TECO A510s Instruction Manual

Page 1
Page 2
I
Table of Contents
Preface ........................................................................................................................................................... 0-1
1.1 Before Supplying Power to the Inverter ...................................... . ............................................................. 1-1
1.2 Wiring ............................................................ .... ... .... .... .... .... ... .... .... ....... .... .... .... ..................................... .. 1-2
1.3 Before Operation ............ ....... .... .... .... ... .... .... .... ... .... .... .... ... ........ .... ... .... .... .... .... .... ... ................................ 1-3
1.4 Parameters Setting ........................................... ... .... .... .... ... .... .... .... .... ....... .... .... .... ... .... ............................ 1-3
1.5 Operation ...................................................... .... ... .... .... ....... .... .... .... .... ... .... .... .... .... ................................... 1-4
1.6 Maintenance, Inspection and Replacement ........................... .... .... ....... .... .... .... ... .... ........ .... ... .... ............. 1-5
1.7 Disposal of the Inverter ........................................................... .... .... .... ... .... .... .... ....... .... ............................ 1-5
2.1 Nameplate Data .......................................................................... .... .... ... .... .... .... ... .................................... 2-1
2.2 Inverter Models – Motor Power Rating (HD-Heavy Duty) ........................................................................ 2-2
Chapter 3 Environment and Installation .............................................................. ....................................... 3-1
3.1 Environment .............................................................................................................................................. 3-1
3.2 Installation ................................................................................................................................................. 3-2
3.3 External View .............................................................................. .... .... ... .... .... .... ... .... ................................ 3-3
3.4 Warning Labels ................................................................ ... .... .... .... .... ... ........ .... ... .... ................................ 3-5
3.5 Removing the Front Cover and Keypad ................................................................................................... 3-6
3.5.1 Standard type ................................................................................... ........ ... .... .... .... ........................ 3-6
3.5.2 Built-in filter type (400V 1 ~60HP) ................................................ .............................................. ... 3-12
3.6 Wire Gauges and Tightening Torque ........... .... ... .... .... .... .... ... .... .... .... ... .... .... .... ... ........ .... .... ... ............... 3-13
3.7 Wiring Peripheral Power Devices ............................................... ............................................................ 3-14
3.8 General Wiring Diagram ................................................................. .... ... .... .... .... ... .... .... .... ...................... 3-19
3.9 User Terminals .......................... .... .... ... .... ........ ... .... .... .... ... .... .... .... .... ... ........ .... ... .... .............................. 3-20
3.10 Power Terminals ................................................................................................................................... 3-24
3.11 Input / Output Section Block Diagram .................................................................................................. 3-29
3.11.1 Cooling Fan Supply Voltage Selection (400V class) ......................................................................... 3-33
3.12 Inverter Wiring ................................................................................................................................... ... 3-35
3.13 Input Power and Motor Cable Length ..................................................................... .... .... .... ... ............... 3-36
Page 3
II
3.14 Cable Length vs, Carrier Frequency ............................................. ............................................. ........... 3-36
3.15 Installing an AC Line Reactor ............................................................................................................... 3-36
3.16 Power Input Wire Size, NFB and MCB Part Numbers ......................................................................... 3-37
3.17 Control Circuit Wiring ..................................................... ....................................................................... 3-39
3.18 Inverter Specifications ....................................... ................................................................................... 3-41
3.19 Inverter Derating Based on Carrier Frequency .................................................................................... 3-48
3.20 Inverter Derating Based on Temperature ............................................................................................. 3-51
3.21 Inverter Dimensions .............................................................................................................................. 3-52
3.22 Dimensions for Models with Built-in Filter ............................................................................................ 3-61
Chapter 4 Keypad and Programming Functions ................................................ ... .... .... .... .... ... .... ........ ..... 4-1
4.1 LED Keypad ............................................................................................................................................ .. 4-1
4.1.1 Keypad Display and Keys ............................................................................... .... .... .... ... ................. 4-1
4.1.2 Seven Segment Display Description ............................................................................................... 4-3
4.1.3 LED Indicator Description ............... .... .... ... .... .... .... .... ... .... .... .... ... ........ .... ... .... .... .... .... ... ................. 4-5
4.1.4 Power-up Monitor ............................................................................. ........ ... .... .... .... ... ..................... 4-7
4.1.5 Modifying Parameters/ Set Frequency Reference ........................................................................ .. 4-8
4.1.6 Operation Control ......................................................................... .... .... .... ... .... ........ ...................... 4-10
4.2 LCD Keypad (Option) ............................................................................................................................. 4-11
4.2.1 Keypad Display and Keys ............................................................................... .... .... .... ... ............... 4-11
4.2.2 Keypad Menu Structure ................................................................................................................ 4-13
4.3 Parameters .................................... ... ........ .... .... ... .... .... .... .... ... .... .... .... ... .... ........ ... .... .............................. 4-18
4.4 Description of Parameters ...................................................................................................................... 4-85
4.5 Built-in PLC Function ........................................ ....... .... .... .... ... .... .... .... ... .... .... .... ... .... .... ........................ 4-318
4.5.1 Basic Command ................................................................................... .... .... ... .... .... .... ................ 4-318
4.5.2 Basic Command Function ................................................. .... .... ... .... .... .... ....... .... .... .... ... ............. 4-319
4.5.3 Application Functions .................................................... .... .... .... ... .... .... .... .... ... .... .... .................... 4-320
4.6 Modbus Protocol Descriptions ........................................................................... .... ... .... .... .................... 4-329
4.6.1 Communication Connection and Data Frame ............................................................................. 4-329
4.6.2 Register and Data Format ........................................................................................................... 4-333
4.6.3 Parameter Data .................................................................................... .... .... ... .... ........................ 4-342
4.7 Profibus Communication Protocol ....................................... ... .... .... .... ... ........ .... ... .... .... .... ... ................. 4-353
4.7.1 Descriptions .................................... .... .... ... .... .... .... ....... .... .... .... ... .... .... .... ... .... .... ........................ 4-353
4.7.2 Specifications ................................................................ .... .... ... .... .... .... .... ... .... .... ........................ 4-353
4.7.3 Wiring .................................................................................... ... .... .... .... .... .... ... ............................ 4-354
Page 4
III
4.7.4 Installation & Setting ................................................................................................................... 4-354
4.7.5 Descriptions of Terminals, LED and DIP switch ......................................................................... 4-356
4.7.6
Parameter setting .................................................................................... ... .... .... ........ ... ............. 4-357
4.7.7 Profibus I/O List ................................................................. .... .... ... ........ .... .... ... .... ........................ 4-357
4.7.8 Error Messages List .................................................................................................................... 4-362
4.7.9 GSD File ................................................................. ... .... .... .... ... .... .... ........ .... ... .... .. .. .................... 4-362
Chapter 5 Check Motor Rotation and Direction ......................................................................................... 5-1
Chapter 6 Speed Reference Command Configuration .............................................................................. 6-1
6.1 Reference from the Keypad ........................................................................... ............................................ 6-1
6.2 Reference from External Analog Signal (0-10V / 4-20mA) ........................................................................ 6-2
6.3 Reference from Serial Communication RS485 ............... ....... .... .... .... ... .... .... .... ... ........ .... ... .... .... .... .......... 6-4
6.4 Reference from Pulse Input ....................................................................................................................... 6-6
6.5 Reference from two Analog Inputs ............................................................................................................ 6-7
6.6 Change Frequency Unit from Hz to rpm ............................................. ....................................................... 6-7
Chapter 7 Operation Method Configuration (Run / Stop) .......................................................................... 7-1
7.1 Run / Stop from the LED/ LCD Keypad ..................................................................................................... 7-1
7.2 Run / Stop from External Switch / Contact or Pushbutton ......................................................................... 7-2
7.3 Run / Stop from Serial Communication RS485 ......................................................................................... 7-4
Chapter 8 Motor and Application Specific Settings ................................................................................... 8-1
8.1 Set Motor Nameplate Data ........................................................................ .... .... ... .... .... ............................. 8-1
8.2 Acceleration and Deceleration Time .................................................................................................... ...... 8-2
8.3 Torque Compensation Gain ...................................................................................................................... 8-3
8.4 Automatic Energy Saving Functions .......................................................................................................... 8-4
8.5 Emergency Stop ................................... .... .... .... ... .... .... .... .... ... .... .... .... ....... .... .... ... .... .... ............................. 8-6
8.6 Forward and Reverse Jog ....................................... .... .... .... ... .... .... .... ... .... .... .... ... .... .... .... ......................... 8-7
8.7 Direct / Unattended Startup ....................................................................................................................... 8-7
8.8 Analog Output Setup ................................................................................................................................. 8-8
Page 5
IV
Chapter 9 Using PID Control for Constant Flow / Pressure Applications ............................................... 9-1
9.1 What is PID Control ............................................................................... .... ........ ... .... .... ............................. 9-1
9.2 Connect Transducer Feedback Signal .................................................................................................... 9-3
9.3 Engineering Units ............... ... .... ........ ... .... .... .... ... .... .... .... .... ... .... .... ....... .... .... .... .... ... ................................. 9-4
9.4 Sleep / Wakeup Function ................................. ... .... .... .... ... ........ . ....... ... .... .... .... ... .... .... .... ......................... 9-5
Chapter 10 Troubleshooting and Fault Diagnostics ............................................................................... 10-1
10.1 General .......................................................................................................................................... ....... 10-1
10.2 Fault Detection Function ....................................................................................................................... 10-1
10.3 Warning / Self-diagnosis Detection Function ....................................................................................... 10-7
10.4 Auto-tuning Error ................................................................................................................................ 10-15
10.5 PM Motor Auto-tuning Error ................................................................................................................ 10-16
Chapter 11 Inverter Peripheral Devices and Options .................................... ....... .... .... .... .... ... .... .... .... .. . 11-1
11.1 Braking Resistors and Braking Units .................................................................................................... 11-1
11.2 AC Line Reactors .................................................................................................................................. 11-4
11.3 Input Noise Filters ................................................................. .... .... .... ... ........ .... .... ... .............................. 11-6
11.4 Input Current and Fuse Specifications ............................. ................................... .......................... ....... 11-8
11.5 PG Speed Feedback Card ................................................................................................................. 11-10
11.6 Other Options ..................................................................................................................................... 11-14
11.7
Communication Options ................................................... ................................................................. 11-17
Appendix A: Communication Networks ................................................................................................... A1-1
A1.1 RS485-- Network (Modbus) ................................................................................................................. A1-1
A1.2 Profibus DP Network ................................................. ....... .... .... .... .... ... .... .... .... .... ... .............................. A1-2
Appendix B: UL Instructions ....................................................................................................................... B-1
Page 6
0-1
Preface
The A510S product is an inverter designed to control a three-phase induction motor. Please read this manual carefully to ensure correct operation, safety and to become familiar with the inverter functions.
The A510S inverter is an electrical / electronic product and must be installed and handled by qualified service personnel.
Improper handling may result in incorrect operation, shorter life cycle, or failure of this product as well as the motor.
All A510S documentation is subject to change without notice. Be sure to obtain the latest editions for use or visit our website at http://globalsa.teco.com.tw
Available Documentation:
1. A510S Start-up and Installation Manual
2. A510S Instruction Manual
Ensure you have sound knowledge of the device and familiarize yourself with all safety information and precautions before proceeding to operate the inverter.
Ensure you have sound knowledge of the inverter and familiarize yourself with all safety information and precautions before proceeding to operate the inverter.
Please pay close attention to the safety precautions indicated by the warning
and
caution
symbol.
Warning
Failure to ignore the information indicated by the warning symbol may result in death or serious injury.
Caution
Failure to ignore the information indicated by the caution symbol may result in minor or moderate injury and/or substantial property damage.
Page 7
1-1
Chapter 1 Safety Precautions
1.1 Before Supplying Power to the Inverter
Warning
The main circuit must be correctly wired. For single phase supply use input terminals (R/L1, T/L3) and for three phase supply use input terminals (R/L1, S/L2, T/L3). Terminals U/T1, V/T2, W/T3 must only be used to connect the motor. Connecting the input supply to any of the U/T1, V/T2 or W/T3 terminals will cause damage to the inverter.
Caution
To avoid the front cover from disengaging or other physical damage, do not carry the
inverter by its cover. Support the unit by its heat sink when transporting. Improper handling can damage the inverter or injure personnel, and should be avoided.
To avoid the risk of fire, do not install the inverter on or near flammable objects. Install on
nonflammable objects such as metal surfaces.
If several inverters are placed inside the same control panel, provide adequate
ventilation to maintain the temperature below 40°C/104°F (50°C/122°F) without a dust cover) to avoid overheating or fire.
When removing or installing the digital operator, turn off the power first, and then follow the
instructions in this manual to avoid operator error or loss of display caused by faulty connections.
Warning
This product is sold subject to IEC 61800-3. In a domestic environment this product may
cause radio interference in which case the user may need to apply corrective measures.
Motor over temperature protection is not provided.
Page 8
1-2
1.2 Wiring
Warning
Always turn OFF the power supply before attempting inverter installation and wiring of
the user terminals.
Wiring must be performed by a qualified personnel / certified electrician.
Make sure the inverter is properly grounded. (200V Class: Grounding impedance shall
be less than 100. 400V Class: Grounding impedance shall be less than 10Ω.)
Make sure the inverter is properly grounded. It is required to disconnect the ground wire
in the control board to avoid the sudden surge causing damage on electronic parts if it is
improperly grounded.
RCD is required to be in compliance with the protection norm of B-type leakage current.
Please check and test emergency stop circuits after wiring. (Installer is responsible for
the correct wiring.)
Never touch any of the input or output power lines directly or allow any input of output power
lines to come in contact with the inverter case.
Do not perform a dielectric voltage withstand test (megger) on the inverter this will result in
inverter damage to the semiconductor components.
Caution
The line voltage applied must comply with the inverter’s specified input voltage. (See
product nameplate section 2.1)
Connect braking resistor and braking unit to the designated terminals. (See section 3.10)
Do not connect a braking resistor directly to the DC terminals P (+) and N (-), otherwise fire
may result.
Use wire gauge recommendations and torque specifications. (See Wire Gauge and Torque
Specification in section 3.6)
Never connect input power to the inverter output terminals U/T1, V/T2, W/T3.
Do not connect a contactor or switch in series with the inverter and the motor.
Do not connect a power factor correction capacitor or surge suppressor to the inverter
output.
Ensure the interference generated by the inverter and motor does not affect peripheral
devices.
