TECO JNEV-202~203-H1, JNEV-202~203-H1F, JNEV-202~203-H3, JNEV-401~403-H3, JNEV-401~403-H3F Operating Manual

Page 1
Microprocessor Controlled
IGBT Drive
Inverter Motor Speed Regulator
Operating Manual
EV Series 110V 0.20.75KW (0.21HP) 220V 0.22.2KW (0.23HP) 440V 0.752.2KW (13HP)
This manual may be modified when necessary because of improvement of the product, modification, or changes in specifications, This manual is subject to change without notice.
Distributor
Ver:03 2006.05
10F., No.3-1, Yuancyu St., Nangang District, Taipei City 115, Taiwan Tel :+886-2-6615-9111 Fax :+886-2-6615-0933
http://www.teco.com.tw
Page 2
i
Quick Start Guide
This guide is to assist in installing and running the inverter to verify that the drive and motor are working properly. Starting, stopping and speed control will be from the keypad. If your application requires external control or special system programming, consult the 7300EV Instruction Manual supplied with your inverter.
Step 1 Before starting the inverter
Please refer to chapter one (Preface) and chapter two (Safety Precautions) of the 7300EV Instruction Manual. Verify drive was installed in accordance with the procedures as described in chapter three (Environment description and installation). If you feel this was abnormal, do not start the drive until qualified personnel have corrected the situation. (Failure to do so could result in serious injury.)
Check inverter and motor nameplates to determine that they have the same HP and voltage
ratings. (Ensure that full load motor amps do not exceed that of the inverter.)
Remove the terminal cover to expose the motor and power terminals.
a. Verify that AC power is wired to L1(L), L2, and L3(N) . b. Verify that Motor leads are connected to T1, T2, and T3 . c. IF brake module is necessary, please connect terminal voltage of the braking unit to +
and - of the inverter.
Step2 Apply power to the drive.
Apply AC power to the drive and observe operator. Three 7-segment display should show power voltage for 3~5 seconds and then show Frequency Command, factory sets 5.00. (Frequency Command of 7-segment display should be flashed all the time.)
Power Indicator
Page 3
ii
Step3 Check motor rotation without load.
z Press RUN Key. 7-segment Display will indicates 00.0to 05.0. Such value is the frequency
output value.
z Check the operation direction of the motor.
IF the direction of the motor is incorrect: Press STOP Key, turn off the AC power supply. After Power indicator LED is off, change over theT1 and T2. Supply the power again, then check the motor direction.
z Press STOP key.
Step4 Check full speed at 50Hz/60Hz
z Change the frequency with ¿,À arrow mark , please press DATA/ENTER after setting
frequency.
z Set frequency to 50Hz/60Hz according to the above regulations. z Press RUN Key, inspect the motor operation as motor accelerates to full load. z Press STOP Key, inspect the motor operation as motor deceleration.
Step5 Other settings
As for other function, please refer to 7300EV user manual. Set acceleration time ………………………………… P. 4-9 Set deceleration time ………………………………… P. 4-9 Set upper frequency limit ….………………………... P. 4-12 Set lower frequency limit ……………………………. P. 4-12 Set motor rated current ………………………………P. 4-30 Set control mode (Vector, V/F) ………………………P. 4-26
Step6 vector Mode Settings
When the EV inverter is set to run in Vector Mode (C14=000), the motor parameters needs to be set. The required in formation should be readily available on the nameplate of the motor. (Motor kw=0.75 ¯ HP) The parameters to set for vector operation ave: Motor Rated Current (Amps) (F43) See page 4-23 Motor Rated Voltage (Volts) (F44) See page 4-23 Motor Rated Frequency (Hz) (F45) See page 4-23 Motor Rated Power (KW) (F46) See page 4-23 Motor Rated Speed (RPM) (F47) See page 4-23 Additional Vector Mode Settings to adjust for optimum operations are: Torque boost gain (F48) See page 4-23 Slip compensation gain (F49) See page 4-24 Low Frequency Voltage Compensation (F50) See page 4-25
Page 4
iii
7300EV user manual
Table of Contents
Tutorial
........................................................................................................................ i
Content...................................................................................................................... iii
Preface..................................................................................................................... 0-1
Preface.................................................................................................................... 0-1
Product inspection .................................................................................................. 0-1
Chapter 1 Safety precautions............................................................................... 1-1
1.1 Operation precautions ....................................................................................... 1-1
1.1.1 Before power up ........................................................................................ 1-1
1.1.2 During power up ....................................................................................... 1-2
1.1.3 Before operation........................................................................................ 1-2
1.1.4 Leakage current ........................................................................................ 1-2
1.1.5 During operation....................................................................................... 1-3
1.1.6 Useable environment ................................................................................. 1-3
Chapter 2 Model definition.................................................................................. 2-1
Chapter 3 Mounting and installation of the JNEV drive................................ 3-1
3.1 Environment ..................................................................................................... 3-1
3.2 Mounting and installation.................................................................................. 3-3
3.3 Wiring rules ...................................................................................................... 3-7
3.3.1 Notice for wiring........................................................................................ 3-7
3.3.2 Suitable MC, MCCB, fuse and wire specification ....................................... 3-9
3.3.3 Precautions for peripheral applications....................................................3-10
3.4 Inverter specification....................................................................................... 3-14
3.4.1 Basic specifications..................................................................................3-14
3.4.2 General specifications.............................................................................. 3-15
3.5 7300EV wiring diagram................................................................................... 3-17
3.6 Description of inverter terminal....................................................................... 3-18
3.7 Dimension ....................................................................................................... 3-21
3.8 Installation and design considerations.............................................................. 3-24
Page 5
iv
Chapter 4 Programming instructions & parameter list.................................. 4-1
4.1 Keypad description............................................................................................4-1
4.1.1 Keypad description....................................................................................4-1
4.1.2 Operation instruction of the keypad........................................................... 4-1
4.2 Parameter functions list..................................................................................... 4-3
4.3 Parameter functions description....................................................................... 4-10
Chapter 5 Trouble shooting and maintenance.................................................. 5-1
5.1 Trouble indication and corrective action............................................................ 5-1
5.1.1 Fault/Error display and diagnostics ........................................................... 5-1
5.1.2 Set up& interface errors ............................................................................ 5-4
5.1.3 Keypad operation error description........................................................... 5-5
5.2 General functional troubleshooting.................................................................... 5-6
5.3 Troubleshooting flowcharts 7300EV series......................................................... 5-7
5.4 Routine and periodic checks............................................................................. 5-13
Chapter 6 Peripherals components.....................................................................6-1
6.1 Input side AC reactor ........................................................................................ 6-1
6.2 EMC filter......................................................................................................... 6-1
6.3 Option card....................................................................................................... 6-6
6.3.1 RS-485 option card.................................................................................... 6-6
6.3.2 RS-232 option card.................................................................................... 6-7
6.3.3 Program copy option card ......................................................................... 6-8
6.3.4 Remote keypad.......................................................................................... 6-9
6.3.5 2 IN/1OUT card....................................................................................... 6-10
6.3.6 PDA link ................................................................................................. 6-11
Appendix 1 7300EV inverter parameter setting list........................... Appendix 1
Page 6
v
Figure index
Figure 3-1 Panel and enclosure arrangement for drives............................................... 3-1
Figure 3-2 Mounting and clearance requirements........................................................ 3-1
Figure 3-3 Din rail mounting of the JNEV Drive ......................................................... 3-2
Figure 3-4 Side-by-side mounting of the JNEV Drive................................................... 3-2
Figure 3-5 NEMA 4 mounting instructions.................................................................. 3-4
Figure 3-6 NEMA 4 wiring diagram............................................................................3-4
Figure 3-7 M/N XX-YYY-N4S (115,230V model) connection diagram.......................... 3-5
Figure 3-8 M/N XX-YYY-N4 (115,230V model) connection diagram............................ 3-6
Figure 3-9 Typical installation schematic....................................................................3-10
Figure 3-10a Installation examples.............................................................................3-11
Figure 3-10b Installation examples using a filter.........................................................3-11
Figure 3-10c Installation examples with adjacent signal conductors............................3-11
Figure 3-11 Grounding filtered units..........................................................................3-12
Figure 3-12 Processing the ends of twisted pair tables.................................................3-12
Figure 3-13 Grounding example, multiple drives........................................................3-12
Figure 3-14 EV wiring diagram..................................................................................3-17
Figure 3-15 Power terminal locations.........................................................................3-18
Figure 3-16 Signal terminal locations .........................................................................3-19
Figure 3-17 EV drive frame 1 dimensions...................................................................3-21
Figure 3-18 EV drive frame 2 dimensions...................................................................3-22
Figure 3-19 EV drive IP65 (switch) frame 1 dimensions..............................................3-23
Figure 3-20 EV drive IP65 (no switch) frame 1 dimensions.........................................3-23
Figure 3-21 Common bus configurations....................................................................3-24
Figure 4-1 Keypad layout............................................................................................ 4-1
Figure 4-2 Keypad operations sequence....................................................................... 4-1
Figure 4-3 Wiring details
a. Fwd/stop-reverse/stop wiring detail ....................................................4-11
b. Run/stop-forward/reverse wiring detail...............................................4-11
c. 3-wire run/stop detail .........................................................................4-11
Figure 4-4 Control method sequences.........................................................................4-12
Figure 4-5 Frequency limits .......................................................................................4-12
Figure 4-6 Acceleration/deceleration prohibit.............................................................4-15
Figure 4-7 AIN gain & bias setting examples..............................................................4-16
Figure 4-8 Frequency detection
a. Frequency Reached (F21/C46=1) .........................................................4-17
b. Frequency Reached (F21/C46=2) .........................................................4-18
c. Frequency Reached (F21/C46=3) ......................................................... 4-18
d. Frequency Reached (F21/C46=4) .........................................................4-19
Page 7
vi
Figure 4-9 Output current detection...........................................................................4-19
Figure 4-10 DC injection braking...............................................................................4-21
Figure 4-11 Output torque capacity ...........................................................................4-23
Figure 4-12 Slip compensation ...................................................................................4-23
Figure 4-13 Low frequency voltage compensation.......................................................4-24
Figure 4-14 V/F patterns
a. User configured V/F pattern...............................................................4-26
b. Pre configured V/F pattern.................................................................4-27
Figure 4-15 V/Hz curves with varying base voltages ...................................................4-28
Figure 4-16 PID flow control diagram........................................................................4-30
Figure 4-17 Sleep/wake mode.....................................................................................4-31
Figure 4-18 Communication error timing pattern.......................................................4-35
Figure 5-1 General troubleshooting flowchart............................................................. 5-7
Figure 5-2 OC, OL fault troubleshooting..................................................................... 5-9
Figure 5-3 OV, LV fault troubleshooting....................................................................5-10
Figure 5-4 Drive running troubleshooting diagnostics ................................................5-11
Figure 5-5 Motor overload / overheating diagnostics ..................................................5-12
Figure 5-6 Uneven speed operation diagnostics...........................................................5-12
Figure 6-1 External filter dimensions
a. JNFS21017-20.8-07................................................................................ 6-3
b. JNFS21019-8.9-07................................................................................. 6-3
c. JNFS21015-22-07 .................................................................................. 6-4
d. JNFS21016-15-07.................................................................................. 6-4
e. JNFS 20858-7-07 ................................................................................... 6-5
Figure 6-2 JNSIF-485 module ..................................................................................... 6-6
Figure 6-3 JNSIF-485 wiring diagram......................................................................... 6-6
Figure 6-4 RS232 option card
a. JNSIF-232 cable.................................................................................... 6-7
b. JNSIF-232 wiring diagram.................................................................... 6-7
Figure 6-5 Program copy unit
a. JNSIF-MP module ................................................................................ 6-8
b. JNSIF-MP wiring diagram.................................................................... 6-8
Figure 6-6 Remote keypad module
a. JNSDOP remote keypad.........................................................................6-9
b. Remote keypad wiring diagram..............................................................6-9
Figure 6-7 Input/output expansion card
a. JNSIF-IO card.....................................................................................6-10
b. JNSIF-IO wiring diagram ....................................................................6-10
Page 8
Preface
0-1
Preface
Preface
To extend the performance of the product and ensure personnel safety, read this manual thoroughly before using the inverter. Should there be any problem in using the product that can not be solved with the information provided in the manual, contact your nearest TECO distributor or sales representative who will be willing to help you.
Precautions
The inverter is an electrical product. For your safety, there are symbols such as “Danger”, “Caution” in this manual as a reminder to pay attention to safety instructions on carrying, installing, operating, and checking the inverter. Be sure to follow the instructions for highest safety.
Indicates a potential hazard that causes death or serious personal injury if misused
Indicates that the inverter or the mechanical system might be damaged if
misused
Danger
z Do not touch any circuit boards or parts while the charging indicator is still lit after turning the power off.(the light will fade after approximately 5 minutes.)
z Do not connect any wires when the inverter is powered. Do not check parts and signals on circuit boards when the inverter is in operation.
z Do not disassemble the inverter nor modify any internal wires, circuits, or parts. z Ground the ground terminal of the inverter properly, for 200V class ground to 100 or
below, 400v class ground to 10 or below.
Product Inspection
TECO’s inverters have all passed the function test before delivery. Please check the following when you receive and unpack the inverter:
z The model and capacity of the inverter is the same as those specified on your order. z Is there any damage caused by transportation. If so, do not apply the power.
Contact TECO’s sales representatives if any of the above problems happened.
Caution
z Do not perform a voltage test on parts inside the inverter. High voltage can destroy these
semiconductor parts.
z Do not connect T1 (U), T2 (V), and T3 (W) terminals of the inverter to any AC input power
source.
z CMOS ICs on the inverter’s main board are sensitive to static electricity. Do not touch the
main board.
Danger
Caution
Page 9
Chapter 1 Safety Precautions
1-1
Chapter 1 Safety Precautions
1.1 Operation Precautions
1.1.1 Before Power Up
Caution
The line voltage applied must comply with the inverter’s specified input voltage.(See the
nameplate)
Danger
Make sure the main circuit connections are correct. L1(L), L2, and L3(N) are power-input terminals and must not be confused with T1, T2 and T3. Otherwise, inverter damage can
result.
Caution
z To avoid the front cover from disengaging, or other damge do not carry the inverter by its
covers. Support the drive by the heat sink when transpoting. Improper handling can damage
the inverter or injure personnel and should be avoided.
z To avoid fire, do not install the inverter on a flammable object. Intall on nonflammable objects
such as metal.
z If several inverters are placed in the same control panel, provide heat removal means to
maintain the temperature below 50oC to avoid overheat or fire.
z When removing or installing the LCD operator, turn the power off first, and follow the LCD
instructions in the diagram to avoid operator error or no display caused by bad connections.
Warning
This product complies with IEC 61800-3, with built-in Filter in an unrestricted distribution
and with use of external filter in restricted distribution. Under some environments with electric-magnetic interruption, product should be tested before used.
Page 10
Chapter 1 Safety Precautions
1-2
1.1.2 Du ring Power up
Danger
zThe inverter still has control power immediately after power loss. When the power is re-
supplied, the inverter operation is controlled by F41.
zThe inverter operation is controlled by F04 and C09 and the status of (FWD/REV RUN
switch) when power is re-supplied. (F39 /F40) Power loss ride through / Auto reset after fault).
