1
Table 7 Key's functions
Key Name Function
PRGM DRIVE
DSPL
JOG
FWD
REV
RESET
EDIT
ENTER
PRGM/DRIVE
key
DSPL key
JOG key
FWD/REV
key
RESET key
INCREMENT
key
DECREMENT
key
EDIT/ENTER
key
Switches over between program mode (PRGM) and drive mode (DRIVE).
Display operation status Enable jog operation from LCD digital operator in operation
(DRIVE). Select the rotation direction from LCD digital operator. Set the number of digital for user constant settings. Also It
acts as the reset key when a fault has occurred. Select the menu items, groups, functions, and user constant
name, and increment set values. Select the menu items, groups, functions, and user constant
name, and decrement set values. Select the menu items, groups, functions, and user constants
name, and set values (EDIT). After finishing the above action, press the key (ENTER).
RUN
RUN key
Start inverter operation in (DRIVE) mode when the digital operator is used. The LED will light.
Stop inverter operation from LCD digital operator. The
STOP
STOP key
STOP key can be enabled or disabled by setting the parameter Sn-07 when operating from the control circuit terminal.
RUNSTOP indicator lights or blinks to indicate the 3 operating status:
Inverter output frequency
STOP
Frequency setting
RUN
STOP
STOP
ON
RUN
Blink
OFF
2-2
Display contents in DRIVE mode and PRGM mode
□□
□□
PRGM mode
DSPL
An-
Bn-
Sn-
Cn-
monitor/set
□□
monitor/set
□□
monitor/set
monitor/set
□□
DSPL
DSPL
DSPL
Power on
PRGM DRIVE
DRIVE mode
Frequency reference
value displayed
display monitor/set item
Un-
An-
□□
Bn-
□□
*1
DSPL
DSPL
DSPL
monitor
DSPL
monitor/set
DSPL
monitor/set
*2
DSPL
Sn-
Cn-
□□
□□
DSPL
monitor
monitor
DSPL
*3
+
RESET
*1 When the inverter is powered up, the inverter system immediately enters into DRIVE
mode. Press the occurs, press the
PRGM DRIVE
key, the system will switch into PRGM mode. If the fault
PRGM DRIVE
key and enter into DRIVE mode to monitor the corresponding Un-□□ contents. If a fault occurs in the DRIVE mode, the corresponding fault will be displayed. Press the
key and reset the fault.
RESET
*2 The monitored items will be displayed according to the settings of Bn-12 and Bn-13. *3 When in the DRI VE mode, press the
DSPL
key and
key, the setting values
RESET
of Sn- and Cn-□□ will only be displayed for monitoring but not for changing or setting.
2-3
Parameter description
The inverter has 4 groups of user parameters:
Parameters
Description
An-□□ Frequency command Bn-□□ Parameter groups can be changed during running
Sn-□□ System parameter groups (can be changes only after stop)
Cn-□□ Control parameter groups (can be changed only after stop)
The parameter setting of Sn-03 (operation status) will determine if the setting value of different parameter groups are allowed to be changed or only to be monitored, as shown below:
DRIVE mode
PRGM mode
Sn-03
To be set To be monitored To be set To be monitored
*1
0
An,Bn Sn,Cn An,Bn,Sn,Cn
1 An Bn,(Sn,Cn)
*2
An Bn,Sn,Cn
*1 : Factory setting *2 : When in DRIVE mode, the parameter group Sn-, Cn- can only be monitored if the
key and the
RESET
DSPL
key are to be pressed simultaneously.
*3 : After a few trial and adjustment, the setting value Sn-03 is set to be “1” so as not be
modified again.
2-4
Example of using LCD digital operator
Note : Before operation: Control parameter Cn-01 value must be set as the
input AC voltage value. For example, Cn-01=380 if AC input voltage is 380.
This example will explain the operating of the inverter according to the following time chart.
OPERATION MODE
(1)
POWER
ON
(2) (3) (4) (5) (6) (7) (8)
FWD JOG
OPERATION
SET INPUT
VOLTAGE
Example of operation
Description
When Power on
(1)
(2)
Input voltage
setting (e.g. AC
input voltage is
(continued)
380V )
Select frequency reference value displayed
Select PRGM mode Select
PARAMETER
CONTROL
Display Cn-01 setting Input Voltage 380V
FWD RUN
FREQUENCY
SETTING
Key Sequence
PRGM DRIVE
DSPL
EDIT
ENTER
RESET
EDIT
ENTER
60 Hz
REV RUN
FREQ REF.
VALUE CHANGED
Digital Operator
Freq. Cmd.000.00Hz
An -01 Freq. Cmd. 1
press 3
times
Input Voltage
Cn-01 = 440.0V
Input Voltage
Cn-01 = 380.0V
Input Voltage
Entry Accepted
FWD
Display
TECO
Cn -01-
STOP
REV
60Hz
Remark
LED OFF
Display for 0.5 sec
DRIVE
2-5
(continued)
Description
Key Sequence
Digital Operator
Display
Remark
(3)
(4)
(5)
FWD JOG
Frequency setting
FWD run
Select DRIVE mode Select output frequency
displayed Select direction of rotation
(When power on, initially defaulted FWD)
Jog operation Select frequency cmd
displayed
15 Hz
Change frequency cmd Set new frequency cmd
Select O/P frequency displayed
Running operation
PRGM DRIVE
DSPL
JOG
DSPL
RESET
EDIT
ENTER
DSPL
RUN
press
4 times
Freq. Cmd.000.00Hz
TECO
Freq. Cmd.0.00 Hz
O/P Freq. 0.00 Hz
O/P Freq. 6.00 Hz Freq. Cmd. 6.00 Hz
Freq. Cmd.000.00Hz
TECO
Freq. Cmd.015.00Hz
TECO
Freq. Cmd.015.00Hz
TECO
Entry Accepted
O/P Freq. 0.00 Hz Freq. Cmd. 15.00 Hz
O/P Freq. 15.00 Hz Freq. Cmd. 15.00 Hz
DRIVE
LED ON
FWD
LED ON
Displayed for 0.5sec
Confirm the display.
LED ON
RUN
(6)
Frequency
command change
(7)
(8)
REV RUN
STOP
Select frequency cmd displayed
60 Hz
Change reference value
Enter new frequency cmd setting
Select frequency cmd displayed
Change to REV
Decrement to STOP
DSPL
RESET
EDIT
ENTER
DSPL
FWD
REV
STOP
press
4 times
Freq. Cmd.015.00Hz
TECO
Freq. Cmd.060.00Hz
TECO
Freq. Cmd.060.00Hz
TECO
Entry Accepted
O/P Freq. 60.00 Hz
Freq. Cmd. 60.00 Hz
O/P Freq. 60.00 Hz
Freq. Cmd. 60.00 Hz
O/P Freq. 0.00 Hz Freq. Cmd. 60.00 Hz
Displayed for 0.5sec Confirm the display.
LED
REV
ON
LED
STOP
ON
(Blinking while decel.)
RUN
2-6
Example of display (use and keys to display monitored items/contents)
Description
Display Frequency Command
Display Moniter Content s *1
Display Output Current
Display Output Voltage
Display DC Voltage
Display Output Voltage
Display Output Current
Key Sequence
DSPL
Digital Operator
Display
Freq. Cmd. 60.00Hz
TECO
Freq. Cmd. 60.00 Hz
O/P Freq. 60.00 Hz
Freq. Cmd. 60.00 Hz
O/P I 12.5 A
Freq. Cmd. 60.00 Hz
O/P Volt. 220.0 V
Freq. Cmd. 60.00 Hz
DC Volt. 310.0 V
Freq. Cmd. 60.00 Hz
O/P Volt. 220.0 V
Freq. Cmd. 60.00 Hz
O/P I 12.5 A
Remark
*1. The monitor contents can be selected by the setting of Bn-12 and Bn-13
2-7
3. Parameter Setting
3.1 Frequency command (in Multi-speed operation) An*1-□□
Under the DRIVE mode, the user can monitor the parameters and set their values.
*2
Parameter
No.
An-01 Frequency Command 1
An-02 Frequency Command 2
An-03 Frequency Command 3
An-04 Frequency Command 4
An-05 Frequency Command 5
An-06 Frequency Command 6
An-07 Frequency Command 7
An-08 Frequency Command 8
An-09 Frequency Command 9
An-10 Frequency Command 10
An-11 Frequency Command 11
An-12 Frequency Command 12
An-13 Frequency Command 13
An-14 Frequency Command 14
An-15 Frequency Command 15
An-16 Frequency Command 16
An-17
Name LCD Display (English)
Jog Frequency
Command
An-01= 000.00Hz
Freq. Cmd. 1
An-02= 000.00Hz
Freq. Cmd. 2
An-03= 000.00Hz
Freq. Cmd. 3
An-04= 000.00Hz
Freq. Cmd. 4
An-05= 000.00Hz
Freq. Cmd. 5
An-06= 000.00Hz
Freq. Cmd. 6
An-07= 000.00Hz
Freq. Cmd. 7
An-08= 000.00Hz
Freq. Cmd. 8
An-09= 000.00Hz
Freq. Cmd. 9
An-10= 000.00Hz
Freq. Cmd. 10
An-11= 000.00Hz
Freq. Cmd. 11
An-12= 000.00Hz
Freq. Cmd. 12
An-13= 000.00Hz
Freq. Cmd. 13
An-14= 000.00Hz
Freq. Cmd. 14
An-15= 000.00Hz
Freq. Cmd. 15
An-16= 000.00Hz
Freq. Cmd. 16
An-17= 000.00Hz
Jog Freq. Cmd.
Setting Range
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
0.00400.00Hz
Setting
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 0.00Hz
0.01Hz 6.00Hz 3-56
Unit
Factory
Setting
Ref.
Page
3-54 3-70 3-71
*1. At factory setting, the value of “Setting Unit” is 0.01Hz. *2. The displayed “Setting Unit” can be changed through the parameter Cn-28.
3-1
3.2 Parameters Groups Can Be Changed during Running Bn-□□
A
Under the DRIVE mode, the Parameter group can be monitored and set by the users.
Function
Acc/Dec
time
Analog
Frequency
Multi-
Function
Analog
Input
Torque
Boost
Monitor
Multi-
Function
Analog Output
PID
Control
Parameter
No.
Bn-01 Acceleration Time 1
Bn-02 Deceleration Time 1
Bn-03 Acceleration Time 2
Bn-04 Deceleration Time 2
Bn-05
Bn-06
Bn-07
Bn-08
Bn-09
Bn-10
Bn-11 Auto Torque Boost Gain
Bn-12 Monitor 1
Bn-13 Monitor 2
Bn-14
Bn-15
Bn-16 PID Detection Gain
Bn-17 PID Proportional Gain
Bn-18 PID integral time
Bn-19 PID Differential Time
Bn-20 PID Bias
Analog Frequency Cmd
Multi-Function Analog
Multi-Function Analog
Multi-Function Analog
Multi-Function Analog
Name
Analog Frequency
Cmd. Gain (Voltage)
Analog Frequency
Cmd. Bias (Voltage)
nalog Frequency Cmd
Gain. (Current)
Bias (Current)
Input Gain
Input Bias
Output AO1 Gain
Output AO2 Gain
LCD display
(English)
Bn-01= 0010.0s
Acc. Time 1
Bn-02= 0010.0s
Dec. Time 1
Bn-03= 0010.0s
Acc. Time 2
Bn-04= 0010.0s
Dec. Time 2
Bn-05= 0100.0%
Voltage Cmd. Gain
Bn-06= 000.0%
Voltage Cmd. Bias
Bn-07= 0100.0%
Current Cmd. Gain
Bn-08= 000.0%
Current Cmd. Bias
Bn-09= 0100.0% Multi_Fun. ~Gain
Bn-10= 000.0%
Multi_Fun. ~Bias
Bn-11= 0.5
Auto_Boost Gain
Bn-12= 01
Display: Freq.Cmd.
Bn-13= 02
Display: O/P Freq.
Bn-14= 1.00
~Output AO1 Gain
Bn-15= 1.00
~Output AO2 Gain
Bn-16= 01.00
PID Cmd. Gain
Bn-17= 01.00
PID P_gain
Bn-18= 10.00s
PID I_Time
Bn-19= 0.00s
PID D_Time
Bn-20= 0%
PID Bias
Setting range
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.01000.0%
-100.0%100.0%
0.01000.0%
-100.0%100.0%
0.01000.0%
-100.0%100.0%
0.02.0
118
118
0.012.55
0.012.55
0.0110.00
0.0110.00
0.00100.00s
01.00s
0109%
Setting
Unit
0.1s 10.0s
0.1s 10.0s
0.1s 10.0s
0.1s 10.0s
0.10% 100.00%
0.10% 0.00%
0.10% 100.00%
0.10% 0.00%
0.10% 100.00%
0.10% 0.00%
0.1 0.5 3-5
1 1
1 2
0.01 1
0.01 1
0.01 1
0.01 1
0.01s 10.00s
0.01s 0.00s
1% 0%
Factory Setting
Ref.
Page
3-4
3-5
3-5
3-6
3-7
3-7
3-2
Function
Auto_Run
Time
Function
Timer
Function
Energy
Saving
Parameter
No.
Bn-21
Bn-22
Bn-23
Bn-24
Bn-25
Bn-26
Bn-27
Bn-28
Bn-29
Bn-30
Bn-31
Bn-32
Bn-33
Bn-34
Bn-35
Bn-36
Bn-37
Bn-38
1st_Step Time Under
2nd_Step Time Under
3rd_Step Time Under
4th_Step Time Under
5th_Step Time Under
6th_Step Time Under
7th_Step Time Under
8th_Step Time Under
9th_Step Time Under
10th_Step Time Under
11th_Step Time Under
12th_Step Time Under
13th_Step Time Under
14th_Step Time Under
15th_Step Time Under
16th_Step Time Under
Name
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Auto_Run Mode
Timer Function
On_Delay Time
Timer Function
Off_Delay Time
Bn-39 Energy_Saving Gain
Monitor Bn-40 Monitor 3
LCD display
(English)
Bn-21= 0000.0s
Time 1
Bn-22= 0000.0s
Time 2
Bn-23= 0000.0s
Time 3
Bn-24= 0000.0s
Time 4
Bn-25= 0000.0s
Time 5
Bn-26= 0000.0s
Time 6
Bn-27= 0000.0s
Time 7
Bn-28= 0000.0s
Time 8
Bn-29= 0000.0s
Time 9
Bn-30= 0000.0s
Time 10
Bn-31= 0000.0s
Time 11
Bn-32= 0000.0s
Time 12
Bn-33= 0000.0s
Time 13
Bn-34= 0000.0s
Time 14
Bn-35= 0000.0s
Time 15
Bn-36= 0000.0s
Time 16
Bn-37= 0000.0s
ON_delay Setting
Bn-38= 0000.0s
OFF_delay Setting
Bn-39= 100%
Eg.Saving Gain
Bn-40=00
Display : Set_Freq.
Setting range
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
0.06000.0s
Setting
Unit
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
0.1s 0.0s
Factory Setting
Ref.
Page
3-70 3-71
3-9
0.06000.0s
50150
0.1s 0.0s
1% 100% 3-10
00~18 1 0 3-10
3-3
8
Function
Pulse
Input
PID
Feedback
Display
Parameter
No.
Bn-41 Pulse Input Upper Limit
Bn-42 Pulse Input Gain
Bn-43 Pulse Input Bias
Bn-44 Pulse Input Delay Time
Bn-45*1
Bn-46
PID Feedback Display
PID Feedback Display
*1
Name
at 0%
at 100%
LCD display
(English)
Bn-41=1440 Hz
Pulse_Mul._Up_Bound
Bn-41=100.0 %
Pulse_Mul._Gain
Bn-41=000.0 %
Pulse_Mul._Bias
Bn-41=0.10 s
Pulse_Mul._Filter
Bn-45= 0000
PID Display at 0%
Bn-46= 1000
PID Display at 0%
Setting range
1440~32000 1 Hz 1440
0.0~1000.0 0.10% 100
-100.0~100.0 0.1Hz 0
0.00~2.00 0.01s 0.1
1~9999*1 1
1~9999
*1
Setting
Unit
1
Factory Setting
*2
0
*2
1000
Ref.