Page 9
1-3
1.3 Before Operation
Warning
Make sure the inverter capacity matches the parameters 13-00.
Reduce the carrier frequency (parameter 11-01) If the cable from the inverter to the
motor is greater than 80 ft (25m). A high-frequency current can be generated by stray capacitance between the cables and result in an overcurrent trip of the inverter, an increase in leakage current, or an inaccurate current readout.
Be sure to install all covers before turning on power. Do not remove any of the covers while
power to the inverter is on, otherwise electric shock may occur.
Do not operate switches with wet hands, otherwise electric shock may result.
Do not touch inverter terminals when energized even if inverter has stopped, otherwise
electric shock may result.
1.4 Parameters Setting
Caution
Do not connect a load to the motor while performing a rotational auto-tune.
Make sure the motor can freely run and there is sufficient space around the motor when
performing a rotational auto-tune.
Page 10
1-4
1.5 Operation
Warning
Be sure to install all covers before turning on power. Do not remove any of the covers while
power to the inverter is on, otherwise electric shock may occur.
Do not connect or disconnect the motor during operation. This will cause the inverter to
trip and may cause damage to the inverter.
Operations may start suddenly if an alarm or fault is reset with a run command active.
Confirm that no run command is active upon resetting the alarm or fault, otherwise accidents may occur.
Do not operate switches with wet hands, otherwise electric shock may result.
It provides an independent external hardware emergency switch, which emergently shuts
down the inverter output in the case of danger.
If automatic restart after power recovery (parameter 07-00) is enabled, the inverter will start
automatically after power is restored.
Make sure it is safe to operate the inverter and motor before performing a rotational
auto-tune.
Do not touch inverter terminals when energized even if inverter has stopped, otherwise
electric shock may result.
Do not check signals on circuit boards while the inverter is running.
After the power is turned off, the cooling fan may continue to run for some time.
Caution
Do not touch heat-generating components such as heat sinks and braking resistors.
Carefully check the performance of motor or machine before operating at high speed,
otherwise Injury may result.
Note the parameter settings related to the braking unit when applicable.
Do not use the inverter braking function for mechanical holding, otherwise injury may
result.
Do not check signals on circuit boards while the inverter is running.
Page 11
1-5
1.6 Maintenance, Inspection and Replacement
Warning
Wait a minimum of five minutes after power has been turned OFF before starting an
inspection. Also confirm that the charge light is OFF and that the DC bus voltage has dropped below 25Vdc.
Never touch high voltage terminals in the inverter.
Make sure power to the inverter is disconnected before disassembling the inverter.
Only authorized personnel should perform maintenance, inspection, and replacement
operations. (Take off metal jewelry such as watches and rings and use insulated tools.)
Caution
The Inverter can be used in an environment with a temperature range from 14°
~104(140) °F (-10~+40(60)°C) and relative humidity of 95% non-condensing.
The inverter must be operated in a dust, gas, mist and moisture free environment.
1.7 Disposal of the Inverter
Caution
Please dispose of this unit with care as an industrial waste and according to your
required local regulations.
The capacitors of inverter main circuit and printed circuit board are considered as
hazardous waste and must not be burned.
The Plastic enclosure and parts of the inverter such as the top cover board will release
harmful gases if burned.
Page 12
2-1
Chapter 2 Model Description
2.1 Nameplate Data
It is essential to verify the A510S inverter nameplate and make sure that the A510S inverter has the correct rating so it can be used in your application with the proper sized AC motor.
Unpack the A510S inverter and check the following:
(1) The A510S inverter and start-up and installation manual are contained in the package. (2) The A510S inverter has not been da maged during transportation there sho uld be no de nts or parts
missing.
(3) The A510S inverter is the type you ordered. You can check the type and specifications on the main
nameplate. (4) Check that the input voltage range meets the input power requirements. (5) Ensure that the motor HP matches the motor rating of the inverter.
HD: Heavy Duty (Constant Torque); ND: Normal Duty (Variable Torque) (1HP = 0.746 kW)
Product Na m e & Motor Rating
Input Power Specifications Out put P owe r Spec ific a t ions
Series No
UL and CE Marks
Code No
(P/N Bar code) (S/N Bar code)
Model Identification
Page 13
2-2
2.2 Inverter Models – Motor Power Rating (HD – Heavy Duty)
200V Class
Voltage A510S Model
Applied
Motor
(HP)
Applied
Motor
(KW)
Filter
with without
1ph/3ph,
200~240V
+10%/-15%
50/60Hz
A510-2001-SH
1
0.75
A510-2002-SH
2
1.5
A510-2003-SH
3
2.2
3ph, 200~240V
+10%/-15%
50/60Hz
A510-2005-SH3
5
3.7
A510-2008-SH3
7.5
5.5
A510-2010-SH3
10
7.5
A510-2015-SH3
15
11
A510-2020-SH3
20
15
A510-2025-SH3
25
18.5
A510-2030-SH3
30
22
A510-2040-SH3
40
30
A510-2050-SH3
50
37
A510-2060-SH3
60
45
A510-2075-SH3
75
55
A510-2100-SH3
100
75
A510-2125-SH3
125
94
A510-2150-SH3
150
112
Short Circuit Rating: 200V Class: 5kA
Page 14
2-3
400V Class
Voltage A510S Model
Applied
Motor
(HP)
Applied
Motor
(KW)
Filter
with without
3ph, 380~480V
+10%/-15%
50/60Hz
A510-4001-SH3
1 0.75
A510-4001-SH3F
1 0.75
A510-4002-SH3
2 1.5
A510-4002-SH3F
2 1.5
A510-4003-SH3
3 2.2
A510-4003-SH3F
3 2.2
A510-4005-SH3
5 3.7
A510-4005-SH3F
5 3.7
A510-4008-SH3
7.5 5.5
A510-4008-SH3F
7.5 5.5
A510-4010-SH3
10 7.5
A510-4010-SH3F
10 7.5
A510-4015-SH3
15 11
A510-4015-SH3F
15 11
A510-4020-SH3
20 15
A510-4020-SH3F
20 15
A510-4025-SH3
25 18.5
A510-4025-SH3F
25 18.5
A510-4030-SH3
30 22
A510-4030-SH3F
30 22
A510-4040-SH3
40 30
A510-4040-SH3F
40 30
A510-4050-SH3
50 37
A510-4050-SH3F
50 37
A510-4060-SH3
60 45
A510-4060-SH3F
60 45
A510-4075-SH3
75 55
A510-4100-SH3
100 75
A510-4125-SH3
125 94
A510-4150-SH3
150 112
A510-4175-SH3
175 130
A510-4215-SH3
215 160
A510-4270-SH3 270 200
A510-4300-SH3
300 220
A510-4375-SH3
375 280
A510-4425-SH3
425 315
Short Circuit Rating: 400V Class: 5kA
Page 15
2-4
575/690V Class
Voltage A510S Model
Applied
Motor
(HP)
Applied
Motor
(KW)
Filter
with without
3ph, 575V
+10%/-15%
50/60Hz
A510-5001-SH3 1 0.75
A510-5002-SH3 2 1.5
A510-5003-SH3 3 2.2
A510-5005-SH3 5 3.7
A510-5008-SH3 7.5 5.5
A510-5010-SH3 10 7.5
3ph, 575~690V
+10%/-15%
50/60Hz
A510-6015-SH3 15 11
A510-6020-SH3 20 15
A510-6025-SH3 25 18.5
A510-6030-SH3 30 22
A510-6040-SH3 40 30
A510-6050-SH3 50 37
A510-6060-SH3 60 45
A510-6075-SH3 75 55
A510-6100-SH3 100 75
A510-6125-SH3 125 94
A510-6150-SH3 150 112
A510-6175-SH3 175 130
A510-6215-SH3 215 160
A510-6250-SH3 250 185
A510-6270-SH3 270 200
Short Circuit Rating: 575/690V Class: 5kA
Page 16
3-1
Chapter 3 Environment and Installation
3.1 Environment
The environment will directly affect the proper operation and the life span of the invert er. To ensure
that the inverter will give maximum service life, please comply with the following environmental
conditions:
Protection Protection Class
IP20/NEMA 1 or IP00
Operating Temperature
Ambient Temperature: (-10°C - +40°C (14 -104 °F) Without Cover: -10°C - +50°C (14-122 °F);
but it is required to derate 2% of
current at each additi onal 1
°C. The maximum operating temperature is 60°C. If several inverters are placed in the same control panel, provide a heat removal means to maintain ambient t emperatures below 40°C
Storage Temperature
-20°C - +70°C (-4 -158 °F)
Humidity
95% non-condensing Relative humidity 5% to 95%, free of moisture. (Follow IEC60068-2-78 standard)
Altitude
Altitude: Below 1000 m (3281 ft.) It is required to derate 1% of current at each additional 100 m. The maximum altitude is 3000 m.
Installation Site
Avoid exposure to rain or moisture. Avoid direct sunlight. Avoid oil mist and salinity. Avoid corrosive liquid and gas. Avoid dust, lint fibers, and small metal filings. Keep away from radioactive and flammable materials. Avoid electromagnetic interference (soldering machines, power machines). Avoid vibration (stamping, punching machines etc.).
Add a vibration-proof pad if the situation cannot be avoided.
Shock
Maximum acceleration: 1.0G (9.8m/s²), from 49.84 to 150 Hz Displacement amplitude : 0.3mm (peak value), from 10 to 49.84 Hz (Follow IEC60068-2-6 standard)
Page 17
3-2
3.2 Installation
When installing the inverter, ensure that inverter is installed in upright position (vertical direction) and there is adequate space around the unit to allow normal heat dissipation as per the following Fig. 3.2.1
5.9in.
150mm
X
5.9in.
150mm
Air Flow
Ambient
temperature
-10 to +40°C
5.9in.
150mm
X
5.9in.
150mm
Fig 3.2.1: A510S Installation space
X = 1.18” (30mm) for inverter ratings up to 25HP X = 1.96” (50mm) for inverter ratings 30HP or higher
Important Note: The inverter heatsink temperature can reach up to 194°F / 90°C during operation; make sure to
use insulation material rated for this temperature.
Page 18
3-3
3.3 External View
(a) 200V 1 ~ 7.5 HP / 400V 1 ~ 7.5 HP / 575V 1~ 3 HP
Mounting Hole
Rings (4 rings)
Nameplate
and Barcode
Terminal Cover
Digital Operator
Front Cover
Fan Cover
Anti-dust Cover
(Wall-mounted type, IEC IP20) (Wall-mounted type, IEC IP20, NEMA1)
(b) 200V 10 ~ 25 HP / 400V 10 ~ 30 HP / 575V 5~10HP / 690V 15~40HP
(Wall-mounted type, IEC IP20) (Wall-mounted type, IEC IP20, NEMA1)
Page 19
3-4
(c) 200V 30 ~ 40 HP / 400V 40 ~ 75 HP / 690V 50~75HP
Mounting Hole
Rings (4 rings)
Nameplate
and Barcode
Terminal Cover
Digital Operator
Front Cover
(Wall-mounted type, IEC IP20, NEMA1)
(d) 200V 50 ~ 100 HP / 400V 100 ~ 215 HP / 690V 100~270HP
Mounting Hole
Rings (4 rings)
Nameplate
and Barcode
Terminal Cover
Digital Operator
Front Cover
Mounting Hole
Rings (4 rings)
Nameplate
and Barcode
Terminal Cover
Digital Operator
Front Cover
Anti-dust Cover
Wiring Box
(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20, NEMA1)
Page 20
3-5
(e) 200V 125 ~ 150 HP / 400V 270 ~ 425 HP
Mounting Hole
Rings (4 rings)
Nameplate
and Barcode
Terminal Cover
Digital Operator
Front Cover
Mounting Hole
Rings (4 rings)
Nameplate
and Barcode
Terminal Cover
Digital Operator
Front Cover
Anti - dust Cov e r
Wiring Box
(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20, NEMA1)
3.4 Warning Labels
Important: Warning information located on the front cover must be read upon installation of the inverter.
(a) 200V: 1-7.5HP / 400V: 1-7.5HP /575V 1~ 3 HP
(b) 200V: 10HP / 400V: 10-20HP /575V 5~10HP
(c)
200V: 15-150HP / 400V: 20(F)-425HP/690V 15~270HP
Page 21
3-6
3.5 Removing the Front Cover and Keypad
Caution
Before making any wiring connections to the inverter the front cover needs to be
removed.
It is not required to remove the digital operator before making any wiring connections. Models 200V, 1 – 25 HP and 400V, 1 – 30 HP and
575V/690V 1 – 40 HP have a
plastic cover. Loosen the screws and remove the cover to gain access to the terminals and make wiring connections. Place the plastic cover back and fasten screws when wiring connections have been made.
Models 200V, 30 - 150HP and 400V, 40 - 425HP and
690V 50 - 270HP have a metal
cover. Loosen the screws and remove the cover to gain access to the terminals and make wiring connections. Place the metal cover back and fasten screws when wiring connections have been made.
3.5.1 Standard Type
(a) 200V: 1 ~ 7.5 HP / 400V: 1 ~ 7.5 HP /575V: 1~3HP
Step 1: Unscrew
Step 2: Remove cover
Page 22
3-7
Step 3: Make wire connections and place cover back Step 4: Fasten screw
(b) 200V: 10 ~ 25 HP / 400V: 10 ~ 30 HP /575V: 5~10HP/690V 15~40HP
Step 1: Unscrew cover Step 2: Remove cover
Page 23
3-8
Step 3: Make wire connections and place cover back Step 4: Fasten screw
(c) 200V: 30 ~ 40 HP / 400V: 40 ~ 75 HP /690V: 50~75HP (Chassis Type)
Step 1: Unscrew cover Step 2: Remove cover
Page 24
3-9
Step 3: Make wire connections and place cover back Step 4: Fasten screw
(d) 200V: 50 ~ 100 HP / 400V: 100 ~ 215 HP /690V: 100~270HP (Chassis Type)
Step 1: Unscrew cover Step 2: Remove cover
Page 25
3-10
Step 3: Make wire connections and place cover back Step 4: Fasten screw
(e) 200V: 125 ~ 150 HP / 400V: 270 ~ 425 HP (Chassis Type)
Step 1: Unscrew cover Step 2: Remove cover
Page 26
3-11
Step 3: Make wire connections and place cover back Step 4: Fasten screw
Page 27
3-12
3.5.2 Built-in filter type (400V: 1 ~ 60 HP)
Step 1: Unscrew cover Step 2: Remove cover
Step 3: Unscrew filter section Step 4: Remove filter cover
Step 5: Make connections and place filter cover back Step 6: Fasten screw
Page 28
3-13
3.6 Wire Gauges and Tightening Torque
To comply with UL standards, use UL approved copper wires (rated 75° C) and round crimp terminals (UL Listed products) as shown in table below when connecting to the main circuit terminals. TECO recommends using crimp terminals manufactured by NICHIFU Terminal Industry Co., Ltd and the terminal crimping tool recommended by the manufacturer for crimping terminals and the insulating sleeve.