1. When F04=000, the inverter will not auto restart when power is re-supplied.
2. When F04=001 and operation switches (FWD/REV RUN) is OFF, the inverter will not auto restart when power is re-supplied.
3. When F04=001and operation switch ON and C09=000, the inverter will auto restart
when power is re-supplied. Please turn OFF the run ( start) switch to avoid damage to machine and injury to personnel before the power is re-supplied.
zWhen C09=000 (direct start on power up), please refer to the description and warning for
C09 (Page 4-27) to verify the safety of operator and machine.
1.1.3 Before operation
Caution
Make sure the model and inverter capacity match the F00 setting (Page 4-12).
1.1.4 Leakage current
Warning
Warning! EV series built in Filter type leakage current can exceed the IEC standard limit
of 3.5mA. Please ground the inverter as shown in figures 3.5 and 3.6.
Operation with ungrounded supplies:
1. Filtered inverters CANNOT be used on ungrounded supplies.
2. Unfiltered inverters can be used on ungrounded supplies. If any output phase is shorted to
ground, the inverter may trip with OC.(over current trip)
Operation with Residual Current Device(RCD):
1. A filtered inverter with the trip limit of the RCD is 300mA
2. The neutral of the supply is grounded, as is the inverter.
3. Only one inverter is supplied from each RCD.
Page 11
Chapter 1 Safety Precautions
1-3
1.1.5 Du ring operation
Danger
Do not connect or disconnect the motor while inverter is operating the motor. The inverter and the
disconnect device can sustain damage from high levels of switch-off current transients.
Danger
z To avoid electric shock, do not take the front cover off while power is on.
The motor will restart automatically after stop when auto-restart function is enabled. In this case, care
must be taken while working around the drive and associated equipment .
zNote: The operation of the stop switch is different than that of the emergency stop switch.
The stop switch has to be activated to be effective. Emergency stop has to be de-activated
to become effective.
Caution
z Do not touch heat-generating components such as heat sinks and brake resistors. z The inverter can drive the motor from low speed to high speed. Verify the allowable speed ranges of
the motor and the associated machinery.
z Note the settings related to the braking unit.
z Do not check signals on circuit PCB while the inverter is running.
Caution
Allow a minimum of 5 minutes power down before attempting to disassemble or check the components within the drive.
1.1.6 Useable environment
Caution
When the inverter top dust cover has been removed the drive can be installed in a non-
condensing environment with temperature ranging between –10oC to +50 oC and relative humidities of 95% or less, but the environment should be free from water and metal dust.
Page 12
Chapter 2 Model description
2-1
Chapter 2 Model description
Inverter model Model:JNEV-201-H1
Input power I/P: AC 1 PH
200-240V 50/60Hz
O/P: AC3PH 0~264V
Output power 1.6KVA 4.2A
TECO ELECTRIC&MACHINERY CO.,LTD.
JNEV - 2 P5 - H 1 F N4S
Series:
Input voltage :
Max suitable motor capacity:
SPEC Power supply Noise filter Enclosure
1: 110V P2: 0.25 HP H: standard 1:single phase Blank : none 2: 230V P5: 0.5 HP 3:three phase F: built-in
N4S:IP65 with water and dust proof switch
4: 460V 01: 1.0 HP 02: 2.0 HP
N4:IP65 without water and dust proof switch
03: 3.0 HP Blank: IP20
Page 13
Chapter 3 Environment description and installation
3-1
Chapter 3 Mounting and installation of the JNEV drive
3.1Environment
The environment will directly affect the proper operation and the life of the inverter, so install the inverter in an environment that complies with the following conditions:
z Ambient temperature: 14~122 deg F (-10 to 50 deg C)
z Avoid exposure to rain or moisture. z Avoid direct sunlight.
z Avoid smoke and salinity.
z Avoid corrosive liquid and gas.
z Avoid dust, lint fibers, and metal filings.
z Keep away from radio active and
flammable materials.
z Avoid electromagnetic interference (soldering machines, power machine).
z Avoid vibration (stamping, punchpress). Add a vibration-proof pad if the situation can not
be avoided.
z If several inverters are placed in the same control panel, provide heat remoual means to
maintain the temperature below 50oC. See figure 3-1 for proper drive arrangment.
(Correct ) (Incorrect ) (Correct) (Incorrect)
Figure 3-1 Panel and enclosure arrangement for drives
z Place the front side of the inverter outward and the top upward to improve heat dissipation.
(A)Front view (B)Side view
Figure 3-2 Mounting and clearance requirements
Panel
Enclosure
fan
fan
Enclosure
JNEV
Page 14
Chapter 3 Environment description and installation
3-2
z All JNEV drives in IP-20 Enclosures can be DIN-RAIL mounted as shown below.
Figure 3-3 Din Rail Mounting of the JNEV Drive
zAll JNEV Drives in IP-20 enclosures can be mounted side-by-side as shown below. (ambient
temperature below 122˚ F)(50 oC).
Figure 3-4
Side-by-side Mounting of the JNEV Drive
Page 15
Chapter 3 Environment description and installation
3-3
3.2 Mounting and installation
Do not use the inverter in an environment with the following conditions:
Direct sunlight
Corrosive gas and liquid
Oil
Salt
Wind, rain, and water
drops may get into
Iron filings, dust
Extreme low temperature
Electromagnetic wave
and ultra high wave
Radioactive materials
Inflammable materials
Excessive high
tem
p
erature
Page 16
Chapter 3 Environment description and installation
3-4
EV-1P2/1P5/101/2P2/2P5/201- -N4X(IP65)TYPE INSTALLATION :
Figure 3-5 NEMA4 Mounting Instructions
NOTE :
1. POWER SWITCH , REV-0-FWD SWITCH AND Potentiometer are only for EV-1P2~201- N4S TYPE
2. Power supply cable : #14 AWG (2.0m )
3. Motor cable : #16 AWG (1.25m )
4. Tightening Torque : (1). Power/Motor cable (plug in) Terminal : 4.34 in-lb (2). Remote control wire : 3.47 in-lb (3). Outer Cover (M4) : 5.20 in-lb
T1 T2 T3
NOTE: (1). Input source : single-phase(L1,L2,
(PE) ) must
be connected to a 100~120 or 200~240 supply.
(2). Output Motor : three-phase(T1,T2,T3,
(PE) ).
Caution :
Do not start or stop the inverter using the
main circuit power.
FOR EV-1P2~201- -N4S TYPE :
Set REV-0-FWD switch at 0 position so that the inverter has no run signal before power-up. Otherwise, injury may result.
10V
AIN
0V
L1
L2
FWD REV 24V
3
PHASE
IM
AC INPUT
POWER
REV-0-FWD
SWITCH
Potentiometer
AC
100~120
or
200~240
50/60HZ
(PE)
(PE)
(PE)
(PE)
(PE)
(PE)
Figure 3-6 NEMA4 wiring diagram
Page 17
Chapter 3 Environment description and installation
3-5
Figure 3-7 M/N XX-YYY-N4S (115V, 230V models) connection diagram
TM1
TM2
Page 18
Chapter 3 Environment description and installation
3-6
Figure 3-8 M/N XX-YYY-N4 (115V, 230 MODELS) connection diagram
TM1
TM2
Page 19
Chapter 3 Environment description and installation
3-7
3.3 Wiring Rules
3.3.1 Notice for wiring
A. Tightening torque:
Connect cables with a screwdriver or other suitable tools per the tightening torques listed below.
Securing torque
Horsepower Power source Tightening torque for TM1 terminal
0.25/0.5/1 100-120V
0.25/0.5/1 200-240V
0.74/0.1
(LBS-FT / KG-M)
8.66/10
(LBS-IN/KG-CM)
2/3 200-240V
1/2/3 380-480V
1.286/0.18
(LBS-FT/KG-M)
15.97/18
(LBS-IN/KG-CM)
B. Power wires:
Power wires connect to terminals L1(L), L2, L3 (N), T1, T2, T3, P and N. Select power wire in accordance with the following criteria: (1) Use wires with copper core only. Insulating materials with diameters should be based on
working conditions at 221oF (105oC).
(2) The minimum nominal voltage of 240Vac type connectors is 300V, and 480Vac type
connector is 600V.
C. Control wire:
Control wire is connected to the TM2 control terminal. Select wire in accordance with the following criteria: (1) Use copper core only. The insulating materials with diameters should be based on working
conditions at 221oF (105oC).
(2) To avoid noise interference, do not route the control wiring in the same conduit with power
wires and motor wiring.
D. Nominal electrical specifications of the terminal block:
The following are nominal values of TM1:
Horsepower Power source Volts Amps
0.25 / 0.5 / 1 100-120V
0.25 / 0.5 / 1 200-240V
600 15
2 / 3 200-240V
1 / 2 / 3 380-480V
600 40
Note: Nominal values of input and output signals (TM2) – follow the specifications of class 2
wiring.
Page 20
Chapter 3 Environment description and installation
3-8
E. Fuse types
Drive input fuses are provided to disconnect the drive from power in the event that a component fails in the drive’s power circuitry. The drive’s electronic protection circuitry is designed to clear drive output short circuits and ground faults without blowing the drive input fuses. Below table shows the EV input fuse ratings.
To protect the inverter most effectively, use fuses with current-limit function.
RK5, CC/T type fuse for EV
110V class(1
φ)
JNEV-
HP KW KVA 100% CONT
Output AMPS (A)
Max.RK5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
1P2-H1
0.25 0.2 0.53 1.7
10 20
1P5-H1
0.5 0.4 0.88 3.1
15 30
101-H1
1 0.75 1.6 4.2
20 40
220V class(1φ)
JNEV-
HP KW KVA 100% CONT
Output AMPS (A)
Max.RK5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
2P2-H1
0.25 0.2 0.53 1.7
8 15
2P5-H1
0.5 0.4 0.88 3.1
10 20
201-H1
1 0.75 1.6 4.2
15 30
202-H1
2 1.5 2.9 7.5
20 40
203-H1
3 2.2 4.0 10.5
25 50
220V class(3φ)
JNEV-
HP KW KVA 100% CONT
Output AMPS (A)
Max.RK5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
2P2-H3
0.25 0.2 0.53 1.7
5 8
2P5-H3
0.5 0.4 0.88 3.1
8 10
201-H3
1 0.75 1.6 4.2
12 15
202-H3
2 1.5 2.9 7.5
15 20
203-H3
3 2.2 4.0 10.5
20 30
440V class(3φ)
JNEV-
HP KW KVA 100% CONT
Output AMPS (A)
Max.RK5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
401-H3
1 0.75 1.7 2.3
6 10
402-H3
2 1.5 2.9 3.8
10 15
403-H3
3 2.2 4.0 5.2
10 20
*Fuse ratings are based upon 300V fuses for 120V i nvert ers, and 300V fuses for 230V inverters, and 500V for 460V
inverters
Page 21
Chapter 3 Environment description and installation
3-9
3.3.2 Options and wiring specifications
MCCB/ MC/ Fuse
z Warranty and replacement service does not apply to damage caused by the following conditions.
(1)MCCB or fuse is not installed, improperly installed, or improperly sized, and
has resulted in inverter damage.
(2)MC or capacitor or surge absorber is installed between the inverter and the
motor.
EV model
JNEV□□□H1(F)/H3 JNEV□□□ H3(F)
1P2/2P2/1P5/2P5 101/201 202 203 401/402/403
Fuse
10A
300Vac
20A
300Vac
30A
300Vac
15A/600Vac
Main circuit terminal
(TM1/TM3)
Wire dimension
(14AWG)2.0mm2
Terminal screw
M4
Wire
dimension
(12AWG)
3.5mm
2
Terminal
screw
M4
Wire dimension
(14AWG)2.0mm
2
Terminal screw
M4
Signal terminal
(TM2)
1~12
Wire dimension (#18AWG)0.75mm
2
Terminal screw M3
zUse a single fuse for 1φ L/N model. For 3φ models, each L1(L)/L2/L3(N) phase must be fused.
zPlease utilize three phase squirrel cage induction motor with appropriate capacity for inverter.
zIF the inverter is used to drive more than one motor, the total capacity must be smaller than the
capacity of the AC drive. Additional thermal overload relays must installed in front of each motor.
zDo not install phase advancing capacitors, LC, or RC components between inverter and motor.
Page 22
Chapter 3 Environment description and installation
3-10
3.3.3Precautions for peripheral applications:
Power supply:
zMake sure the correct voltage is applied to avoid damaging the
inverter.
zA molded-case circuit breaker or fused disconnect must be
installed between the AC source and the inverter.
Molded-case circuit breaker:
zUse a molded-case circuit breaker that conforms to the rated
voltage and current of the inverter to control the power and protect the inverter.
zDo not use the circuit breaker as the run/stop switch for the
inverter.
Fuse:
zA suitable fuse should be installed with inverter rated voltage and
current when a MCCB is not being used.
Earth Leakage circuit breaker:
z Install a leakage breaker to prevent problems caused by current
leakage and to protect personnel. Select current range up to 200mA, and action time up to 0.1 second to prevent high frequency failure.
Magnetic contactor:
zNormal operations do not need a magnetic contactor. When
performing functions such as external control and auto restart after power failure, or when using a brake controller, install a
magnetic contactor.
z
Do not use the magnetic contactor as the run/stop switch for the
inverter.
AC Line Reactor for power quality:
zWhen inverters are supplied with high capacity (above 600KVA) power source, a AC reactor can be connected to improve the PF.
Input noise filter:
zA filter must be installed when there are inductive loads
affecting the inverter.
Inverter:
zOutput terminals T1, T2, and T3 are connected to U, V, and W
terminals of the motor. If the motor is reversed while the inverter is set to run forward, just swap any two terminals of T1, T2, and T3.
zTo avoid damaging the inverter, do not connect the input
terminals T1, T2, and T3 to AC input power.
zConnect the ground terminal properly.( 230 V series: Rg
<100; 460 V series: Rg <10.)
Figure 3-9 Typical installation
schematic
Page 23
Chapter 3 Environment description and installation
3-11
Make external connections as shown in figure 3-10. Check after wiring to make sure all connections are correct. (Do not use the control circuit buzzer to check connections)
(A) Main circuit must be separated from other high voltage or high current power line to avoid
noise interference. Refer to following figures:
z The inverter uses dedicated power line A general noise filter may not provide correct results
z Please added a noise filter or separation transformer when the inverter shares the power line with other machines.
.
z A noise filter in the output of the main circuit can suppress conductive noise. To prevent radiative
noise, the wires should be put in a ferromagnetic metal pipe and separated from all other signal lines by at least 1ft.
Metal box
Power
Power
EV
EV
EV
Powe
r
Power
濾波
EV
EV
Power
Power
General noise filter
Machine
Machine
Machine
Genera l noise filter
Machine
S
pecial noise filter
Separation transformer
Insulation transformer
Figure3-10 b Installation examples using a filter
Figure3-10a Installation examples
Incorrect
Incorrect
Figure 3-10c Installation examples with adjacent signal conductors
Correct
Page 24
Chapter 3 Environment description and installation
3-12
z The power supply and output PE terminals must be both connected to ground to increase noise immunity of the built-in Filter.
