ISSUED
10/28/2016
TYPE
ASGHJM
PERFORMANCE DATA
3-PHASE INDUCTION MOTOR
NAMEPLATE INFORMATION
OUTPUT
HP KW
2 1.49
FRAME
SIZE
6
184T
VOLTS
230/460
HZPOLE
60
RATED
AMBIENT
40oC
TYPICAL PERFORMANCE
FULL
LOAD
RPM MIN% NOM%
FULL LOAD
EFFICIENCY
3/4 LOAD%1/2 LOAD
%
FULL LOAD
%
1165 85.5 87.5 86.0 83.0
CURRENTS
NO LOAD FULL LOAD LOCKED ROTOR
AT
200
VOLT
AT
208
VOLT
AT
230
VOLT
AT
460
VOLT
AT
200
VOLT
AT
208
VOLT
AT
230
VOLT
VOLT
4.23 4.58 5.60 2.80 8.64 8.30 7.51 3.76
ENCLOSURE
ODP
CATALOG#
DJMP0026
INS.
CLASS
NEMA
DESIGN
TIME
RATING
F B CONT.
POWER FACTOR MAXIMUM
3/4 LOAD%1/2 LOAD
%
POWER FACTOR
CORRECTION
SERVICE
FACTOR
1.15
KVAR57.0 48.0 36.0 1.90
AT
460
AT
200
VOLT
AT
208
VOLT
43.5 45.2
AT
230
VOLT
AT
460
VOLT
50.0 25.0
LETTER
NEMA
KVA
CODE
L
TORQUE
FULL
LOAD
lb-ft
LOCKED
ROTOR
%FLT
PULL
UP
%FLT
BREAK
DOWN
%FLT
9.01 160 110 240
SAFE STALL
TIME IN
SECONDS
COLD
HOT COLD HOT
ALLOWABLE
STARTS
PER HOUR
64 45 2 1
APPROVED:
M. PRATER
ROTOR
2
WR
2
lb-ft
SOUND
PRESSURE
LEVEL @ 3 FT
dB(A)
52
DRAWING NO.
INERTIA
LOAD
WK
ALLOWABLE
2
2
ACCEL TIME
WK
2
2
LOAD
WK
Sec.
6.70
ALLOWABLE
2
WK
Sec.
19.960.346 30 90
2
31057DJMP0026
REV.
0

DATE: CATALOG NO.:
June 17, 2005
CONNECTION DIAGRAM
SCHEMATIC - 2Y/Y CONNECTION
DJMP0026
ACROSS THE LINE CONNECTION
LINE
230 VOLT CONNECTION
LINE
460 VOLT CONNECTION
DWG NO.
DAC-1566-2

INSTALLATION AND
MAINTENANCE INSTRUCTIONS
FOR THREE PHASE
INDUCTION MOTORS
Frames 56 and 143T - 449TZ