Wire size
mm2 (AWG)
Terminal
screw
size
Model of the round crimp
terminal
Fastening torque
kgf.cm (in.lbs)
Model of
insulating
sleeve
Model of
crimp tool
0.75 (18)
M3.5 R1.25-3.5 8.2 to 10 (7.1 to 8.7) TIC 1.25 NH 1
M4 R1.25-4 12.2 to 14 (10.4 to 12.1) TIC 1.25 NH 1
1.25 (16)
M3.5 R1.25-3.5 8.2 to 10 (7.1 to 8.7) TIC 1.25 NH 1
M4 R1.25-4 12.2 to 14 (10.4 to 12.1) TIC 1.25 NH 1
2 (14)
M3.5 R2-3.5 8.2 to 10 (7.1 to 8.7) TIC 2 NH 1 / 9 M4 R2-4 12.2 to 14 (10.4 to 12.1) TIC 2 NH 1 / 9
M5 R2-5 22.1 to 24 (17.7 to 20.8) TIC 2 NH 1 / 9
M6 R2-6 25.5 to 30.0 (22.1 to 26.0) TIC 2 NH 1 / 9
3.5 / 5.5 (12/10)
M4 R5.5-4 12.2 to 14 (10.4 to 12.1) TIC 5.5 NH 1 / 9
M5 R5.5-5 20.4 to 24 (17.7 to 20.8) TIC 5.5 NH 1 / 9 M6 R5.5-6 25.5 to 30.0 (22.1 to 26.0) TIC 5.5 NH 1 / 9 M8 R5.5-8 61.2 to 66.0 (53.0 to 57.2) TIC 5.5 NH 1 / 9
8 (8)
M4 R8-4 12.2 to 14 (10.4 to 12.1) TIC 8 NOP 60
M5 R8-5 20.4 to 24 (17.7 to 20.8) TIC 8 NOP 60 M6 R8-6 25.5 to 30.0 (22.1 to 26.0) TIC 8 NOP 60
M8 R8-8 61.2 to 66.0 (53.0 to 57.2) TIC 8 NOP 60
14 (6)
M4 R14-4 12.2 to 14 (10.4 to 12.1) TIC 14 NH 1 / 9 M5 R14-5 20.4 to 24 (17.7 to 20.8) TIC 14 NH 1 / 9
M6 R14-6 25.5 to 30.0 (22.1 to 26.0) TIC 14 NH 1 / 9
M8 R14-8 61.2 to 66.0 (53.0 to 57.2) TIC 14 NH 1 / 9
22 (4)
M6 R22-6 25.5 to 30.0 (22.1 to 26.0) TIC 22 NOP 60/ 150H
M8 R22-8 61.2 to 66.0 (53.0 to 57.2) TIC 22 NOP 60/ 150H
30 / 38 (3 /2)
M6 R38-6 25.5 to 30.0 (22.1 to 26.0) TIC 38 NOP 60/ 150H M8 R38-8 61.2 to 66.0 (53.0 to 57.2) TIC 38 NOP 60/ 150H
50 / 60 (1/1/0)
M8 R60-8 61.2 to 66.0 (53.0 to 57.2) TIC 60 NOP 60/ 150H M10 R60-10 102 to 120 (88.5 to 104) TIC 60 NOP 150H
70 (2/0)
M8 R70-8 61.2 to 66.0 (53.0 to 57.2) TIC 60 NOP 150H
M10 R70-10 102 to 120 (88.5 to 104) TIC 60 NOP 150H
80 (3/0)
M10 R80-10 102 to 120 (88.5 to 104) TIC 80 NOP 150H M16 R80-16 255 to 280 (221 to 243) TIC 80 NOP 150H
100 (4/0)
M10 R100-10 102 to 120 (88.5 to 104) TIC 100 NOP 150H M12 R100-12 143 to 157 (124 to 136) TIC 100 NOP 150H M16 R80-16 255 to 280 (221 to 243) TIC 80 NOP 150H
Page 29
3-14
3.7 Wiring Peripheral Power Devices
Caution
After power is shut off to the inverter the capacitors will slowly discharge. Do NOT touch
the inverter circuit or replace any components until the “CHARGE” indicator is off.
Do NOT wire or connect/disconnect internal connectors of the inverter when the inverter
is powered up or after power off but the “CHARGE”” indicator is on.
Do NOT connect inverter output U, V and W to the AC power source. This will result in
damage to the inverter.
The inverter must be properly grounded. Use terminal E to connect earth ground and
comply with local standards.
It is required to disconnect the ground wire in the control board if the inverter is not
grounded.
Do NOT perform a dielectric voltage withstand test (Megger) on the inverter this will result in
inverter damage to the semiconductor components.
Do NOT touch any of the components on the inverter control board to prevent damage to
the inverter by static electricity.
200V: 1HP~2HP/ 400V: 1HP~3HP
Disconnect the ground wire of J1. on the
control board
(
C/B).
Page 30
3-15
200V: 3HP~8HP/ 400V: 5HP~8HP/575V: 1~3HP
200V: 10HP/ 400V: 10~20HP/575V: 5~10HP
Disconnect the ground wire of
isolated metal plate.
Disconnect the ground wire of J1. on the
control board
(
C/B).
Page 31
3-16
200V: 15- 25HP/ 400V: 25~30HP/690V: 15~40HP
200V: 30-40HP/ 400V: 40-75HP/690V: 50~75HP
Disconnect the ground wire of
isolated metal plate.
Disconnect the ground wire of
isolated metal plate.
Page 32
3-17
200V: 50HP/ 400V: 100HP and the above/690V: 100HP
Caution
Refer to the recommended wire size table for the appropriate wire to use. The voltage
between the power supply and the input terminals of the inverter may not exceed 2%.
Phase-to-phase voltage drop (V) =
3 ×resistance of wire (/km) × length of line m)
× current×10
-3
.
(km=3280 x feet) / (m=3.28 x feet )
Reduce the carrier frequency (parameter 11-01) If the cable from the inverter to the
motor is over 25m (82ft). A high-frequency current can be generated by stray capacitance between the cables and result in an overcurrent trip of the inverter, an increase in leakage current, or an inaccurate current readout.
To protect peripheral equipment, install fast acting fuses on the input side of the inverter.
Refer to section 11.4 for additional information.
Disconnect the ground screw below the C/B and ground studs of
isolated metal plate.
Page 33
3-18
Power Supply
M
C
C
B
Molded
Circuit
Breaker
Magnetic
Contactor
AC
Reactor
Fast
Acting
Fuse
Input Noise
Filter
A510
Inverter
Ground
Induction
Motor
Ground
Output Noise
Filter
Power supply:
Make sure the correct voltage is applied to avoid damaging the
inverter.
Molded-case circuit breaker (MCCB) or fused disconnect:
A molded-case circuit breaker or fused disconnect must be installed
between the AC source and the inverter that conforms to the rated voltage and current of the inverter to control the power and protect the
inverter.
Do not use the circuit breaker as the run/stop switch for the
inverter.
Ground fault detector / breaker:
Install a ground fault breaker to prevent problems caused by
current leakage and to protect personnel. Select current range up to 200mA, and action time up to 0.1 second to prevent high frequency failure.
Magnetic contactor:
Normal operations do not need a magnetic contactor. When performing
functions such as external control and auto restart after power failure, or when using a brake controller, install a magnetic contactor.
Do not use the magnetic contactor as the run/stop switch for
the inverter.
AC line reactor for power quality:
When inverters are supplied by a high capacity power source (>
600KVA), an AC reactor can be connected to improve the power factor.
Install Fast Acting Fuse:
To protect peripheral equipment, install fast acting fuses in accordance
with the specifications in section 11.4 for peripheral devices.
Input Noise filter:
A filter must be installed when there are inductive loads affecting the
inverter. The inverter meets EN55011 Class A, category C3 when the TECO special filter is used. See section 11.3 for peripheral devices.
Inverter:
Output terminals T1, T2, and T3 are connected to U, V, and W terminals
of the motor. If the motor runs in reverse while the inverter is set to run forward, swap any two terminals connections for T1, T2, and T3.
To avoid damaging the inverter, do not connect the output
terminals T1, T2, and T3 to AC input power.
Connect the ground terminal properly. (200V class: Rg <100;
400V class: Rg <10.)
Output Noise filter:
An output noise filter may reduce system interference and induced
noise.
Motor:
If the inverter drives multiple motors the output rated current of the
inverter must be greater than the total current of all the motors.
Page 34
3-19
3.8 General Wiring Diagram
L1/R
L2/S
L3/T
U/T1
V/T2
W/T3
B1/P
B2 *1
3Ø Induction motor
E
Main Power Section
+10V: Power for Analog Input
(max. 20mA)
AI1: Multi-Function Analog Input
AI2: Multi-Function Analog Input
PI Pulse Input 32kHz Max.
S1
DOG
DO1
Multi-Functional transistor
digital outputs
Open Collector, 48V
@50mA
(opto-isolated)
(R1A)
(R1C)
(R1B)
NC
NO
Multi-Function
Relay Output
External
Analog
Inputs
Digital Input
Section
+
-
Contact rating: 250 VAC < 1.0A 30 VDC < 1.0A
-
Ground < 100
Analog
Output 1
Analog
Output 2
AO1
AO2
GND
Analog Outputs AO1 : 0 – 10 VDC AO2 : 0 – 10 VDC / 4-20m
A
DO2
S2
S3
S4
S5
S6
S7
S8
24V Power terminal for digital signal (source)
A510S
Multi-
Functional
Digital Inputs
External base block
Jog Command
Multi-Step Speed Ref. 3
Fault Reset
Multi-Step Speed Ref. 2
Multi-Step Speed Ref. 1
FWD / STOP
REV / STOP
Factory Default
RS485
Communication Port
V
I
L1(R)
L2(S)
L3(T)
M
a
g
n
e
t
i
c
C
o
n
t
a
c
t
o
r
M
C
C
B
A
C
R
e
a
c
t
o
r
F
a
s
t
A
c
t
i
n
g
F
u
s
e
s
AC Input Voltage
Braking Resistor
SW2
Note 1
R2A
R2C
24VG Digital signal common (sink)
GND: Analog Signal Common
-10V: Power for Analog Input
Pulse Input
0V
4 ~ 20mA / 0 ~ 10V, 250K
-10V ~ 0 ~ 10V, 20K
F1
F2
Run Permissive Input
SOURCE PNP
SINK NPN (DEFAULT)
SW3
P
P
P
CN6 (RJ45)
S(-)
S(+)
2:
1:
PO
GND
Multi-function pulse output 32kHz Max.
P
CN3
Option Card (PG)
*5
*5
*4
*3
*2
*5
*6
*7
(-10~10V/0~10V, 20K)
(0~10V/4~20mA, 250K)
Vcc 24V 12V 5V
R2K 750 100
SW4
*10
Notes:
*1: Models 200V 1 ~ 25HP and 400V 1 ~ 40HP or lower ratings have a built-in braking transistor. To use this braking transistor
a braking resistor can be connected between B1 and B2.
*2: Use SW3 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function digital
input terminals S1~S8.
*3: Use SW2 to switch between voltage (0~10V/-10~10V) and current (4~20mA) input for Multi-function analog input 2 (AI2).
*4: Run Permissive input F1 and F2 is a normally closed input. This input should be closed to enable the inverter output. To
activate this input remove the jumper wire between F1 and F2.
*5: Models 200V 3HP and 400V 5HP and higher ratings include terminals -10V, S(+), S(-),R2A-R2C and PO-GND.
*6. 200V 2HP and 400V 3HP and lower ratings include terminal DO2.
*7: When using the open collector for pulse input, it doesn’t need resistance because of built-in pull-up resistance.
*8: AO2 default setting is 0~+10V.
*9 Both 200V class 50HP~150HP and 400V class 100HP~425HP have built-in DC reactors.
*10 It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel connection.
Please refer to Appendix A
Page 35
3-20
3.9 User Terminals (Control Circuit Terminals)
200V: 1 ~ 2 HP, 400V: 1 ~ 3HP
200V: 3 ~ 150 HP, 400V: 5 ~ 425HP, 575V:1~10HP, 690V:15~270HP
Page 36
3-21
Description of User Terminals
Type Terminal Terminal Function Signal Level / Information
Digital
input
signal
S1
2-wire forward/ stop (default) * 1
Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22k
S2
2-wire reversal/ stop (default) * 1
S3
Multi-speed/ position setting command 1 (default) * 1
S4
Multi-speed/ position setting command 2 (default) * 1
S5
Multi-speed/ position setting command 3 (default) * 1
S6
Fault reset (default) * 1
S7
JOG frequency command (default) * 1
S8
External B.B.(Base Block) stop (coast to stop) (default) * 1
24V Power supply
24V
Digital signal SOURCE point (SW3 switched to SOURCE )
±15%, Max. output current: 250mA (The sum of all loads connected )
24VG
Common terminal of Digital signals Common point of digital signal SINK ( SW3 switched to SINK )
Analog
input
signal
+10V
Power for external speed potentiometer +10V (Max. current , 20mA)
-10V
Only above 200V 3HP/ 400V 5HP (include) support this terminal function
-10V (Max. current , 20mA)
AI1
Multi-function analog input for speed reference (0-10V input)/(-10V~10V input)
From 0 to +10V, From -10V to +10V Input impedance : 20K Resolution: 11bit + 1
AI2
Multi-function analog input terminals *2, can use SW2 to switch voltage or current input (0~10V)/(4-20mA)
From 0 to +10V, From -10V to +10V Input impedance: 200K From 4 to 20 mA Input impedance: 250K Resolution: 11bit + 1
GND
Analog signal ground terminal ----
E
Shielding wire’s connecting terminal (Ground) ----
Analog
output
signal
AO1
Multi-function analog output terminals *2 (0~10V output)
From 0 to 10V, From 4 to 20mA
(Load < 500)
PWM Frequency: 10KHz
AO2
Multi-function analog output terminals *2. can use SW6 to switch voltage or current input (0~10V / 4-20mA output)
GND
Analog signals ground terminal
Pulse
output
signal
PO
Pulse output, Band width 32KHz, only above 200V 3HP/ 400V 5HP (include) support this terminal function.