Page
3-11
3-11
*1. These parameters are available for 74.03 and later software version only. *2. The displayed “Setting Unit” and “Setting Range” can be changed through parameter Cn-28 and
Sn-70.
(1) Acceleration Time 1 (Bn-01) (2) Deceleration Time 1 (Bn-02) (3) Acceleration Time 2 (Bn-03) (4) Deceleration Time 2 (Bn-04)
Set individual Acceleration/Deceleration times Acceleration time: the time required to go from 0% to 100% of the maximum
output frequency Deceleration time: the time required to go from 100% to 0% of the maximum output frequency If the acceleration/deceleration time sectors 1 and 2 are input via the
multi-function inputs terminal g~j, the acceleration/Deceleration can be switched between 2 sectors even in the running status.
Output frequency
Cn-02
Bn-01
Bn-03
Control circuit terminals
Open : Close :
Bn-02
Bn-04
select the 1st sector Acc./Dec. time
(Parameters Bn-01, Bn-02 set)
select the 2nd sector ACC/DEC time
(Parameters Bn-03, Bn-04 set)
Time
5 ~
Fig. 9. Acceleration and Deceleration time
Note :
1. To set the S-curve characteristics function, please refer to the description of Cn-41~Cn-44.
2. The S-curve characteristic times can be set respectively for beginning-accel. end-accel.,
beginning-decel., and end-decel. through the parameters setting of Cn-41~Cn-44.
3-4
(5) Analog Frequency Command Gain (Voltage) (Bn-05) (6) Analog Frequency Command Bias (Voltage) (Bn-06) (7) Analog Frequency Command Gain (Current) (Bn-07) (8) Analog Frequency Command Bias (Current) (Bn-08) (9) Multi-function Analog Input Gain (Bn-09) (10) Multi-function Analog Input Bias (Bn-10)
For every different analog frequency command (voltage or current) and
multi-function analog inputs, their corresponding gain and bias should be specified respectively.
command value
Max. output
frequency
Max. output
frequency
gain 100
bias
100
0V
(4 mA)
10V
(20 mA)
Input voltage (Input current) * ( ) If current command is used
Fig. 10. Analog input gain and bias
(11) Auto Torque Boost Gain (Bn-11)
The inverter can increase the output torque to compensate the load increase
automatically through the auto torque boost function. Then the output voltage will increase. As a result, the fault trip cases can be decreased. The energy efficiency is also improved. In the case that the wiring distance between the inverter and the motor is too long (e.g. more than 100m), the motor torque is a little short because of voltage drop. Increase the value of Bn-11 gradually and make sure the current will not increase too much. Normally, no adjustment is required.
output
voltage
100 %
torque
increase
torque
decrease
Base frequency
Fig. 11. Adjust the auto torque boost gain Bn-11 to increase the output torque.
If the driven motor capacity is less than the inverter capacity (Max. applicable
motor capacity), raise the setting.
If the motor generates excessive oscillation, lower the setting.
3-5
(12) Monitor 1 (Bn-12) (13) Monitor 2 (Bn-13)
In the DRIVE mode, 2 inverter input/output statuses can be monitored at the same
time. The specified items can be set through the setting of Bn-12 and Bn-13. For more details, refer to Table 8.
Example:
Bn-12= 02
(1)
Bn-13= 01
(2) Bn-12= 03
Bn-13= 05
(3) Bn-12= 11
Bn-13= 12
Note : While monitoring, use the
displayed. But the setting of Bn-12 and Bn-13 does not change.
Table 8 Setting of Monitoring contents
Setting
Bn-12= 01 Freq.Cmd. Bn-13= 01 Freq.Cmd. Bn-12= 02 O/P Freq. Bn-13= 02 O/P Freq. Bn-12= 03 O/P I Bn-13= 03 O/P I Bn-12= 04 O/P V Bn-13= 04 O/P V Bn-12= 05 DC Volt Bn-13= 05 DC Volt Bn-12= 06 Term. VIN Bn-13= 06 Term. VIN Bn-12= 07 Term. AIN Bn-13= 07 Term. AIN Bn-12= 08 Term. AUX Bn-13= 08 Term. AUX Bn-12= 09 ~ Output(AO1) Bn-13= 09 ~ Output(AO1) Bn-12= 10 ~ Output(AO2) Bn-13= 10 ~ Output(AO1)
Bn-12= 11 I/P Term Bn-13= 11 I/P Term Bn-12= 12 O/P Term Bn-13= 12 O/P Term Bn-12= 13 Sp. FBK Bn-13= 13 Sp. FBK Bn-12= 14 Sp. Compen. Bn-13= 14 Sp. Compen. Bn-12= 15 PID I/P Bn-13= 15 PID I/P Bn-12= 16 PID O/P(Un-16) Bn-13= 16 PID O/P(Un-16) Bn-12= 17 PID O/P(Un-17) Bn-13= 17 PID O/P(Un-17) Bn-12= 18 Motor Sp. Bn-13= 18 Motor Sp.
Monitoring
contents
Display O/P Freq. 15.00Hz
Freq.Cmd. 15.00Hz
Display O/P I 21.0A
DC Volt 311V
Display I/P Term. 00101010
O/P Term. 00010010
or key to show the next lower-row
Setting
Monitoring
contents
3-6
(14) Multi-function Analog Output AO1 Gain (Bn-14) (15) Multi-function Analog Output AO1 Gain (Bn-15)
Multi-function analog output AO1 and AO2 can be set for their individual voltage
level respectively.
Multi-functional analog output AO1
(output contents depend on Sn-33)
Multi-functional analog output AO2
( output contents depend on Sn-34)
10.0 V * Bn-14
10.0 V * Bn-15
Terminal
AO1
Terminal
AO2
(16) PID Detection Gain (Bn-16) (17) PID Proportional Gain (Bn-17) (18) PID Integral Time (Bn-18) (19) PID Differential Time (Bn-19) (20) PID Bias (Bn-20)
The PID control function is a control system that matches a feedback value (i.e., a
detected value) to the set target value. Combining the proportional (P), integral (I) and derivative (D) control make the control possible to achieve required response with the constant setting and tuning procedure of proportional gain Bn-17, integral time Bn-18 and derivative time Bn-19.
See the appendix on page App.1 for “PID Parameter Setting”. Fig. 12 is a Block diagram of the inverter’s internal PID control. If both the target value and feedback value are set to 0, adjust the inverter output
frequency to zero.
Target
value
(multi-functional
analog input terminal
Aux when Sn-29 = 09)
Detected value
Ref. Com.terminal¡G Vin 0 ~ 10 V (Sn-24 = 0) Ain 4 ~ 20mA (Sn-24 = 1) while PID enabled
Bias
Bn-16
(P)
Bn-17
(I)
Bn-18
(D)
Bn-19
PID control input
(Un-15)
integral upper_limit
Cn-55
Upper_limit (+/- 109 %)
PID control O/P 1
Bn-20
(Un-16)
Fig. 12. Block diagram for PID control in inverter
(For the version before 30.17)
3-7
1st order delay
constant
Cn-56
Freq. Com.
PID control O/P 2
(Un-17)
Deviation
Target value
(P)
(I)
(D)
Deviation
Bn-18
Deviation
20 ms
Detected value
t
Fig. 13. Response of PID control for step-shape (deviation) input
Deviation = Target value-Detected value ×Bn-16. P’s control output = deviation ×Bn-17. I’s control output will increase with time and the output will be equal to the
deviation after time specified by parameter Bn-18 The parameter Cn-55 will prevent the calculated value of the integral control (with the integral time Bn-18) in the PID control from exceeding the fixed amount.
Bn-19
D’s control output = difference × (
)
5 m sec
Note: The enable PID function, parameter Sn-64 must be set to 1
30.18 newly revised version inverter develops 8 PID control modes as following description:
0: Unavailable 1: (Positive characteristic) input of differential controller is balance of feedback value
and frequency value. 2: (Positive characteristic) input of differential controller is feedback value 3: (Positive characteristic) refers to frequency and PID control output. Input of
differential controller is balance of feedback value and frequency value. 4: (Positive characteristic) refers to frequency and PID control output. Input of
differential controller is feedback value 5: (Negative characteristic) input of differential controller is balance of feedback value
and frequency value. 6: (Negative characteristic) input of differential controller is feedback value 7: (Negative characteristic) refers to frequency and PID control output. Input of
differential controller is balance of feedback value and frequency value. 8: (Negative characteristic) refers to frequency and PID control output. Input of
differential controller is feedback value.
3-8
+
+
Fig. 14. PID Control Block diagram (After Version 30.18)
(21) Time Setting in Auto_Run Mode (Bn-21Bn-36)
PID control output 1 (Un-16)
In Auto_Run mode, the time setting for individual step is described on “(Sn-44~60)
auto run mode selection and enable”.
(22) Timer ON_Delay Time (Bn-37) (23) Timer OFF_Delay Time (Bn-38)
The timer function is enabled when the timer function input setting (Sn-25~28=19)
and its timer function output setting (Sn-30~32=21) are set for the multi-function input and output respectively.
These inputs and outputs serve as general-purpose I/O. Setting ON/OFF delay
time (Bn-37/38) for the timer can prevent chattering of sensors, switches and so on.
When the timer function input ON times is longer than the value set for Bn-37, the
timer function output turns ON.
When the timer function input OFF time is longer than the value set for Bn-38, the
timer function output turns OFF. An example is shown below.
Timer function input
Timer function output
ON ON
ON ON
Bn-37 Bn-37Bn-38 Bn-38
Fig. 15. An operation example of timer function
3-9
(24) Energy Saving Gain (Bn-39)
Input the energy saving command while a light load causes the inverter output
voltage to be reduced and save energy. Set this value as a percentage of the V/F pattern. The setting range is 50~150%. The factory setting is 100% and the energy saving function is disabled. If the energy saving gain Bn-39 is not 100%, the energy saving function is enabled.
In energy saving mode (Bn-39100), the output voltage will automatically
decrease and be proportional to energy saving gain Bn-39. The Bn-39 setting should not be small so that the motor will not stall.
The energy saving function is disabled in the PID close-loop control and during
acceleration and deceleration.
Run command
V/f(Cn-01 & Cn-08) * Bn-39
Output voltage
0.1 sec 0.1 sec
Fig. 16. Time chart for energy-saving operation
(25) Monitor 3 (Bn-40)
The parameter sets immediate display content as power on. When Bn-40 = 00, inverter power on, the first line will display frequency
command, while the second line will display characters “TECO” as following diagram:
Freq . Cmd. : 15.00 Hz
TECO
When Bn-4000, that is Bn-40=01~18, LCD will display the set monitor items
while inverter power on. The first line display content is determined by Bn-12. The second line is determined by Bn-40 as following diagram:
Set Bn-12=01 Bn-40=02
Freq . Cmd. : 15.00 Hz O / P Freq.: 00.00 Hz
Bn-40=01~18 parameter description is same with Bn-12, Bn-13.
Please refer to Table 1, Monitor item set.
3-10
(26) Pulse Input setting (Bn-41~Bn-44)
Setting Sn-05=3 before starting Pulse Input function. Please refer to Sn-05. Please refer to the following figure:
Upper Limit 100%
External Input
Frequency
Bn-44
Pulse Input
Delay
Command Value
Max. Output Freq.
Max. Output Freq.
× ×
Bn-41 Pulse Input Upper Limit
Bn-42
100
Bn-43
100
0%
100% Input Freq.
Upper Limit 100%
Command Value
(27) PID Feedback Display at 0% (Bn-45) (28) PID Feedback Display at 100% (Bn-46)
These parameters are available for 74.03 and later software version only. The PID feedback can be input from control terminal VIN (0~10V) or AIN
(4-20mA).
The PID feedback value can be monitored by the monitoring parameter Un-34.
The display content can be set by Cn-28, Sn-70, Bn-45 and Bn-46. Cn-28 sets the decimal point position of Un-34. Sn-70 sets the unit of Un-34. Bn-45 is the equivalent value displayed for 0% PID Feedback. Bn-46 is the equivalent value displayed for 100% PID Feedback.
Target
PID
Primary
Delay
Frequency Command
Feedback
Signal
Bn-16
Bn-45,46
PID Feedback Display
(Un-34)
The decimal point position and the unit of Bn-45, Bn-46 can be set by Cn-28 and
Sn-70. It is necessary to set the value of Cn-28 and Sn-70 before Bn-45 and Bn-46 are set.
Ex PID feedback signal is pressure signal. 0% for 5.0 PSI, and 100% for 100.0
PSI. Set Sn-70 = 3 (unit as PSI)
Cn-28 = 10000 (1 decimal) Bn-45 = 005.0PSI (display at 0%) Bn-46 = 100.0PSI (display at 100%)
3-11
3.3 Control Parameters Cn-□□
Function
V/F
Pattern
Setting
Motor
Parameter
DC Braking
Function
Frequency
Limit
Frequency
Jump
Parameter
No.
Name
Cn-01 Input Voltage
Cn-02 Max. Output Frequency
Cn-03 Max. Output Voltage
Cn-04 Max. Voltage Frequency
Cn-05 Middle Output Frequency
Cn-06
Voltage At Middle Output
Frequency
Cn-07 Min Output Frequency
Cn-08
Voltage At Min. Output
Frequency
Cn-09 Motor Rated Current
Cn-10
No Load Current Of
Motor
Cn-11 Rated Slip Of Motor
Cn-12
Cn-13
Cn-14
Line-To-Line Resistance
Of Motor
Torque Compensation Of
Core Loss
DC Injection Braking
Starting Frequency
Cn-15 DC Braking Current
Cn-16
Cn-17
Cn-18
Cn-19
DC Injection Braking
Time At Stop
DC Injection Braking
Time At Start
Frequency Command
Upper Bound
Frequency Command
Lower Bound
Cn-20 Frequency Jump Point 1
Cn-21 Frequency Jump Point 2
Cn-22 Frequency Jump Point 3
Cn-23 Jump Frequency Width
LCD display
(English)
Cn-01= 230.0V
Input Voltage
Cn-02= 060.0Hz
Max. O/P Freq.
Cn-03= 230.0Hz
Max. Voltage
Cn-04= 060.0Hz
Max. Volt Frequency
Cn-05= 003.0Hz
Middle O/P Freq.
Cn-06= 014.9V
Middle Voltage
Cn-07= 001.5Hz
Min O/P Freq.
Cn-08= 007.9V
Min. Voltage
Cn-09= 0003.3A
Motor Rated I
Cn-10= 30%
Motor No-Load I
Cn-11= 0.0%
Motor Rated Slip Cn-12= 05.732
Motor Line R
Cn-13= 0064W
Core Loss
Cn-14= 01.5Hz
C Braking Start F
Cn-15= 050%
DC Braking Current
Cn-16= 00.5s
DC Braking Stop Time
Cn-17= 00.0s
DC Braking Start Time
Cn-18= 100%
Freq.Cmd. Up Bound
Cn-19= 000%
Freq. Cmd. Low Bound
Cn-20= 000.0Hz
Freq. Jump 1
Cn-21= 000.0Hz
Freq. Jump 2
Cn-22= 000.0Hz
Freq. Jump 3
Cn-23= 01.0Hz
Freq. Jump Width
Setting range
150.0255.0V
50.0400.0Hz
0.1255.0V
0.1400.0Hz
0.1400.0Hz
0.1255.0V
0.1400.0Hz
0.1255.0V
Setting
Unit
*2
0.1V 230.0V
0.1Hz 60.0Hz
*2
0.1V 230.0V
0.1Hz 60.0Hz
0.1Hz 3.0Hz
*2
0.1V 15.5V
0.1Hz 1.5Hz
*2
0.1V 8.2V
*3 0.1A 3.3A*4 3-15
099%
09.9%
065.535
065535W
0.110.0 Hz
0100%
0.025.5s
0.025.5s
0109%
0109%
0.0400.0Hz
0.0400.0Hz
0.0400.0Hz
0.025.5Hz
1% 30%
0.10% 0.00%
0.001 5.732
1W 64
0.1Hz 1.5Hz
1% 50%
0.1s 0.5s
0.1s 0.0s
1% 100%
1% 0%
0.1Hz 0.0Hz
0.1Hz 0.0Hz
0.1Hz 0.0Hz
0.1Hz 1.0Hz
Factory
Setting
*1
*4
*4
Ref.