(A)The control circuit wiring and main circuit wire/ other high voltage/current
power wiring should be separated to avoid noise interruption.
z In order to prevent noise interference which could cause inverter faults, the control circuit signal
should be shielded and twisted. Please refer to figure 3-12. The wiring distance should be less than 150ft (50m).
(B)Connect ground terminals as follows:
(200V class ground <100 ; 400V class ground
<10 .)
z Ground wiring AWG is sized per the electrical equipment specifications and should be made as
short as possible.
z Do not share the ground of the inverter with other high current loads (welding machine, high power
motor).Connect the terminal to its own ground.
z Do not make a loop when several inverters share a common ground point.
(a) Good (b) Good (c) Bad
(C)To ensure maximum safety, use correct wire size for the main power circuit and control circuit. (See table in section 3.2.2)
(D)Verify that all wiring is correct, wires are intact, and terminal screws are secured.
Do not connect this end
Shield sheath
Armor
Wrapped with insulating tape
To ground terminal
Ground
Figure 3-11 Grounding filtered units
Figure 3-12 Processing the ends of twisted pair cables
Figure 3-13 Grounding examples: multiple drives
Page 25
Chapter 3 Environment description and installation
3-13
z When the connection between the inverter and the motor is too long, consider the voltage drop of
the circuit. Phase-to-phase voltage drop (V) =
3 ×resistance of wire (/km)×length of line (m)×current×10-3. And the carrier frequency must be
adjusted based on the length of the line.
The length of the line between the inverter and the motor
Below 25m Below 50m Below 100m Over100m
Carrier Frequency Below 16KH z Below 1 2 KH z Below 8KH z Below 5KH z
Settings of F40 parameter 16 12 8 5
Page 26
Chapter 3 Environment description and installation
3-14
3.4 Inverter Specification
3.4.1 Basic specification
460V model
EV-□□□-H3(F)
Model
401 402 403
Horse power (HP)
1 2 3
Max.applicable Motor Output HP*1(KW)
1.0(0.75) 2.0(1.50) 3.0(2.2)
Rated output current (A)
2.3 3.8 5.2
Rated capacity (KVA)
1.7 2.9 4.0
Input voltage range(V)
3PH 380~480V+10%,-15%(50/60Hz)
Output voltage range(V)
3PH 0~480V
Input current (A)
3 4.8 6.6 Inverter Weight Lb (KG) Inverter with filter Weight Lb (KG)
3.31(1.26)
3.70(1.37)
3.35(1.29)
3.75(1.4)
3.42(1.34)
3.82
(1.45)
Maximum momentary power
loss time (S)
1.0 2.0 2.0
Enclosure
IP20
* Based on a 4-Pole Motor
120V model 230V model
EV-□□□-H1
Single phase
EV-□□□-H1(F)
Three phase
EV-□□□-H3
Model
1P2 1P5 101 2P2 2P5 201 202 203 2P2 2P5 201 202 203
Horsepower (HP) 0.25 0.5 1 0.25 0.5 1 2 3 0.25 0.5 1 2 3
Max.Applicable Motor output.HP*1 (KW)
0.25
(0.2)
0.5
(0.4) 1 (0.75)
0.25
(0.2)
0.5
(0.4)1 (0.75)2 (1.5)3 (2.2)
0.5
(0.2)
0.5
(0.4) 1 (0.75) 2 (1.50)3 (2.2)
Rated output current (A) 1.7 3.1 4.2 1.7 3.1 4.2 7.5 10.5 1.7 3.1 4.2 7.5 10.5
Rated capacity (KVA) 0.53 0.88 1.60 0.53 0.88 1.60 2.90 4.00 0.53 0.88 1.60 2.90 4.00
Input voltage range(V)
1PH
100~120V+10%,
-15%(50/60Hz)
1PH
200~240V+10%,
-15%(50/60Hz)
3PH
200~240V+10%,
-15%(50/60Hz)
Output voltage range(V)
3PH 0~240V
Input current (A) 7.1 12.2 17.9 4.3 5.4 10.4 15.5 21 3.0 4.0 6.4 9.4 12.2
Inverter Weight Lb Inverter with filter weight
Kb (KG)
1.37
(0.62)
1.50
(0.68)
1.59
(0.72)
1.43
(0.65)
1.57
(0.71)
1.48
(0.67)
1.71
(0.73)
1.48
(0.67)
1.71
(0.73)
2.20
(1)
2.76
(1.25)
2.31
(1.05)
2.87
(1.3)
1.34
(0.61)
1.34
(0.61)
1.46
(0.66)
2.09
(0.95)
2.20
(1.0)
Maximum momentary
power loss time (S)
1.0 1.0 1.0 1.0 1.0 1.0 2.0 2.0 1.0 1.0 1.0 2.0 2.0
Enclosure IP20
Page 27
Chapter 3 Environment description and installation
3-15
3.4.2 General Specifications
Range 0~200Hz
Initial Drive 100%/3Hz (Vector mode)
Speed Control Range (Vector mode) 20:1 Speed Control
Precision
±0.5%(Vector mode)
Setting resolution※1
Digital: 0.1Hz(0~99.9Hz)/1Hz(100~200Hz); analog: 0.06Hz/ 60Hz
Keypad setting
Set directly with▲▼ keys or the VR on the keypad
Display 7 segment*3 Displays; frequency/DC Voltage/Output Voltage /
Current/ inverter parameters/fault log/program version/PID feedback control potentiometer.
External signal setting •External / 0(2)-10V/ 0(4)-20mA
•Performs up/down controls with multi-functional contacts on the terminal base
Frequency control
Frequency limit function
Upper/lower frequency limits, and two skip frequencies.
Carrier frequency 4~16KHz (default 10KHz, above 10KHz with De-rating)
V/F pattern 6 fixed patterns 50Hz/60Hz, 1 programmable
Acc/dec control Two-stage acc/dec time (0.1~999s) Multi-functional analog
output
6 functions (refer to F26 description)
Multi-functional input
19 functions (refer to F11~F14 description)
Multi-functional output
16 functions (refer to F21 description)
DI(digital input)
NPN/PNP alternative : 4 points standard, 2 points optional (S1~S4
standard, S5~S6 optional)
DO(digital output)
Relay output *Form A contact ---- set to multi-function output. External multi-function output *option 1 point ( open collector transistor 24V, 600mA)
AI(analog input)
Set speed command and PID feedback signal (speed ,PID 4~20mA /0~10V)or MFIT S7
General control
Other functions
Instantaneous power loss on restart, Speed search, fault restart, DC
injection braking, torque boost, 2/3wire control, PID function
Communication control
•RS485 Option card: Modbus RTU/ASCII mode, 4800~38400 bps, max. 254 stations
•PC/PDA software
Operation temperature
14~122 deg F(-10~50 deg C) IP20, 14~104 deg F(-10~40 deg C)
IP65
Storage temperature
-4~140 deg F( -20~60 deg C)
Humidity 0 – 95% RH (non condensing)
Vibration immunity 1G(9.8m/s2) EMI/EMS
Compatibility
Built-in class B/ external: class A, accordance with EN61800-3 first non limit/ limit environment
LVD Accordance with EN50178
Enclosure IP20
Safety Class UL508C
Page 28
Chapter 3 Environment description and installation
3-16
Over load protection Inverter rated current 150%/1min International
conformity
UL/CE
Over voltage 230V Class: DC voltage >400V 460V Class: DC voltage >800V
Under voltage 230V Class: DC voltage <190V 460V Class: DC voltage <380V Instantaneous power
loss restart
Set to enable or disable
Stall prevention ACC/DEC/ Operation stall prevention and stall prevention level. Output terminal
short circuit
Electronic circuit protection
Other faults Electronic circuit protection
Protective Functions
Other functions
Over current, over voltage, under voltage, over load, instantaneous power loss
restart, ACC/DEC/ Operation stall prevention, output terminal sort circuit, grounding error, reverse limit, directly start as power on and fault reset limit.
Note1: The setting resolution of above 100 Hz is 1Hz when controlled by keypad, and 0.01
Hz when controlled using computer(PC) or programmable controller(PLC).
Note2: EV-1P2~101-H1;2P2~201-H1/H3401~403-H3 type (Fc=10KHz) with option filter
complies with EN61800-3 first environment restricted distribution.
EV-202~203-H1/H3 type (Fc=10KHz) with option filter complies with EN61800-3 first environment unrestricted distribution.
EV-2P2~201-H1F type (Fc=10KHz) & EV-202~203-H1F type (Fc=6KHz) with Build in
filter complies with EN61800-3 first environment unrestricted distribution.
(IP65) EV-2P2~403-H1(3)FN4(S) series & EV-401~403-H3F type (Fc=10KHz) with
Build in filter complies with EN61800-3 first environment restricted distribution.
Page 29
Chapter 3 Environment description and installation
3-17
3.5 EV Wiring diagram
(3)24V
10k
Note 1:- Connect inputs to
Terminal 3 ( internal 24vdc) for PNP mode ( Positive switching) . Or to terminal 8 ( Common) for NPN mode( Negative switching) .
Note2:- External 24 Vdc may be used to supply the external contacts at each input (Connect the 0V of the external supply to Common ( terminal 8).)
Example: Main circuit wiring diagram
* Not used for single-phase operation
L1(L)
L2*
L3(N)
T1
T2
T3
IM
(4)S1
(5)S2
(6)S3
(7)S4
(8)COM
(9) 10V
(10)AIN
(11)COM
(12)FM+
2 1
FM
1.SW1: Digital signal selection (NPN/PNP)
2.SW2: Control signal selection V/I
RA(1
)
RB(2)
Multi-function digital output
Multi function digital input Accept DC 12/24V signal
NPN common point
Power terminal
Single phase 100~120V
1/3 phase 200~240V
3 phase 380~480V
Multi-function analog input
Set speed
PID feed back input
S5 S6
Option interface
Multi-function
output input card
(2 IN/ 1 out)
Remote ke
yp
ad
Braking Unit
PE
24V/0.6A
PNP common poin
t
PE
T+
T-
Figure 3-14 Wir ing d i ag r am
Page 30
Chapter 3 Environment description and installation
3-18
3.6 Description of Inverter Terminal
Descriptions of power terminals
Symbol Description
L1 ( L )
L2
L3 ( N )
Main power input Single-phase: L/N*
Three-phase: L1/L2/L3
DC power and braking unit connection terminals. (match with braking units and
braking resistor to brake)
T1
T2
T3
Inverter output
PE Grounding terminals (2 points)
* Braking units are required for applications where a load with high inertia needs to be stopped rapidly. Use a power-matched braking unit and resistor to dissipate the energy generated by the load while stopping. Otherwise inverter will trip on over voltage.
* Terminal at L2 will be non-functional for single-phase units.
Figure 3-15 Power terminals locations
Page 31
Chapter 3 Environment description and installation
3-19
Control signal terminals block description 1 2 3 4 5 6 7 8 9 10 11 12
TM2
Symbol Description
RA
RB
Multi-functional output terminal Normally open contact
Rated contact capacity:
(250VAC/10A)
Contact description: (refer to
parameter F21)
10V Supply for external potentiometer for speed reference.
AIN Analog frequency signal input terminal or multi-function input terminal S7 (high
level : 8V/low level: 2V), adaptable to PNP (refer to parameter F15 description)
24V
PNP (SOURCE) input, S1~S4 (S5/S6/S7) common terminal, (set SW1 to PNP and connect option card power.)
COM
NPN (SINK) input, S1~S4 (S5/S6) common terminal, (set SW1 to NPN, and analog input, connect option card power, output signal common terminal.)
FM+
Multi-function analog output + terminal (refer to parameter F26 description), output signal: DC 0-10V.
Symbol Description
S1
S2
S3
S4
Multi-function input terminals (refer to parameters F11~F14 description)
RA
RB
24V
S1
S2
S3
S4
COM
10V
AIN
COM
FM+
Figure 3-16 Signal terminal locations
Page 32
Chapter 3 Environment description and installation
3-20
SW function description
SW1 Type of external signal Remarks
NPN input (SINK)
PNP input (SOURCE)
Factory default
SW2 Type of external signal Remarks
0~10V DC analog signal
4~20mA analog signal
Effective when parameter F05=2 (analog input
signal from TM2)
V
I
V
I
Page 33
Chapter 3 Environment description and installation
3-21
3.7 Dimension
(1) IP20 Frame1: Single phase: JNEV-1P2~201-H1/H1F
Three phase: JNEV-2P2~201-H3
Figure 3-17 EV drive frame1 dimensions
Page 34
Chapter 3 Environment description and installation
3-22
(2) IP20 Frame2: Single phaseJNEV-202~203-H1/H1F
Three phase JNEV-202~203-H3 Three phase JNEV-401~403-H3/H3F
Unit: inch/mm
LENGTH
A B C D
Frame 1 5.2/132 4.86/123.5 2.64/67 3.03/77 Frame 2 5.2/132 4.86/123.5 4.25/108 4.65/118
LENGTH
MODEL
E F G
Frame 1 5.13/130.5 5.06/128.45 0.315/8
Frame 2 5.83/148 5.67/144 0.315/8
MODEL
Figure 3-18 EV drive frame2 dimensions
Page 35
Chapter 3 Environment description and installation
3-23
(3) IP65 Frame1(switch) EV-1P2/1P5/101/2P2/2P5/201-N4S(IP65 type):
z IP65 Frame1(no switch) EV-1P2/1P5/101/2P2/2P5/201-N4(IP65 type):
Figure 3-19 EV drive IP65 (switch) frame 1 dimensions
Figure 3-20 EV drive IP65 (no switch) Frame 1 dimensions
Page 36
Chapter 3 Environment description and installation
3-24
3.8 Installation and design consideration
Note 1. Common bus connections from a common input power supply as shown above.
Note 2. When connecting a drive or drives’ DC bus connections in parallel with larger. Hp rated
drives, use a magnetic contactor with the ⊕&⊖ terminals, otherwise, inverter damage can result.
Note: If ⊕⊖ terminal block be used, please take off the TB label as shown below.
Common bussing of drives allow for load-sharing and therefore can save energy. Adding a
braking unit to improve brake capacity is also acceptable.
must power on the same time
Figure 3-21 Common bus configurations
connection
connection
Page 37
Chapter 4 Software index
4-1
Chapter 4 Programming instructions & Parameter list
4.1 Keypad description
4.1.1
Keypad display
4.1.2 Operation Instruction of the keypad
*1: Display flashes with set frequency in stop mode, but it is solid in run mode. *2: The frequency can be set during both stop and run modes.