Max. Frequency: 32KHz Open Collector output
GND
Analog signals ground terminal ----
Page 37
3-22
Type Terminal Terminal Function Signal Level / Information
Pulse input
signal
PI
Pulse command input, Bandwidth: 32KHz
L: from 0.0 to 0.5V H: from 4.0 to 13.2V Max. Frequency: 0 - 32KHz Built-in pull-up resistance. When open collector input is used, it is not required to connect resistance.
GND
Analog signals ground terminal ----
Digital output
DO1
Multi-function(open collector transistor) output *1
48Vdc, 2~50mA Open-collector output
DO2
(Frame
one only)
DOG
Open collector transistor digital ground
Relay
output
R1A
Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, With the same functions as DO1/DO2
Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A
R1B
R1C
R2A-R2C
(Frame 2
and
above)
With the same functions as DO1/DO2
Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A
Run
Permissive
Input
F1
On: normal operation. Off: stop. (Jumper wired between F1 and F2 has to be removed by using external contact to stop.)
24Vdc, 8mA, pull-up
F2
24V Ground
RS-485
port
S (+)
RS485/ Modbus communication protocol Differential input and output
S (-)
Grounding
E (G)
Grounding to earth Shield the connecting terminal
----
Notes:
*1:Multi-function digital input/ output can be referred to in this manual.
- Group 03: External Terminals Digital Input / Output Function Group.
*2:Multi-function analog input/ output can be referred to in this manual..
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.
Page 38
3-23
Caution
Maximum output current capacity for terminal 10V is 20mA.
Multi-function analog output AO1 and AO2 are used for an analog output meter. Do not
use these outputs for feedback control.
Control board’s 24V and ±10V are to be used for internal control only, Do not use the
internal power-supply to power external devices.
Page 39
3-24
3.10 Power Terminals
Terminal
200V: 1 ~ 25HP 400V: 1 ~ 40HP
575V: 1 ~ 10HP
690V: 15 ~ 40HP
200V: 30 ~ 150HP 400V: 50 ~ 425HP 690V: 50 ~ 270HP
R/L1
Input Power Supply (For single phase use terminals R/L1 and S/L2)
S/L2 T/L3
B1P
B1P: DC power supply B1PB2: external braking resistor
-
B2
-: DC power supply or
connect braking module
-
U/T1
Inverter output
V/T2
W/T3
E Ground terminal
200V: 1 ~ 2HP, 400V: 1 ~ 3HP
R/L1S/L2T/L3B1/P U/T1V/T2W/
T3
B2
T
200V: 3 ~ 7.5HP, 400V: 5 ~ 7.5HP, 575V: 1~3HP
200V: 10HP, 400V: 10 ~ 15HP , 575V: 5~10HP
Terminal screw size
T
M4 M4
Terminal screw size
T
M4 M4
Terminal screw size
T
M6 M6
Page 40
3-25
400V: 20HP (Frame 3)
R/L1S/L2T/
L3
U/T1V/T2W/
T3
B1/P B2
T
200V: 15~25HP, 400V: 20 ~ 30HP, 690V: 15~40HP
R/L1S/L2T/
L3
U/T1V/T2W/
T3
B1/P B2
T
400V: 40HP
R/L1S/L2T/
L3
U/T1V/T2W/
T3
B1/P B2
T
200V: 30 ~40HP, 400V: 50 ~ 75HP
Terminal screw size
T
M6 M5
Terminal screw size
T
M6 M6
Terminal screw size
T
M6 M8
Terminal screw size
T
M8 M8
Page 41
3-26
690V: 50~75HP
200V: 50~60HP, 400V: 100HP
Terminal screw size
Power supply T
400V 75HP M8 M10
200V 50-60HP/ 400V 100HP M10 M10
Terminal screw size
T
M6 M6
T
Page 42
3-27
690V: 100~150HP
400V : 125HP
Power supply
690V 100~150HP M10
Terminal screw size
T
M10 M10
Page 43
3-28
200V: 75~100HP, 400V: 150~215HP, 690V: 175~270HP
Terminal screw size
T
M10 M10
200V: 125~150HP, 400V: 270~425HP
Terminal screw size
T
M12 M10
Notes: For wire gauges and screw torques, please refer to the table in section 3.6.
Page 44
3-29
3.11 Input / Output Power Section Block Diagram
The following diagrams 1 - 8 show the basic configuration of the power sections for the range of horsepower and input voltages. This is shown for reference only and is not a detailed depiction.
1: 200V: 1 HP / 400V: 1 ~ 2 HP
2: 200V: 2 ~ 25 HP / 400V: 3 ~ 40 HP / 575V:1~10HP / 690V: 15~40HP
Page 45
3-30
3: 200V: 30 ~ 40 HP / 400V: 50 ~ 75 HP/ 690V: 50~150HP
Main Power Section
Control
Circuit
Cooling Fan
DC /DC
Converter
DC /DC
Converter
4: 200V: 50 ~ 60 HP / 400V: 100 ~ 125 HP
Page 46
3-31
5: 200V: 75, 100 HP
6: 400V: 150HP, 175HP, 215 HP / 690V: 175~270HP
L1/R
L2/S
L3/T
U/T1
V/T2
W/T3
P
Main Power Section
+
-
N
Control
Circuit
Cooling Fan
DC /DC
Converter
DC Link Reactor
AC/DC
E
Page 47
3-32
7: 200V: 125, 150 HP
8: 400V: 270HP, 300HP, 375HP, 425 HP
L1/R
L2/S
L3/T
U/T1
V/T2
W/T3
P
Main Power Section
+
-
N
Control
Circuit
Cooling Fan
DC /DC
Converter
DC Link Reactor
AC/DC
E
Page 48
3-33
3.11.1 Cooling Fan Supply Voltage Selection (400V class)
The inverter input voltage range of the A510 400V class models ranges from 380 to 480Vac. In these
models the cooling fan is directly powered from the power supply. Inverter models A510-4125/ 4150/
4175/ 4215/ 4270/ 4300/ 4375/ 4425 requires the user to select the correct jumper position based on
the inverter input voltage ("440V" is the default position for these models). Please select the correct
position according to the input voltage. If the voltage setting is too low, the cooling fan will not provide
adequate cooling for the inverter resulting in an over-heat error. If the input voltage is greater than
460Vac, select the “460V” position.
(1) 400V 150HP~215HP
(2) 400V:270HP~425HP
The inverter input voltage range of the A510s 600V class models ranges from 575 to 690Vac. In these models the cooling fan is directly powered from the power supply. Inverter models A510s-6175~6270equires the user to select the correct jumper position based on the inverter input voltage ("690V" is the default position for these models). Please select the correct
Page 49
3-34
position according to the input voltage. If the voltage setting is too low, the cooling fan will not provide adequate cooling for the inverter resulting in an over-heat error. If the input voltage is greater than 690Vac, select the “690V” position.
(3)690V:175HP~270HP
Page 50
3-35
3.12 Inverter Wiring
Wiring Precautions
!
Do NOT remove any protective covers or attempt any wiring while input power is applied. Connect all wiring before applying input power. When making wiring changes after power up, remove input power and wait a minimum of five minutes after power has been turned off before starting. Also confirm that the charge lamp is off and that DC voltage between terminals B1/P or (+) and (-) does not exceed 25V, otherwise electric shock may result.
Only authorized personnel should work on the equipment. (Take off metal
jewelry such as watches and rings and use insulated tools.), otherwise electric
shock or injury may result.
(A) Power input terminals
1. The Input power supply voltage can be connected in any phase sequence to power input terminals R/L1,
S/L2, or T/L3 on the terminal block.
2. DO NOT connect the AC input power source to the output terminals U/T1, V/T2 and. W/T3.
3. Connect the output terminals U/T1, V/T2, W/T3 to motor lead wires U/T1, V/T2, and W/T3, respectively.
4. Check that the motor rotates forward with the forward run source. If it does not, swap any 2 of the output
cables to change motor direction.
5. DO NOT connect phase correcting capacitors or LC/RC noise filter to the output circuit.
(B) Grounding
1. Connect the ground terminal (E) to ground having a resistance of less than 100.
2. Do not share the ground wire with other devices, such as welding machines or power tools.
3. Always use a ground wire that complies with the local codes and standards for electrical equipment and
minimize the length of ground wire.
4. When using more than one inverter, be careful not to loop the ground wire, as shown below in Fig. 3.12.1.
A510S A510S
A510S
A510S A510S A510S
a) Correct
b) Correct
A510S A510S A510S
c) Incor rec t
Loop
Fig. 3.12.1 Inverter Grounding
Page 51
3-36
3.13 Input Power and Motor Cable Length
The length of the cables between the input power source and /or the motor and inverter can cause a significant phase to phase voltage reduction due to the voltage drop across the cables. The wire size shown in Tables 3.16.1 is based on a maximum voltage drop of 2%. If this value is exceeded, a wire size having larger diameter may be needed. To calculate phase tot phase voltage drop, apply the following formula:
Phase-to-phase voltage drop (V) =
3 ×resistance of wire (/km) × length of line( m) × current
(A) × 10
-3
.
(km=3280 x feet) (m=3.28 x feet)
3.14 Cable Length vs. Carrier Frequency
The allowable setting of the PWM carrier frequency is also determined by motor cable length and is specified in the following Table 3.14.1.
Table 3.14.1 Cable Length vs. Carrier Frequency
Cable length between
the inverter and
Motor in m (ft.).
< 30 m
(100)
30 – 50
(100 – 165)
50 – 100
(166 - 328)
> 100
(329)
Recommended carrier
frequency allowed
Parameter 11-01
16kHz
(max)
10 kHz
(max)
5 kHz (max)
2 kHz (max)
3.15 Installing an AC Line Reactor
If the inverter is connected to a large-capacity power source (600kVA or more), install an optional AC reactor on the input side of the inverter. This also improves the power factor on the power supply side.
Page 52
3-37
3.16 Power Input Wire Size, NFB and MCB Part Numbers
The following table shows the recommended wire size, molded case circuit breakers and magnetic contactors for each of the A510S models. It depends on the application whether or not to install a circuit breaker. The NFB must be installed between the input power supply and the inverter input (R/L1, S/L2, T/L3).
Note: When using a ground protection make sure the current setting is above 200mA and trip delay time is 0.1
sec of higher.
Table 3.16.1 Wiring instrument for 200V/400V class
A510S Model wire diameter (mm2)
NFB*4 MC*4
Power
horse
power
(HP)*1
Rated
KVA
HD/ND
Rated
current
(A)
HD/ND
Main
circuit
*2
Grounding
line
E(G)
Control
line*3
200V
1 Ø3Ø
1HP 1.9/2.3 5/6 2~5.5 2~5.5 0.52 TO-50EC(15A) CU-11 2HP 3/3.7 8/9.6 2~5.5 3.5~5.5 0.5~2 TO-50EC(20A) CU-11 3HP 4.2/4.6 11/12 3.5~5.5 3.5~5.5 0.5~2 TO-50EC(30A) CU-11
200V
3 Ø
5HP 6.7/8.4 17.5/22 5.5 5.5 0.52 TO-50EC(30A) CU-16
7.5HP 9.5/11.4 25/30 8
5.58 0.5~2
TO-100S(50A) CU-18
10HP 12.6/16.0 33/42 8 5.58 0.52 TO-100S(50A) CU-25 15HP 17.9/21.3 47/56 14 8
0.5~2
TO-100S(100A) CU-50
20HP 22.9/26.3 60/69 22 8 0.52 TO-100S(100A) CU-65 25HP 27.8/30.1 73/80 22 14
0.5~2
TO-225S(100A) CU-80
30HP 32.4/41.9 85/110 38 14 0.52 TO-225S(150A) CN-100 40HP 43.8/52.6 115/138 60 22
0.5~2
TO-225S(175A) CN-125
50HP 55.3/64.4 145/169 80 22 0.52 TO-225S(200A) CN-150 60HP 68.6/76.2 180/200 100 22
0.5~2
TO-225S(225A) CN-180
75HP 81.9/95.3 215/250 150 22 0.52 TO-400S(300A) CN-300
100HP 108/118.9 283/312 200 38
0.5~2
TO-400S(400A) CN-300
125HP 132/137.2 346/400 300 38
0.5~2
TO-400S(400A) SK-400
150HP 158/172 415/450 250*2P 50
0.5~2
TO-800S(800A) SK-600
400V
3 Ø
1HP 2.6/3.1 3.4/4.1 2~5.5 2~5.5 0.52 TO-50EC(15A) CU-11 2HP 3.2/4.1 4.2/5.4 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-11 3HP 4.2/5.3 5.5/6.9 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-11 5HP 7/9.2 9.2/12.1
25.5 3.55.5 0.52
TO-50EC(15A) CU-18
7.5HP 11.3/13.3 14.8/17.5 3.5~5.5 3.5~5.5 0.5~2 TO-50EC(20A) CU-18
10HP 13.7/17.5 18/23 5.5 5.5
0.5~2
TO-50EC(30A) CU-25
15HP 18.3/23.6 24/31 8 8 0.52 TO-100S(50A) CU-25 20HP 23.6/29.0 31/38 8 8
0.5~2
TO-100S(50A) CU-35
25HP 29.7/33.5 39/44 8 8
0.5~2
TO-100S(50A) CU-50
30HP 34.3/44.2 45/58 14 8
0.5~2
TO-100S(75A) CU-50
40HP 45.7/55.6 60/73 22 8
0.5~2
TO-100S(100A) CU-65
50HP 57.2/67.1 75/88 22 14
0.5~2
TO-100S(100A) CU-80
60HP 69.3/78.5 91/103 38 14
0.5~2
TO-225S(150A) CN-100
75HP 89.9/111 118/145 60 22
0.5~2
TO-225S(175A) CN-125
100HP 114/128 150/168 80 22
0.5~2
TO-225S(225A) CN-150
125HP 137/159 180/208 150 22
0.5~2
TO-400S(300A) CN-300
150HP 165/191 216/250 150 22
0.5~2
TO-400S(300A) CN-300
Page 53
3-38
A510S Model wire diameter (mm2)
NFB*4 MC*4
Power
horse
power
(HP)*1
Rated
KVA
HD/ND
Rated
current
(A)
HD/ND
Main
circuit
*2
Grounding
line
E(G)
Control
line*3
175HP 198/226 260/296 200 30
0.5~2
TO-400S(400A) CN-300
215HP 225/250 295/328 250 30
0.5~2
TO-400S(400A) CN-300
270HP 290/332 380/435 300 38
0.5~2
TO-400S(400A) SK-400
300HP 343/393 450/515 250*2P 50
0.5~2
TO-800S(800A)
SK-600
(800A)
375HP 400/446 523/585 250*2P 50
0.5~2
TE-1000(1000A)
SK-600
(800A)
425HP 446/446 585/585 250*2P 50
0.5~2
TE-1000(1000A)
SK-600
(800A)
575V
3 Ø
1HP 1.7/3.0 1.7/3.0 2~5.5 2~5.5 0.52 TO-50EC(15A) CU-11
2HP 3/4.2 3/4.2 2~5.5 2~5.5 0.52 TO-50EC(15A) CU-11
3HP 4.2/5.8 4.2/5.8 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-11
5HP 6.6/8.8 6.6/8.8 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-11
7.5HP 9.9/12.1 9.9/12.2
3.55.5
3.55.5 0.52 TO-50EC(15A) CU-18
10HP 11.4/14.4 11.4/14.5
3.55.5
5.5 0.52 TO-50EC(20A) CU-25
575~690V
3 Ø
15HP 17.9/22.7 15/19 5.5 8 0.52 TO-50EC(30A) CU-25
20HP 22.7/26.3 19/22 8 8 0.52 TO-50EC(30A) CU-35
25HP 26.3/32.3 22/27 8 8 0.52 TO-100S(50A) CU-35
30HP 32.3/40.6 27/34 8 8 0.52 TO-100S(50A) CU-50
40HP 40.6/50.2 34/42 8 8 0.52 TO-100S(50A) CU-50
50HP 50.2/62.1 42/52 14 8 0.52 TO-100S(75A) CU-65
60HP 64.5/74.1 54/62 14 14 0.52 TO-100S(100A) CU-80
75HP 74.1/95.6 62/80 22 14 0.52 TO-225S(150A) CN-100
100HP 103/118 86/99 38 22 0.52 TO-225S(150A) CN-125
125HP 114/149 99/125 60 38
0.5~2
TO-225S(175A) CN-150
150HP 157/175 131/147 60 60
0.5~2
TO-225S(175A) CN-150
175HP 176/194 147/163 80 60 0.52 TO-225S(225A) CN-300
215HP 195/253 163/212 150 80 0.52 TO-225S(225A) CN-300
250HP 230/258 192/216 150 150 0.52 TO-400S(400A) CN-300
270HP 258/294 216/246 150 150
0.5~2
TO-400S(400A) CN-300
*1: Constant torque rating.