Page
*1
3-15
*1
3-15
*1
3-16
3-17
3-17
3-18
3-18
3-12
Function
Retry
Function
Stall
Prevention
Parameter
No.
Cn-24
Cn-25
Cn-26
Name
Number of Auto Restart
Attempt
Stall Prevention During
Acceleration
Stall Prevention During
Running
LCD display
(English)
Cn-24= 00
Retry Times
Cn-25= 170%
Acc. Stall
Cn-26= 160%
Run Stall
Setting range
010
30200%
30200%
Setting
Unit
Factory Setting
Ref.
Page
1 0 3-19
1% 170%
3-20
1% 160%
Comm.
Fault
detection
Display
Unit
Frequency
Agree
Detection
Torque
Detection 1
Carrier
Frequency
Speed
Search
Control
Cn-27
Cn-28
Cn-29
Cn-30
Cn-31
Cn-32
Cn-33
Communication Fault
Detection Time
LCD Digital Operator
Display Unit
Freq. Agree Detection
Level During Accel.
Freq. Agree Detection
Level During Decel.
Frequency Agree
Detection Width
Torque
Detection Level 1
Torque
Detection Time 1
Cn-34 Carrier frequency setting
Cn-35
Speed Search Detection
Level
Cn-36 Speed Search Time
Cn-37 Min. Baseblock Time
Cn-38
V/F Curve in Speed
Search
Cn-27=01.0s
Comm. Flt Det. Time
Cn-28= 00000
Operator Disp. Unit
Cn-29= 000.0Hz
Acc. Freq. Det.Level
Cn-30= 000.0Hz
Dec. Freq. Det. Level
Cn-31= 02.0Hz
F Agree Det. Width
Cn-32= 160%
Tq. Det. Level 1
Cn-33= 00.1s
Tq. Det. Time 1
Cn-34= 6
Carry_Freq Setting
Cn-35= 150%
Sp-Search Level
Cn-36= 02.0s
Sp-Search Time
Cn-37= 0.5s
Min. B.B. Time
Cn-38= 100
Sp-search V/F Gain
0.1~25.5s 0.1s 1s 3-20
0-39999 1 0 3-21
0.0400.0Hz
0.0400.0Hz
0.125.5Hz
0.1Hz 0.0Hz
0.1Hz 0.0Hz
0.1Hz 2.0Hz
3-22
0~200% 1% 160%
3-23
0.0~25.5s 0.1s 0.1s
16
0200%
0.125.5s
1 6 3-24
1% 150%
0.1s 2.0s 3-24
0.55.0s
10100%
0.1s 0.5s
1% 100%
Low
Voltage
Cn-39
Detection
Slip Comp. Cn-40
Cn-41
S-curve
Cn-42
time
Cn-43
Cn-44
Low Voltage Alarm
Detection Level
Slip Compensation
Primary Delay Time
S-curve Characteristic
Time at Accel. Start
S-curve Characteristic
Time at Accel. End
S-curve Characteristic
Time at Decel. start
S-curve Characteristic
Time at Decel. end
Cn-39= 200V
Low Volt. Det. Level
Cn-40= 02.0s
Slip Filter
Cn-41= 0.0s
S1 Curve Time
Cn-42= 0.0s
S2 Curve Time
Cn-43= 0.0s
S3 Curve Time
Cn-44= 0.0s
S4 Curve Time
3-13
150210V
0.025.5s
0.01.0s
0.01.0s
0.01.0s
0.01.0s
1V 200V
*1
3-26
0.1s 2.0s 3-26
0.1s 0.0s
0.1s 0.0s 3-26
0.1s 0.0s
0.1s 0.0s
Function
Speed
feedback
control
PID
Control
Sensorless
Vector
Control
Torque
Detection 2
Parameter
No.
Name
Cn-45 PG Parameter
Cn-46 Pole no. of Motor
Cn-47 ASR Proportional Gain 1
Cn-48 ASR Integral Gain 1
Cn-49 ASR Proportional Gain 2
Cn-50 ASR Integral Gain 2
Cn-51 ASR Upper Bound
Cn-52 ASR Lower Bound
Cn-53
Cn-54
Cn-55
Cn-56
Cn-57
Cn-58
Cn-59
Cn-60
Excessive Speed
Deviation Detection Level
Overspeed Detection
Level
PID Integral Upper
Bound
PID Primary Delay Time
Constant
Motor Line-to-Line
Resistance (R1)
Motor Rotor Equivalent
Resistance (R2)
Motor Leakage
Inductance (Ls)
Motor Mutual
Inductance (Lm)
Cn-61 Slip Compensation Gain
Cn-62*5
Cn-63*5
Torque
Detection Level 2
Torque
Detection Time 2
LCD display
(English)
Cn-45= 0000.0
PG Parameter
Cn-46= 04P Motor Pole
Cn-47= 0.00
ASR Gain 1
Cn-48= 01.0s
ASR Intgl. Time 1
Cn-49= 0.02
ASR Gain 2
Cn-50= 01.0s
ASR Intgl. Time 2
Cn-51= 05.0%
ASR Up Bound
Cn-52= 00.1%
ASR Low Bound
Cn-53= 10%
Sp.Deviat. Det.Level
Cn-54= 110%
Over Sp.Det. Level
Cn-55= 100%
PID I-Upper Cn-56= 0.0s
PID Filter
Cn-57= 02.233
Mtr LINE_R
Cn-58= 01.968
Mtr ROTOR_R Cn-59= 9.6mH
Mtr LEAKAGE_X Cn-60= 149.7mH
Mtr MUTUAL_X
Cn-61= 1.00
SLIP GAIN
Cn-62= 160%
Tq. Det. Level 1
Cn-63= 00.1s
Tq. Det. Time 1
Setting range
0.03000.0P/R
232P
0.002.55
0.110.0S
0.002.55
0.110.0S
0.110.0%
0.110.0%
150%
1120%
0109%
0.02.5s
0.00160.000
0.00160.000
0.01200.00mH
0.16553.5mH
0.002.55
Setting
Unit
0.1P/R 0.0P/R
2P 4P
0.01 0
0.1s 1.0s
0.01 0.02
0.1s 1.0s
0.10% 5.00%
0.10% 0.10%
1% 10%
1% 110%
1% 100%
0.1s 0.0s
0.001 2.233
0.001 1.968
0.01mH 9.6mH *4
0.1mH 149.7mH
0.01 1
Factory Setting
0~200% 1% 160%
0.0~25.5s 0.1s 0.1s
Ref.
Page
3-27
3-28
3-28
*4
3-28
*4
3-29
*4
3-23
*1 These are for a 230V class inverter. Value(*1) for a 460V class inverter is double. *2 These are for a 230V class inverter. Value(*2) for a 460V class inverter is double. *3 The setting range is 10% ~200% of the inverter rated current. *4 The factory setting values will vary based upon the inverter capacity selection (Sn-01) value. In
this case, the setting is for 4-pole, 230V, 60Hz, 1Hp TECO standard induction motors.
*5. These parameters are available for 74.03 and later software version only.
3-14
(1) Input Voltage Setting (Cn-01)
Set inverter voltage to match power supply voltage at input side (e.g. : 200V/230V,
380V/415V/440V/460V)
(2) V/F Curve Parameter Settings (Cn-02Cn-08)
The V/F curve can be set to either one of the preset curves (setting Sn-02=0~14)
or a customer user-set curve (setting Sn-02=15).
Setting Cn-02Cn-08 can be set by the user when Sn-02 has been set to “15”.
The user-defined V/F curve can be specified through the settings of Cn-02~Cn-08 as shown in Fig. 17. The factory setting is straight line for the V/F curve.
(Cn-05=Cn-07, Cn-06 is not used) as shown below (230V/60Hz case).
Voltage
Voltage
(Factory Setting)
Cn-03
Cn-06
Cn-08
(Cn-08=Cn-06)
0
Cn-07
Cn-05
Cn-04
Cn-02
Freq.
220V
Cn-03
13
0
1.5 Hz
(Cn-07=Cn-05) (Cn-04=Cn-02)
60 Hz
Freq.
Fig. 17. User-defined V/F curve
In low speed operation (<3Hz), a larger torque can be generated by increasing the
slope of V/F curve. However, the motor will be hot due to over-excitation. At the same time the inverter will be more inclined to fault. Based upon the applied load, properly adjust the V/F curve according to the magnitude of monitored current into the motor.
The four frequency settings must satisfy the following relationship, otherwise an
error message “V/F Curve Invalid” will display.
(a)
Max. output freq. Max. voltage freq. Mid. Output freq. Min. output freq.
(Cn-02) (Cn-04) (Cn-05) (Cn-07)
(b) Max. output volt. Mid. output volt. Min. output voltage
(Cn-03) (Cn-06) (Cn-08)
If Mid. Output frequency (Cn-05) = Min. output frequency (Cn-07), the setting
(Cn-06) is not effective.
(3) Motor Rated Current (Cn-09)
Electronic overload thermal reference current The factory setting depends upon the capacity type of inverter (Sn-01). The setting range is 10%~200% of the inverter rated output current.
Set the rated current shown on the motor name plate if not using the TECO 4-pole
motor.
3-15
(4) Motor No-Load Current (Cn-10)
This setting is used as a reference value for torque compensation function. The setting range is 0~99% of the inverter rated current Cn-09 (100%). The slip compensation is enabled when the output current is greater than motor
no-load current (Cn-10). The output frequency will shift from f1 to f2 (>f1) for the positive change of load torque. (See Fig. 18)
Slip compensation =
Motor rated current (Cn-09) – Motor no-load current (Cn-10)
Motor rated slip (Cn-11) ×(Output current – Motor no-load current(Cn-10))
Load torque
f1
smaller load
f2 larger load
speed
Fig. 18. Output frequency with slip compensation.
(5) Motor Rated Slip (Cn-11)
This setting is used as a reference value for torque compensation function. See Fig.
17. The setting is 0.0~9.9% as a percentage of motor Max. voltage frequency (Cn-04) as 100%.
The setting is shown in Fig. 19 in the constant torque and constant output range. If
setting Cn-11 is zero, no slip compensation is used.
There is no slip compensation in the cases when the frequency command is less
than the Min. output frequency or during regeneration.
Motor rated slip (Cn-11) =
Cn-02 Cn-04
Motor rated freq. (Hz) ×(Rated speed( RPM) – Motor No. of poles )
×100%
Max-voltage freq (Cn-04) ×120
Cn-11
Cn-11
Cn-02Cn-04
Fig. 19. Slip compensation limit
3-16
(6) Motor Line-to-Line Resistance (Cn-12) (7) Motor Iron-Core Loss (Cn-13)
It is for torque compensation function. The default setting depends upon the
inverter capacity (Sn-01). Normally, the setting does not need to be altered. See Table 10~11 on page 3-39.
(8) DC Injection Braking Starting Frequency (Cn-14) (9) DC Injection Braking Current (Cn-15) (10) DC Injection Braking Time at Stop (Cn-16) (11) DC Injection Braking Time at Start (Cn-17)
The DC injection braking function decelerates by applying a DC current to the
motor. This happens in the 2 cases:
a. DC injection braking time at start: It is effective for temporarily stopping and then
restarting, without regeneration, a motor coasting by inertia.
b. DC injection braking time at stop: It is used to prevent coasting by inertia when
the motor is not completely stopped by normal deceleration when there is a large load. Lengthening the DC injection braking time (Cn-16) or increasing the DC injection braking current (Cn-15) can shorten the stopping time.
For the DC injection braking current (Cn-15), set the value for the current that is
output at the time of DC injection braking. DC injection braking current is set as a percentage of inverter rated output current, with the inverter rated output current taken as 100%.
For the DC injection braking time at start (Cn-17), set the DC injection braking
operating time when the motor is started.
For the DC injection braking starting frequency (Cn-14), set the frequency for
beginning DC injection braking for deceleration. If the excitation level is less than the Min. output frequency (Cn-07), the DC injection braking will begin from Min. output frequency.
If the DC injection braking time at start (Cn-17) is 0.0, the motor starts from the
Min. output frequency and no DC injection braking are enabled.
If the DC injection braking time at stop (Cn-16) is 0.0, no DC injection braking is
enabled. In this case, the inverter output will be blocked off when the output frequency is less than the DC injection braking at start frequency (Cn-14).
Cn-07
Min. output frequency
Cn-17
DC injection braking at st ar t
Fig. 20. DC injection braking time chart
Cn-14
DC injection braking
starting frequency
Cn-16
DC injection braking at st op
3-17
(12) Frequency Command Upper Bound (Cn-18) (13) Frequency Command Lower Bound (Cn-19)
The upper and lower bounds of the frequency command are set as a percentage of
the Max. output frequency (Cn-02 as 100%), in increments of 1%.
The relationship Cn-18 > Cn-19 must be abided by. If not, an error message “Freq.
Limit Setting Error” may occur.
When the frequency command is zero and a run command is input, the motor
operates at the frequency command lower bound (Cn-19). The motor will not operate, however, if the lower limit is set lower than the Min. output frequency (Cn-07).
Output frequency
100%
Cn-18
Cn-19
frequency command
100%
Fig. 21. Upper and lower bounds of the frequency command
(14) Frequency Jump Point 1 (Cn-20) (15) Frequency Jump Point 2 (Cn-21) (16) Frequency Jump Point 3 (Cn-22) (17) Jump Frequency Width (Cn-23)
These settings allow the “jumping” of certain frequencies within the inverter’s
output frequency range so that the motor can operate without resonant oscillations caused by some machine systems.
Output
frequency
Cn-21
Cn-22 Cn-23
Cn-23
Cn-20
Cn-23
22-Cn 21-Cn 20-Cn
Set frequency command
Fig. 22. setting jump frequencies
3-18
Operation is prohibited within the jump frequency range, but changes during
acceleration and deceleration are smooth with no jump. To disable this function, set the jump frequency 13 (Cn-20Cn-22) to 0.0Hz.
For the jump frequency 13 (Cn-20Cn-22), set the center frequency to be
jumped.
Be sure to set the jump so that Cn-20 Cn-21 Cn-22. If not, a message “Jump
frequency setting error” is displayed. For Cn-23, set the jump frequency bandwidth. If Cn-23 is set as 0.0Hz, the jump frequency function is disabled.
(18) Number of Auto Restart Attempt (Cn-24)
The fault restart function will restart the inverter even when an internal fault
occurs during inverter operation. Use this function only when continuing operation is more important than possibly damaging the inverter.
The fault restart function is effective with the following faults. With other faults,
the protective operations will engage immediately without attempting to restart operation.
Over-current ‧Ground fault ‧Main circuit over-voltage
The fault restart count will automatically increase upon the restart activated and
will be cleared in the following cases:
a. When the operation is normal for 10 minutes after a fault restart is performed.
b. When the fault-reset input is received after the protection operation has been
activated and the fault confirmed. (e.g., by pressing
or enable Fault reset
RESET
terminal e)
c. When the power is turned off and on again.
When one of the multi-function output terminals (RA-RB-RC or R1A-R1B-R1C,
DO1, DO2 or R2A-R2C) is set to restart enabled, the output will be ON while the fault restart function is in progress. See page 63 for the setting of (Sn-30~Sn-32).
3-19
(19) Stall Prevention Level During Acceleration (Cn-25) (20) Stall Prevention Level During Running (Cn-26)
A stall occurs if the rotor can not keep up with the rotating electromagnetic field in
the motor stator side when a large load is applied or a sudden acceleration or deceleration is performed. In this case, the inverter should automatically adjust the output frequency to prevent stall.