Power LED (Red)
Frequency display in stop mode
VALUE
VALUE
DATA
ENT
DATA
ENT
Output voltage
DC voltage
Output current
PID Feedback
DSP
FUN
DSP FUN
F10=001, inverter
displays status
DSP
FUN
F××
F××
×××
×××
^
V
After 0.5s
DATA
ENT
DATA
ENT
Power ON
˙
˙
˙
~
DSP
FUN
DSP
FUN
DSP FUN
RUN
STOP
RUN
STOP
Blinking output
frequency in run mode
^
V V
VALUE
VALUE
DSP
FUN
DSP
FUN
DATA
ENT
DATA
ENT
Figure 4-1 Keypad layout
Figure 4-2 Keypad Operations Sequence
Page 38
Chapter 4 Software index
4-2
z Remote/Local change function
Local mode
Run command via RUN/STOP key on the keypad
Frequency command
When C41=000: only UP/DOWN key on the keypad can control and F05 setting has
no effect.
When C41=001: only VR on the keypad can control and F05 setting has no effect.
• Remote mode
Run command from Run parameter (F04) control setting
Frequency command from Frequency parameter (F05) control setting
Remote/Local change mode
on keypad is achieved by simultaneously pressing /RESET and
DATA/ENT. Each successive operation toggles between local and remote.
Note: The inverter must be stopped.
Page 39
Chapter 4 Software index
4-3
4.2 Parameter function list Basic parameter function list
F Function Description Range/ Code
Factory Default
Remarks
00
Inverter horse power
capacity
01 Acceleration time 1 00.1~999s 05.0 *1 *2
02 Deceleration time 1 00.1~999s 05.0 *1 *2
03 Motor rotation direction
000: Forward 001: Reverse
000 *1
04 Run command source
000: keypad 001: External Terminal 002: Communication Control
000
05 Frequency command source
000: UP/Down Key on control panel 001: Potentiometer on control panel 002: AIN input signal from (TM2) 003: Multi-function input terminal
UP/DOWN function
004: RS-485 Communication
frequency setting
000
06
External control operation mode
000: Forward/ Stop-Reverse/Stop 001: Run/ Stop-Forward/Reverse 002:3-wire—Run/ Stop
000
07 Frequency upper limit 01.0 ~200Hz 50.0/60.0 *2
08 Frequency lower limit 00.0 ~200Hz 00.0 *2
09 Stopping method
000: Decelerate to stop 001: Coast to stop
000
10 Status display parameters
000: No display 001: Display
000 *1
11 Terminal S1 Function 000
12 Terminal S2 Function 001
13 Terminal S3 Function 005
14 Terminal S4 Function 006
15 Terminal AIN Function
000: Forward 001: Reverse 002: Preset Speed Command 1 003: Preset Speed Command 2 004: Preset Speed Command 3 005: Jog frequency Command 006: Emergency stop(E.S.) 007: Base Block (b.b.) 008: Select 2
nd
accel / decel time 009: Reset 010: Up command 011: Down command 012: Control signal switch 013: Communication control signal switch 014: Acceleration/deceleration prohibit 015: Master/Auxiliary speed source select 016: PID function disable 017: Analog frequency signal
input( terminal AIN) 018: PID feedback signal (terminal AIN)
019: DC Brake signal
017
16 AIN signal select
000: 0~10V(0~20mA) 001: 4~20mA(2~10V)
000
17 AIN Gain (%) 000~200 100 *1
Page 40
Chapter 4 Software index
4-4
18 AIN Bias (%) 000~100 000 *1
19 AIN Bias
000: Positive 001: Negative
000 *1
20 AIN Slope Direction
000: Positive 001: Negative
000 *1
21 Multi-function output RY1
000: Run 001: Frequency reached (Set frequency ± F23) 002: Frequency is within the range set by (F22±F23) 003: Frequency Detection (>F22) 004: Frequency Detection (<F22) 005: Fault terminal 006: Auto reset and restart 007: Momentary power loss 008: Emergency Stop(E.S.) 009: Base Block (b.b.) 010: Motor overload protection 011: Inverter overload protection 012: retain 013: Power On 014: Communication error 015: Output current detection(>F26)
000
22
Output frequency at the Set value (Hz)
00.0~200 00.0 *1
23
Frequency detection range (±Hz)
00.0~30.0 00.0 *1
24 Output current set value 000~100% 000
25
Output current detection time
00.0~25.5(Sec) 00.0
26
Multi-function output analog type selection (0~10Vdc)
000: Output frequency 001: Set frequency 002: Output voltage 003: DC voltage 004: Output current 005: PID feedback signal
000 *1
27
Multi-function analog output gain (%)
000~200% 100 *1
28
Preset frequency 1 (Main frequency setting)
00.0~200Hz 05.0 *1
29 Preset frequency 2 00.0~200Hz 05.0 *1
30 Preset frequency 3 00.0~200Hz 10.0 *1
31 Preset frequency 4 00.0~200Hz 20.0 *1
32 Preset frequency 5 00.0~200Hz 30.0 *1
33 Preset frequency 6 00.0~200Hz 40.0 *1
34 Preset frequency 7 00.0~200Hz 50.0 *1
35 Preset frequency 8 00.0~200Hz 60.0 *1
36 Jog frequency instruction 00.0~200Hz 05.0 *1
37
DC braking time 00.0~25.5 Sec 00.5
38
DC braking start frequency 01.0~10.0 Hz 01.5
Page 41
Chapter 4 Software index
4-5
39
DC braking level 000~020% 005
40
Carrier frequency 004~016 010 4~16K
41 Auto Restart for power-loss
000: Enable 001: Disable
000
42
Auto-restart times
000~005
000
43
Motor rated current
*4
44 Motor rated voltage *4
45 Motor rated frequency *4
46 Motor rated power *4
47 Motor rated speed *4
48 Torque Boost Gain (Vector) 001~450
49
Slip Compensation Gain (Vector)
001~450
50
Low frequency voltage compensation
000~40
51
Advanced parameter function display
000: don’t display 001: display
000 *1
52 Factory default
010: Reset to factory default (50Hz) 020: Reset to factory default (60Hz)
000
53 Software version CPU Version *3 *4
54 Latest 3 fault records *3 *4
Advanced function parameter list(Enable access to these parameters by setting F51=001)
C Function Description Range/ Code
Factory
default
Remarks
00 Reverse run instruction
000: Reverse enable 001: Reverse disable
000
01
Acceleration stall­prevention
000: Acceleration stall prevention enable 001: Acceleration stall prevention disable
000
02
Acceleration stall­prevention level (%)
050 - 200 200
03
Deceleration stall­prevention
000: Deceleration stall prevention enable 001: Deceleration stall prevention disable
000
04
Deceleration stall­prevention level (%)
050 - 200 200
05 Run stall-prevention
000: Run stall prevention available 001: Run stall prevention unavailable
000
06
Run stall-prevention level (%)
050 - 200 200
07
Stall prevention time
during run
000: according to decel time set in F02 001: according to decel time set in C08
000
08
Stall prevention deceleration time set
00.1 – 999 Sec 03.0
09 Direct start on power up
000: Direct start available 001: Direct start disabled
001
10 Reset mode
000: RUN instruction is OFF, Reset
command is available.
001: Whether RUN instruction is OFF or
ON, Reset command is available.
000
Page 42
Chapter 4 Software index
4-6
11 Acceleration time 2 00.1~999 Sec 05.0
*1 *2
12 Deceleration time 2 00.1~999 Sec 05.0
*1 *2
13 Fan control
000: Auto-run at set temperature 001: Run when inverter runs 002: Always run 003: Always stop
001
This function only available for IP20 type, For IP65 type , fan will run while power is on.
14 Control mode
000:Vector control 001:V/F Control
000 *4
15
V/F Pattern setting 001 ~ 007
001/004
16
V/F base output voltage set
198~265V / 380~530V 220/440
17
Max output frequency (Hz)
00.2 – 200 50.0/60.0
18
Output voltage ratio at max frequency (%)
00.0 – 100 100
19 Mid frequency(Hz) 00.1 – 200 25.0/30.0
20
Output voltage ratio at mid frequency (%)
00.0 – 100 50.0
21
Min output frequency (Hz)
00.1 – 200 00.5/00.6
22
Output voltage ratio at Min frequency (%)
00.0 – 100 01.0
23
Torque Boost Gain (V/F)
00.0 ~ 30.0% 00.0 *1
24
Slip Compensation Gain (V/F)
00.0 ~100% 00.0 *1
25 Motor no load current
Varies with
motor rating *4
26
Electronic thermal relay protection for motor (OL1)
000: Enable motor protection 001: Disable motor protection
000
27
Skip frequency 1(Hz) 00.0~200 00.0 *1
28
Skip frequency 2(Hz) 00.0~200 00.0 *1
29
Skip frequency range (±Hz)
00.0~30.0 00.0 *1
30 PID operation mode
000: PID Function unavailable 001: PID control, Bias D control 002: PID Control, Feedback D control 003: PID Control, Bias D reverse
characteristics control.
004: PID Control, Feedback D reverse
characteristics control.
000
31 PID Error gain 0.00 – 10.0 1.00 *1
32 P: Proportional gain 0.00 – 10.0 01.0 *1
Page 43
Chapter 4 Software index
4-7
33 I: Integral time (s) 00.0 – 100 10.0 *1
34 D: Differential time (s) 0.00 – 10.0 0.00 *1
35 PID OFFSET
000: Positive direction 001: Negative direction
000 *1
36 PID OFFSET adjust (%) 000 – 109 000 *1
37 PID Update time (s) 00.0 - 02.5 00.0 *1
38
PID Sleep mode
threshold
00.0~200Hz 00.0
39 PID Sleep delay time 00.0~25.5 00.0
40
Frequency Up/ Down control using MFIT
000: UP/Down command is available.
Set frequency is held when inverter stops.
001: UP/Down command is available.
Set frequency resets to 0Hz when inverter stops.
002: UP/Down command is available.
Set frequency is held when inverter stops. Up/Down is available in stop.
000
41
Local/Remote frequency control select (Run command by the Run/Stop key)
000: UP/Down key on keypad sets
frequency
001: Potentiometer on the keypad set
frequency
000
42
Terminal S5 function (option)
007
43
Terminal S6 function (option)
000: Forward 001: Reverse 002: Preset Speed Command 1 003: Preset Speed Command 2 004: Preset Speed Command 3 005: Jog Frequency Command 006: Emergency Stop(E.S.) 007: Base Block (b.b.) 008: Select 2nd accel/decel time. 009: Reset 010: Up Command 011: Down Command 012: Control signal switch 013: Communication control signal
switch 014: Acceleration/ deceleration disable 015: Master/auxiliary speed source select 016: PID function disable
017: Analog frequency signal
input( terminal AIN)
018: PID feedback signal (terminal AIN) 019: DC Brake signal
009
44
Multi-function input terminal S1~S6 signal scan time (mSec ×8)
001~100 010
45
Confirming AIN signal scan time (mSec x 8 )
001~100 050
Page 44
Chapter 4 Software index
4-8
46
Multi-function output
T+,T- (option)
000: Run 001: Frequency reached (Set frequency ± F23) 002: Frequency is within the range set by (F22±F23) 003: Frequency detection (>F22) 004: Frequency detection (<F22) 005: Fault terminal 006: Auto-restart 007: Momentary power loss 008: Emergency Stop(E.S.) 009: Base Block(b.b.) 010: Motor overload protection 011: Inverter overload protection 012: retain 013: Power ON 014: Communication error 015: Output current detection(>F26)
005
47
Remote keypad control selection
000: Disable (no signal loss detection) 001: Enable. On signal loss stop
according to F09 002: Enable. Runs at the last set
frequency. On signal loss
Stop is according to F04 setting or
Stop key on keypad.
000
Stop inverter then connect remote keypad for proper operation *4
48 Copy module
000: Copy module disable 001: copy to module from inverter 002: copy to inverter from module 003: read/ write check
000 *3
49
Inverter communication address
001 ~ 254 001 *3 *4
50 Baud rate (bps)
000: 4800 001: 9600 002: 9200 003: 38400
003 *3 *4
51 Stop bit
000: 1 Stop bit 001: 2 Stop bit
000 *3 *4
52 Parity bit
000: No parity 001: Even parity 002: Odd parity
000 *3 *4
53 Data bits
000: 8 bits data 001: 7 bits data
000 *3 *4
54
Communication error detection time
00.0 ~ 25.5 Sec 00.0 *3*5
55
Communication error
operation selection
000: Deceleration to stop.
(F02: Deceleration time 1). 001: Coast to stop. 002: Deceleration to stop.
(C12: Deceleration time 2). 003: continue operating.
000 *3*5
Page 45
Chapter 4 Software index
4-9
Note: *1: Can be modified in Run mode.
*2: Frequency resolution is 1Hz for settings above 100 Hz.
*3: Cannot be modified during communication.
*4: Do not change while making factory setting.
F52 factory setting is 020(60HZ) and motor parameter value is 170.
F52 factory setting is 010(50HZ) and motor parameter value is 140.
*5: Available in Software version 1.2 or later
Page 46
Chapter 4 Software index
4-10
4.3 Parameter function description Basic function parameter list
F00 Inverter horse power capacity
F00 Inverter model F00 Inverter model 1P2 1P2
203
203
1P5
1P5
401
401
101
101
402
402
2P2
2P2
403
JNEV
403
2P5 2P5
201
JNEV
201
202 202
F01 Acceleration time 1 (s): 00.1 – 999
F02 Deceleration time 1 (s): 00.1 – 999
Formula for acceleration/deceleration time: Denominator is based on the setting of Cn14 a) Motor rating frequency (Sensor less vector control C14=000) b) Max output frequency (V/f mode C14=001)
a)
Set frequency Set frequency
Acceleration time = F01× Deceleration time =F02 × (vector)
F45(rated frequency) F45(rated frequency)
b)
Set frequency Set frequency
Acceleration time =F01× Deceleration time = F02 × (V/F)
C17(Max output frequency) C17(Max output frequency)
F03 Motor rotation direction 000: Forward
001: Reverse
Parameter F04 =000 must be set to 000 for this function to be effective.
F04 Run signal source
000: keypad 001: External Terminal 002: Communication Control
1.) F04=000, inverter is controlled by keypad.
2.) F04=001, inverter is controlled by external terminal.
3.) F04=002, inverter is controlled by serial communication.
F05 Frequency signal source
000: UP/Down Key on keypad 001: Potentiometer on keypad 002:TM2 input signal (Terminal AIN) 003: Multi-function input terminal UP/DOWN function 004: Frequency set by communication method (When C47=1,Remote Keypad has priority)
1.) F5=001, when any of parameter group F11~ F15 is set to 015 and multi-function input terminal
is OFF, the frequency is set by the potentiometer on the Keypad. If the multi-function input terminal is ON, the frequency is set by the analog signal (auxiliary speed) from TM2.
2.) F5=002, when any of parameter group F11~ F15 is set to 015 and multi-function input terminal
is OFF, the frequency is set by the analog signal (auxiliary speed) from TM2. If the multi­function input terminal ON, the frequency is set by the potentiometer on Keypad.
Page 47
Chapter 4 Software index
4-11
3.) Up/Down terminal: please refer to description of parameter group F11~ F15 (multi-function
input terminal).
4.) Priority of reading frequency command: Jog> preset frequency > (Keypad▲▼ or TM2 UP/ Down or communication)
F06 : External control operation mode 000: Forward/ Stop-Reverse/Stop
001: Run/ Stop-Forward/Reverse 002: 3-wire—Run/ Stop
1.) F06 is only available when F04 = 001 (external terminal).