*2: The main circuit terminals: R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, B1P, B2,
,
+
*3: Control line is the terminal wire on the control board.
*4: The NFB and MCB listed in the table are of TECO product numbers, products with same rated specification of
other brands may be used. To reduce electrical noise interference, ensure that a RC surge absorber (R: 10/
5W, C: 0.1f/1000VDC) is added to both sides of MCB coil.
Page 54
3-39
3.17 Control Circuit Wiring
(1) Separate the wiring for control circuit terminals from main circuit wiring for terminals
(R/L1,
S/L2, T/L3, U/T1, V/T2, W/T3)
.
(2) Separate the wiring for control circuit terminals R1A-R1B-R1C (or R2A, R2C) (Relay outputs)
from wiring for terminals
-
, A01, A02, GND, DO1, DO2, DOG, +10V, (-10V), AI1, AI2 and
GND wiring.
(3) Use shielded twisted-pair cables (#24 - #14 AWG / 0.5 -2 mm
2
) shown in Fig. 3.17.1 for control circuits to minimize noise problems. The maximum wiring distance should not exceed 50m (165 ft).
Fig. 3.17.1 Shielded Twisted-Pair
(4) When the digital multi-function output terminals (DO1, DO2) are connected to an external relay,
a freewheeling diode should be connected across the relay coil to prevent an inductive voltage spike from damaging the output circuitry as shown in Fig. 3.17.2 below.
+ 48V max.
A510S
DO1, DO2
Free-w heeling diode
(100V, > 100mA)
50 mA max.
Relay Coil
Fig. 3.17.2 Photo-Coupler Connected to an External Relay
Page 55
3-40
(5) In Section 3.8 the control boards referenced have a jumper SW3 that can select the digital
input to terminals - to be set for SINK or SOURCE. The following Fig. 3.17.3 (a.) – (d.) shows examples for the various SINK / Source interfaces.
24VG
Sink
Source
24VG
Sink
Source
NPN
+24V
Inpu t Digital
Terminals S1 - S8
Inpu t Digital
Terminals S1 - S8
(a.) Op en Collec tor Interface
(b.) NPN Sensor Interface
Sink Configuration
+24V
Sink
Source
Inpu t Digital
Terminals S1 - S8
(c.) Open Collector Interface
Source Configuration
(d.) PNP Sensor Interface
24VG
Sink
Source
PNP
+24V
Inpu t Digital
Terminals S1 - S8
SW3
SW3
SW3
SW3
Fig. 3.17.3 Sink / Source Configurations
Page 56
3-41
3.18 Inverter Specifications
Basic Specifications 200V class
Inverter capacity (HP) 1 2 3 5 7.5 10 15 20 25
Out
p
ut rated
Heavy Duty type
H.D.
(150%/1min)
Rated output Capacity (KVA)
1.9 3 4.2 6.7 9.5 12.6 17.9 22.9 27.8
Rated output current (A)
5 8 11 17.5 25 33 47 60 73
Maximum applicable motor
*1
HP
(KW)
1
(0.75)2 (1.5)3 (2.2)5 (3.7)
7.5
(5.5)10(7.5)
15
(11)
20
(15)
25
(18.5)
Motor rated current (A)
*1
3.4 6.1 8.7 13.5 20.1 25.1 36.7 50.3 62.9
Normal Duty
type
N.D.
(120%/1min)
Rated output Capacity (KVA)
2.3 3.7 4.6 8.4 11.4 16.0 21.3 26.3 30.1
Rated output current (A)
6 9.6 12 22 30 42 56 69 80
Maximum applicable motor *1HP
(KW)
2
(1.5)3 (2.2)5 (3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
Motor rated current (A)
*1
6.1 8.7 13.5 20.1 25.1 36.7 50.3 62.9 72.9
The maximum output voltage (V)
3-phase, 200V ~ 240V
The maximum output frequency (Hz)
Based on parameter setting 0.1~599.0 Hz
Powe
r
Rated voltage, frequency
Single/3-phase
200V~240V, 50/60Hz
3-phase 200V~240V, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
Inverter capacity (HP) 30 40 50 60 75 100 125 150
Out
p
ut rated
Heavy Duty type
H.D.
(150%/1min)
Rated output Capacity (KVA)
32.4 43.8 55.3 68.6 81.9 108 132 158
Rated output current (A)
85 115 145 180 215 283 346 415
Maximum applicable motor *1HP
(KW)
30
(22)
40
(30)50(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
Motor rated current (A)
*1
72.9 96.7 124 143.5 183.5 230 272 344
Normal Duty type
N.D.
(120%/1min)
Rated output Capacity (KVA)
41.9 52.6 64.4 76.2 95.3 118.9 152.4 172
Rated output current (A)
110 138 169 200 250 312 400 450
Maximum applicable motor *1HP
(KW)
40
(30)
50
(37)60(45)
75
(55)
100
(75)
125
(90)
150
(110)
175
(130)
Motor rated current (A)
*1
96.7 124 143.5 183.5 230 272 344 370
The maximum output voltage (V)
3-phase, 200V ~ 240V
The maximum output frequency (Hz)
Based on parameter setting 0.1~599.0 Hz
Powe
r
Rated voltage, frequency
Single/3-phase
200V~240V, 50/60Hz
3-phase 200V~240V, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
Page 57
3-42
Basic Specifications 400V class
Inverter capacity (HP) 1 2 3 5 7.5 10 15 20 25 30
Out
p
ut rated
Heavy Duty type
H.D.
(150%/1min)
Rated output Capacity (KVA)
2.6 3.2 4.2 7 11.3 13.7 18.3 23.6 29.7 34.3
Rated output current (A)
3.4 4.2 5.5 9.2 14.8 18 24 31 39 45
Maximum applicable motor *1HP
(KW)
1
(0.75)2 (1.5)3 (2.2)5 (3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
Motor rated current (A)*1
1.7 3.1 4.2 7 10.1 12.6 18.6 24.8 31.1 36.3
Normal Duty type
N.D.
(120%/1min)
Rated output Capacity (KVA)
3.1 4.1 5.3 9.2 13.3 17.5 23.6 29.0 33.5 44.2
Rated output current (A)
4.1 5.4 6.9 12.1 17.5 23 31 38 44 58
Maximum applicable motor *1HP
(KW)
2
(1.5)3 (2.2)5(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)40(30)
Motor rated current (A)*1
3.1 4.2 7 10.1 12.6 18.6 24.8 31.1 36.3 48.7
The maximum output voltage (V)
3-phase 380V~ 480V
The maximum output frequency (Hz)
Based on parameter setting 0.1~599.0 Hz
Powe
r
Rated voltage, frequency
3-phase 380V ~ 480V, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
Inverter capacity (HP) 40 50 60 75 100 125 150 175 215
Out
p
ut rated
Heavy Duty type
H.D.
(150%/1min)
Rated output Capacity (KVA)
45.7 57.2 69.3 89.9 114 137 165 198 225
Rated output current (A)
60 75 91 118 150 180 216 260 295
Maximum applicable motor *1HP
(KW)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
175
(132)
215
(160)
Motor rated current (A)*1
48.7 59 70.5 88 114 145 175 205 248
Normal Duty type
N.D.
(120%/1min)
Rated output Capacity (KVA)
55.6 67.1 78.5 111 128 159 191 226 250
Rated output current (A)
73 88 103 145 168 208 250 296 328
Maximum applicable motor *1HP
(KW)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
175
(132)
215
(160)
250
(185)
Motor rated current (A)*1
59 70.5 88 114 145 175 205 248 270
The maximum output voltage (V)
3-phase 380V~480V
The maximum output frequency (Hz)
Based on parameter setting 0.1~599.0 Hz
Powe
r
Rated voltage, frequency
3-phase 380V ~ 480V, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
Page 58
3-43
Inverter capacity (HP) 270 300 375
425
Output rated
Heavy Duty type
H.D.
(150%/1min)
Rated Output capacity (KVA)
290 343 400
446
Rated output current (A)
380 450 523
585
Maximum applicable motor *1HP
(KW)
270
(200)
300
(220)
375
(280)
425
(315)
Motor rated current (A)*1
300 348 465 500
Normal Duty type
N.D.
(120%/1min)
Rated Output capacity (KVA)
332 393 446
446
Rated output current (A)
435 515 585
585
Maximum applicable motor *1HP
(KW)
300
(220)
335
(250)
425
(315)
425
(315)
Motor rated current (A)*1
348 465 500 615
The maximum output voltage (V)
3-phase 380V~480V
The maximum output frequency (Hz)
Based on parameter setting 0.1~ 599.0 Hz
Power
Rated voltage, frequency
3-phase 380V ~ 480V 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
Basic Specifications 575/690V class
Inverter capacity (HP) 1 2 3 5 7.5 10 15 20 25 30
Output rated
Rated output Capacity (KVA)
1.7 3.0 4.2 6.6 9.9 11.4 17.9 22.7 26.3 32.3
Heavy Duty type H.D. (150%/1min)
Rated output current (A)
1.7 3.0 4.2 6.6 9.9 11.4 15 19 22 27
Maximum applicable motor *1HP (KW) for 575v
1
(0.75)2 (1.5)3 (2.2)5 (3.7)
7.5
(5.5)
10
(7.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
Maximum applicable motor *1HP (KW) for 690v
1
(0.75)2 (1.5)3 (2.2)5 (3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
Rated output Capacity (KVA)
3.0 4.2 5.8 8.8 12.2 14.5 22.7 26.3 32.3 40.6
Normal Duty type N.D. (120%/1min)
Rated output current (A)
3.0 4.2
5.8
8.8
12.2
14.5
19 22 27 34
Maximum applicable motor *1HP (KW) for 575v
2
(1.5)3 (2.2)4 (3)5 (3.7)
10
(7.5)
10
(7.5)
15 (11)
20
(15)
25
(18.5)
30
(22)
Maximum applicable motor *1HP (KW) for 690v
- - - - - - 20 (15)
25
(18.5)
30
(22)
40
(30)
The maximum output voltage (V)
3-phase575/690V
The maximum output frequency (Hz)
Based on parameter setting 0.1~599.0 Hz
Power
Rated voltage, frequency
3-phase 575V, 50/60Hz 3-phase 575/690v, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
Page 59
3-44
Inverter capacity (HP) 40 50 60 75 100 125 150 175 215 250 270
Output rated
Rated output Capacity (KVA)
40.6 50.2 64.5 74.1 103 114 157 176 195 230 258
Heavy Duty type H.D. (150%/1min)
Rated output current (A)
34 42 54 62 86 99 131 147 163 192 216
Maximum applicable motor
*1
HP (KW) for 575v
30
(22)40(30)50(37)60(45)75(55)
100 (75)
125 (90)
150
(110)
150
(110)
200
(150)
200
(150)
Maximum applicable motor
*1
HP (KW) for 690v
40
(30)50(37)60(45)75(55)
100 (75)
125 (90)
150
(110)
175
(132)
215
(160)
250
(185)
270
(202)
Rated output Capacity (KVA)
50.2
64.5
74.1
95.6 114 149 176 195 253 258 294
Normal Duty type N.D. (120%/1min)
Rated output current (A)
42 52 62 80 99
125
147
163
212 216 246
Maximum applicable motor
*1
HP (KW) for 575v
40
(30)50(37)60(45)75(55)
100 (75)
125 (90)
150
(110)
150
(110)
200
(150)
200
(150)
250
(185)
Maximum applicable motor
*1
HP (KW) for 690v
50
(37)60(45)75(55)
100
(75)
125 (90)
150
(110)
175
(132)
215
(160)
250
(185)
270
(202)
335
(251)
The maximum output voltage (V) 3-phase575/690V
The maximum output frequency (Hz) Based on parameter setting 0.1~599.0 Hz
Power
Rated voltage, frequency
3-phase 575/690v, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
*1: Take TECO standard 4-pole induction motor as the base.