The stall prevention function can be set independently for accelerating and
running.
Stall Prevention During Acceleration: See Fig.23. Stop acceleration if Cn-25
setting is exceeded. Accelerate again when the current recovers.
Stall Prevention During running : See Fig.24. Deceleration is started if the run stall
prevention level Cn-26 is exceeded, especially when an impact load is applied suddenly. Accelerate again when the current level is lower than Cn-26.
Load
current
Load
current
Cn-25
Output
frequency
The output frequency is
controlled to prevent stalling
Time
Time
Fig. 23 Acceleration stall prevention
Cn-26
Output
frequency
decreases to prevent stalling
Deceleration time
upon Bn-02, Bn-04
The output frequency
Time
Time
Fig. 24 Run stall prevention function
function
Set the parameters Cn-25 and Cn-26 as a percentage of inverter rated current
(100% corresponds to inverter rated current).
See page 3-48, 3-49 for stall prevention function selection.
(21) Communication Fault Detection Time (Cn-27)
Please refer to “MODBUS/PROFIBUS Application Manual”.
3-20
(22) LCD Digital Operator Display Unit (Cn-28)
It sets the units to be displayed for the frequency command and frequency
monitoring. and sets the decimal points of PID feedback display (Un-34), PID feedback display at 0% and 100% (Bn-45, 46) as described below:
Table 9 LCD digital Operator Display unit
Setting / Reading Content
Cn-28
Frequency command/monitoring PID Feedback
0 Units of 0.01 Hz
1 Units of 0.01%
2 to 39
40 to
39999
Set in the units of r / min (0 to 39999).
r / min = 120 x frequency reference (Hz) /
Cn-28
(Set the number of motor poles in Cn-28, only even data is allowed)
The position of decimal point is set by the value of the 5th digit of Cn-20.
5th digit = 0: Displayed as XXXX
5th digit = 1: Displayed as XXX.X
5th digit = 2: Displayed as XX.XX
5th digit = 3: Displayed as X.XXX
The 1st digit to 4th digits of Cn-28 set the value of 100% frequency.
Displayed as XXXX Unit specified by Sn-70
y 5th digit = 0:
Displayed as XXXX
y 5th digit = 1:
Displayed as XXX.X
y 5th digit = 2:
Displayed as XX.XX
y 5th digit = 3:
displayed as X.XXX
st
The 1
digit to 4th digits of Cn-28 are not used.
Example 1:
When the set value of 100% speed is 200.0, Cn-28 = 12000 is set.
60% speed is displayed as 120.0 at Cn-28 = 12000.
Example 2:
When the set value of 100% speed is 65.00, Cn-28 = 26500 is set.
60% speed is displayed as 39.00 at Cn-28 = 26500.
3-21
Unit specified by Sn-70
(23) Frequency Agree Detection Level During Acceleration (Cn-29) (24) Frequency Agree Detection Level During Deceleration (Cn-30) (25) Frequency Agree Detection Width (Cn-31)
Frequency detection function: Set the multi-function output terminals (control
circuit terminals RA-RB-RC or R1A-R1B-R1C, DO1, DO2 or R2A-R2C) to output the desired Frequency Agree signal, Setting Frequency Agree and Output Frequency Detection level (through proper setting of Sn-30 ~ Sn-32).
The time chart for Frequency Detection operation is described as follows:
Function Frequency Detection Operation Description
When output freq. is within freq.
command +/- freq. Detection width (Cn-31), frequency agree output is “ON”.
Set Sn-30Sn-32 to be “02” for the
setting of frequency agree output.
Frequency
Agree
freq. command
output freq.
freq. agree
signal output
Cn-31
FWD
REV
Cn-31
ONOFF
Setting
Frequency
Agree
Output
Frequency
Detection 1
Output
Frequency
Detection 2
freq. command
output freq.
agree freq.
signal output
output freq.
output freq.
detection 1 signal
output freq.
output freq.
detection 2 signal
OFF
Cn-29
Cn-29
Cn-31
ON
Cn-31
ON OFF
Cn-31
OFF
Cn-31
Cn-31
ONONOFF
Cn-31
Cn-31
ON OFF ON OFF
Cn-29
Cn-30
Cn-29
Cn-30
Cn-29
FWD
REV
Cn-30
Cn-31
Cn-30
Cn-31
FWD
REV
FWD
REV
After acceleration, the output freq.
reaches freq. Agree detection level during acceleration (Cn-29) and within freq. Agree detection width (Cn-31), agreed freq. output is “ON”.
Set Sn-30Sn-32 to be “03”.
During acceleration, the output freq. is
less than freq. agree detection level during acceleration (Cn-29), output freq. Detection 1 is “ON”.
During deceleration, the output freq. is
less than freq. agree detection level during deceleration (Cn-30), output freq. Detection 1 is “ON”.
Set Sn-30Sn-32 to be “04” for the
setting of output freq. detection.
During acceleration, the output freq. is
larger than freq. Agree detection level during acceleration (Cn-29), output freq. detection 2 is “ON”.
During deceleration, the output freq. is
larger than freq. Agree detection level during deceleration (Cn-30), output freq. detection 2 is “ON”.
Set Sn-30Sn-32 to be “05” for the
setting of output freq. detection.
3-22
(26) Torque Detection Level 1 (Cn-32) (27) Torque Detection Time 1 (Cn-33) (28) Torque Detection Level 2 (Cn-62) (29) Torque Detection Time 2 (Cn-63)
Cn-62, 63 are available for 74.03 and later software version only. Both Overtorque Detection Function and Undertorque Detection Function are
included in Torque Detection Function. The Overtorque Detection Function detects excessive mechanical load from an increase of output current. The Undertorque Detection Function detects broken fan belt from a decrease of output current.
An overtorque 1 condition is detected when the output current exceeds the Torque
Detection Level (Cn-32, Cn-62) for longer than the Torque Detection Time 1 (Cn-33, Cn-63). See Fig.25-a below.
An undertorque condition is detected when the output current is lower than the
Torque Detection Level (Cn-32, Cn-62) for longer than the Torque Detection Time (Cn-33, Cn-63). See Fig.25-b below.
When Torque Detection 1 is enabled through the setting Sn-12, be sure to set
Torque Detection Level 1 (Cn-32) and Torque Detection Time 1 (Cn-33).
The Multi-Function Output Terminals (Control Circuit Terminals RA-RB-RC or
R1A-R1B-R1C, DO1, DO2 or R2A-R2C) can be set to indicate an overtorque condition or an undertorque condition has been detected.
Motor
Current
Cn-32
Overtorque Detection Signal
Cn-33
ON
ON
Cn-33
Hysteresis
Width 5%
Fig. 25-a. Overtorque Detection Time Chart
Motor
Current
Cn-32
Hysteresis
Width 5%
Undertorque Detection Signal
ON
Cn-33
ON
Cn-33
Fig. 25-b. Underorque Detection Time Chart
3-23
ON
Properly setting the value of Sn-12 (Torque Detection 1 Selection) and Sn-69
(Torque Detection 2 Selection) and will allow
a. Enable only during frequency agreement. Continue operation even after detection. b. Enable only during frequency agreement. Stop operation after detection. c. Enable at anytime. Continue operation even after detection. d. Enable at anytime. Stop operation after detection.
(30) Carrier Frequency Setting (Cn-34)
Lower the carrier frequency can decrease the noise interference and leakage
current. Its setting is shown below.
Carrier frequency(kHz) = 2.5kHz* Cn-34 setting
Cn-34 =
1 2 6*543
(2.5 kHz) (15 kHz)
Carrier frequency
Audio noise
(louder) (insensible)
*factory setting
The output frequency does not need to be adjusted, except in the following cases.
a. If the wiring distance between the inverter and motor is long, lower the carrier
frequency as shown below to allow less leakage current.
>
Wring distance < 100ft. 100-165ft. 166-328ft.
329ft.
Carrier frequency (Cn-34) <15kHz <10kHz <5KHz <2.5KHz
b. If there is great irregularity in speed or torque, lower the carrier frequency.
(31) Speed Search Detection Level (Cn-35) (32) Speed Search Time (Cn-36) (33) Min. Baseblock Time (Cn-37) (34) Speed Search V/F Curve (Cn-38)
The speed search function will search the speed of a frequency coasting motor
from the frequency command or max. frequency downward. And it will restart up smoothly from that frequency or max. frequency. It is effective in situations such as switching from a commercial power supply to an inverter without tripping occurred.
The timing of speed search function as shown below :
3-24
FWD(or REV) run command
Speed search command
<0.5 sec
Max output frequency (or running frequency
while the speed search
is being performed)
Output frequency
Min baseblock time
voltage at speech search
ouput voltage
speed search operation
Synchronous speed dectection
retuen to voltage at
normal operation
Fig. 26. Speed search timing chart
The speed search command can be set through the multi-function contact input
terminal g ~ j (By setting the parameters Sn-25 ~ Sn-28).
If Sn-25 ~ Sn-28= 21 : Speed search is performed from Max. output frequency
and motor is coasting freely.
If Sn-25 ~ Sn-28= 22 : Speed search starts from the frequency command when
the speed search command is enabled.
After the inverter output is blocked, the user should input speed search command
then enable run operation, the inverter will begin to search the motor speed after the min. baseblock time Cn-37.
Speed search operation, if the inverter output current is less than Cn-35, the
inverter will take the output frequency as the real frequency at that time. From those values of real frequency, the inverter will accelerate or decelerate to the set frequency according to the acceleration or deceleration time.
While the speed search command is being performed, the user can slightly
decrease the setting of V/F curve (Cn-38) in order to prevent the OC protection function enabled. Normally, the V/F curve need not be changed. (As below)
Speed search operating V/F curve = Cn-38 * (normal operating V/F curve )
Note : 1. The speed search operation will be disabled if the speed search command is
enacted from the Max. frequency and the setting frequency. (I.e., Sn-25=20, Sn-26=21 and multi-function input terminals g, h is used at the same time).
3-25
2. Make sure that the FWD/REV command must be performed after or at the same time with the speed search command. A typical operation sequence is shown below.
Ry1
Speed search command
Ry1
Ry2
RWD/REV run command
3. When the speed search and DC injection braking are set, set the Min. baseblock time (Cn-37). For the Min. baseblock time, set the time long enough to allow the motor’s residual voltage to dissipate. If an overcurrent is detected when starting a speed search or DC injection braking, raise the setting Cn-37 to prevent a fault from occurring. As a result, the Cn-37 setting cannot be set too small.
(35) Low Voltage Alarm Detection Level (Cn-39)
In most cases, the default setting Cn-39 need not be changed. If an external AC
reactor is used, decrease the low voltage alarm detection level by adjusting Cn-39 setting smaller. Be sure to set a main-circuit DC voltage so that a main circuit undervoltage is detected.
(36) Slip Compensation Primary Delay Time (Cn-40)
In most cases, the setting Cn-40 need not be changed. If the motor speed is not
stable, increase the Cn-40 setting. If the speed response is slow, decrease the setting of Cn-40.
(37) S-curve Characteristic Time at Acceleration Start (Cn-41) (38) S-curve Characteristic Time at Acceleration End (Cn-42) (39) S-curve Characteristic Time at Deceleration Start (Cn-43) (40) S-curve Characteristic Time at Deceleration End (Cn-44)
Using the S-curve characteristic function for acceleration and deceleration can
reduce shock to the machinery when stopping and starting. With the inverter, S-curve characteristic time can be set respectively for beginning acceleration, ending acceleration, beginning deceleration and ending deceleration. The relation between these parameters is shown in Fig. 27.
3-26
Run
command
Output
frequency
ON
S2
OFF
S3
S1
Cn-41
Cn-42 Cn-43
S4
Cn-44
Time
Fig. 27. S curve
After the S-curve time is set, the final acceleration and deceleration time will be as
follows:
Acc. time = selected Acc. Time 1 (or 2) +
Dec. time = selected Dec. Time 1 (or 2) +
(Cn-41) + (Cn-42)
2
(Cn-43) + (Cn-44)
2
(41) PG Parameter (Cn-45)
The parameter is set in the unit of pulse/revolution. The factory setting is 0.1 P/R.
(42) Pole Number of Motor (Cn-46)
Cn-45 and Cn-46 must meet the following relationship:
2 * Cn-45 * Cn-02
< 32767
Cn-46
If not, an error message “Input Error” will be displayed
(43) ASR Proportion Gain 1 (Cn-47) (44) ASR Integral Gain 1 (Cn-48)
Set the proportion gain and integral time of the speed control (ASR)
(45) ASR Proportion Gain 2 (Cn-49) (46) ASR Integral Gain 2 (Cn-50)
Use these constants to set different proportional gain and integral time settings for
high-speed operation.
3-27
Proportional gain
Integral time
Cn-49
Cn-47
0 % 100 %
Output
frequency
Cn-50
Cn-48
0 % 100 %
Output
frequency
Fig. 28.
(47) ASR Upper Bound (Cn-51) (48) ASR Lower Bound (Cn-52)
These settings of Cn-51 and Cn-52 will limit the ASR range.
(49) Excessive Speed Deviation Detection Level (Cn-53)
This parameter set the level of detecting PG speed deviation. The value of Cn-02
is referred as 100%, the default unit setting is 1%.
(50) Overspeed Detection Level (Cn-54)
Set this parameter for detecting overspeed. The value of Cn-02 is referred as 100%,
the default unit setting is 1%. Please refer to the setting of Sn-43.
(51) PID Integral Upper Bound (Cn-55) (52) PID Primary Delay Time Constant (Cn-56)
Please refer to Fig. 14 “Block diagram for PID control in inverter” The parameter Cn-55 prevents the calculated value of the integral control of PID
from exceeding the fixed amount. The value is limited within 0-109% of Max. output frequency (100%). Increase Cn-55 will improve the integral control. If hunting cannot be reduced by decreasing the Bn-18 or increasing Cn-56, Cn-55 has to decrease. If the setting of Cn-55 is too small, the output may not match the target setting.
The parameter Cn-56 is the low-pass filter setting for PID control output. If the
viscous friction of the mechanical system is high, or if the rigidity is low, causing the mechanical system to oscillate, increase the setting Cn-56 so that it is higher than the oscillation period. It will decrease the responsiveness, but it will prevent the oscillation.
(53) Motor Line-to-Line Resistance R1 (Cn-57)
Set the motor’s terminal resistance (including the motor external cable resistance)
in unit.
The default setting depends upon the type of inverter (but do not include the motor
external motor cable resistance).
3-28
This value will be automatically set during autotuning. See “Motor parameter
autotuning selection” on page 3-73.
Increase the setting when the generating torque is not large enough at low speed. Decrease the setting when the generating torque is extremely high and cause
overcurrent trip at low speed.
(54) Motor Rotor Equivalent Resistance R2 (Cn-58)
Set the motor’s rotor Y-equivalent model resistance in  unit. The default setting depends upon the type of inverter. Normally this value isn’t
shown on the motor’s nameplate, so it might be necessary to contact motor manufactor.
This value will be automatically set during autotuning. See “Motor parameter
autotuning selection” on page 3-73.
(55) Motor Leakage Inductance Ls (Cn-59)
Set the motor’s rotor Y-equivalent model leakage inductance in mH unit. The default setting depends upon the type of inverter. This value will be automatically set during autotuning. See “Motor parameter
autotuning selection” on page 3-73.
(56) Motor Mutual Inductance Lm (Cn-60)
Set the motor Y-equivalent model mutual inductance in mH unit. The default setting depends upon the type of inverter. This value will be automatically set during autotuning. See “Motor parameter
autotuning selection” on page 3-73.
Note: The Induction Motor Y-equivalent model
LsR1
I
d
L
m
(57) Slip Compensation Gain (Cn-61)
The parameter Cn-61 improves speed accuracy while operating with a load. Usually, the setting Cn-61 need not be changed. Adjust the setting if the speed
accuracy is needed to improve.
When actual speed is low, increase the set value. When actual speed is high, decrease the set value.