2.) When both forward and reverse commands are ON, this will result in a stopped mode.
Note: In 3 wire control mode terminals S1-S3 are used, therefore parameters
F11~ F13 are ineffective.
(1). NPN input signal:
S1 (Forward/Stop) S2 (Reverse/Stop) COM (Common)
(2). PNP input signal:
Parameter F06 = 001, Control method is as follows:
(1). NPN input signal:
S1 (Run/Stop) S2 (Forward / Reverse) COM (Common)
(2). PNP input signal:
S1 (Run/Stop) S2 (Forward / Reverse) 24V(Common)
Parameter F06 = 002, Control method is as follows:
(1). NPN input signal:
(2). PNP input signal:
S1 (Run) S2 (Stop) S3 (Forward/ reverse)
COM (Common)
S1 (Run) S2 (Stop) S3 (Forward/ Reverse) 24V (Common)
S1 (Forward/Stop) S2 (Reverse/Stop) 24V(Common)
Parameter F06 = 000, Control method is as follows:
Figure 4-3a Fwd/stop-Reverse/Stop wiring detail
Figure 4-3b RUN/STOP-Forward/Reverse Wiring detail
Figure 4-3c 3-WIRE Run/Stop detail
Page 48
Chapter 4 Software index
4-12
Note: C00=001, reverse command is disabled.
F07 Frequency upper limit (Hz): 01.0 - 200
F08 Frequency lower limit (Hz): 00.0 - 200
Note: If F07 = 0 Hz and frequency command = 0 Hz, the inverter will 0-speed stop.
If F08 > 0 Hz and frequency command F08, inverter will run at F08 set value.
F09 Stopping method 000: Decelerate to stop
001: Free run ( Coast) to stop
1.) F09 = 000: after receiving stop command, the motor will decelerate to stop according to setting of F02, deceleration time 1.
2.) F09 = 001: after receiving stop command, the motor will free-run (Coast) to stop.
F10 Status monitoring display
000: Disable
001: Enable.
F10 = 001 displays motor current, voltage, DC bus voltage, and PID feedback.
Out put frequency
F07 (Frequency upper limit)
F08 (Frequency lower limit)
(Note)
Commanded Frequency
Terminal
Terminal
Terminal
Figure 4-4 Control Method Sequences
Figure 4-5 Frequency Limits
Page 49
Chapter 4 Software index
4-13
F11~15 Selectable Functions for input terminals ( S1-S4& AIN )
000: Forward run 001: Reverse run 002: Preset speed command 1 003: Preset speed command 2 004: Preset speed command 3 005: Jog frequency command
006: External Emergency stop(E.S.) 007: Base block (b.b.) 008: Switch to 2nd acceleration/ deceleration time 009: Reset 010: Up command 011: Down command 012: Control signal switch 013: Communication mode. Disable – Enable. 014: Acceleration/deceleration prohibit 015: Master/Auxiliary speed switch 016: PID function prohibit 017: Analog frequency signal input ( terminal AIN)
018: PID feedback signal (terminal AIN)
019: DC Brake signal
1.) S1-AIN on TM2 are multi-function input terminals which can be set to the above 19 functions.
2.) F11~F15 function description:
F11~F15=000/001(Forward/ Reverse)
Forward command ON sets the inverter running forward, while OFF stops, the inverter. F11 factory default is forward command. Reverse command ON sets the inverter running reverse, While OFF, the inverter stops. F12 factory default is reverse command.
If forward –reverse command are ON at the same time the inverter is in Stop
mode.
F11~F15=002~004(Preset speed command 1~3)
When run signal is applied and the selected external multi-function input terminal is on, the inverter will run at one of 8 preset speeds which are controlled by the status of the terminals. The corresponding speeds are programmed in parameters F28 to F36 as shown in the table below.
F11~F15=005(Jog frequency command)
When run signal is applied and the selected external multi-function input terminal is on and set to Jog speed, the inverter will run according to F36 setting.
Priority of the frequencies: Jog > preset speed
Preset Speed
Command 3
Set value=004
Preset Speed
Command 2
Set value=003
Preset Speed
Command 1
Set value=002
Jog Frequency
Command
Set value=005
Output
frequency
set value
X X X 1 F36
0 0 0 0 F28 0 0 1 0 F29 0 1 0 0 F30 0 1 1 0 F31 1 0 0 0 F32 1 0 1 0 F33 1 1 0 0 F34 1 1 1 0 F35
Page 50
Chapter 4 Software index
4-14
F11~F15=006: Emergency Stop (E.S)
The inverter will decelerate to stop on receiving the external emergency stop signal. The display will be blinking with “E.S”. The inverter will only start again when the Emergency Stop signal is removed and the start signal is turned off and then on again (remote start mode) or the Run key is pressed (keypad mode). Removing the Emergency Stop signal before the inverter has fully stopped will not inhibit the Emergency Stop operation. Output relay can be set to Emergency. Stop fault by setting F21=008
F11~F15=007:
Base Block (b.b.)
The inverter will stop immediately on receiving the Base Block signal regardless of the setting of F09 and blink “b.b”. The inverter will auto restart at speed search when the Base Block signal is released.
F11~F15=008: Switching to 2nd acceleration/ deceleration time
When the external terminal is ON it selects the 2nd acceleration/ deceleration time. (see
parameters C11,C12)
F11~F15=009: Reset command
When the reset command ON, the inverter will be disabled. Reset table faults will be cleared.
F11~F15=010/011: UP / DOWN function: (Controlled by acceleration/deceleration times)
Set F05=003, to enable the UP/DOWN function. Note: the UP/DOWN key on the Keypad is
unavailable for changing frequency directly.
Set C40=000, When UP/DOWN terminal is ON, the inverter begins acceleration/deceleration to a
frequency and stops acceleration/ deceleration when the UP/ DOWN signal has been released. The
drive continues to run at the most recent set speed.
The inverter will decelerate to stop or free run to stop when the run command is OFF according to F09. The speed at which the inverter stops will be stored in F28.
NOTE: UP/DOWN key is now unavailable for modifying frequency. It should be modified by setting
Parameter F28.
Set C40=001, The inverter will run from 0Hz on receiving run command.
UP/DOWN action is similar to the above description. When the run command is released, the inverter
will decelerate to stop or free run to stop ( 0 Hz) according to the setting of F09.
The inverter will output from 0Hz in next operation.
Note: UP/ DOWN commands are disabled if both terminals are ON at the same time.
F11~F15=012: Control signal switch
External control terminal OFF: operation signal/ frequency signal is controlled by F04/F05.
External control terminal ON: Operation signal/frequency signal is controlled by Keypad display.
F11~F15=013: Communication mode select.
External control terminal OFF: in communication, the inverter is controlled by master (PC or PLC)
run/ frequency signal and allows parameter modification. The Keypad and TM2 run/frequency signal is not available for inverter at this time. The keypad is only available for display of voltage/ current/ frequency and read parameters but cannot modify them. It is also available for emergency stop. External control terminal ON: PC/PLC can read and modify parameters. BUT all controls are from the keypad. (Not affected by settings of F04 & F05).
F11~F15=014: Acceleration/deceleration Disable.
When the external control terminal ON, the inverter will stop acceleration/ deceleration will the signal is released. The motion is as follows:
Page 51
Chapter 4 Software index
4-15
F11~F15=015 Master/Auxiliary speed switch
1) F05=001, when one of the parameters F11~ F15 is set to 015, and multi-function input terminal is OFF, the frequency is set by the potentiometer on the Keypad(Master speed), When the multi-function input terminal is ON, the frequency is set by the analog signal on TM2 (Auxiliary speed AIN).
2.) F05=002, when one of the parameters F11~ F15 is set to 015, and multi-function input
terminal is OFF, the frequency is set by the analog signal on TM2,
(Master Auxiliary speed AIN); While multi-function input terminal is ON, the frequency is set by the potentiometer on the Keypad (Auxiliary speed).
F11~F15=016 (PID function Disable)
When input terminal is on, PID functions set by C30 are disabled. When input terminal is the PID functions are enabled.
F15=017 Analog frequency signal input (Terminal AIN)
Frequency reference can be set by 0-10Vdc or 4-20mA on terminal AIN as set by F16 and SW2.
F15=018 PID Feedback signal input (Terminal AIN)
PID feedback can be connected to AIN terminal 0-10Vdc/0~20mA or 2~10V/4-20mA as set by F16 and SW2.
F11~F15=019 DC Brake signal
When TM2 DC Brake signal is OFF, and the brake time of F37 has not been over , then brake time is according to set value of F37; When TM2 DC Brake signal is ON, and the brake time of F37 has already been over , the brake is stopped according to DC Brake signal OFF of TM2.
F16 AIN signal select
000: 0~10V/0~20mA 001: 2~10V/4~20mA
F16: AIN signal select: set SW2 to appropriate V/I signal selection
F16=000: 0~10V/0~20mA F16=001: 2~10V/4~20mA
Run signal
Acceleration /deceleration prohibit
Output frequency
Note: Acceleration/deceleration prohibit is
unavailable if Run signal is OFF. (RAMP to stop)
Figure 4-6 Acceleration/Deceleration Prohibit
Page 52
Chapter 4 Software index
4-16
1.) F19= 000: 0V (4mA) corresponding to lower frequency limit, 10V (20mA) corresponding to upper frequency limit.
2.) F19= 001: 10V (20mA) corresponding to lower frequency limit, 0V (4mA) corresponding to upper frequency limit.
Fig 4-7a setting: Fig 4-7b setting:
F17 F18 F19 F20
F17 F18 F19 F20
A 100﹪ 050% 000 000
C 100﹪ 050% 000 001
B 100﹪ 000% 000 000
D 100﹪ 000% 000 001
Fig 4-7c setting: Fig 4-7d setting:
F17 F18 F19 F20 F17 F18 F19 F20
E 100﹪ 020% 001 000
F 100﹪ 050% 001 001
F17 AIN Gain (%) 000 - 200 F18 AIN Bias (%) 000 - 100
Upper frequency limit (F07=60.0)
Upper frequency limit (F07=60.0)
V
60Hz
30Hz
Bias
0Hz
0V (4mA)
A
B
5V 10V
(20mA)
100% 050%
000%
Fig 4-7a
Upper frequency limit (F07=60.0)
Hz
V
60Hz
30Hz
0Hz 0V
(4mA)
C
D
5V
10V (20mA)
Bias
100%
050%
000%
Fig 4-7b
Hz
Upper frequency limit (F07=60.0)
Hz
V
60Hz
30Hz
0Hz
E
2V (7.2mA)
10V (20mA)
Bias
-000%
-020%
-100%
Fig 4-7c
Hz
V
60Hz
30Hz
0Hz
F
5V
(12mA)
10V (20mA)
Bias
-000%
-050%
-100%
Fi
g
4-7
d
Page 53
Chapter 4 Software index
4-17
F19 AIN Bias: 000: Positive 001: Negative F20 AIN signal slope direction. 000: Positive 001: Negative C45 AIN signal scan time confirmation. (mSec × 8): 001 – 100
Refer to F17/F18 description The inverter reads A/D average value every C45 x 8mS. The user can set scan interval time according to noise levels in the operation environment. Extend C45 if noise is a problem, however the response speed will be slower.
F21 Multi function output RY1
000: Run 001: Frequency reached (Preset target frequency ± F23) 002: Frequency reached (Preset output frequency level (F22) ±F23) 003: Frequency Detection (>F22) 004: Frequency Detection (<F22) 005: Fault output 006: Auto restart 007: Momentary power loss 008: Emergency Stop(E.S.) 009: Base Block(b.b.) 010: Motor overload protection 011: Inverter overload protection 012: retain 013: Power On 014: Communication error 015: Output current detection
F22 Preset Output frequency reached =00.0 ~ 200Hz
F23 Frequency detection range =00.0 ~ 30Hz
Figure 4-8a Frequency Reached (F21/C46=1)
Page 54
Chapter 4 Software index
4-18
F21/C46=002 Preset output Frequency F22 ± F 23 re a ch ed.
F21/C46=003 Fre q ue n cy det ect io n Fo u t> F 22
Figure 4-8b Frequency Reached (F21/C46=2)
Figure 4-8c Frequency Detection (F21/C46=3)
Page 55
Chapter 4 Software index
4-19
F21/C46=004 F r e q u e n c y d e t e c t i o n F o u t ﹤ F 2 2
F24 Output current reached setting value
F25 Output current detection time
F21: Output current detection value >F24 C46: Output current detection value >F24 F24: Setting value (000~100%) by motor rated current (F43) F25: Setting value (00.0~25.5) unit : sec
When setting value is 015
Iloa
d
Figure 4-8d Frequency Detection (F21/C46=4)
Figure 4-9 Output current detection
Page 56
Chapter 4 Software index
4-20
Multi-function analog output: F26 Multi-function output analog type selection
001: Set frequency 002: Output frequency 003: DC voltage 004: Output current 005: PID feedback signal
F27 Multi-function analog output gain = 000 ~ 200%
0-10 Vdc output from the FM+ multi-function analog output terminal. Output can be set to any of the above selections.
F27 is used to scale the output signal supplied to the externally connected analog device.
F26=005, PID Feedback. The analog input to terminal AIN (0-10vdc or 4-20mA), will be outputted from terminal FM+ as 0-10Vdc. Note: Due to hardware limits, the max output voltage from FM+ terminal will be limited to 10V.
Keypad, jog, and preset frequency setting (MFIT):
Note1: Frequency selection will be made according to the setting of terminals S1-S4 & AIN and also setting of parameters F11 – F15 as required. Note2: Selected preset frequency values should be programmed in parameters F28- F36 as required.
1) F11~F15=002-004 (Preset frequency Command 1~3)
When the run signal is applied and any of the selected multi-function input terminals is ON, the inverter will run at the preset frequency according to the table below.
2) F11~F15=005 (Jog Frequency Command)
External input terminal is set to Jog operation. When ON, the inverter will run at Jog frequency.
Parameter Description Frequency range Factory default
F28 Preset frequency 1 (Hz) 00.0 - 200 05.0 F29 Preset frequency 2 (Hz) 00.0 - 200 05.0 F30 Preset frequency 3 (Hz) 00.0 - 200 10.0 F31 Preset frequency 4 (Hz) 00.0 - 200 20.0 F32 Preset frequency 5 (Hz) 00.0 - 200 30.0 F33 Preset frequency 6 (Hz) 00.0 - 200 40.0 F34 Preset frequency 7 (Hz) 00.0 - 200 50.0 F35 Preset frequency 8 (Hz) 00.0 - 200 60.0 F36 Jog frequency (Hz) 00.0 - 200 05.0
Page 57
Chapter 4 Software index
4-21
Set frequency priority: Jog Preset frequency External analog frequency signal
Preset
Frequency
Command 3
Set value =004
Preset
Frequency
Command 2
Set value =003
Preset
Frequency
Command 1
Set value =002
Jog frequency
Command
Set value =005
Output
frequency
0 0 0 0 F28 0 0 1 0 F29 0 1 0 0 F30 0 1 1 0 F31 1 0 0 0 F32 1 0 1 0 F33 1 1 0 0 F34 1 1 1 0 F35
X X X 1 F36
F37 DC braking time (s) : 00.0~25.5
F38 DC braking start frequency (Hz) : 01.0~10.0
F39 DC braking level (%) : 00.0~20.0%
F37 / F38: DC braking time and start frequency, per the following figure:
F40 Carrier frequency (KHz) : 004-016
Set this parameter to a level from 4-16KHz as required. (Default is 10 KHz).