*2: A510S model is designed to use in heavy duty conditions, the factory setting is the HD (Heavy Duty type) mode.
*3: The overload capacity of A510S model HD (Heavy Duty) is 150% / 1min, 200% / 2sec. See the table below for the carrier
frequency default setting and range.
*4: The overload capacity of A510S model ND (Normal Duty) is 120%/1min, carrier range: 2 KHz ~ 16 KHz, the default setting
is 2 KHz. The default setting is 1.5 KHz for 575/690v inverter that over 215hp
*5: If it is greater than default carrier frequency, you need to adjust the load current based on the de-rating curve.
Inverter Voltage and Capacity HD mode
carrier frequency range
HD mode
carrier frequency factory setting
200V class 400V class
1~20HP 1~30HP 2~16KHz 8KHz
25HP - 2~12KHz 6KHz
30~40HP 40~50HP 2~12KHz (*6) 5KHz
50~100HP 60~175HP 2~10KHz (*6) 5KHz
125HP 2~10KHz 4KHz
- 215HP 2~8KHz 3KHz
125~150HP 2~5KHz 5KHz
270-375HP 2~5KHz 4KHz
425HP 2~5KHz 2KHz
Inverter Voltage and Capacity HD mode
carrier frequency range
HD mode
carrier frequency factory setting
575Vclass 690Vclass
1~10HP - 1.5~16KHz 8KHz
15~75HP 15~75HP 1.5~8KHz 4KHz 100~150HP 100~150HP 1.5~6KHz 3KHz 175~270HP 175~270HP 1.5~4KHz 2KHz
*6: If control mode (00-00) is set to 2 (SLV mode) and maximum frequency (01-02) is larger than 80Hz, the carrier frequency
range is 2~8 KHz.
Page 60
3-45
The following table shows maximum output frequency for each control mode.
Duty Cycle Control mode Other settings Maximum output frequency
Heavy Duty (00-27=0)
V/F V/F + PG SLV2
maximum frequency set to 599Hz
599Hz
SLV
200V 1~10HP, 400V 1~15HP 150Hz 200V 15~25HP, 400V 20HP 110Hz 400V 25~30HP 100Hz 200V 30~150HP, 400V 40~425HP, carrier (11-01) is set as 8K or below 8K
100Hz
200V 30~100HP, 400V 40~175HP, carrier (11-01) is above 8K
80Hz
SV unlimited 400Hz PMSV unlimited
Twice of Base frequency
PMSLV unlimited
Base frequency
Normal Duty (00-27=1)
V/F V/F + PG
maximum frequency set to 599Hz
599Hz
Page 61
3-46
General Specifications
Control characteristics
Operation mode
LCD keypad with parameter copy function (Optional Seven-segment display * 5 + LED keypad)
Control mode V/F, V/F+PG, SLV, SV, PMSV, PMSLV, SLV2* with space vector PWM mode Frequency control range 0.1Hz~599.0Hz Frequency accuracy (Temperature change)
Digital references: ±0.01(-10 to +40°C) Analog references: ±0.1% (25°C ±10°C )
Speed control accuracy ±0.1% ( vector control(SV))±0.5% ( vector control / open-loop)
Frequency setting resolution
Digital references: 0.01Hz, Analog references: 0.03Hz/60Hz (If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz )
Output frequency resolution
0.01Hz (If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz )
Inverter overload
Rated output current 150%/1 min, 200%/2sec (HD mode),120%/1 min (ND mode) Factory 150%/1 min, 200%/2sec
Frequency setting signal 0 to +10VDC / 4 to 20mA or -10V to +10VDC and pulse input command frequency
A
cceleration / deceleration time 0.0 - 6000.0 second (separately set acceleration and deceleration time )
Voltage, frequency characteristics
Custom V/f curve based on parameters
Braking torque +/- 20%
Main control functions
A
uto-tuning, Zero Servo, torque control, position control, Droop, Soft-PWM, over-voltage protection, dynamic braking, speed search, frequency traversing, instantaneous power fault restart, PID control, automatic torque compensation, automatic speed regulation, RS-485 communication standard, speed feedback control, simple PLC function, 2 sets of analog outputs, safety switch.
Other functions
A
ccumulated power-on / run time, 4 sets of fault history records and latest fault record state, energy-saving function setting, single phase protection, smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up / Down operation, MODBUS protocol, pulse output, engineering units, SINK / SOURCE digital inputs.
Protection functions
Stall protection
Stall prevention level can be set independently in acceleration, deceleration and constant speed.
Instantaneous over current (OC) and output short-circuit (SC) protection
Inverter stops when the output current exceeds 200% of the inverter rated current.
Inverter overload Protection (OL2)
HD mode: If inverter rated current 150%/1 min., or 200%/2sec is exceeded inverter stops, factory default carrier frequency setting is 8~2KHz. ND mode: If inverter rated current 120%/1 min is exceeded inverter stops , factory default carrier frequency is 2KHz.
Motor overload (OL1) protection Electrical overload protection curve I²T
Over voltage(OV) protection
If the main circuit DC voltage rises over 410V (200V class) / 820V (400V class), and over 1050V (575V class) / 1230V (690V class),the motor stops running.
Under voltage (UV)
If the main circuit DC voltage falls below 190V (200V class) / 380V (400V class),and 546V (575/690V class), the motor stops running.
A
utomatic restart after
instantaneous power fault
Power fault exceeds 15ms.
A
utomatic restart function available after instantaneous power fault in 2sec.
Overheat protection(OH) Uses temperature sensor for protection.
Ground Fault protection(GF) Use current sensor for protection.
DC bus charge indicator When main circuit DC voltage 50V, the CHARGE LED turns on.
Output Phase Loss Protection (OPL)
If the OPL is detected the motor stops automatically.
Page 62
3-47
* PM motor for A510s575/690v is under development.
Environment
Specification
Location
Indoor (protected from corrosive gases and dust).
Ambient temperature
-10~+40°C (14°F~104°F) (IP20/NEMA1), -10~+50°C (14°F~122°F) (IP00) ) without de-rating; with de-rating, its maximum operation temperature is 60°C (140°F)
Storage temperature
-20~+70°C (-4°F~+158°F)
Humidity
95RH or less ( no condensation )
Altitude and vibration
Altitude of 1000m (3181ft) or below ; 1.0G, IEC60068-2-6
Communication function
RS-485 standard (MODBUS RTU / ASCII protocol) (RJ45)
PLC function
Built-in
EMI protection
The built-in noise filter complies with EN61800-3 available for inverters 400V 215HP or below.
EMS protection
EN61800-3
Certification
CE
EN61800-3 (CE & RE) EN61800-5-1 (LVD)
UL
UL508C
Option
Open collector/line driver /PM encoder feedback card
Page 63
3-48
3.19 Inverter Derating Based on Carrier Frequency
200V Models
1 - 20 HP 25 HP
0 2kHz 8kHz 16kHz
ND
HD
80% of HD
Fc
Iout
0 2kHz 6kHz 12kHz
ND
HD
80% of HD
Fc
Iout
30 40 HP 50 - 100 HP
0 2kHz 5kHz 12kHz
ND
HD
80% of HD
Fc
Iout
0 2kHz 5kHz 10kHz
ND
HD
80% of HD
Fc
Iout
125 – 150 HP
Page 64
3-49
400V Models
1 - 30 HP 40 - 50 HP
0 2kHz 8kHz 16kHz
ND
HD
60% of HD
Fc
Iout
60 175 HP 215 HP
270 - 375 HP 425 HP
0 2kHz 5kHz
ND
HD
Fc
Iout
4kHz
90% of HD
0 2kHz 5kHz
ND
HD
Fc
Iout
90% of HD
575/690V Models
Page 65
3-50
575V 1 - 10 HP 575/690V 15 - 30 HP
0 2kHz 8kHz 16kHz
ND
HD
80% of HD
Fc
Iout
0 2kHz 5kHz 10kHz
ND
HD
80% of HD
Fc
Iout
575/690V 40 - 60 HP 575/690V 75HP
0 2kHz 5kHz 10kHz
ND
HD
80% of HD
Fc
Iout
575/690V 100 - 150 HP 575/690V 175 - 270 HP
8kHz
83%
8kHz
70%
4kHz
6kHz
1.5kHz
2kHz
4kHz
Page 66
3-51
3.20 Inverter Derating Based on Temperature
0 40°C 60°C
ND
HD
Temperature
Iout
60% of ND
60% of HD
Page 67
3-52
3.21 Inverter Dimensions
(a) 200V: 1 – 7.5HP / 400V: 1 - 7.5HP/ 575V:1-3HP (IP20/NEMA1)
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 t d
Net Weight in kg
(lbs)
A510-2001-SH
130
(5.12)
215
(8.46)
150
(5.91)
118
(4.65)
203
(7.99)5 (0.20)
M5
2.2
(4.9)
A510-2002-SH
130
(5.12)
215
(8.46)
150
(5.91
118
(4.65)
203
(7.99)5 (0.20)
M5
2.2
(4.9)
A510-2003-SH
140
(5.51)
279
(10.98
)
177
(6.97)
122
(4.80)
267
(10.51)7 (0.28)
M6
3.8
(8.4)
A510-2005-SH3
140
(5.51)
279
(10.98)
177
(6.97)
122
(4.80)
267
(10.51)7 (0.28)
M6
3.8
(8.4)
A510-2008-SH3
140
(5.51)
279
(10.98)
177
(6.97)
122
(4.80)
267
(10.51)7 (0.28)
M6
3.8
(8.4)
A510-4001-SH3
130
(5.12)
215
(8.46)
150
(5.91
118
(4.65)
203
(7.99)5 (0.20)
M5
2.2
(4.9)
A510-4002-SH3
130
(5.12)
215
(8.46)
150
(5.91
118
(4.65)
203
(7.99)5 (0.20)
M5
2.2
(4.9)
A510-4003-SH3
130
(5.12)
215
(8.46)
150
(5.91
118
(4.65)
203
(7.99)5 (0.20)
M5
2.2
(4.9)
A510-4005-SH3
140
(5.51)
279
(10.98
)
177
(6.97)
122
(4.80)
267
(10.51)7 (0.28)
M6
3.8
(8.4)
A510-4008-SH3
140
(5.51)
279
(10.98)
177
(6.97)
122
(4.80)
267
(10.51)7 (0.28)
M6
3.8
(8.4)
A510-5001-SH3
140
(5.51)
279
(10.98)
177
(6.97)
122
(4.80)
267
(10.51)7 (0.28)
M6
3.8
(8.4)
A510-5002-SH3 140
(5.51)
279
(10.98)
177
(6.97)
122
(4.80)
267
(10.51)7 (0.28)
M6
3.8
(8.4)
A510-5003-SH3
140
(5.51)
279
(10.98)
177
(6.97)
122
(4.80)
267
(10.51)7 (0.28)
M6
3.8
(8.4)
Page 68
3-53
200V: 10 - 25HP / 400V: 10 - 30HP / 575V: 5~10HP / 690V: 15~40HP (IP20/NEMA1)
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 t d
Net Weight in kg
(lbs)
A510-2010-SH3
210
(8.27)
300
(11.81)
215
(8.46)
192
(7.56)
286
(11.26)
1.6
(0.06)
M6
6.2
(13.67)
A510-2015-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
A510-2020-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
A510-2025-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
A510-4010-SH3
210
(8.27)
300
(11.81)
215
(8.46)
192
(7.56)
286
(11.26)
1.6
(0.06)
M6
6.2
(13.67)
A510-4015-SH3
210
(8.27)
300
(11.81)
215
(8.46)
192
(7.56)
286
(11.26)
1.6
(0.06)
M6
6.2
(13.67)
A510-4020-SH3
210
(8.27)
300
(11.81)
215
(8.46)
192
(7.56)
286
(11.26)
1.6
(0.06)
M6
6.2
(13.67)
A510-4025-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
A510-4030-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
A510-5005-SH3
210
(8.27)
300
(11.81)
215
(8.46)
192
(7.56)
286
(11.26)
1.6
(0.06)
M6
6.2
(13.67)
A510-5008-SH3
210
(8.27)
300
(11.81)
215
(8.46)
192
(7.56)
286
(11.26)
1.6
(0.06)
M6
6.2
(13.67)
A510-5010-SH3
210
(8.27)
300
(11.81)
215
(8.46)
192
(7.56)
286
(11.26)
1.6
(0.06)
M6
6.2
(13.67)
A510-6015-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
Page 69
3-54
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 t d
Net Weight in kg
(lbs)
A510-6020-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
A510-6025-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
A510-6030-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
A510-6040-SH3
265
(10.43)
360
(14.17)
225
(8.86)
245
(9.65)
340
(13.39)
1.6
(0.06)
M8
10
(22.05)
Page 70
3-55
(b) 200V: 30 - 40HP / 400V: 40 - 75HP / 690V 50~75HP (IP20/NEMA1)
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 t d
Net Weight in kg
(lbs)
A510-2030-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
30
(66.14)
A510-2040-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
30
(66.14)
A510-4040-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
30
(66.14)
A510-4050-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
30
(66.14)
A510-4060-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
30
(66.14)
A510-4075-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
35
(77.16)
A510-6050-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
30
(66.14)
A510-6060-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
30
(66.14)
A510-6075-SH3
286.5
(11.29)
525
(20.67)
252
(9.92)
220
(8.66)
505
(19.88)
3.3
(0.13)
M8
30
(66.14)
Page 71
3-56
(c) 200V: 50 - 100HP / 400V: 100 - 215HP / 690V: 100~270HP (IP00)
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 t d
Net Weight in kg
(lbs)
A510-2050-SH3
344
(13.54)
580
(22.83)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
46.7
(102.96)
A510-2060-SH3
344
(13.54)
580
(22.83)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
46.7
(102.96)
A510-2075-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
A510-2100-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
A510-4100-SH3
344
(13.54)
580
(22.83)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
46.7
(102.96)
A510-4125-SH3
344
(13.54)
580
(22.83)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
46.7
(102.96)
A510-4150-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
A510-4175-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
A510-4215-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
A510-6100-SH3
344
(13.54)
580
(22.83)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
46.7
(102.96)
Page 72
3-57
(d) 200V: 50 - 100HP / 400V: 100 - 215HP/ 690V: 100~270HP (IP20/ NEMA1)
A510-6125-SH3
344
(13.54)
580
(22.83)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
46.7
(102.96)
A510-6150-SH3
344
(13.54)
580
(22.83)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
46.7
(102.96)
A510-6175-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
A510-6215-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
A510-6250-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
A510-6270-SH3
459
(18.07)
790
(31.10)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
88
(194.01)
Page 73
3-58
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 t d
Net Weight in kg
(lbs)
A510-2050-SH3
348.5
(13.72)