I
q
R2
s
s : slip
3-29
3.4 System Parameters Sn-□□
Function
Capacity
Setting
V/F Curve Sn-02
Operator
Status
Operation
Control
Mode
Selection
Parameter
No.
Sn-01
Sn-03 Operator Display
Sn-04
Sn-05
Sn-06
Sn-07
Sn-08
Sn-09
Name
Inverter Capacity
Selection
V/F Curve
Selection
Run Source
Selection
Frequency Command
Selection
Stopping
Method
Selection
Priority of
Stopping
Prohibition of
REV Run
Output Frequency
Up/Down Function
LCD display
(English)
Sn-01= 01
220V 1HP
Sn-02= 01
V/F curve
Sn-03= 00
Setting Valid
Sn-04= 0
Run source
Operator
Sn-05= 0
Ref. Cmd.
Operator
Sn-06= 0
Dec. Stop
Sn-07= 0
Stop Key Valid
Sn-08= 0
Allow Reverse
Sn-09= 0
Inhibit UP/DOWN
Description
Inverter capacity selection *1 3-39
0~14 : 15 fixed V/F curve pattern 15 : arbitrary V/F pattern selection
0 : An-□□, Bn-□□, Cn-□□, Sn-□□ setting
& reading enabled
1 : An-□□, setting & reading enabled
Bn-□□,Cn-□□,Sn-□□ reading only 2~5 : reserved 6 : clear fault message 7 : 2-wire initialization (230V/460V) 8 : 3-wire initialization (230V/460V) 9 : 2-wire initialization (200V/415V) 10 : 3-wire initialization (200V/415V) 11 : 2-wire initialization (200V/380V) 12 : 3-wire initialization (200V/380V) 13~15 : reserved Run source 0 : Operator 1 : Control terminal 2 : RS-485 communication Frequency Command 0 : Operator 1 : Control circuit terminal 2 : RS-485 communication 3 : Pulse input 0 : Deceleration to Stop 1 : Coast to Stop 2 : Whole_range braking stop 3 : Coast to Stop with Timer
(restart after time Bn-02) If operation command from control terminal or RS-485 communication port 0 : operator stop key effective 1 : operator stop key not effective
0 : reverse run enabled 1 : reverse run disabled
0 : Reference frequency is changed
through the key ”UP/DOWN” pressing,
later followed by key “EDIT/ENTER”
pressing, and then this output freq. will
be acknowledged. 1 : reference frequency will be
acknowledged immediately after the
key ”UP/DOWN” pressing.
Factory Setting
0
0
0
0
0
0
Ref.
Page
3-40
3-43
3-43
3-45
3-30
Function
Operation
Control
Mode
Selection
Protection
Charac-
teristic.
selection
Parameter
No.
Sn-10
Sn-11
Sn-12
Sn-13
Sn-14
Sn-15
Name
Frequency Command
Characteristics
Selection
Scanning Times at
Input Terminal
Torque Detection
1 Selection
Output Voltage
Limit Selection
Stall Prevention
During Acc.
Function
Selection
Stall Prevention
During Dec.
Function
Selection
LCD display
(English)
Sn-10= 0
Ref. Cmd. Fwd.
Char.
Sn-11= 0
Scan Time 5 ms
Sn-12= 0
Tq.Detect Invalid
Sn-13= 0
V Limit Invalid
Sn-14= 1
Acc. Stall Valid
Sn-15= 1
Dec. Stall Valid
Description
0 : Reference command has forward
characteristics
(0~10V or 4~20mA/0~100% 1 : Reference command has reverse
characteristics
(10~0V or 20~4mA/0~100%) 0 : scan and confirm once per 5 ms 1 : continuously scan and confirm twice per
10 ms
Option 5-8 are available for 74.03 and later
software version only.
0 : Torque detection function 1 is not
effective. 1 : Overtorque is detected only at
frequency agree. Continue operation
after detection. 2 : Overtorque is detected only at
frequency agree. Stop operation after
detection. 3 : Overtorque is detected during running
(Accel.,Decel. included). Continue
operation after detection. 4 : Overtorque is detected during running
(Accel., Decel included). Stop operation
after detection. 5 : Undertorque is detected only at
frequency agree. Continue operation
after detection. 6 : Undertorque is detected only at
frequency agree. Stop operation after
detection. 7 : Undertorque is detected during running
(Accel.,Decel. included). Continue
operation after detection. 8 : Overtorque is detected during running
(Accel., Decel included). Stop operation
after detection. 0 : V/F output voltage is limited
1 : V/F output voltage is not limited
0 : invalid (Too much a torque may cause
the stall) 1 : valid (stop acceleration if current
exceeds Cn-25 setting)
0 : invalid (installed with external brake
unit) 1 : valid (no external brake unit used)
Factory Setting
0
0
0
0
1
1
Ref.
Page
3-46
3-47
3-48
3-31
Function
Protection
Charac-
teristic.
selection
Protection
Charac-
teristic.
Selection
Parameter
No.
Sn-16
Sn-17
Sn-18
Sn-19
Sn-20
Sn-21
Sn-22
Sn-23
Sn-24
Name
Stall Prevention
During Running
Function Selection
Fault Retry
Setting
Operation Selection At Power Loss
Zero Speed
Braking Operation
Selection
External Fault
Contact e
Contact Selection
External Fault
Contact e
Detection Selection
External Fault
Operation
Selection
Motor Overload
Protection
Selection
Frequency Command
Characteristics
Selection at
External Analog
Input Terminal
LCD display
(English)
Sn-16= 1
Run Stall Valid
Sn-17= 0
Retry No O/P
Sn-18= 0
PwrL_to_ON Stop
O/P
Sn-19= 0
Z_braking Invalid
Sn-20= 0
Term.3 NO_Cont.
Sn-21= 0
All Time Ext. Fault
Sn-22= 1
Ext. Fault Free run
Sn-23= 1
Cold Start Over
Load
Sn-24= 0
~ Cmd. VIN
Description
0 : invalid 1 : valid –Deceleration time1 for stall
prevention during running (no external brake unit used)
2 : valid –Deceleration time2 for stall
prevention during running (no external brake unit used)
0 : Do not output fault retry.
(The fault contact does not operate.)
1 : Output fault retry.
(The fault contact operates.)
0 : stop running 1 : continue to run
(analog) Speed reference is 0 during running on, the braking function selection 0 : invalid 1 : valid
0 : A-contact (normally open input) 1 : B-contact (normally close input)
0 : detect all time 1 : detect only during operation
0 : dec. to stop (upon dec. time1 Bn-02) 1 : coast (free run) to stop 2 : dec. to stop (upon dec. time1 Bn-04) 3 : continue operating Electronically motor overload protection selection 0 : electronically motor overload protection
invalid
1 : standard motor cold start overload
protection characteristics
2 : standard motor hot start overload
protection characteristics
3 : special motor cold start overload
protection characteristics
4 : special motor hot start overload
protection characteristics Frequency command characteristics selection at external analog input terminal 0 : voltage signal 0~10V (VIN) 1 : current signal 4~20mA (AIN) 2 : addition of voltage signal 0~10V and
current signal 4~20 mA (VIN+AIN) 3 : subtraction of current signal 4~20mA
and voltage signal 0~10V (VIN-AIN)
Factory Setting
Ref.
Page
1
0
3-49
0
0
0
0
1
3-50
1
0 3-51
3-32
Function
Multi-
function
Input
Contact
Selection
Multi-funct ion Analog
Input
Selection
Multi-
function
Digital
Output
Selection
Multi-
function
Analog
Output
Selection
Parameter
No.
Sn-25
Sn-26
Sn-27
Sn-28
Sn-29
Sn-30
Sn-31
Sn-32
Sn-33
Sn-34
Sn-35
Name
Multi-Function
Input Terminal g
Function Selection
Multi-Function
Input Terminal h
Function Selection
Multi-Function
Input Terminal i
Function Selection
Multi-Function
Input Terminal j
Function Selection
Multi-Function
Analog Input
(AUX) Function
Selection
Multi-Function
Output Terminal
(RA-RB-RC)
Function Selection
Multi-Function
Output Terminal
(DO1) Function
Selection
Multi-Function
Output Terminal
(DO2) Function
Selection
Multi-Function
Analog Output
(AO1) Function
Selection
Multi-Function
Analog Output
(AO2) Function
Selection
Pulse Output
Multiplier
Selection
LCD display
(English)
Sn-25= 02
Multi-Fun.
Command1
Sn-26= 03
Multi-Fun.
Command2
Sn-27= 06
Jog Command
Sn-28= 07
Acc. & Dec Switch
Sn-29= 00
Auxiliary Freq.
Cmd.
Sn-30= 13
Fault
Sn-31= 00
Running
Sn-32= 01
Zero Speed
Sn-33= 00
Term. AO1 Freq.
Cmd.
Sn-34= 01
Term . A O2 O/P
Freq.
Sn-35= 1
Pulse Mul. 6
Description
00~25
01~26
02~27
03~29
The factory setting is multi-function command1
The factory setting is multi-function command2
The factory setting is jog command
The factory setting is Acc. & Dec. Interrupt
Multi-function analog input
00~16
terminal (AUX) as Auxiliary frequency command. (factory setting)
Terminal (RA-RB-RC or
00~25
R1A-R1B-R1C) as fault output (factory setting)
Terminal (DO1-DOG) as digital
00~25
output during running (factory setting).
Terminal (DO2-DOG or R2A-R2C)
00~25
as digital output at zero speed (factory setting)
0 : Freq. Cmd. (10.V/MAX frequency
command, Cn-02) 1 : Output frequency (10.V/MAX. output
frequency) 2 : Output current (10.V/input rated current) 3 : Output voltage (10.V/input voltage,
Cn-01) 4 : DC voltage
(10.V/400.V or 10.V/800.V) 5 : External analog input command
VIN (0.~10.V/0.~10.V) 6 : External analog input command AIN
(0.~10.V/4.~20.mA) 7 : Multi-function analog input (AUX)
(10.V/10.V) 8 : PID control input 9 : PID control output1 10:PID control output2 11:Communication Control When multi-function output terminal (DO1,DO2) is set as pulse signal output 0:1F 1:6F 2:10F 3:12F 4:36F
Factory Setting
Ref.
Page
02
03
3-51
06
07
00
3-60
13
00
3-63
01
00
3-67
01
1 3-67
3-33
Function
RS-485
Commu-
nication
Function
Parameter
No.
Name
Sn-36 Inverter Address
Sn-37
RS-485 Comm.
Baud Rate Setting
RS-485 Comm.
Sn-38
Transmission Parity Setting
LCD display
(English)
Sn-36= 01
Inverter Address
Sn-37= 1
Baud rate 2400
Sn-38= 0
Reversed Bit
Description
Factory Setting
Inverter address can be set as 1~31 01
0 : 1200 bps 1 : 2400 bps 2 : 4800 bps
1
3 : 9600 bps
0 : no parity 1 : even parity
0
2 : odd parity
Ref.
Page
3-68
PG Speed
Control
Sn-39
Sn-40
Sn-41
Sn-42
Sn-43
RS-485 Comm.
Fault Stop
Selection
PG Speed Control
Function
Operation
Selection At PG
Open Circuit
Operation
Selection
At PG Large
Speed Deviation
Operation
Selection
At PG Overspeed
Detection Deviation
Sn-39= 0
1st. Dec. stop
Sn-40= 0
PG Invalid
Sn-41= 0
1st. Dec. Stop
Sn-42= 0
1st. Dec Stop
Sn-43= 0
1st. Dec. Stop
0 : deceleration to stop (Bn-02) 1 : coast to stop 2 : deceleration to stop (Bn-04) 3 : continue to run
0 : without speed control 1 : with speed control 2 : with speed control but no integration
control during Acc/Dec.
3 : with speed control and integration
control during Acc/Dec.
0 : deceleration to stop (Bn-02) 1 : coast to stop 2 : deceleration to stop (Bn-04) 3 : continue to run
0 : deceleration to stop (Bn-02) 1 : coast to stop 2 : deceleration to stop (Bn-04) 3 : continue to run
0 : deceleration to stop (Bn-02) 1 : coast to stop 2 : deceleration to stop (Bn-04) 3 : continue to run
0
0
0
3-69
0
0
3-34
A
Function
uto_Run
Mode
Parameter
No.
Sn-44
Sn-45
Sn-46
Sn-47
Sn-48
Sn-49
Sn-50
Name
Operation Mode
Selection During
Auto_Run
Auto_Run Mode
Operation
Selection1
Auto_Run Mode
Operation
Selection2
Auto_Run Mode
Operation
Selection3
Auto_Run Mode
Operation
Selection4
Auto_Run Mode
Operation
Selection5
Auto_Run Mode
Operation
Selection6
LCD display
(English)
Sn-44= 0
Auto_Run Invalid
Sn-45= 0
Auto_Run Stop
Sn-46= 0
Auto_Run Stop
Sn-47= 0
Auto_Run Stop
Sn-48= 0
Auto_Run Stop
Sn-49= 0
Auto_Run Stop
Sn-50= 0
Auto_Run Stop
Description
0 : Auto_Run mode not effective 1 : Auto_Run mode for one single cycle.
(continuing running from the unfinished
step if restarting) 2 : Auto_Run mode be performed
periodically (continuing running from the
unfinished step if restarting) 3 : Auto_Run mode for one single cycle,
then hold the speed of final step to run.
(continuing running from the unfinished
step if restarting) 4 : Auto_Run mode for one single cycle.
(starting a new cycle if restarting) 5 : Auto_Run mode be performed
periodically (starting a new cycle if
restarting) 6 : Auto_Run mode for one single cycle,
then hold the speed of final step to run.
(starting a new cycle if restarting)
0 : stop (Bn-02) 1 : forward 2 : reverse
Factory Setting
0
0
0
0
0
0
0
Ref.
Page
3-70
3-35
A
Function
uto_Run
Mode
*2
Sensorless
Vector
Control
Parameter
No.
Name
Auto_Run Mode
Sn-51
Operation
Selection7
Auto_Run Mode
Sn-52
Operation
Selection8
Auto_Run Mode
Sn-53
Operation
Selection9
Auto_Run Mode
Sn-54
Operation
Selection10
Auto_Run Mode
Sn-55
Operation
Selection11
Auto_Run Mode
Sn-56
Operation
Selection12
Auto_Run Mode
Sn-57
Operation
Selection13
Auto_Run Mode
Sn-58
Operation
Selection14
Auto_Run Mode
Sn-59
Operation
Selection15
Auto_Run Mode
Sn-60
Operation
Selection16
Sn-61
Sn-62
Applied Torque
Mode
Language
Selection
Sn-63 Parameter Copy
Sn-64 PID Function
*4
Sn-65
Brake Resistor
Protection
Motor Parameters
Sn-66
Sn-67
Autotuning
Selection
Control Mode
Selection
LCD display
(English)
Sn-51= 0
Auto_Run Stop
Sn-52= 0
Auto_Run Stop
Sn-53= 0
Auto_Run Stop
Sn-54= 0
Auto_Run Stop
Sn-55= 0
Auto_Run Stop
Sn-56= 0
Auto_Run Stop
Sn-57= 0
Auto_Run Stop
Sn-58= 0
Auto_Run Stop
Sn-59= 0
Auto_Run Stop
Sn-60= 0
Auto_Run Stop
Sn-61= 0
Const. Tq. Load
Sn-62= 0
Language: English
Sn-63=0
Not Load
Sn-64=0
PID Invalid
Sn-65=0
Protect Invalid
Sn-66=0
AUTO TUNE SEL
Sn-67=0
CNTRL MODE
SEL
Description
0 : stop (Bn-02) 1 : forward 2 : reverse
0 : constant torque 1 : variable(quadratic) torque 0 : English 1 : Traditional Chinese 0 : not loaded (copied) 1 : upload from digital operator to inverter 2 : download from inverter to digital
operator 3 : inspect the EEPROM of digital operator 4 : inspect the EEPROM of inverter 0 : PID invalid 1 : PID valid 0 : Braking resistor protection invalid 1 : Braking resistor protection valid
0 : Autotuning invalid 1 : Autotuning valid
0 : V/F control mode (include V/F control
with pulse generator feedback) 1 : Sensorless Vector Control Mode
Factory Setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Ref.