*Note: In situations where there is excessive audible noise from the motor or it is required to reduce
electrical noise from the inverter caused by use of long cable then the carrier frequency can be
adjusted as follows:
To reduce noise due to long cable decrease carrier frequency.
To reduce motor audible noise increase carrier frequency. However the output current from the
inverter will be de-rated according to the table on page 4-24.
F40
Carrier frequency
F40
Carrier frequency
F40
Carrier frequency
F40
Carrier frequency
004 4KHz 008 8KHz 012 12KHz 016 16KHz 005 5KHz 009 9KHz 013 13KHz 006 6KHz 010 10KHz 014 14KHz 007 7KHz 011 11KHz 015 15KHz
F38
HZ
t
F37
Figure 4-10 DC Injection Braking t
t
F38
HZ
TM2
DC
Brake
Signal
019
Page 58
Chapter 4 Software index
4-22
Corresponding list of current and carrier frequency
F41 Auto restart on momentary power loss.
000: Enable
001: Disable
F41=000: Auto restart after a momentary power loss is enabled on resumption of power and
applying the run signal, according to setting of parameter F4.
The Inverter will carry out an auto speed search, once the motor rotation speed is found then it will accelerate to the running speed before the power loss. F41=001: Disable.
F42 Auto restart times: 000 ~ 005
1.) F42=000: The inverter will not auto-restart on fault trip.
2.) F42>000 The Inverter will carry out an auto search 0.5 sec after the fault trip, and while the inverter output is switched off and the motor is coasting to stop. Once the rotation speed is determined the inverter will accelerate or decelerate to speed before the fault.
3.) Auto restart is not available for OL1, OL2, OH, BB, faults. Note: Auto restart will not function while DC injection braking or deceleration to stop Is performed.
F43 Motor rated current (A) F44 Motor rated voltage (Vac) F45 Motor rated frequency (Hz) F46 Motor rated power (KW) F47 Motor rated speed (RPM) : F47 X 10= Motor rated speed
F48 Torque boost gain (Vector), C14=000
Performance: If the motor load is determined to be too large increase the output torque.
(load current) (compensation gain)
Model
Carrier frequency
EV-1P2/2P2
H1/H1F/H3
EV-1P5/2P5
H1/H1F/H3
EV-101/201
H1/H1F/H3
EV-202
H1/H1F/H3
EV-203
H1/H1F/H3
EV-401
H3/H3F
EV-402 H3/H3F
EV-403 H3/H3F
4~10K 1.7 3.1 4.2 7.5 10.5 2.3 3.8 5.2
12K
1.7 3.1 4.2 7.5 10.5 2.2 2.2 3.7
14K
1.6 3.0 4.0 7.0 10.0 2.2 2.2 3.6
16K 1.5 2.8 3.8 6.8 8.7 2.1 2.1 3.5
Te I ¯ Gain
Page 59
Chapter 4 Software index
4-23
• Torque/Speed curve pattern:
• Operating frequency range: 0~Motor rate frequency
• When the motor output torque is not enough and increase F48 setting value.
• When the motor is erratic or vibrates decrease F48 setting value.
• The max. Output torque limit to the inverter is current rated.
• If increase F48 setting value then the output current is too large. Please increase C49 setting value on the same time.
F49 Slip compensation gain (vector), C14=000
Performance: If the motor load appears too large, increase slip compensation.
(load current) (compensation gain)
• Torque/Speed curve pattern:
• Operating frequency range: 0~motor rated frequency.
• When the motor output rotation speed is too low increase F49 setting value.
• When the motor is erratic or vibrates, decrease F48 setting value.
• The max. output rotation speed limit to the motor max. setting frequency.
• If increase F49 setting value then the output current is too large. Increase C48 setting value at the same time.
RPM
ΔTe:Increase output torque capacity
Torque
C %
B %
A %
Q
F
sli
p
I ¯ Gain
A %
B %
C %
Q
RPM
F
slip
Figure 4-11 Output Torque Capacit
y
Figure 4-12 Slip Compensation
Page 60
Chapter 4 Software index
4-24
F50 Low frequency voltage compensation, C14=000
Performance: During low frequency Increase F50 setting value to increase output voltage and low frequency torque. Decrease F50 setting value to decrease output voltage and low frequency torque.
• Output voltage/frequency curve pattern:
• Operating frequency range:
• During low frequency use:
When the motor output torque is insufficient, increase F50 setting value. When the motor is vibrating excessively, decrease F50 setting value.
F51 Advanced parameter function
display
000:Disable access to advanced parameters ( Group C ) 001:Enable access to advanced parameters ( Group C )
F51=000. Parameter group C can not be displayed or accessed. F51=001. Enable display and access to parameter group C.
F52 Factory default 010: Reset parameters to factory default (50Hz)
020: Reset parameters to factory default (60Hz)
F53 Software version
F54 Fault records (Latest 3 times)
Advanced Parameters List (Group C parameters)
C00 Reverse run
000: Reverse enable
001: Reverse disable
When F04=000 and C00=001, F03 (motor direction) is disabled, the inverter is set to forward
operation.
When F04=001 or 002, and C00=001, reverse command is disabled.
F
0~12HZ / 60HZ 0~10HZ / 50HZ
Figure 4-13 Low Frequency Voltage Compensation
Page 61
Chapter 4 Software index
4-25
C01 Acceleration stall-prevention:
=000: Enable Stall prevention during Acceleration.
=001: Disable Stall prevention during Acceleration. C02 Acceleration stall-prevention level: 050% ~ 200% C03 Deceleration stall-prevention:
= 000: Enable Stall prevention during deceleration.
= 001: Disable Stall prevention during deceleration. C04 Deceleration stall-prevention level: 050% ~ 200% C05 Run stall-prevention:
= 000: Enable Stall prevention in Run mode.
= 001: Disable Stall prevention in Run mode. C06 Run stall-prevention level: 050% ~ 200% C07 Stall prevention time during run mode.
= 000: Set by parameter F02 (Deceleration 1). = 001: Set by parameter C08.
C08 Stall prevention deceleration time: 00 .1 ~ 9 99s
1.) When the Acceleration time is set too low, the inverter could trip on Over Current (OC).
If the time can not be increased then trip prevention can be used. A trip prevention level has to be programmed. When the inverter detects this level it holds the acceleration until the current is below this set level and then continues with acceleration.
2.) When the Deceleration time is set too low the inverter could trip on Over Voltage (OV).
If the time can not be increased then trip prevention can be used. A trip prevention level has to be programmed. When the inverter detects this level it holds the deceleration until the voltage is below this set level and then continues with deceleration.
3.) The Inverter could trip (Stall) during run mode due to an impact load or sudden change of the
load. Stall prevention in run mode will detect a programmed stall level (C06) for a period of time (C07). If the level exceeds C06, then the inverter reduces its frequency (speed) to provide the required additional torque to overcome the stall. Once this level is below the programmed stall level, then it ramps up to its normal running speed.
C09 Direct start on power up
000: Enable direct start on power up. 001: Disable direct start on power up.
Danger:
1.) When C09=000 and external run mode (F04=001), the inverter will auto start when the power
is supplied to the inverter and the run switch is ON.
This feature should only be considered when all safety implications of its use have been investigated. (Risk assessment for maintenance, use of warning labels etc.) We recommend that this mode stay disabled.
2.) When C09=001 and external run mode (F04=001), the inverter will not auto start when power
is supplied and the RUN switch is ON.
Inverter display will blink "SP1" error message. It can only restart after the RUN switch was turned off and ON again.
Page 62
Chapter 4 Software index
4-26
C10 Reset mode
000: Reset is enable when RUN switch is OFF. 001: Reset is enable with RUN switch OFF or ON.
C10=000. Fault can not be reset, therefore the inverter can not start when the RUN switch is in ON position. (F4=001)
C11 2nd acceleration time (s): 00.1 – 999 C12 2nd deceleration time (s): 00.1 – 999
C13 Fan control
000: Auto-run by temperature 001: Run when inverter running 002: Always run.
003: Always stop.
1.) C13=000: The fan will auto run at or above a set certain temperature in order to extend the life span of the fan.
2.) C13=001: The fan runs as long as inverter is running.
3.) C13=002: The fan runs as long as power is supplied.
3.) C13=003: The fan does not run at any time.
C14 Control mode Vector control or V/F control
C17 Max. output frequency (HZ) = 5 0. 0 – 2 00 Hz
C18 Output voltage ratio at max. frequency (%) = 0 0.0 – 10 0 %
C19 Mid frequency (HZ) = 00.1 – 200Hz
C20 Output voltage ratio at mid. frequency (%) = 00.0 – 100%
C21 Min. output frequency (HZ) = 00.1 – 200Hz
C22 Output voltage ratio at min. frequency (%) = 00.0 – 100%
C17~C22 please refer to C15 description
C15 Preset V/F patterns = 1 – 7
C15 = 007. Select user-set v/f pattern by setting parameters C17~C22.
See the diagram below. Care should be taken when this feature is used as improper setting of
these parameters will have an adverse effect on motor performance.
Figure 4-14a User configured V/F pattern
Page 63
Chapter 4 Software index
4-27
C15 = 001– 006 fixed V/F patterns (see below).
Spec
Purpose
C15 V/F Pattern
Spec
Purpose
C15 V/F Pattern
General
001
General
004
High starting torque
002
High starting torque
005
50 Hz System
Variable torque
003
60 Hz System
Variable torque
006
Figure 4-14b Pre-configured V/F patterns
Page 64
Chapter 4 Software index
4-28
C16 VF base output voltage set
At C17=60HZ
C18=100%
For 200~240V, patterns based an output voltage are shown below. (Corresponding settings for 400­480 volts input: multiply by 2)
When the output voltage is set higher than the input voltage, the max output voltage is limited to the max input voltage.
C23 Torque Boost Gain (V/F) (%) 00.0 – 30.0%
C24 Slip Compensation Gain (V/F) (%) 00.0 – 100%
C25 Motor no load current (A)
Motor no load current varies with inverter capacity F00. Please adjust according the actual conditions.
C26 Electronic thermistor protection for motor (OL1) :
000: Protection Enabled
001: Protection Disabled
C27 Skip frequency 1 (Hz) : 00.0 –200 C28 Skip frequency 2 (Hz) : 00.0 –200 C29 Skip frequency range (± Hz) : 00.0 –30.0
Example: C27=10.0Hz/C28=20.0Hz / C29=02.0Hz
10Hz ±2Hz= 8-12Hz
20Hz ±2Hz=18-22Hz Skip frequencies
C29
C28
C27
60.0Hz (C17)
C16=240
C16=220
C16=200
240
220
200
Figure 4-15 V/HZ curves with varying base voltages
Page 65
Chapter 4 Software index
4-29
C30 =1: D is the deviation of PID error in the unit time (C34).
=2: D is the deviation of feedback value in the unit time (C34).
=3: D is the deviation of PID error in the unit time (C34). If the deviation is positive, the
output frequency decreases, and vice versa.
=4: D is the deviation of feedback value in unit time (C34).When the deviation is positive, the
frequency decreases, and vice versa.
C31 PID error gain : 0.00 - 10.0
C31 is PID error gain, that is feedback value = feedback value × C31.
C32 P: Proportional gain : 0.00 - 10.0
C32: Proportional gain for P control.
C33 I: Integral time (s) : 00.0 - 100
C33: Integral time for I control
C34 D: Differential time (s) : 0.00 - 10.0
C34: Differential time for D control.
C35 PID offset 000: Positive direction
001: Negative direction
C36 PID offset adjust (%) : 000 ~ 109%
PID operation result can be adjusted by C36 (C35 effects the polarity of C36).
C30 PID operation mode
000: PID Function disabled. 001: PID Control, Deviation is derivative controlled 002: PID Control, Feedback is derivative controlled. 003: Same as 001 but (reverse characteristics control).
004: Same as 002 but (reverse characteristics control).
Page 66
Chapter 4 Software index
4-30
C37 PID update time (s): 00.0 - 02.5
C37: the refresh time of the PID output command.
Note: PID function is used in flow control, external fan wind volume control, and temperature
control. See flow control diagram below.
1. In PID mode select, AIN on TM2 is the PID feedback signal (Set F15=018.)
2. The PID command (set point) is selected by parameter F05 (selections 000 & 001).
This value is stored in F28.
PID sleep mode requires setting all functions below C30=001~004(PID Enable) F15=018(AIN is PID feedback signal) F28=PID preset frequency
C38 sleep start frequency, unit: Hz
C39 PID sleep delay time, unit: Sec
When PID output frequency becomes lower than the PID sleep start frequency (C38) for a period of time (C39),then the inverter output will decelerate to zero speed(Sleep mode). When the PID output frequency becomes higher than the sleep start frequency (C38), the inverter output accelerates to PID output frequency (Wake mode). Refer to figure 4-17. .
C38 PID Sleep start frequency (Hz) 00.0~200Hz
C39 PID Sleep delay time (sec) 00.0~25.5sec
Figure 4-16 PID flow control diagram
Page 67
Chapter 4 Software index
4-31
Timing diagram is as following:
C40 Frequency Up/Down control using MFIT :
000: When using Up/Down command, the set frequency by this function will be
stored after the inverter stops.
UP/DOWN function is not available in stop mode.
001: When using Up/Down command, the set frequency will be reset to 0Hz after
the inverter stops.
002: When using Up/Down command, the set frequency will be stored after the
inverter stops. UP/DOWN function is available in stop mode.
1) C40=000: when the RUN signal is ON, the inverter will accelerate to the F28 setting then
continue to run at the set command speed. When UP/DOWN terminal is activated, the inverter
begins to accelerate/decelerate until the signal is released then. It run at the reached speed.
When the RUN signal is OFF, the inverter decelerates to stop (or coasts to stop) according to
the setting of F09. The last output frequency when the RUN signal is OFF, will be stored in F28.
UP/DOWN Key is unavailable in stop. The stored frequency can not be changed by Up/Down
Terminal, but can be changed by the content of F28 by keypad.
2) C40=001: the inverter will run from 0 Hz as the run signal is applied.
UP/DOWN operation method is same as C40=000. But on next RUN signal is ON, inverter
always starts up from 0Hz.
3) C40=002: Same as when C40=001 but UP/DOWN is available while in stop mode.
Fi
g
ure 4-17 Sleep/ Wake Mode
Page 68
Chapter 4 Software index
4-32
C41 Local /Remote control select description
Local mode
Run command
The Run/Stop pad on the keypad controls inverter F04 setting has no effect on control.
Frequency command
When C41=000: the UP/DOWN pad on the keypad controls the drive and the F05 setting has
no effect.