740
(29.13)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
49.7
(109.57)
A510-2060-SH3
348.5
(13.72)
740
(29.13)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
49.7
(109.57)
A510-2075-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
A510-2100-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
A510-4100-SH3
348.5
(13.72)
740
(29.13)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
49.7
(109.57)
A510-4125-SH3
348.5
(13.72)
740
(29.13)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
49.7
(109.57)
A510-4150-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
A510-4175-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
A510-4215-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
A510-6100-SH3
348.5
(13.72)
740
(29.13)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
49.7
(109.57)
A510-6125-SH3
348.5
(13.72)
740
(29.13)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
49.7
(109.57)
A510-6150-SH3
348.5
(13.72)
740
(29.13)
300
(11.81)
250
(9.84)
560
(22.05)
1.6
(0.06)
M8
49.7
(109.57)
A510-6175-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
A510-6215-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
A510-6250-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
A510-6270-SH3
463.5
(18.25)
1105
(43.50)
324.5
(12.78)
320
(12.60)
760
(29.92)
1.6
(0.06)
M10
94.4
(208.12)
Page 74
3-59
(e) 200V: 125 - 150HP / 400V: 270 - 425HP (IP00)
Inverter Model
Dimensions in mm (inch)
W H D W1 W2 H1 t d
Net Weight in kg
(lbs)
A510-2125-SH3
690
(27.17)
1000
(39.37)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
184
(405.65)
A510-2150-SH3
690
(27.17)
1000
(39.37)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
184
(405.65)
A510-4270-SH3
690
(27.17)
1000
(39.37)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
184
(405.65)
A510-4300-SH3
690
(27.17)
1000
(39.37)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
184
(405.65)
A510-4375-SH3
690
(27.17)
1000
(39.37)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
184
(405.65)
A510-4425-SH3
690
(27.17)
1000
(39.37)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
184
(405.65)
Page 75
3-60
(f) 200V: 125 - 150HP / 400V: 270 - 425HP (IP20/NEMA1)
Inverter Model
Dimensions in mm (inch)
W H D W1 W2 H1 t d
Net Weight in kg
(lbs)
A510-2125-SH3
692
(27.24)
1313
(51.69)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
196
(432.11)
A510-2150-SH3
692
(27.24)
1313
(51.69)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
196
(432.11)
A510-4270-SH3
692
(27.24)
1313
(51.69)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
196
(432.11)
A510-4300-SH3
692
(27.24)
1313
(51.69)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
196
(432.11)
A510-4375-SH3
692
(27.24)
1313
(51.69)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
196
(432.11)
A510-4425-SH3
692
(27.24)
1313
(51.69)
410
(16.14)
530
(20.87)
265
(10.43)
960
(37.80)2 (0.08)
M12
196
(432.11)
Page 76
3-61
3.22 Dimensions for Models with Built-in Filter
(a) 400V: 1 - 7.5HP
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 H2 t d
Net Weight in kg
(lbs)
A510-4001-SH3F
130
(5.12)
306
(12.05)
150
(5.91)
118
(4.65)
203
(7.99)
215
(8.46)
5 M5
3.5
(7.71)
A510-4002-SH3F
130
(5.12)
306
(12.05)
150
(5.91)
118
(4.65)
203
(7.99)
215
(8.46)
5 M5
3.5
(7.71)
A510-4003-SH3F
130
(5.12)
306
(12.05)
150
(5.91)
118
(4.65)
203
(7.99)
215
(8.46)
5 M5
3.5
(7.71)
A510-4005-SH3F
140
(5.51)
400
(15.75)
177
(6.97)
122
(4.80)
267
(10.51)
279
(10.98)
7 M6
5.5
(12.13)
A510-4008-SH3F
140
(5.51)
400
(15.75)
177
(6.97)
122
(4.80)
267
(10.51)
279
(10.98)
7 M6
5.5
(12.13)
Page 77
3-62
(b) 400V: 10 - 30HP
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 H2 t d
Net Weight in kg
(lbs)
A510-4010-SH3F
210
(8.27)
416.5
(16.40)
215
(8.46)
192
(7.56)
286
(11.26)
300
(11.81)
1.6
(0.06)
M6
8.0
(17.63)
A510-4015-SH3F
210
(8.27)
416.5
(16.40)
215
(8.46)
192
(7.56)
286
(11.26)
300
(11.81)
1.6
(0.06)
M6
8.0
(17.63)
A510-4020-SH3F
265
(10.43)
500
(19.69)
225
(8.86)
245
(9.65)
340
(13.39)
360
(14.17)
1.6
(0.06)
M8
12.5
(27.56)
A510-4025-SH3F
265
(10.43)
500
(19.69)
225
(8.86)
245
(9.65)
340
(13.39)
360
(14.17)
1.6
(0.06)
M8
12.5
(27.56)
A510-4030-SH3F
265
(10.43)
500
(19.69)
225
(8.86)
245
(9.65)
340
(13.39)
360
(14.17)
1.6
(0.06)
M8
12.5
(27.56)
Page 78
3-63
(c) 400V: 40 - 60HP
Inverter Model
Dimensions in mm (inch)
W H D W1 H1 H2 t d
Net Weight in kg
(lbs)
A510-4040-SH3F
286.5
(11.28)
679
(26.73)
252
(9.92)
220
(8.66)
505
(19.88)
525
(20.67)
3.3
(0.13)
M8
32.5
(71.65)
A510-4050-SH3F
286.5
(11.28)
679
(26.73)
252
(9.92)
220
(8.66)
505
(19.88)
525
(20.67
3.3
(0.13)
M8
32.5
(71.65)
A510-4060-SH3F
286.5
(11.28)
679
(26.73)
252
(9.92)
220
(8.66)
505
(19.88)
525
(20.67
3.3
(0.13)
M8
32.5
(71.65)
Page 79
4-1
Chapter 4 Keypad and Programming Functions
4.1 LED Keypad
4.1.1 Keypad Display and Keys
5 Digit, 7 Segment
LED Display
Run Status
Indicator
8 button Membrane Keypad
Stop Status
Indicator
Fault Status Indicator
Forward Direction Status Indicator
Reverse Direction Status Indicator
External Reference Indicator
External Sequence Indicator
DISPLAY Description
5 Digit LED Display
Monitor inverter signals, view / edit parameters, fault / alarm display.
LED INDICATORS
FAULT
LED ON when a fault or alarm is active.
FWD
LED ON when inverter is running in forward direction, flashing when stopping.
REV
On when inverter is running in reverse direction, flashing when stopping.
SEQ
LED ON when RUN command is from the external control terminals or from serial communication
REF
LED ON when Frequency Reference command is from the external control terminals or from serial communication
Page 80
4-2
KEYS (8) Description
RUN
RUN Inverter in Local Mode
STOP
STOP Inverter
Parameter navigation Up, Increase parameter or reference value
Parameter navigation down, decrease parameter or reference value
FWD/REV
Used to switch between Forward and Reverse direction
DSP/FUN
Used to scroll to next screen Frequency screen
Function selectionMonitor parameter
/ RESET
Selects active seven segment digit for editing with the ▲▼ keys Used to reset fault condition.
READ / ENTER
Used to read and save the value of the active parameter
Auto-Repeat Keys
Holding the UP or DOWN key for a longer period of time will initiate the auto-repeat function resulting in the
value of the selected digit to automatically increase or decrease.
Page 81
4-3
4.1.2 Seven Segment Display Description
Actual LED Display Actual LED Display Actual LED Display Actual LED Display
0
A
L Y
1
B
n
-
2
C
o
°
3
D
P _
4
E
q
.
5
F
r
6
G
S
7
H
t
8
I
u
9
J
V
Display output frequency Frequency Reference Set Frequency Reference
LED lights on LED flashes Flashing digit
At power-up, the display will show the frequency reference setting and all LEDs are flashing. Press the
(UP) or (DOWN) key to enter the frequency reference edit mode, use the /RESET key to select which digit to edit (flashing). Use the (UP) or (DOWN) key to modify the value and press the READ / ENTER key to save the frequency reference and switch back to the frequency reference display mode.
During run operation, the display will show the output frequency.
Note: When in edit mode and the READ / ENTER is not pressed within 5 sec, the inverter will switch back to
the frequency reference display mode.
Page 82
4-4
LED Display Examples
Seven Segment Display Description
1. Displays the frequency reference at power-up.
2. Displays the actual output frequency during run operation.
Displays parameter code.
Displays the setting value of parameter.
Displays input voltage.
Displays inverter current.
Displays DC Bus Voltage.
Displays temperature.
Displays PID feedback value; The displayed digit is set by 12-01.
Error display; refer to chapter 5 Troubleshooting and Maintenance.
Displays AI1/ AI2 input (0100%)
Page 83
4-5
4.1.3 LED Indicator Description
Fault LED
State Description FAULT LED
Off
No Fault Active
Illuminated
Fault Active
Forward LED
State Description FWD LED
Off
Inverter in reverse direction
Illuminated
Inverter is running in forward direction
Flashing
Forward direction active, no run command
Reverse LED
State Description REV LED
Off
Inverter in forward direction
Illuminated
Inverter is running in reverse direction
Flashing
Reverse direction active, no run command
RUN LED
State Description RUN LED
Off
Inverter stopped
Illuminated
Inverter running
Flashing
Inverter stopped or stopping
Page 84
4-6
SEQ LED
State Description SEQ LED
Off
Sequence controlled from keypad
Illuminated
Sequence set from external source
REF LED
State Description REF LED
Off
Frequency reference set from keypad
Illuminated
Frequency reference set from external source
Run / Stop Status Indicators
Page 85
4-7
4.1.4 Power-up Monitor
Power-up
Changing Monitor at Power-up
12- 00 Display Selection
Range
Highest bit -> 0 0 0 0 0 <- Lowest bit The setting range for each bit is 0 ~ 7 from the highest bit to the lowest bit.
0: No display 4: Temperature 1: Output current 5: PID feedback 2: Output voltage 6: AI1 value 3: DC voltage 7: AI2 value
Example: 12- 00=10000
DSP/FUN
DSP/FUN
DSP/FUN
After 3 sec.
Switch
Mode
Parameter Selection
Output Current
Frequency Reference
Display Voltage Class
at Power-up
Page 86
4-8
Example: 12- 00=12345
4.1.5 Modifying Parameters/ Set Frequency Reference
Example: Modifying Parameters
Page 87
4-9
Example: Set Frequency Reference
Inverter stopped: Inverter is running:
Fl ashin g for 3 secon ds
Press RUN 1x
Di sp lay Vol t ag e C lass
Display Voltage Class
Output Frequency
Outp u t fr equ ency
Set Frequency Reference 0.01 Hz
Set Frequency Reference completed.
Flashing for 3 seconds
Display Frequency Reference
Set Frequency Reference
Set Frequency Reference 0.1 Hz
Set Frequency Reference 0.1 Hz
Set Frequency Reference 1Hz
Set Frequency Reference 1 Hz
Set Frequency Reference + 1Hz
Set Frequency Reference +1 Hz
Pr ess </RESET
1x
Press </RESET
1x
Press </RESET
1x
Pres s </RESET
1x
Press READ/ENTER
1x
Set Frequency Reference
Press 1x
Press </RESET
1x
Press 1x
Press 1x
Press 1x
Press READ/ENTER
1x
Pres s </RESET
1x
Di spl ay Frequency Refere nce
Inverter automatically reverts back to display th e o u tp u t frequency if no mo d ifications ar e made within 5 sec.
Note: When upper or lower limit is reached during editing of the frequency reference, the edit value will
automatically rollover from the lower limit to the upper limit or from the upper limit to the lower limit.
Page 88
4-10
4.1.6 Operation Control
REV command
FWD command
RUN command
REV command
Stop command
FWD command
FWD
Indicator
REV
Indicator
REVREV
REV
FWDFWD FWD FWD FWD FWD FWD
REV
REV REV
REV
Power on
RUN
Indicator
STOP
Indicator
RUN RUN RUN RUN RUN RUNRUN
STOP STOP STOP STOP STOP STOP STOP
Output Frequency
Running StoppingStopped
FWD
RUN
STOP
REV
Stopped
Page 89
4-11
4.2 LCD Keypad
4.2.1 Keypad Display and Keys
LCD Display
Run Status
Indicator
8 button Membrane Keypad
Stop Status
Indicator
Fault Status Indicator
Forward Direction Status Indicator
Reverse Direction Status Indicator
External Reference Indicator
External Sequence Indicator
Fref Ref
12-16=005.00Hz
Monitor
12-17=000.00Hz 12-18=0000.0A
DISPLAY Description
LCD Display
Monitor inverter signals, view / edit parameters, fault / alarm display.
LED INDICATORS
FAULT
LED ON when a fault or alarm is active.
FWD
LED ON when inverter is running in forward direction, flashing when stopping.
REV
On when inverter is running in reverse direction, flashing when stopping.
SEQ
LED ON when RUN command is from the external control terminals or from serial communication
REF
LED ON when Frequency Reference command is from the external control terminals or from serial communication
Page 90
4-12
KEYS (8) Description
RUN
RUN Inverter in Local Mode
STOP
STOP Inverter
Parameter navigation Up, Increase parameter or reference value
Parameter navigation down, decrease parameter or reference value
FWD/REV
Used to switch between Forward and Reverse direction
DSP/FUN
Used to scroll to next screen Frequency screen
Function selectionMonitor parameter
/ RESET
Selects active seven segment digit for editing with the ▲▼ keys Used to reset fault condition.
READ / ENTER
Used to read and save the value of the active parameter
Auto-Repeat Keys
Holding the UP or DOWN key for a longer period of time will initiate the auto-repeat function resulting in the
value of the selected digit to automatically increase or decrease.
Page 91
4-13
4.2.2 Keypad Menu Structure
Main Menu
The A510S inverter main menu consists of two main groups (modes). The DSP/FUN key is used to switch between the monitor mode and the parameter group mode.
Mode Description
Monitor Mode
View inverter status, signals and fault data.