Page
3-70
3-72
3-73
3-73
3-36
Function
Parameter
No.
Name
Sn-68 Control selection
Operation
Control
Mode
Sn-69
Torque Detection
*3
2 Selection
Selection
LCD display
(English)
Sn-680000
Control selection
Sn-69= 0
Tq.Detect Invalid
Description
The very parameter is available for 30.15
and later version
–––1: Output phase lose protection
function valid
–––0: Output phase lose protection
function invalid
––1–: Reserved ––0–: Reserved
(Bit3 function is available for 30.16 and
later version)
–1––: ±10V analog voltage input function is
valid
–0––: ±10V analog voltage input function is
invalid
1–––: Frequency Up/Down hold function
valid
0–––: Frequency Up/Down hold function
invalid
* only 4P101C01301 control base board
supports input of ±10V analog voltage.
0 : Torque detection function 2 is not
effective. 1 : Overtorque is detected only at
frequency agree. Continue operation
after detection. 2 : Overtorque is detected only at
frequency agree. Stop operation after
detection. 3 : Overtorque is detected during running
(Accel.,Decel. included). Continue
operation after detection. 4 : Overtorque is detected during running
(Accel., Decel included). Stop operation
after detection. 5 : Undertorque is detected only at
frequency agree. Continue operation
after detection. 6 : Undertorque is detected only at
frequency agree. Stop operation after
detection. 7 : Undertorque is detected during running
(Accel.,Decel. included). Continue
operation after detection. 8 : Overtorque is detected during running
(Accel., Decel included). Stop operation
after detection.
Factory Setting
Ref.
Page
0 3-73
0 3-47
3-37
Function
Parameter
No.
*3
Sn-70
Name
Engineering Unit
LCD display
(English)
Sn-70= 0
Unit : NONE
Description
0 : NONE 1 : FPM (feet per minute) 2 : CFM (cubic feet per minute) 3 : PSI (pounds per square inch) 4 : GPH (gallons per hour) 5 : GPM (gallons per minute) 6 : in 7 : ft 8 : /s (units per second) 9 : /m (units per minute) 10 : /h (units per hour) 11 : °F 12 : inW (inches in water column) 13 : HP 14 : m/s (meters per second) 15 : MPM (meters per minute) 16 : CMM (cubic meters per minute) 17 : W 18 : kW 19 : m 20 : °C
Factory Setting
Ref.
Page
0 3-74
*1. The default setting will depend upon the different inverter capacity.
*2. Sensorless vector control is available after the version of 30.00.
*3. These parameters are available for 74.03 and later software version only.
*4. This parameter is not available after the version of 30.21.
3-38
(3) Inverter capacity selection (Sn-01)
The inverter capacity has already been set at factory according to the following
tables. Whenever the control board is replaced, the setting Sn-01 must be set again according to the following tables.
Whenever the setting Sn-01 has been changed, the inverter system parameter
settings should be changed based upon the constant torque (CT) load (setting of Sn-61= 0) or variable torque (VT) load (Sn-61= 1).
Table 10 230V Class Inverter Capacity Selection
Sn-01 setting 001 002 003 004 005 006
CT(Sn-610) VT(Sn-611)
Item name Inverter rated capacity (KVA)
Inverter rated current (A) 4.8 6.4 9.6 17.5 24 32 Max. applicable capacity (HP) 1 1 2 2 3 3 5.4 7.5 7.5 10 10 10
Motor rated
Cn-09
current (A) Motor line
Cn-12
impedance (Ω) Core loss torque
Cn-13
compensation (W)
Cn-34 Carrier freq.(kHz) 10 10 10 5 10 10 10 5 10 10 10 10
Factory Setting
Cn-37
Min. baseblock time (sec)
Sn-02 V/F curve 01 07*1 01 07*1 01 07*1 01 07*1 01 07*1 01 07*1
Max. carrier freq. (kHz) 15 10 15 5 15 15 15 5 15 10 15 15
Sn-01 setting 007 008 009 010 011
CT(Sn-610) VT(Sn-611)
Item name Inverter rated capacity (KVA)
Inverter rated current (A) 48 64 80 96 130
CT VT CT VT CT VT CT VT CT VT CT VT
2 2.7 4 7.5 10.1 13.7
3.4 3.4 6.1 6.1 8.7 8.7 14.6 20.1 20.1 25.1 25.1 25.1
5.732 5.732 2.407 2.407 1.583 1.583 0.684 0.444 0.444 0.288 0.288 0.288
64 64 108 108 142 142 208 252 252 285 285 285
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.7 0.7 0.7 0.7 0.7
CT VT CT VT CT VT CT VT CT VT
20.6 27.4 34 41 54
Max. applicable capacity (HP) 15 20 20 25 25 25 30 40 40 40
Motor rated
Cn-09
current (A) Motor line
Cn-12
impedance (Ω) Core loss torque
Cn-13
compensation (W)
Cn-34 Carrier freq.(kHz) 10 5 10 5 10 10 10 5 10 10
Factory Setting
Cn-37
Sn-02
Min. baseblock time (sec)
V/F curve
36.7 50.3 50.3 62.9 62.9 62.9 72.9 96.7 96.7 96.7
0.159 0.109 0.109 0.077 0.077 0.077 0.060 0.041 0.041 0.041
370 471 471 425 425 425 582 536 536 536
0.7 0.7 0.7 0.7 1.0 1.0 1.0 1.0 1.0 1.0
01 07*1 01 07*1 01 07*1 01 07*1 01 07*1
Max. carrier freq. (kHz) 10 5 10 5 10 10 10 5 10 10
3-39
Table 11 460V Class Inverter Capacity Selection
Sn-01 setting 021 022 023 024 025 026 027
CT(Sn-610) VT(Sn-611)
Item name
Inverter rated capacity (KVA)
Inverter rated current (A)
Max. applicable capacity (HP)
Motor rated current
Cn-09
(A) Motor line
Cn-12
impedance (Ω) Core loss torque
Cn-13
compensation (W)
Carrier freq. (kHz)
Cn-34
Factory Setting
Min. baseblock time
Cn-37
(sec)
V/F curve
Sn-02
Max. carrier freq. (kHz) 15 5 15 5 15 15 15 5 15 10 15 5 10 5
Sn-01 setting 028 029 030 031 032 033 034
CT(Sn-610) VT(Sn-611)
Item name
Inverter rated capacity (KVA)
Inverter rated current (A)
Max. applicable capacity (HP)
Motor rated current
Cn-09
(A) Motor line
Cn-12
impedance (Ω) Core loss torque
Cn-13
compensation (W)
Carrier freq. (kHz)
Cn-34
Factory Setting
Min. baseblock time
Cn-37
(sec)
V/F curve
Sn-02
CT VT CT VT CT VT CT VT CT VT CT VT CT VT
2.2 3.4 4.1 7.5 10.3 12.3 20.6
2.6 4 4.8 8.7 12 15 24
1 1 2 2 3 3 5.4 7.5 7.5 10 10 15 15 20
1.7 1.7 2.9 2.9 4 4 7.3 10.2 10.2 12.6 12.6 18.6 18.6 24.8
22.927 22.927 9.628 9.628 6.333 6.333 2.735 1.776 1.776 1.151 1.151 0.634 0.634 0.436
64 64 108 108 142 142 208 252 252 285 285 370 370 471
10 5 10 5 10 10 10 5 10 10 10 5 10 5
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.7 0.7 0.7 0.7 0.7 0.7 0.7
01 07*1 01 07*1 01 07*1 01 07*1 01 07*1 01 07*1 01 07*1
CT VT CT VT CT VT CT VT CT VT CT VT CT VT
27.4 34 41 54 68 82 110 32 40 48 64 80 96 128
20 25 25 30 30 30 40 50 50 50 60 75 75 100
24.8 31.1 31.1 36.3 36.3 36.3 48.7 59.0 59.0 59.0 70.5 80.0 80.0 114
0.436 0.308 0.308 0.239 0.239 0.239 0.164 0.133 0.133 0.133 0.110 0.074 0.074 0.027
471 425 425 582 582 582 536 641 641 641 737 790 790 1800
10 5 10 5 10 10 10 5 10 10 10 5 10 5
0.7 0.7 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
01 07*1 01 07*1 01 07*1 01 07*1 01 07*1 01 07*1 01 07*1
Max. carrier freq. (kHz) 10 5 10 5 10 10 10 5 10 10 10 5 10 5
*1 Use the variable torque patterns when there is a quadratic or cubic relationship between the speed
and load, such as in fan or pump applications. The user can properly choose the desired (V/f) patterns (Sn-02=04, 05, 06, or 07) based upon the load torque characteristics.
*2 In the fan or pump applications, the load torque have a quadratic or cubic relationship between
the speed and load. The inverter capacity rating can be increased to a value that doubles its own specified capacity rating in some special case. But, due to the real hardware limitation, 230V 1HP, 2HP, 3HP, 10HP, 25HP, 40HP and 460V 1HP, 2HP, 3HP, 30HP, 50HP can not be adapted any larger capacity.
(4) V/F curve selection (Sn-02)
Set the inverter input voltage (Cn-01) first to match the power supply voltage. The
V/f curve can be set to ant of the following.
Sn-02 = 00~14: one of 15 pre-set curve patterns = 15: V/F pattern can be set by the user through setting of Cn-01~Cn-08
3-40
Table 12 V/F curve of 1~2 HP compact size, 230V Class MA inverter *
Specifications Sn-02 V/F Pattern
(V)
230
(00)
50Hz 00
15.5
8.2
1.3 2.5
0
60Hz Satu-
ration
01 15
230
(V)
(02)
60Hz
50Hz Satu-
General Purpose
ration
02
15.5
8.2 0
230
(01),(15)
1.5 3 (V)
(03)
Specifications Sn-02 V/F Pattern
Low
Starting
50Hz
Torque
High
Starting
(Hz)
50
Torque
Low
Starting
08
09
10
230
16.7
16.1
8.5
8.3 0
230
Torque
60Hz
High Staring Torque
High
Starting
(Hz)
60
50
Torque
11
16.7
16.1
8.5
8.3 0
230
(V)
(09)
1.3 2.5
(V)
(11)
1.5 3 (V)
(12)
(08)
(10)
(Hz)
50
(Hz)
60
72Hz 03
Va r ia b l e
Torque 1
50Hz
Va r ia b l e
Torque 2
Va r ia b l e
Torque 3
60Hz
Va r ia b l e
Variable Torque Characteristic
Torque 4
15.5
8.2
1.5
3
0
(V)
230
04
05
06
07
57.5
40.2
8.2
7.4 0
230
57.5
40.2
8.2
7.4 0
1.3 (V)
1.5
(05)
25
(07)
30
60
(04)
(06)
(Hz)
72
(Hz)
50
Rated Output Operation (Machine Tool)
(Hz)
60
90Hz 12
15.5
8.2 0
230
120Hz 13
15.5
8.2 0
230
180Hz 14
15.5
8.2 0
1.5 (V)
1.5 (V)
1.5
3
(13)
3
(14)
3
60
60
60
* These values are for the 230V class; double the values for 460V class inverters.
Consider the following items as the conditions for selecting a V/f pattern.
They must be suitable for
(1) The voltage and frequency characteristic of motor. (2) The maximum speed of motor.
Select high starting torque only in the following conditions.
(1) The power cable length is long [492ft (150m) and above]. (2) Voltage drop at startup is large. (3) AC reactor is inserted at the input side or output side of the inverter. (4) A motor with capacity smaller than the maximum applicable inverter capacity
is used.
90
120
180
(Hz)
(Hz)
(Hz)
3-41
Table 13 V/F curve of 3~40 HP, 230V Class MA inverter *
Specifications
50Hz 00
60Hz Satu-
60Hz
General Purpose
ration
50Hz Satu-
ration
Sn-02
01 15
02
V/F Pattern
(V)
220
(00)
14
7.5
1.3 2.5
0
(V)
220
(02)
14
7.5
1.5 3
0
(V)
220
(03)
(01),(15)
Specifications
Low
Starting
Torque
50Hz
High
(Hz)
50
60Hz
High Staring Torque
(Hz)
60
50
Starting
Torque
Low
Starting
Torque
High
Starting
Torque
Sn-02
08
09
10
11
V/F Pattern
(V)
220
(09)
15.2
14.6
7.7
7.6
1.3 2.5
0
(V)
220
(11)
15.2
14.6
7.7
7.6
1.5 3
0
(V)
220
(08)
(10)
(Hz)
50
(Hz)
60
(12)
Variable Torque Characteristic
72Hz 03
Va r ia b l e
Torque 1
50Hz
Va r ia b l e
Torque 2
Va r ia b l e
Torque 3
60Hz
Va r ia b l e
Torque 4
04
05
06
07
14
7.5
220
55
38.5
7.5
6.8
220
55
38.5
7.5
6.8
1.5
3
0
(V)
(Hz)
72
60
(05)
(04)
1.3
0
25
(V)
(Hz)
50
(07)
(06)
1.5
0
30
(Hz)
60
Rated Output Operation (Machine Tool)
90Hz 12
14
7.5
0
220
120Hz 13
14
7.5
0
220
180Hz 14
14
7.5
0
1.5
3
(V)
(Hz)
90
60
(13)
1.5
3
(V)
(Hz)
120
60
(14)
1.5
3
(Hz)
180
60
* These values are for the 230V class; double the values for 460V class 3~75HP
inverters. † Consider the following items as the conditions for selecting a V/f pattern. They must be suitable for
(1) The voltage and frequency characteristic of motor. (2) The maximum speed of motor.
‡ Select high starting torque only in the following conditions. Normally, the selection
if not required.
(1) The power cable length is long [492ft (150m) and above]. (2) Voltage drop at startup is large. (3) AC reactor is inserted at the input side or output side of the inverter. (4) A motor with capacity smaller than the maximum applicable inverter capacity
is used.
3-42
(5) Operator Display (Sn-03)
Parameter code (Sn-03= 0 or 1)
Set the parameter Sn-03 as 0 or 1 to determine the access status as follows.
Sn-03
0 An, Bn Sn, Cn An, Bn, Sn, Cn 1 An Bn, Sn, Cn An Bn, Sn, Cn
DRIVE mode PRGM mode
Set Read Only Set Read Only
Initialized setting of parameter (Sn-03= 7~12)
Except the parameter of Sn-01~02 and Sn-61, the parameter groups of An-□□, Bn-□□, Cn-□□ and Sn-□□ can be initialized as factory setting according to the different input voltage. At the same time, the terminal gj can be set as 2-wire or 3-wire operation mode under different setting of Sn-03. Please see
2-/3-wire operation mode on page 3-53.
(6) Run Source Selection (Sn-04)
The parameter is used to select the source of run command.
Sn-04 = 0 : digital operator = 1 : control circuit terminal = 2 : RS-485 communication
If Sn-04 is set as 1, the run source is from the control circuit terminal. Under the
initial setting of 2-wire operation (through setting of Sn-03=7 or 9 or 11), the run source will be FWD/STOP, REV/STOP.
If Sn-04 is set as 1, the run source is from the control circuit terminal. Under the
initial setting of 3-wire operation (through setting of Sn-03=8 or 10 or 12), the run source will be RUN, STOP, FWD/ REV.
For more details, see “2-/3- wire operation” on page 3-53.
(7) Frequency Command Setting Method Selection (Sn-05)
The parameter is used to select the source of frequency command.
Sn-05 = 0 : digital operator = 1 : control circuit terminal = 2 : RS-485 communication
(8) Stopping Method Selection (Sn-06)
Setting the stopping method used when a stop command is executed.