When C41=001: the potentiometer on the keypad controls frequency, and F05 setting has no
effect.
• Remote mode
Run command is by the run parameter (F04) setting
Frequency command from the frequency parameter (F05) setting
• Control select mode is changed by simultaneously pressing V/RESET and DATA/ENT keys
(Drive must be in stop mode)
Refer to F11~F14
1.) If the C44 scan time is set to 80 ms as an example (i.e N=10) then digital input signals on for less
than 80 msec will be ignored.
2.) If the scan signal is seen for N times (scan times), the inverter takes it as signal change. If it is seen
for less than N times, it is seed as noise. One scan time: 8ms.
3.) User can set scan interval time according to noise in the operation environment. Extend C44/C45 if
noise is a problem, however this will reduce the scan response time.
C42/43 (option card)
S5/S6 terminal on MFIT Setting 000: Forward 001: Reverse 002: Preset speed command 1 003: Preset speed command 2 004: Preset speed command 3 005: Jog Frequency Command 006: Emergency Stop (E.S.) 007: Base Block (b.b.) 008: Switching to 2
nd
acceleration/ deceleration time. 009: Reset 010: Up Command 011: Down Command 012: Control signal switch 013: Communication control signal switch 014: Acceleration/ deceleration disable 015: Master/ auxiliary speed switch 016: PID function disable
C44: Multi-function input terminal S1~S6 signal scan time (N. msec ×8), N = (1~100 times).
C45: AIN signal scan time (N. msec ×8), N = (1~100 times).
Page 69
Chapter 4 Software index
4-33
C46 (Option card) Multi-function output T+, T-
000: Run 001: Frequency reached [Preset target frequency ± F23] 002: Frequency reached [ Preset output frequency level (F22) ±F23]
003: Frequency detection (>F22)
004: Frequency detection (<F22)
005: Fault.
006: Auto-restart
007: Momentary power loss
008: Emergency Stop (E.S.)
009: Base Block (b.b.)
010: Motor overload protection
011: Inverter overload protection
012: retain
013: Power ON
014: Communication error
015: Output current detection
Refer to F21 description:
C47 Remote keypad control selection
000: Disable 001: Enable. Operation according to F09 on signal loss. 002: Enable. Operation at the last set frequency on signal loss. (Stop mode by Inverter keypad or F04 parameter as appropriate).
When C47=001, C49~C53 set parameter disable the following parameters will be auto set: Inverter communication address: No 1 Data bytes: 8 bit
Baud rated (bps): 38400 Parity bytes: no parity Stop bytes: 1 bit
Note: 1. Connect remote keypad while in stop mode, and the control priority is with the
Remote keypad.
2. If the remote keypad is connected in run mode, it will not be effective until the inverter has stopped.
C48 Copy module
000: Copy module Disabled 001: Copy to module from inverter (Read) 002: Copy to inverter from module (write) 003: Read/ write check (Compare the parameters).
Note: Module copy function is applicable only to inverters with the same voltage and KW
rating.
C49 set communication address, for the specific inverter when multi-inverters are controlled by
communication method.
C50 Baud rate (bps)
000: 4800 001: 9600 002: 19200 003: 38400
C49 Inverter communication address: 001~ 254
Page 70
Chapter 4 Software index
4-34
C51 Stop bit
000: 1 Stop bit 001: 2 Stop bit
C52 Parity bit
000: No parity 001: Even parity 002: Odd parity
C53 Data bits
000: 8 bits data 001: 7 bits data
1. RS-485 communication: (requires RS485 port device)
1 to 1 control: PC or PLC or controller controls one inverter (C49 is set to 001~254).
1 to multiple drives control: PC or PLC or other controllers control several inverters (up to 254 inverters with C49 set as 001~254). When the communication address =000, the inverter is controlled by communication regardless of the C49 setting.
2. RS-232communication: (requires RS232 port) 1 to 1 control: PC or PLC or controller controls one inverter (C49 is set to 001~254).
Note: a. The BAUD RATE(C50) and communication format (C51/C52/C53) of PC (or PLC or
other controller) and inverter should be the same.
b. The inverter will validate the modified parameters after the parameters modified by PC.
c. Communication protocol: refer to EV communication protocol description.
d. Parameter C49~C53 can’t be changed via communication module
C54/ C55 Communication error detection time / Communication error operation selection
(1) Time –out detection time: 00.0~25.5sec; setting 00.0 sec: disable time-out function.
Default: 00.0sec
*Cannot be modified during communication.
(2) Time-out operation selection:
000: Deceleration to stop (F02: Deceleration time 1). 001: Free run to stop. 002: Deceleration to stop (C12: Deceleration time 2). 003: Continue operating.
Default=000
*Cannot be modified during communication.
Page 71
Chapter 4 Software index
4-35
C54/C55 Communication error parameter timing pattern
Master
Slave
(EV)
Tx
T3 > C54
F21=014 or C46=014
T3T2 T1
0,1,2 (≠3
)
000 B Dec from F02 002 B Dec from C12
If F02<C12
RY
Frequency
001 B free Run
Frequency
C55=001
003 B keep Run
COT
Display always show COT until Reset
Display show
0,1,2,3
Reset or Master send data again
Reset
Master
Command
Run Commend
(only F04=002) Communication
2
0
1
Fre
q
uency
C55=000 or 002
C55=003
Figure 4-18 Communication error timing pattern
Page 72
Chapter 5 Trouble shooting and maintenance
5-1
Chapter 5 Troubleshooting and maintenance
5.1Trouble indication and corrective action
5.1.1 Fault/ Error display and Diagnostics
1. Un- reset able / un recoverable Errors
Display Error Cause Corrective Action
EEPROM
problem
EEPROM problem Change EEPROM
Over voltage during
stop
Voltage
Detection circuit malfunction
Repair or replace unit
Under voltage
during stop
1. Power voltage too low
2. Restraining resistor or fuse burnt out.
3. Detection circuit malfunctions
1. Check if the power voltage is correct or not
2. Replace the restraining resistor or the fuse
3. repair or replace unit
The inverter is
overheated during
stop
1. Thermal Detection circuit malfunction
2. Ambient temperature too high or bad ventilation
1. Repair or replace unit
2. Improve ventilation conditions
or relocate inverter
Current
transducer
detection error
Current transducer or circuit error.
Repair or replace unit
Note: “@” the Failure contact does not operate.
EPR
CTR
OV
@
LV
@
OH
@
Page 73
Chapter 5 Trouble shooting and maintenance
5-2
2. Errors which can be recovered both manually and automatically
Display Error Cause Corrective Action
Over current at
start
1.Motor winding and frame short circuit
2.Motor and ground short circuit
3.Power module is damaged
1. Check the motor
2. Check the wiring
3. Replace the power module
Over-current at
deceleration
The preset deceleration time is too short
Set a longer deceleration time
Over-current at
acceleration
1. Acceleration time is too short
2. The capacity of the motor is higher than the capacity of the inverter
3.Short circuit between the motor
winding and frame.
4.Short circuit between motor wiring and earth
5. IGBT module is damaged
1. Set a longer acceleration time
2. Replace the inverter with the same or greater capacit
y
as
that of the motor
3. Check the motor
4. Check the wiring
5. Replace the IGBT module
Over-current
during run
1. Transient load change
2. Transient power change
Increase inverter capacity
Over voltage
during
operation/
deceleration
1. Deceleration time setting is too short or excessive load inertia
2. Power voltage varies widely
1. Set a longer deceleration time
2. Add a braking resistor or
braking unit
3. Add a reactor at the input
line side
4.Increase inverter capacity
High heat sink
temperature
during
operation
1. Heavy load
2. Ambient temperature too hi
g
h
or bad ventilation
1. Check if there are any
problems with the load
2. Increase inverter capacity
3. Improve ventilation
conditions
4. Inspect the setting value of
parameter C13
OCS
OCD
OCA
OCC
OVC
OHC
Page 74
Chapter 5 Trouble shooting and maintenance
5-3
3. Errors which can only be recovered manually (no auto-restart)
Display Error Cause Corrective Action
Over-current
during stop
1. OC Detection circuit malfunction
2. Bad connection for CT signal cable
Send the inverter back for repair
Motor overload
1. Heavy load
2. Improper settings of F43
1. Increase motor capacity
2. Set F43 correctly according to motor nameplate.
Inverter overload Excessively heavy load Increase inverter capacity
Under voltage
during operation
1. Power voltage too low
2. Power voltage varies
widely
1. Improve power quality.
2. Set a longer acceleration time
3. Add a reactor at the power
input side
4. Contact technical support
Note: “@” means when the inverter fails, the failure contact does not activate.
OC
OL1
OL2
LVC
Page 75
Chapter 5 Trouble shooting and maintenance
5-4
5.1.2 Set up Configuration, Interface Errors.
Display Error Description
Zero speed stop Set frequency is <0.1Hz Increase set frequency
Fail to start
directly
1. If the inverter is set to external control mode (F04=001), and
direct start is disabled (C09=001), the inverter cannot be started and will flash STP1 when the Run switch is ON when applying power (see descriptions of C09).
2. Direct start is possible when C09=000.
Keypad
emergency stop
1. If the inverter is set to external control mode (F04=001), the
inverter will stop according to the setting of F9 when the stop key is pressed. STP2 flashes after stop. Turn the Run switch to OFF and then ON again to restart the inverter.
2. If the inverter is in communication mode and Stop key is enabled, the inverter will stop in the way set by F9 when Stop key is pressed during operation and then flashes STP2. The PC has to send a Stop command then a Run command to the inverter for it to be restarted.
External
emergency stop
The inverter will decelerate to stop and flashes E.S. when there is an external emergency stop signal via the multi-function input terminals(see descriptions of F11~F14).
External base
block
The inverter stops immediately and then flashes b.b. when external base block is input through the multi-functional input terminal (see descriptions of F11~F14).
PID feedback
signal loss
PID feedback signal circuit error detection
REMOTE
KEYPAD cable
broken
1. When REMOTE KEYPAD does not connect with inverter,
this signal will be displayed on the Remote keypad.
2. When REMOTE KEYPAD connects with inverter, this
signal will be displayed on the main keypad.
3. When both REMOTE KEYPAD and main KEYPAD display
this signal means communication errors.
b.b.
PID
———
SP2
E.S.
SP1
SP0
Page 76
Chapter 5 Trouble shooting and maintenance
5-5
5.1.3 Keypad operation error description
Display Error Cause Corrective Action
Key operation
error
1. Attempt to Press or
keys when F05> 0 or in speed operation.
2. Attempt to modify parameters, which can not be modified during Run (see parameter list).
1. or keys can be used
to modify frequencies only when F05=0.
2. Modify parameters only in
stop mode.
Parameter
setting error
1. F07 is within ranges of
C27±C29or C28±C29
2. F07<F08 or F07=F08
1. Modify F32~F33
2. 3-00>3-01
Modification of
parameter is not
allowed during
communication
1. Issue a control command during communication disabled
2. Modify C49~C53 during communication.
1. Issue the enabling command before while communicating.
2. Set up parameters before communicating.
Communication
failure
1. Incorrect wiring.
2. Incorrect settings of communication parameters.
3. Check-sum error.
4. Incorrect communication
verification.
1. Check the hardware and wiring.
2. Check C49~C53
Incorrect
parameter
settings
1. Attempt to modify F00
2. Voltage and current detection circuits are
malfunctioning.
Reset inverter or contact
technical support
Parameter set
error, Copy Unit
failure
1. Set C48=1.2, can not connect with Copy Unit.
2. Copy Unit failure.
3. The voltage and drive
rating on Copy Unit & the
inverter are different.
1.Modify C48
2. Change Copy Unit
3. Copy from keypad to
inverter with only matched HP ratings
Parameters do
not match
Copy the parameter to inverter to verify the parameter not matched.
1. Change Copy Unit
2. The voltage and HP
rating of Copy Unit is
different than the
inverter.
Er1
Er5
Er2
EP1
EP2
Er6
Er7
Page 77
Chapter 5 Trouble shooting and maintenance
5-6
5.2 General functional troubleshooting
Status Checking point Corrective Action
Is power applied to L1, L2, and L3(N)
terminals (is the charging indicator lit)?
Is the power applied?
Turn the power OFF and then ON
again.
Make sure the input line voltage is
correct.
Make sure all terminal screws are
secured firmly.
Are there voltage outputs on T1, T2, and T3 terminals?
Turn the power OFF and then ON again.
Is the motor mechanically overloaded?
Reduce the load to improve
performance.
Are there any problems with the inverter?
Has the forward or reverse run
commands been issued?
See error descriptions to check
wiring and correct if necessary.
Is there an analog input signal?
Is analog frequency input signal
wiring correct?
Is frequency input voltage correct?
Motor does not run
Is operation mode setting correct?
Configure operations through the
digital panel Are wiring for output terminals T1, T2, and T3 correct?
Wiring must match U, V, and W
terminals of the motor.
Motor rotates in
the wrong direction
Are wiring for forward and reverse signals correct?
Check wiring and correct if
necessary. Are wiring for output terminals T1, T2, and T3 correct?
Check wiring and correct if
necessary.
Is the setting of frequency command source correct?
Check the operation mode setting
on the keypad.
Motor rotates
in the wrong direction
The motor speed can not vary
Is the load too large?
Reduce the applied load.
Is the setting of operation mode correct? Confirm the motor’s specifications.
Is the load too large?
Confirm the gear ratio.
Motor running
at too high or
too low speeds.
Are specifications of the motor (poles, voltage…) correct?
Confirm the highest output
frequency.
Is the gear ratio correct? Reduce the load.
Is the setting of the highest output frequency correct?
Minimize the variation of the load.
Increase capacities of the inverter
and the motor.
Motor speed is
incorrect or erratic
Is the load too large?
Add an AC reactor at the power
input side if using single-phase
power.
Check wiring if using three-phase
power.
Page 78
Chapter 5 Trouble shooting and maintenance
5-7
5.3 Troubleshooting Flowcharts 7300EV Series
Is failure fully understood?
Any signs of burnout and
Is main loop I.G.B.T normal
Is the main circuit
diode intact?
Replace I.G.B.T
Replace Diode
Check
and replaceburnt
and damaged parts
Any abnormalities in appearances?
Are displays and indicators of the operating unit present?
Read fault?
Any fault display?
Check Fault log using
parameter F-54 with▼key.
Is the DC input voltage controlling the
p
owercorrectly?
Is +5V control voltage correct.
Is the error eliminated after replacing control board?
Replace the driver boar
d
Check terminals and
wiring
Repl
ace the Le
d
Perform detailedfault checks
* to next page
YES
YES
YES
YES
N
O
NO NO N
O
N
O
NONON
O
NON
O
YES
YES
YES
YES
YES
YES
YES
Repl
ace control board and
di
g
ital operating unit
N
O
YES
EV Inverter faults
Symptoms other than burn out, damage, or fuse meltdown in the inverter?
Fault
messages?
Check according to displayed
fault messages
Vi
sually check controller and
driver boards
Apply power
Any fault display?
Fault log F-54
Replace defective board
Is LED lit?
