ISSUED
05/07/07
TYPE
ASHH
PERFORMANCE DATA
3-PHASE INDUCTION MOTOR
NAMEPLATE INFORMATION
OUTPUT
HP KW
250 187 60
POLE
2
FRAME
SIZE
445TS
VOLTAGE
460
TYPICAL PERFORMANCE
FULL
LOAD
RPM
FULL LOAD
MIN. % NOM. %
EFFICIENCY
3/4 LOAD
%
1/2 LOAD
94.1 95.0 94.6 93.5
HZ
RATED
AMBIENT
40oC
%
INS.
CLASS
F
POWER FACTOR
F. L.
%
88.5
3/4 LOAD%1/2 LOAD
87.7 86.9
NEMA
DESIGN
B
ENCLOSURE
CATALOG#
DHP2502
TIME
RATING
CONT.
POWER FACTOR
%
CORRECTION
ODP
SERVICE
FACTOR
1.15
MAXIMUM
KVAR523550
CURRENTS
NO LOAD FULL LOAD
64.9 278
TORQUE
FULL LOAD
lb-ft
LOCKED
ROTOR
%FLT
PULL
UP
%FLT
370 105 97
SAFE STALL
TIME IN
SECONDS
COLD HOT
ALLOWABLE
STARTS
PER HOUR
COLD
19 14
APPROVED: REVISION
M. PRATER
LOCKED ROTOR
1825
BREAK
DOWN
%FLT
ROTOR
WR
lb-ft
18
SOUND
PRESSURE
LEVEL @ 3 FT
HOT
dB(A)
DRAWING NO.
2
2
8621
NEMA KVA
CODE LETTER
G
INERTIA
NEMA
LOAD
2
WK
2
lb-ft
210
MAX
ALLOWABLE
WK
lb-ft
2
2
210
3A057DHP2502
ACCEL TIME
NEMA
LOAD
WK
Sec
ALLOWABLE
2
4.53210 4.53
MAX
WK
Sec
2
0
Loading...