Setting Function
0 Deceleration to stop
1 Coast to stop
2 DC braking stop: Stops faster than coast to stop, without regenerative operation.
3 Coast to stop with timer: Run sources are disregarded during decel. time.
3-43
The following diagrams show the operation of each stopping method.
a) Deceleration to Stop (Sn-06= 0)
Deceleration to a stop at a rate set with the selected deceleration time.
b) Coast to Stop (Sn-06= 1)
After the stop command is executed, run source is disregarded until the Min. baseblock time Cn-37 has elapsed.
Run
command
Output
frequency
DC injection
beginning frequency
(Cn-14)
ON
OFF
Dec time
braking time
DC injection
Run
command
Output
frequency
The inverter output is shut off when the stop
ON
OFF
command is input
Fig. 29. Deceleration to stop Fig. 30. Coast to Stop
c) Whole Range DC Injection Braking Stop (Sn-06= 2)
DC injection
Run
Comm.
O/P Freq.
ON
OFF
DEC time
braking time
Cn-16 * 10
DC injection braking
time at Run Source off
(Cn-16)
Min. baseblock time
(Cn-37)
DC injection
braking time
10 %
O/P freq. when the stop command is input
100 %
Fig. 31. Whole range DC Injecting Braking Stop
After the stop command is input and the minimum baseblock time (Cn-37) has
elapsed, DC injection braking is applied and the motor stopped.
The DC injection braking time depends upon the output frequency when the stop
command is input and the “DC injection time at stop” setting (Cn-16) as shown in Fig. 31.
Lengthen the minimum baseblock time (Cn-37) when an overcurrent (OC) occurs
during stopping. When the power to an induction motor is turned OFF, the counter-electromotive force generated by the residual magnetic field in the motor can cause an overcurrent to be detected when DC injection braking stop is applied.
3-44
d) Coast to Stop with Timer (Sn-06= 3)
Deceleration time
Run Source
Output
frequency
Input Stop Command.,
inverter stop Output
ON ON ONOFF OFF
T1
(T1 time)
(Bn-02 or
Bn-04)
100 % (Max frequency)
Output frequency at Run Source off
Fig. 32. Coast to Stop with Timer
After the stop command is executed, run sources are disregarded until the time T1
has elapsed. The time T1 depends upon the output frequency when the stop command is executed and upon the deceleration time (Bn-02 or Bn-04).
(9) Priority of Stopping (Sn-07)
This parameter enable or disable the STOP key on the digital operator when the
run source is from an control circuit terminal or RS-485 communicate port while the motor is running.
Sn-07 = 0 : enabled. (The STOP key is enabled at all time during running) = 1 : disabled (The STOP key is disabled when the run source is from
control terminal or RS-485 port)
(10) Prohibition of REV Run (Sn-08)
While the parameter Sn-08 is set as 1. The reverse run of motor is not allowed
(11) Output Frequency UP/DOWN Function (Sn-09)
The output frequency can be increased or decreased (UP/DOWN) through digital
operator
Sn-09 = 0 : Change output frequency through the (
frequency command will be accepted only after the key
/ ) key. The
EDIT
ENTER
has
been pressed.
= 1 : Change output frequency through the (
/ ) key. The
frequency command can be recalled even restarting the inverter if the
EDIT
ENTER
key has been pressed at that time.
The output frequency can be changed (increasing (UP) or decreasing (DOWN))
through either the LCD digital operator or external multi-function input terminal (terminals gj).
3-45
(12) Frequency Command Characteristics Selection (Sn-10)
30.16 previous or later version set Sn-68=–0–– The positive and negative characteristics of analog frequency command (010V/ 420mA) is as follow diagram:
+10V (20mA)
0V (4mA)
0%
100%
+10V (20mA)
0V (4mA)
0%
100%
Positive input characteristics Negative input characteristics
30.17 previous or later version set Sn-68=–1––:
The positive and negative characteristics of analog current input is similar to above description, while of analog voltage input is as follow diagram:
+10V
100% 0V
0%
-10V
-100%
+10V
0V
0%
-10V
100%
-100%
Positive input characteristics Negative input characteristics
Among Sn-68 set, ‘–’ represents 0 or 1. Only 4P101C01301 control board supports input of -10V~+10V analog voltage.
(13) Scan Time at Input Terminal (Sn-11)
Setting of scan frequency of input terminal (Forward/Reverse, multi-function
input)
Sn-11 = 0 : Scan input terminals every 5ms. = 1 : Scan input terminals every 10ms.
3-46
(14) Torque Detection 1 Selection (Sn-12) (15) Torque Detection 2 Selection (Sn-69)
The parameter Sn-69 and settings 5-8 of Sn-12 are available for 74.03 and later
software versions.
The inverter supports 2 sets of torque detection function. Each of them can set as
overtorque detection or undertorque detection.
While Torque Detection 1 is enabled by Sn-12, be sure to set the values of the
Torque Detection Level1 1 (Cn-32) and Torque Detection Time 1 (Cn-33). While Torque Detection 2 is enabled by Sn-69, be sure to set the values of the Torque Detection Level1 2 (Cn-62) and Torque Detection Time 2 (Cn-63).
An overtorque condition is detected when the Overtorque Detection is enabled,
and the current exceeds the Torque Detection Level for longer than the Torque Detection Time.
An undertorque condition is detected when the Undertorque Detection is enabled,
and the current is lower than the Torque Detection Level for longer than the Torque Detection Time.
Sn-12, Sn-69
0 1
2 3 4 5 6 7 8
Torque detection disabled Detect overtorque only during speed agree.
Continue operation after detection. (Minor fault) Detect overtorque only during speed agree. Stop output after detection (Fault) Detect overtorque at any time. Continue operation after detection. (Minor fault) Detect overtorque at any time. Stop output after detection (Fault) Detect undertorque only during speed agree. Continue operation after detection. (Minor fault) Detect undertorque only during speed agree. Stop output after detection (Fault) Detect undertorque at any time. Continue operation after detection. (Minor fault) Detect undertorque at any time. Stop output af ter detection (Fault)
Function Display
“Over Torque 1” or “Over Torque 2” blinks “Over Torque 1” or “Over Torque 2” lights “Over Torque 1” or “Over Torque 2” blinks “Over Torque 1” or “Over Torque 2” lights “Under Torque 1” or “Under Torque 2” blinks “Under Torque 1” or “Under Torque 2” lights “Under Torque 1” or “Under Torque 2” blinks “Under Torque 1” or “Under Torque 2” lights
(16) Output Voltage Limitation Selection (Sn-13)
In low speed region, if the output voltage from V/f pattern is too high, the inverter
will be driven into fault status. As a result, the user can use this option to set the upper bound limit of output voltage.
3-47
Output
t
Voltage
250V
40V
5V
0
Cn-04
40
Cn-04
(Output frequency at Max. output voltage)
Output Voltage Bound
(double the value for 440V class)
Output Frequency
Fig. 33. Output voltage limit
(17) Stall Prevention Selection During Acceleration (Sn-14)
Sn-14 = 0 : Disabled (Accelerate according to the setting. Stall may occurs with
large load)
= 1 : Enabled (Stop acceleration if Cn-25 setting is exceeded. Accelerate
again when current recovers)
Please refer to “Stall prevention level during acceleration” on page 3-20.
(18) Stall Prevention Selection During Deceleration (Sn-15)
If external braking resistor unit is installed, the Sn-15 setting must be disabled
(Sn-15= 0).
If no external braking resistor unit is installed, the inverter can provide about 20%
regenerative braking torque. If the load inertia is so large that it exceeds the regenerative braking torque, the parameter Sn-15 is set as “1”. When setting Sn-15= 1 (enabled) is selected, the deceleration time (Bn-02 or Bn-04) is extended so that a main circuit overvoltage does not occur.
Outpu
Frequency
Deceleration time is extended
to avoid overvoltage trip
time
Deceleration Time (setting value)
Fig. 34. Stall prevention function during deceleration (Sn-15= 1)
3-48
(19) Stall Prevention Selection during Running (Sn-16)
Sn-16 = 0 : Disabled (Stall may occur when a large load is applied) = 1 : Enabled (Deceleration will start if the motor current is larger than the
stall prevention level during running and continues for more than 100ms. The motor is accelerated back to the reference frequency again when the current falls below this level Cn-26).
Please refer to “Stall prevention level during running” on page 3-20.
(20) Operation Selection at Fault Contact during Fault Retrying (Sn-17)
Sn-17 = 0 : Do not output fault restart. (The fault contact does not work) = 1 : Output fault restart. (The fault contact operates)
Please refer to “Number of auto restart attempt” on page 3-19.
(21) Operation Selection at Power Loss (Sn-18)
This parameter specifies the processing to be performed when a momentary power
loss occurs (within 2 sec)
Sn-18 = 0 : When power loss ride through is enabled, operation will be restarted
after a speed search envoked if the power is restored within the allowed time.
= 1 : When power loss ride-through is disabled the inverter will stop after a
momentary power loss. An undervoltage fault will be detected then. If the power is interrupted for more than 2 seconds, the fault contact output will operate and the motor will coast to stop.
(22) Zero Speed Braking Selection (Sn-19)
The run-source and frequency command is input from control circuit under the
setting of Sn-04=1 & Sn-05=1, If Sn-19 is enabled, the blocking torque will be generated in DC-braking mode when the frequency command is 0V and forward –run source is “ON”.
A time-chart shows the above action as below. The zero-braking selection Sn-19 is
set to 1 and the DC-braking current Cn-15 is limited within 20% of rated current.
Run¡þStop signal
(external terminal)
Frequency command
(external terminal)
DC injection
braking (20% Max.)
OFF OFFON
t
t
t
Fig. 35. Zero speed braking operation selection
3-49
(23) External Fault Contact e Contact Selection (Sn-20)
Sn-20 = 0 : Input signal is from A-contact. (Normal-open contact) = 1 : Input signal is from B-contact. (Normal-close contact)
(24) External Fault Contact e Detection Selection (Sn-21)
Sn-21 = 0 : Always detects. = 1 : Detect only during running.
(25) Detection Mode Selection of External Fault (Sn-22)
An external fault is detected (at terminal e), the following operation will be
performed based upon the setting of Sn-22
Sn-22 = 0 : Decelerate to stop with the specified deceleration time Bn-02. = 1 : Coast to stop. = 2 : Decelerate to stop with the specified deceleration time Bn-04. = 3 : Continue running with no regard of external fault.
(26) Motor Overload Protection Selection (Sn-23)
Sn-23 = 0 : Electronic overload protection disable. Sn-23 = 1~4 : Electronic overload protection enabled. The electronic thermal
overload is detected according to the characteristic curves of protection operating time. vs. motor rated current setting (Cn-09).
Sn-23 = 1 : The overload is detected according to the standard motor cold start
curve. = 2 : The overload is detected according to the standard motor hot start curve. = 3 : The overload is detected according to the specific motor cold start curve. = 4 : The overload is detected according to the specific motor hot start curve.
Disable the motor protection function (setting 0) when 2 or more motors are
connected to a single inverter. Use another method to provide overload protection separately to each motor, such as connecting a thermal overload relay to the power line of each motor.
The motor overload protection function should be set as Sn-23= 2 or 4 (hot start
protection characteristic curve) when the power supply is turned on or off frequently, because the thermal values is reset each time when the power is turned off.
For the motor without forced cooling fan, the heat dissipation capability is lower
when in the low speed operation. The setting Sn-23 can be either ‘1’ or ‘2’.
For the motor with forced cooling fan, the heat dissipation capability is not
dependent upon the rotating speed. The setting Sn-23 can be either ‘3’ or ‘4’.
To protect the motor from overload by use of electronic overload protection, be
sure to set the parameter Cn-09 according to the rated current value shown on the motor nameplate.
3-50
Overload Protect Time (min)
5.5
3.5
Low Speed
(<60 Hz)
High Speed
(>60 Hz)
Cold Start
Hot Start
100% 150% 200%
Motor Load Current (%)
(Cn-09 = 100%)
Fig. 36. Motor overload protection curve (Cn-09 setting = 100%)
(27) Frequency Characteristics Command Selection at External Analog Input Terminal
(Sn-24)
Sn-24 = 0 : Frequency command is input at VIN terminal (0~10V) = 1 : Frequency command is input at AIN terminal (4~20mA) = 2 : Frequency command is the addition (VIN + AIN) at VIN (0~10V) and
AIN (4~20mA) terminal. = 3 : Frequency command is the combination (VIN - AIN) at VIN (0~10V)
and AIN (4~20mA) terminal. If the value (VIN - AIN) is negative, the
reference command will take ‘0’ as a result.
On inverter with 4P101C01301control board, if Sn-68=–1––and Sn-05=1 VIN
allowing input ±10V, set Sn-24 to select main frequency:
Sn-24 = 0 : frequency command is controlled by VIN(-10~+10V) input. (Corresponding main frequency: -10V ~ +10V Reverse frequency
100% ~ forward frequency100%) = 1 : frequency command in controlled by AIN(4~20mA) input. (the status of forward/ reverse is set by user) = 2 : frequency command is controlled by VIN and AIN, the sum of both
(VIN + AIN). = 3 : frequency command is controlled by VIN and AIN, the balance of
both (VIN - AIN). (When (VIN + AIN) < 0 or (VIN - AIN) < 0, main frequency switched
to reverse status. Sn-24 = 0、2、3, forward or reverse is control by main frequency command polar.
(28) Multi-Function Input Terminal g Function Selection (Sn-25) (29) Multi-Function Input Terminal h Function Selection (Sn-26) (30) Multi-Function Input Terminal i Function Selection (Sn-27) (31) Multi-Function Input Terminal j Function Selection (Sn-28)
The settings and functions for the multi-function input are listed in Table 14.
3-51
Table 14 Multi-Function Input Setting
Setting Function LCD Display Description
00 Forward/Reverse command 3_Wire Run 3-wire operation mode
2-wire key-pressing input
01
stop command 02 Multi-speed command 1 Multi-Fun. Command 1 03 Multi-speed command 2 Multi-Fun. Command 2 04 Multi-speed command 3 Multi-Fun. Command 3 05 Multi-speed command 4 Multi-Fun. Command 4 06 Jogging Jog Command ON: select jogging frequency
Acc/Dec time switch 07
command
External base-block 08
command A-contact)
External base-block 09
command (B-contact) 10 Inhibit Acc/Dec command Inhibit Acc&Dec Inhibit Acc/Dec (hold frequency) 11 Inverter overheat warning Over Heat Alarm ON: blink show overheat (inverter can proceed running) 12 FJOG Forward Jog ON: forward jog 13 RJOG Reverse Jog ON: reverse jog 14 PID integration reset I_Time Reset ON: Reset PID integration 15 PID control invalid PID Invalid ON: PID control not effective 16 External fault (A-contact) Ext.Fault NO_Cont ON: External fault input (normally open) 17 External fault (B-contact) Ext.Fault NC_Cont OFF: External fault input (normally close) 18 Multi-function analog input ~ Input Valid ON: multi-function analog input (AUX) effective 19 Timer function input Timer Function ON: ON-delay/OFF-delay timer input
20 DC braking command DC Brakin Command
21 Speed search 1 command Max Freq. Sp_Search ON: speed search is performed from max. output frequency 22 Speed search 2 command Set Freq. Sp_Search ON: speed search is performed from reference frequency
23 Local/Remote control I Operator Control
24 Local/Remote control II
RS-485 communication 25
application 26 speed control without PG PG Invalid ON: Speed control without PG
Reset integration of speed 27
control with PG
Frequency Up/Down 28
function 29 Force operation signal Force Run Only Sn-28 can be set as Sn-28=29
2_Wire Stop Key 2-wire operation mode
Multi-speed frequency command selection
Acc.&Dec. Switch
Ext.B.B. NO_Cont ON: inverter output baseblock
Ext.B.B. NC_Cont OFF: inverter output baseblock
Ext. Term. Control
Comm. Control
I_Time Invalid ON: Reset integration of speed control with PG
UP/DOWN Function
OFF: the first stage Acc/Dec time (Bn-01, Bn-02), ON: the second stage Acc/Dec time (Bn-03, Bn-04),
ON: DC injection braking applied when the frequency
output is less than the DC injection start frequency
ON: local mode control (through LCD operator) OFF: Run Source and Frequency Command is determined
according to (Sn-04, Sn-05) setting ON: local mode control (through control circuit terminal) OFF: Run Source and Frequency Command is determined
according to (Sn-04, Sn-05) setting PLC application extension use. (Please refer to
“RS-485 MODBUS/PROFIBUS Application Manual”)
Only Sn-28 can be set as Sn-28=28, terminal i used as up cmd. and terminal j used as down cmd. when Sn-28=28
Note: An error message of “Multi-Fun. Parameter” / “Setting Error” will be displayed
if:
Setting combination of (Sn-25~Sn28) is not organized in monotonically
increasing order.