Parameter Group Mode Access to available parameter groups.
All the available parameter groups are listed in the Parameter Group Mode use the up and down keys to select a group and press Read/Enter key to access its parameters.
Fig. 4.2.2.1 Parameter Group Structure
Notes:
- Always perform an auto-tune on the motor before operating the inverter in vector control (sensorless vector or flux vector). Auto-tuning mode will not be displayed when the inverter is running or when a fault is active.
- To scroll through the available modes, parameter groups or parameter list press and hold the up or down key.
Page 92
4-14
Monitor Mode
In monitor mode inverter signals can be monitored such as output frequency, output current and output voltage, etc…) as well as fault information and fault trace. See Fig 4.2.2.2 for keypad navigation.
Power ON
Monitor
Freq Ref
12-17=000.00Hz 12-18=0000.0A
12-16=005.00Hz
Flt Freq Ref
12-15=000.00Hz
Monitor
Monitor
12-17=000.00Hz 12-18=0000.0A
Flt DC Voltage
12-17=000.00Hz 12-18=0000.0A
00 Basic Func.
01 V/F Pattern.
02 Motor Parameter
Group
DSP FUN
DSP FUN
DSP FUN
DSP FUN
12-14=0000.0V
Fig 4.2.2.2 Monitor Mode
Note:
- To scroll through the available monitor parameter list, press and hold the (up) or ▼ (down) key.
Page 93
4-15
Programming Mode
In programming mode inverter parameters can be read or changed. See Fig 4.2.2.3 for keypad navigation.
Fig 4.2.2.3 Programming Mode
Notes:
- The parameters values can be changed from the Edit screen with the up, down and < / RESET shift key.
- To save a parameter press the READ/ENTER key.
- Refer to section 4.4 for parameter details.
-
Press the (up) or (down) key to scroll parameter groups or parameter list.
Page 94
4-16
Auto-tuning Mode
In the auto-tuning mode motor parameters can be calculated and set automatically based on the selected control mode. See Fig 4.2.2.4 for keypad navigation.
Tune Mo de Sel
READ
ENTER
Motor Ra ted Pow er
0 Rota tion al (0 ~ 2) < 0 >
5.50 KW (0. 00 – 60 0.00 ) < 5.50>
Edi t 17-00
000 .00H z-00 0.0A
Auto-t uning R un
(Press Run Key)
0.0Hz – 0.0A
Autotuning
Abor ted
>>>>>>>>>>>>>>>
00 06. 8 A (00 00.9 ~0009 .2) < 00 06. 8 >
Motor Sel
Autotuning
48. 0Hz – 14. 0A
Autotuning
Successful
>>>>>>>>>>>>>>>>>>>>>>>
48. 0Hz – 14.0 A
(Rota tional)
>>>>>>>>>>>>>>>
Moto r Data Error
ATE01
Uncompleted
>>>>>>>>>>>>>>>
Edi t 17-01
Edi t 17-02
DSP FUN
READ
ENTER
DSP FUN
READ
ENTER
DSP FUN
READ
ENTER
DSP FUN
Edi t 17-10
Edi t
Edi t
Edi t Ed it
1 En ab le (0~1) <0>
Autotuning ?
Edi t
DSP FUN
DSP FUN
READ
ENTER
-01 Tune Mode Sel
-02 Motor Rated P ower
-03 Motor Rated C urr.
PARA 17
-01 Tune Mode Sel
-02 Motor Rated P ower
-03 Motor Rated C urr.
PARA 17
-01 Tun e Mo de Sel
-02 Motor Rate d Power
-03 Motor Rate d Curr.
PARA 17
-08 Mtr No-Load Volt
-10 Au to-tuning Run
-11 Au to-tuning Err
PARA 17
Group
17 Au to- tu ning 18 Sli p Comp en 19 T raver se F unc .
Press or key to change the value.
Warning: Do not use “0”, Rotation Auto-tune, when load is coupled with the motor.
*1HP = 0.746KW
STOP
RUN
Tuning
successful
Tuning
fault
READ
ENTER
DSP FUN
Fig 4.2.2.4 Auto-tuning Mode
Notes:
- Set correct motor parameters by referring to motor nameplate.
- Refer to section 4.4 for parameter details.
Page 95
4-17
4.2.2 Notes:
1. Use the up and down keys to scroll though the auto-tuning parameter list. Depending on the selected control
mode in parameter 00-00, part of auto-tuning parameters will not be accessible. (Refer to the Auto-tuning
Group 17 parameters).
2. After entering the motor nameplate rated output power (17-01), rated current (17-02), rated voltage (17-03),
rated frequency (17-04), rated speed (17-05) and number of motor poles (17-06), select the automatic tuning
mode and press the RUN key to perform the auto-tuning operation. When auto-tuning is successful the
calculated motor parameters will be saved into parameter group 02 (motor parameter).
3. (a) “Rotational” will be displayed during rotational auto-tuning (17-00=0) and the motor will rotate during
auto-tuning. Ensure that it is safe to operate the motor before pressing the RUN key.
(b) “Stationary” will be displayed during stationary auto-tuning (17-00=1), the motor shaft does not rotate.
(c) “R1 Tuning” will be displayed during stationary auto-tuning (17-00=2), the motor shaft does not rotate.
(d) The RUN LED (in the upper left corner of the RUN key) will be lit during auto-tuning.
(e) The LCD display shows “>>>” or "Atund" during the auto-tuning process.
4. Press the STOP key on the keypad to abort the auto-tuning operation.
5. In case of an auto-tuning fault, a fault message and the uncompleted message are displayed on the keypad.
The RUN LED will be flashing and the motor will coast to stop. (Refer to section 10.4 for the Auto-tuning
Faults.) The auto-tuning fault can be cleared by pressing the RESET key after which the keypad displays the
auto-tuning mode again.
All motor parameters (group 02 through group 17 parameters) will revert back to their factory settings if a fault
occurs. The motor data must be entered again before re-starting auto-tuning. The keypad shows “>>>” during
an auto-tuning fault.
6. Upon successful completion of an auto-tune, the RUN LED will turn off. Press the DSP/FUN key to return to
the main menu to select the next operation. The auto-tuning procedure takes approximately 50 seconds.
Page 96
4-18
4.3 Parameters
Parameter group Group Name
Group 00
Basic Parameters
Group 01
V/F Control Parameters
Group 02
IM Motor Parameters
Group 03
External Digital Input and Output Parameters
Group 04
External Analog Input and Output Parameters
Group 05
Multi-Speed Parameters
Group 06
Automatic Program Operation Parameters
Group 07
Start /Stop Parameters
Group 08
Protection Parameters
Group 09
Communication Parameters
Group 10
PID Parameters
Group 11
Auxiliary Parameters
Group 12
Monitoring Parameters
Group 13
Maintenance Parameters
Group 14
PLC Parameters
Group 15
PLC Monitoring Parameters
Group 16
LCD Parameters
Group 17
Automatic Tuning Parameters
Group 18
Slip Compensation Parameters
Group 19
Wobble Frequency Parameters
Group 20
Speed Control Parameters
Group 21
Torque And Position Control Parameters
Group 22
PM Motor Parameters
Parameter Attribute
*1
Parameters can be changed during run operation.
*2
Reserved
*3
Parameter will not reset to default during a factory reset (initialization).
*4
Read-only parameter
*5
Parameter will be displayed in being coupled with the option card.
*6
Parameter will be displayed only in LED keypad.
*7
Parameter will be displayed only in LCD keypad.
Page 97
4-19
Group 00: Basic Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
00-00
Control Mode Selection
0: V/F
0 - O O O O O O O *3
1: V/F+PG 2: SLV 3: SV 4: PMSV 5: PMSLV 6: SLV2
00-01
Motor’s Rotation Direction
0: Forward
0 - O O O O O O O *1
1: Reverse
00-02
Main Run Command Source Selection
0: Keypad
1 - O O O O O O O
1: External Terminal
(Control Circuit)
2: Communication
Control (RS-485)
3: PLC
00-03
Alternative Run Command Selection
0: Keypad
2 - O O O O O O O
1: External Terminal
(Control Circuit)
2: Communication
Control (RS-485)
3: PLC
00-04 Language
0: English
0 - O O O O O O O
1: Simplified Chinese 2: Traditional Chinese 3: Turkish
00-05
Main Frequency Command Source Selection
0: Keypad
1 - O O O O O O O
1: External Terminal
(Analog 1)
2: Terminal Command
UP/DOWN
3: Communication
Control (RS-485) 4: Pulse Input 5: Reserved
6: Reserved 7: AI2 Auxiliary
Frequency
00-06
Alternative Frequency Source Selection
0: Keypad
3 - O O O O O O O
1: External Terminal
(Analog 1)
2: Terminal Command
UP/DOWN
3: Communication
Control (RS-485)
4: Pulse Input
Page 98
4-20
Group 00: Basic Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
5: Reserved
6: Reserved 7: AI2 Auxiliary
Frequency
00-07
Main and Alternative Frequency Command Modes
0: Main Frequency
0 - O O O O O O O
1: Main frequency +
Alternative Frequency
00-08
Communication Frequency Command Range
0.00~599.00
0.00 Hz O O O O O O O
00-09
Communication Frequency Command Memory Selection
0: Don’t save when
power supply is off. (00-08)
0 - O O O O O -
1: Save when power is
off. (00-08)
00-10 Reserved
00-11
PID Lower Limit of Frequency Selection
0: PID Sleep Limit is
Lower Limit of Frequency
0
-
O O O O O O O
1: PID Sleep Limit is 0Hz
00-12
Upper Frequency limit
0.1~109.0 100.0 % O O O O O O O
00-13
Lower Frequency limit
0.0~109.0 0.0 % O O O O O O O
00-14
Acceleration Time 1
0.1~6000.0 * s O O O O O O O *1
00-15
Deceleration Time 1
0.1~6000.0 * s O O O O O O O *1
00-16
Acceleration Time 2
0.1~6000.0 * s O O O O O O O *1
00-17
Deceleration Time 2
0.1~6000.0 * s O O O O O O O *1
00-18
*Jog Frequency 0.00~599.00
6.00 Hz O O O O O O O *1
00-19
Jog Acceleration Time
0.1~0600.0 - s O O O O O O O *1
00-20
Jog Deceleration Time
0.1~0600.0 - s O O O O O O O *1
00-21
Acceleration time 3
0.1~6000.0 * s O O O O O O O *1
00-22
Deceleration time 3
0.1~6000.0 * s O O O O O O O *1
00-23
Acceleration time 4
0.1~6000.0 * s O O O O O O O *1
00-24
Deceleration time 4
0.1~6000.0 * s O O O O O O O *1
00-25
Switch-Over Frequency of
0.00~599.00
0.0 Hz O O O O O O O
Page 99
4-21
Group 00: Basic Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
Acc/Dec Time 1 and Time 4
00-26
Emergency Stop Time
0.1~6000.0
5.0 s O O O O O O O
00-27
HD/ND Mode Selection
***
0: HD (Heavy Duty
Mode)
0 - O O X X X X X *3
1: ND (Normal Duty
Mode)
00-28
Command Characteristic selection of master frequency
0: Positive Characteristic
(0~10V/4~20mA is
corresponding to
0~100%)
0 - O O O O O O O
1: Negative
Characteristic
(0~10V/4~20mA is
corresponding to
100~0%)
00-29
Zero-Speed Operation Selection
0: Operation Based on
Frequency Command
0 - X X X O O X X
1: Stop
2: Operation Based on
the Lowest Frequency 3: Zero-Speed Operation
00-30 Reserved
00-31 Reserved
00-32
Application Selection Presets**
0: General
0 - O O O O O O O
1: Water Supply Pump 2: Conveyor 3: Exhaust Fan 4: HVAC 5: Compressor 6: Hoist** 7: Crane**
00-33
Modified Parameters (only for LCD keypad)
0:Disable
0 - O O O O O O O *7
1:Enable
00-34
~
00-40
Reserved
00-41 User parameter 0
Set 13-06 = 1, start user parameter. The setting range is 01-00 ~24-06 (only for LCD keypad)
00-41 - O O O O O O O *7 00-42 User parameter 1 00-42 - O O O O O O O *7 00-43 User parameter 2 00-43 - O O O O O O O *7 00-44 User parameter 3 00-44 - O O O O O O O *7 00-45 User parameter 4 00-45 - O O O O O O O *7 00-46 User parameter 5 00-46 - O O O O O O O *7
Page 100
4-22
Group 00: Basic Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
00-47 User parameter 6 00-47 - O O O O O O O *7 00-48 User parameter 7 00-48 - O O O O O O O *7 00-49 User parameter 8
Set 13-06 = 1, start user parameter. The setting range is 01-00 ~24-06. (only for LCD keypad)
00-49 - O O O O O O O *7 00-50 User parameter 9 00-50 - O O O O O O O *7 00-51 User parameter 10 00-51 - O O O O O O O *7 00-52 User parameter 11 00-52 - O O O O O O O *7 00-53 User parameter 12 00-53 - O O O O O O O *7 00-54 User parameter13 00-54 - O O O O O O O *7 00-55 User parameter 14 00-55 - O O O O O O O *7 00-56 User parameter 15 00-56 - O O O O O O O *7
00-57
SV High Speed
Mode
0: SV High Speed
Mode1
0 - X X X O X X X
1: SV High Speed
Mode2
*: Refer to the following attachment 1.
**: Before to set up 00-32 Application, it should do initialized setting (parameter 13-08) first. When setting
00-32, the I/O port function changed automatically. To avoid accident, be sure to confirm the I/O port
signal of inverter and external terminal control.
*** If parameter 00-27 is set to ND mode, group 02 motor 1 parameter will automatically adjust to more
than 1 class of it.
If parameter 00-27 is set to HD mode, group 02 motor 1 parameter will automatically adjust to the same
class of it.
It is suggested that parameter 00-27 be set first before motor performs auto-tuning because the
parameter will make the motor parameter automatically be changed.
***** If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to
0.1Hz
Group 01: V/F Control Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
01-00
V/F Curve Selection
0~FF F - O O X X X X O *3
01-01 Reserved
01-02
Maximum Output Frequency of Motor 1
5.0~599.0 60.0 Hz O O O O O O O
01-03
Maximum Output Voltage of Motor 1
200V: 0.1~255.0 220.0
V O O X X X X O
400V: 0.2~510.0 440.0
575V: 0.1~670.0
575.0
690V: 0.1~804.0
690.0
Loading...