N
O
Figure 5-1 General troubleshooting flowchart
Page 79
Chapter 5 Trouble shooting and maintenance
5-8
* from previous page
Check parameters of the inverter
N
O
Perform parameter initializations
Specify operation control method
Set up frequency commands
Is the frequency value displayed in the operating unit
Is there any
drive faults
?
Are there voltage outputs in output terminals T1,T2 and T3.
Connect the motor to run
A
re output currents of each phase even?
The inverter is OK
Replace the control board
Replace the control
board
Is the control board working after re
p
lacement?
Perform detailed fault & function checks
NO NO N
O
YES
YES
YES
YES
YES
N
O
Figure 5-1 General troubleshootingflowchart, CONTD
Page 80
Chapter 5 Trouble shooting and maintenance
5-9
Troubleshooting for OC, OL error displays
Is the main circuit I.G.B.T. working properly?
A
ny
abnormalities in
appearances?
Any faults?
Replace the current sensing circuit
The inverter displays OC, OL errors
Apply power
Input operation commands
Replace I.G.B.T
Replace faulty circuit boards
Is the current detector OK?
Replace the control board
Replace the control board
N
O
N
O
YES
YES
Input frequency command.
I
s the output frequency of the operating unit displayed?
Are there voltage outputs at T1, T2, and T3 output terminals?
Connect the motor to run.
A
ny faults
displayed?
Are output currents of each
p
hase even?
The inverter’s output is OK
Replace the control board
Replace the control board
Is the control board working after
Perform detailed fault checks
YES
YES
YES
YES
N
O
NO N
O
N
O
NO
YES
YES
YES
Yes
No
No
The output frequency of the operating unit display?
No
Yes
Figure 5-2 OC, OL fault troubleshootin
g
Page 81
Chapter 5 Trouble shooting and maintenance
5-10
Troubleshooting for OV, LV error display
The inverter displays OV. LV
I
s the main circuit fuse intact?
Apply power
Fault message
Input operation commands
Input frequency commands
I
s the output frequency of the operating unit displayed?
Are there outputs on output terminals T1, T2, and T3?
motor running
Any Fault
Message
Are currents of all phases
The inverter is OK
Replace the main circuit board
Replace the control board
Replace the control board
Replace the control board
Is the inverter working after replacement?
Perform detailed Fault checks
YES
YES
YES
YES
N
O
N
O
NO N
O
NO
YES
YES
Yes
No
No
Figure 5-3 OV, Fault Troubleshooting
Page 82
Chapter 5 Trouble shooting and maintenance
5-11
Is MCCB
close
d
?
Can MCCB be
closed?
‘LED indicator
lit?
Check for short-circuited wiring
˙Bad power quality
˙or wiring incorrect
EV fault
Set switch to “RUN” position
EV fault
EV fault
YES (normal value within 3%)
YES (motor does not rotate), the phase-to phase voltage is within
3% for all motor leads.
˙Motor over load ˙Motor faults ˙wiring incorrect
YES
YES
NO N
O
Is the operation switch in RUN
p
osition?
N
O
NONONON
O
The motor doesn’t run
Is the voltage between
Leads correct?
Is there output? (Motor leads)
Are
Figure 5-4 Drive Running Troubleshooting diagnostics
Page 83
Chapter 5 Trouble shooting and maintenance
5-12
Motor is overheated
Motor runs unevenly
Is the measured load or the current exceeding the configured value?
Reduce the load Increase ratings of EV and the motor
Select a different motor
EV fault
Correct bad connection
Clear the debris
Bad connection between EV
and the motor
Is EV
running
in low speed for a long time
?
Are voltages between
p
hase even?
Is there any debris
p
reventing cooling
the motor?
YES
YES
YES
YES
YES (measured within +-3% of output
N
O
N
O
N
O
Does it occur when accelerating/ decelerating?
Is the load
freewheeling?
Any vibration or backlash in the
g
ears
Is the acceleration/deceler ation time correct
for the a
pp
lication?
Increase the acc/dec time
Reduce the load
Increase or ratings for
7300EV and the motor
EV faults
Reduce the freewheeling or
add a flywheel
Improve the mechanical system
EV Faults
YES (measured within +-3% of rated output voltage)
YES
YES
YES
NONO NO N
O
Small
Large
A
re output voltages
between
balanced?
No
Figure5-5 Motor Overload/Overheating Diagnostics
Figure5-6 Oneven Speed Operation Diagnostics
Page 84
Chapter 5 Trouble shooting and maintenance
5-13
5.4 Routine and periodic checks
To ensure stable and safe operations, check and maintain the inverter regularly and periodically. The table below lists the items to be check to ensure stable and safe operations. Check these items 5 minutes after the “Charge” indicator goes out to prevent injury to personnel.
Checking
period
Items Details
Daily 1 year
Methods Criteria Remedies
Confirm the temperature and humidity at the machine
Measure with
thermometer and hygrometer according to installation notices.
Temperature: -10 – 50
o
C (14~120oF) Humidity: Below 95% RH
Ambient conditions
around the
machine
Are there inflammable
materials in the vicinity?
Visual check Keep area clear
Improve the ambient
or relocate the drive to a better area.
Any unusual vibration from the machine
Visual, hearing
check
No vibration Secure screws
Installation and grounding of the inverter
Is the grounding resistance correct?
Measure the resistance with the Ground Resistor
200V series: below 100
400V series: below 10
Improve the grounding
Input power voltage
Is the voltage of the main circuit correct?
Measure the
voltage with a multi-tester
Voltage must conform with the specifications
Improve input voltage
Are secure parts loose?
Is the terminal base damaged?
External terminals and internal mounting screws of the inverter
Visual rust stains present?
Visual check Check with a screwdriver
Secure terminals and no rust
Secure or send back for repair
Any unusual bends or breaks?
Internal wiring of the inverter
Any damage of the wire
insulation?
Visual check No abnormalities
Replace or send back for repair
Heat sink Excessive dust or debris?
Visual check No abnormalities Clean up debris or
dust Conductive metal shavings or oil sludge present?
Printed circuit board
Discolored, overheated, or burned parts
Visual check No abnormalities
Clean or replace the
circuit board
Unusual vibration and noise
Visual or hearing check
Replace the cooling
fan
Cooling fan
Excessive dust or debris?
Visual check
No abnormalities
Clean fan
Excessive dust or debris? ○ Visual check No abnormalities Clean component
Power component
Check resistance between each terminals
Measure with a multi-tester
No short circuit or broken circuit in three-phase output
Replace power
component or
inverter Any unusual odor or leakage
Capacitor
Any deformity or protrusion
Visual check No abnormalities
Replace capacitor or
inverter
Page 85
Chapter 6 Peripherals
6-1
Chapter 6 Peripherals Components
6.1 Input side AC reactor
Line input side AC inductance Model
Current (A) inductance (mH)
2P2/2P5-H1(F)/H3 5.0 2.1
201-H1(F)/H3 5.0 2.1 202-H1(F)/H3 19.0 1.1 203-H1(F)/H3 25.0 0.71
401- H3(F)
2.5 8.4
402- H3(F) 5.0 4.2
JNEV-XXX-
HXX
403- H3(F) 7.5 3.6
6.2 EMC filter
The inverter adapts rapid switching components to improve the efficiency of the motor and to reduce the motor noise. Using the EMC Filter allows the EMI (Electromagnetic Interference) and RFI (Radio Frequency interference)to be controlled within a certain range.
EMC standard
The inverter with filter complies with EMC standard 89/336/EEC on electro­magnetic interruption and radio interference. The inverters with filter have passed following test and comply with the specified standard.
EMI radio standard and EMS immunity standa rd: EN 61800-3 1996/A11: 2000 : First Environment Unrestricted Distribution.
EN 61800-3 1996/A11: 2000 : First Environment Restricted Distribution.
Page 86
Chapter 6 Peripherals
6-2
Filter selection:
Inverter model Rated (INPUT)
Build in Filter model
(First Environment
Unrestricted Distribution./
Restricted Distribution.)
Optional Filter model
(First Environment
Unrestricted Distribution./
Restricted Distribution.)
1P2-H1 1 φ 85 ~132V ---------------
JNFS21017-20.8-07
(Restricted Distribution.)
1P5-H1 1 φ 85 ~132V ---------------
JNFS21017-20.8-07
(Restricted Distribution.)
101-H1 1 φ 85 ~132V ---------------
JNFS21017-20.8-07
(Restricted Distribution.)
2P2-H1 1 φ 170 ~264V ---------------
JNFS21017-20.8-07
(Restricted Distribution.)
2P5-H1 1 φ 170 ~264V ---------------
JNFS21017-20.8-07
(Restricted Distribution.)
201-H1 1 φ 170~264V ---------------
JNFS21017-20.8-07
(Restricted Distribution.)
2P2-H1F 1 φ 170~264V
Built in
(Unrestricted Distribution.)
---------------
2P5-H1F 1 φ 170 ~264V
Built in
(Unrestricted Distribution.)
---------------
201-H1F 1 φ 170 ~264V
Built in
(Unrestricted Distribution.)
---------------
2P2-H3 3 φ 170 ~264V ---------------
JNFS21019-8.9-07
(Restricted Distribution.)
2P5-H3 3 φ 170 ~264V ---------------
JNFS21019-8.9-07
(Restricted Distribution.)
201-H3 3 φ 170 ~264V ---------------
JNFS21019-8.9-07
(Restricted Distribution.)
202-H1 1 φ 170 ~264V ---------------
JNFS21015-22-07
(Unrestricted Distribution.)
203-H1 1 φ 170 ~264V ---------------
JNFS21015-22-07
(Unrestricted Distribution.)
202-H1F 1 φ 170 ~264V
Built in
(Unrestricted Distribution.)
---------------
203-H1F 1 φ 170 ~264V
Built in
(Unrestricted Distribution.)
---------------
202-H3 3 φ 170 ~264V ---------------
JNFS21016-15-07
(Unrestricted Distribution.)
203-H3 3 φ 170 ~264V ---------------
JNFS21016-15-07
(Unrestricted Distribution.)
401-H3 3 φ 323~528 V ---------------
JNFS20858-7-07
(Restricted Distribution.)
402-H3 3 φ 323~528 V ---------------
JNFS20858-7-07
(Restricted Distribution.)
403-H3 3 φ 323~528 V ---------------
JNFS20858-7-07
(Restricted Distribution.)
401-H3F 3 φ 323~528 V
Built in
(Restricted Distribution.)
---------------
402-H3F 3 φ 323~528 V
Built in
(Restricted Distribution.)
---------------
JNEVXXX
-HXX
403-H3F 3 φ 323~528 V
Built in
(Restricted Distribution.)
---------------
Page 87
Chapter 6 Peripherals
6-3
EV EXTERNAL FILTER SIZE
z JNFS21017-20.8-07 FOR EV-1P2~201-H1
z JNFS21019-8.9-07 FOR EV-2P2~201-H3
Figure 6-1a External Filter Dimensions JNFS21017-20.8-07
Figure 6-1b External Filter Dimensions JNFS21019-8.9-07
Page 88
Chapter 6 Peripherals
6-4
z JNFS21015-22-07 FOR EV-202~203-H1
z JNFS21016-15-07 FOR EV-202~203-H3
Figure 6-1c External Filter Dimensions JNFS21015-22-07
Figure 6-1d External Filter Dimensions JNFS21016-15-07
Page 89
Chapter 6 Peripherals
6-5
z JNFS20858-7-07 FOR EV-401~403-H3
Figure 6-1e External Filter Dimensions JNFS20858-7-07
Page 90
Chapter 6 Peripherals
6-6
6.3 Option card
6.3.1 RS-485 option card (Model: JNSIF-485)
JNSIF-485 wiring diagram:
Note :
In order to avoid external static electricity interference with option cards function, please replace
cover of the inverter after installing option cards.
Please use isolated RS232 / RS485 converter connections with PC and option card to avoid
equipment damage.
Red cable to 24V Black cable to COM
Figure 6-2 JNSIF-485 MODULE
Figure 6-3 JNSIF-485 wiring diagram
Page 91
Chapter 6 Peripherals
6-7
6.3.2 RS-232 option card (model: JNSIF-232)
JNSIF-232 wiring diagram
1.8 m
RS-232
7300EV SERIES
INVERTER
M
JNSIF-232
CON302 (12P)
SINGLE/THREE-PHASE
POWER SUPPLY
L1 (L) T1 L2 T2 L3 (N) T3
Figure 6-4a JNSIF-232 CABLE
Fi
g
ure 6-4b JNSIF-232 WIRING DIAGRAM
Page 92
Chapter 6 Peripherals
6-8
6.3.3program copy option card (Copy Unit) (model: JNSIF-MP)
JNSIF-MP Wiring diagram
Copy Unit
L1 (L) T1 L2 T2 L3 (N) T3
7300EV
SERIES
INVERTER
JNSIF-MP
CON302 (12P)
M
SINGLE/THREE-PHASE POWER SUPPLY
Figure 6-5a JNSIF-MP MODULE
Fi
g
ure 6-5b JNSIF-MP wiring diagra
m
Page 93
Chapter 6 Peripherals
6-9
6.3.4 Remote keypad (Remote keypad)( M o d e l : J N S D O P - L E D - 2 M )
JNSDOP-LED-2M wiring diagram
* When the inverter is powered on or off the user can set up or remove the remote
keypad. (Must be in remote terminal configuration)
2M
Red cable to 24V Black cable to COM
Figure 6-6a Remote keypad
Figure 6-6b Remote keypad Wiring Diagram
Page 94
Chapter 6 Peripherals
6-10
6.3.5 Input/ Output expansion card(model: JNSIF-IO)
JNSIF-IO wiring diagram
Red cable to 24V Black cable to COM
CON302(12P)
Figure 6-7a JNSIF-IO CARD
Figure 6-7b JNSIF-IO Wiring Diagram
Page 95
Chapter 6 Peripherals
6-11
6.3.6 PDA Link
(1) HP iPAQ Pocket PC h2210. (PDA) / PC hx2190 (2) PDA wire (JNSWPDA). (3) RS-232 Interface Card (JNSIF-232). (4) Inverter
Page 96
Appendix
Appendix Ι
Appendix EVinverter parameter setting list
Customer Name
Model of the inverter:
Location of use:
Customer’s telephone number:
Customer’s address:
Parameter code Setting
Parameter
code
Setting
Parameter
code
Setting
F00 F38 C22 F01 F39 C23 F02
F40
C24 F03 F41 C25 F04 F42 C26 F05 F43 C27 F06 F44 C28 F07 F45 C29 F08 F46 C30 F09 F47 C31 F10 F48 C32 F11 F49 C33 F12 F50 C34 F13 F51 C35 F14 F52 C36 F15 F53 C37 F16 F54 C38 F17 C01 C39 F18 C02 C40 F19 C03 C41 F20 C04 C42 F21 C05 C43 F22 C06 C44 F23 C07 C45 F24 C08 C46 F25 C09 C47 F26 C10 C48 F27 C11 C49 F28 C12 C50 F29 C13 C51 F30 C14 C52 F31 C15 C53 F32 C16 C54 F33 C17 C55 F34 C18 F35 C19 F36 C20 F37 C21
Loading...