Setting 21, 22 (both for speed search command) are set at the same time.
3-52
Forward/Reverse Change (setting : 00)
Under 3-wire initialization mode (Sn-03= 8 or 10 or 12),the multi-function
input terminals g~j have setting “00”, the inverter will be in the 3-wire mode operation. As shown in Fig. 37, the Forward/Reverse change mode is set at the terminal g.
Stop
(B contact)
Run
(A contact)
SC
Run Command
(ON : run)
1
Stop Command
(OFF : stop)
2
FWD/REV Cmd.
(multi-func.
5
input terminal)
Fig. 37. 3-wire mode connection
RUN cmd.
STOP cmd.
FWD/REV
cmd.
Motor
Speed
STOP FWD REV
Fig. 38. Operation sequence in 3-wire mode
> 50 ms
OFF (FWD)
ON or OFF
OFF
(stop)
ON (REV)
FWDSTOP
diagram
Input STOP Command during 2-Wire Mode Operation (setting : 01)
Under a standard 2-wire initialization mode as shown in Fig. 39(a), S1 and S2
can not be both “ON” at the same time.
When S1= “ON” and S2= “OFF”, the motor is FWD running. When S1=”OFF” and S2= “ON”, the motor is REV running. When S1= “OFF” and S2= “OFF”, the motor stops running.
When Sn-25= ‘01’, the 2-wire operation mode has its self-sustaining function.
Only through the multi-function input terminalg, the operator can stop the inverter after pressing the “STOP” key as shown in Fig. 39(b). As shown in Fig. 39(b), the switches S1, S2 and S3 do not need to be the self-sustaining switches. When S1 is depressed “ON”, the motor will be forward running. After S3 is depressed “ON”, the motor will stop. When S2 is depressed “ON”, the motor will be reverse running. After S3 is depressed “ON”, the motor will stop.
OFF
ON
OFF
ON
1
FWD_RUN/STOP
2
REV_RUN/STOP
SC
(a)
S1
S2
S3
1
2
5
SC
FWD_RUN
RWD_RUN
STOP
(b)
S1
S2
Fig. 39. 2-wire mode connection diagram
Note
: 1. For the other setting value (except “00”, “01”), the external operation mode is
defaulted as 2-wire mode and no self-sustaining function. (that is, the inverter will stop when contact
and d are not close.)
c
3-53
2. Under the 2-wire mode, the error message “Freq. Comm. Error” will be displayed in the digital operator when terminal
and d are both ON at the
c
same time, the inverter will stop. After the above case cleared, the inverter will return normal.
Multi-Step Speed Command 1 (Setting : 02) Multi-Step Speed Command 2 (Setting : 03) Multi-Step Speed Command 3 (Setting : 04) Multi-Step Speed Command 4 (Setting : 05) Jog Frequency Selection (Setting : 06) There are 16 (maximum) step speed command selection from the combination of
the Multi-Step Speed Command and jog frequency command.
Multi-Step Speed command 1~4 and Jog Frequency Selection Setting Table.
Terminal j (Sn-28= 05)
Multi-step speed
cmd. 4
0 0 0 0 Freq. Cmd. 1 (An-01)*1 0 0 0 1 Freq. Cmd. 2 (An-02)*2 0 0 1 0 Freq. Cmd. 3 (An-03) 0 0 1 1 Freq. Cmd. 4 (An-04) 0 1 0 0 Freq. Cmd. 5 (An-05) 0 1 0 1 Freq. Cmd. 6 (An-06) 0 1 1 0 Freq. Cmd. 7 (An-07) 0 1 1 1 Freq. Cmd. 8 (An-08) 1 1 1 1 Freq. Cmd. 16 (An-16)
Note: “0” : terminal is “OFF” “1” : terminal is “ON”
Terminal i
(Sn-27= 04)
Multi-step speed
cmd. 3
Terminalh
(Sn-26= 03)
Multi-step speed
cmd. 2
Terminal g (Sn-25= 02)
Multi-step speed
cmd. 1
Selected frequency
An example shows the operation sequence of a multi-step speed and jog command
is as below.
Freq.
Command
Terminal
FWD-REV
Multi-speed
Multi-speed Multi-speed
JOG
Freq.
Cmd.8
(An-08)
Freq.
Cmd.16
(An-16)
OFF
ON
ON
1
5
6
7
8
*1 Ref. Freq. (An-01)
OFF
*2 Aux. Freq. (An-02)
ON
OFF
OFF
Freq.
Cmd.3
(An-03)
ON
Freq.
Cmd.4
(An-04)
Freq.
Cmd.5
(An-05)
ON
Freq.
Cmd.6
(An-06)
OFF
Freq.
Cmd.7
(An-07)
Fig. 40. Time chart for multi-step speed and jog command
3-54
time
*1 When the parameter Sn-05= 0, the reference command is input by the setting of An-01.
Instead, when the parameter Sn-05= 1, the reference command is input from analog command through the terminal VIN and AIN.
*2 If the parameter Sn-29= 0, the auxiliary frequency (the 2nd step frequency setting: AUX
frequency) is input from the AUX terminal. If the parameter Sn-29 0, the 2nd step frequency setting is determined by the parameter of An-02.
Acceleration Time And Deceleration Time Change (Setting : 07)
The acceleration time and deceleration time can be changed through the control
circuit terminal g~j as described on page 3-4.
External Baseblock (A Contact) (Setting : 08)
External Baseblock (B Contact) (Setting : 09)
With either of these settings, the multi-function input terminal controls its
inverter baseblock operation.
During running: As an external baseblock signal is detected, the digital operator
will display a “B.B. Alarm”. Then, the inverter output is blocked. After the baseblock signal is cleared, the motor will resume running according to its then reference signal.
During deceleration : An external baseblock signal is input, the digital operator
will display “ B.B. Alarm”, the inverter is blocked from output and the output frequency will drop to zero. The motor will then coast to stop freely. After this external baseblock signal is cleared, the inverter will stay in stop mode.
Acceleration and Deceleration Ramp Hold (Setting : 10)
With this setting, the signal of Acceleration/deceleration ramp hold (input from
the multi-function input terminals) will pause the Acceleration/deceleration of motor and maintain the then output frequency. The motor will coast to stop if an OFF command is input while the acceleration / deceleration ramp hold input is ON, the then output frequency will be memorized and the command of Acceleration/deceleration ramp hold is released.
FWD/
REV
ACC/DEC
prohibitation
frequency command
output
frqquency
OFF ON
ON ON
HOLD HOLD
OFFOFF
OFF
ON
Fig. 41. Acceleration and deceleration ramp hold
3-55
Inverter Overheat Alarm (Setting : 11)
When the inverter detects a overheat signal “ON”, the digital operator will
change its display as “Overheat Alarm”. And the inverter still maintains its operation. When the overheat signal is “OFF”, the digital operator will restore its previous display automatically. No RESET-key pressing is required.
FJOG Command (Setting : 12)
RJOG Command (Setting : 13)
The jogging can be performed in forward or reverse rotation.
Setting = 12: FJOG command “ON”: Run forward at the jog frequency (An-17). = 13: RJOG command “ON”: Run reverse at the jog frequency (An-17).
The forward jog and reverse jog commands have priority over other frequency
command commands.
The inverter will stop running with the stopping method set by the setting of
Sn-06 if the forward jog and reverse jog commands are both ON for more than 500 ms.
PID Integral Reset (Setting : 14)
In the application of PID control, the integral can be reset to zero (ground)
through the multi-function input terminal g~j (Sn-2528= 14).
PID Control Invalid (Setting : 15)
OFF PID control valid (close-loop)
ON PID control invalid (open-loop)
This setting can be used in the changeover of test run. To disable the PID
function (PID control invalid is “ON”)an open-loop operation or jog operation can be performed in the test. The system can be set up properly after some test
runs. Then, the system can be changed into PID control mode. Moreover, if the feedback signal is not usable, the PID function is disabled through this setting.
The setting of Sn-64 can be used to enable or disable the PID function.
External Fault Contact A (Setting : 16)
External Fault Contact B (Setting : 17)
The external fault input terminal is set to “ON”, an external fault then occurs. If
the external input terminal h is set for the external fault input terminal use, a message of “Fault Ext. Fault 6” will be displayed.
There are 5 terminal to be assigned as external fault inputs, they are terminal e,
g, h, i, j
When an external fault occurs, the inverter will be blocked from output and the
motor will coast to stop.
3-56
Multi-Function Analog Input Setting (Setting : 18)
To disable or enable the multi-function analog input at AUX terminal is
controlled by the input signal at an external terminal. When the PID function is enabled, the original AUX function will be disabled.
Timer Function Input Terminal (Setting : 19)
Refer to the setting of timer function output terminal on page 3-66.
DC Injection Braking Command (Setting : 20)
DC injection braking is used to prevent the motor from rotating due to inertia or
external forces when the inverter is stopped.
The DC injection braking will be performed and the inverter will be stopped if
the DC injection braking input is ON. If a run source or jog command is input, the DC injection braking will be cleared and the motor will begin to run.
Run Command
DC injection
braking Command
Output
frequency
OFF ON
OFF
ON
DC braking
Min. Output freq.
Fig. 42. Time chart for DC injection braking command
Speed Search 1 (Setting : 21)
Speed Search 2 (Setting : 22)
Refer to ‘speed search’ function on page 3-24.
LOCAL/REMOTE Control 1 (setting : 23)
Remote Control
OFF
Run command and frequency command is performed through control circuit input or RS-485 communication port. (It will be set by the combination of settings of Sn-04 and Sn-05.) The REMOTE-REF
SEQ LED light is ON.
DC braking
DC braking start freq.
Local Control
ON
Run command and frequency command is performed through digital operator. The REMOTE-REF
SEQ LED light is OFF.
To change the operation mode from LOCAL to REMOTE mode is effective
only when the inverter is in STOP mode.
3-57
LOCAL/REMOTE Control 2 (setting : 24)
Remote Control
OFF
Run command and frequency command is performed through control circuit input or RS-485 communication port. (It will be set by the combination of settings of Sn-04 and Sn-05.) The REMOTE-REF
SEQ LED light is ON.
Local Control
ON
Run command and frequency command is performed through control circuit terminal. The REMOTE-REF
SEQ LED light is OFF.
To change the operation mode from LOCAL to REMOTE mode is effective
only when the inverter is in STOP mode.
RS-485 Communication Application (Setting : 25)
The multi-function input terminals g ~ j can be used as the extension contact
terminals of PLC with the command communicated through the RS-485 port. (Please refer to the “RS-485 MODBUS/PROFIBUS APPLICATION MANUAL”)
PG-Less Speed Control Action (Setting : 26)
Reset Integration of Speed Control with PG (Setting : 27)
When PG feedback is used, the integral control (to add the PG feedback
compensation) can be disabled or enabled from the external terminals. And, user can use the external terminals to clear the integral value.
frequency command
detected
rotor speed
soft start
limiter
Cn-51
Cn-52
Cn-51, 52
ramp
limit
Cn-47, 49
gain
integral
time
Ts
Cn-48, 50
Fig. 43. PG speed control block diagram
output freq.
(optional)
PG speed feedback
3-58
Frequency UP/DOWN Function (Setting : 28)
The inverter can use either the digital operator or external multi-function input
terminals (terminal i orj) to change the output frequency upward or downward.
By setting the parameters of (Sn-04= 1Sn-05= 1), firstly the run source and
frequency command is set through the control circuit terminals. Secondly, set the parameter Sn-28 = 28 (terminal i will now have the function “UP”, its original function is disabled). Then, terminal i and j can be used for “UP” and “DOWN” function to control /change the output frequency.
Operation sequence as below:
Control circuit terminal i : UP function ON OFF OFF ON Control circuit terminal j : DOWN function OFF ON OFF ON
Operation status
terminal or
1 2
FWD / REV
ACC (UP)
DEC
(DOWN)
Constant (HOLD)
Constant
(HOLD)
terminal
terminal
7
8
U = UP (ACC) status U1 = bounded from upper_limit while ACC D = DOWN (DEC) status D1 = bounded from lower_limit while DEC H = HOLD (Constant) status
UP
DOWN
upper limit
output freq.
lower limit
D1 H D U H HH H D1 H D UD1H D U
U1
Fig. 44. Time chart of output frequency with the UP/DOWN function
Only set through parameter Sn-28 When the frequency UP/DOWN function is being used, the output frequency
will accelerate to the lower_limit (Cn-19) if a run command is pressed.
If under HOLD state, 4th bit of Sn-68 is set to 1 power supply OFF, the inverter
can remember output frequency as power supply OFF. When resupplying the power and operation command ON, the inverter will run at the remembered output frequency.
Under auto operation mode, UP/DOWN operation is unavailable. When the UP/DOWN function and jog frequency command are both assigned to
multi-function inputs, the jog frequency command input has the highest priority.
Under UP/DOWN operation, PID is unavailable.
Forced Run (Setting : 29)
Only set through parameter Sn-28. It is for special use (smoke fan, etc.)
3-59
(32) Multi-Function Analog Input Function Selection (Sn-29)
The settings and functions for the multi-function analog input (terminal AUX) are
listed in Table 15.
Table 15 Multi-function analog input function list
Setting Function LCD Display Description (100% output corresponds to 10 V level)
Auxiliary frequency
00
command Frequency command
01
gain (FGAIN) Frequency command bias
02
1 (FBIAS1) Frequency command bias
03
2 (FBIAS2)
04 Torque detection level 1 Tq. Detect Level 1
Overtorque detection
04
level
Output frequency bias
05
(VBIAS) Scaling of ACC/DEC
06
time(TK)
07 DC injection braking DC Brakin current
Stall prevention level
08
during running
PID control reference
09
input
Frequency command
10
lower limit
11 Jump frequency setting4 Freq Jump 4
Auxilary Freq.Cmd. (Max. output frequency)
Instruction gain 1
Cmd. Bias 1
Cmd. Bias 2
Over Tq. Level
Output Voltage Total output voltage= V/F pattern voltage + VBIAS
Acc&Dec Coeff Real ACC/DEC time= ACC/DEC time (Bn-0~24) / TK
Run Still Level
PID Command
Freq. Cmd. Low
Bound
Total gain (Bn-05, Bn-07) ×FGAIN
Total bias =(Bn-06, Bn-08) + FBIAS1
Total bias =(Bn-06, Bn-08) + FBIAS2
According to analog input voltage (0~10V), change torque detection 1 level (setting of Cn-32 is disabled) According to analog input voltage (0~10V), change overtorque detection level (setting of Cn-32 is
disabled)
According to analog input voltage (0~10V), change the level of DC injection current (0-100%). (inverter rated current=100%, the setting of DC
injection current Cn-15 is disabled ) According to analog input voltage (1.5V~10V), change the level of stall prevention during running (30%200%)
(inverter rated current=100%, the setting Cn-26 is disabled.) Multi-function analog input (terminal AUX) used as PID control reference input (0~10V). Please refer to “PID CONTROL BLOCK DIAGRAM” on page 3-7. Change the frequency command lower-limit (0-100%)
value according to the then analog input voltage (0~10V) (Max. output frequency (Cn-02) corresponds to the 100% analog output. The actual lower-limit is determined by the maximum of Cn-19 and the value corresponding to the multi-function analog input terminal). Set the jump frequency 4, according to analog input voltage (0~10V), while Cn-20~Cn-23 can be used to set the jump frequency 1~3 and their jump frequency width.
3-60
Loading...