Tecnoware UPS EVO DSP PLUS 1.0 MM User Manual

UPS EVO DSP Plus 1.0 MM
Uninterruptible Power Supply
Manuale utente
       
Index
User’s Manual - English ........................................................................ 1
Safety Warnings ................................................................................ 1
1 Introduction ................................................................................. 2
2 General Characteristics ................................................................... 3
3 Receipt and site selection ................................................................ 3
4 Operating Modes ........................................................................... 4
4.1 NORMAL Mode .......................................................................... 5
4.2 BATTERY Mode ......................................................................... 5
4.3 BYPASS Mode ........................................................................... 5
4.4 STAND-BY Mode ........................................................................ 6
5 EXTERNAL DESCRIPTION .................................................................. 6
5.1 Front Panel ............................................................................. 6
5.1.1 LED Panel ...................................................................................7
5.1.2 Buttons ......................................................................................8
5.1.3 Acoustic Alarm .............................................................................8
5.2 Rear Side ................................................................................ 8
6 Electrical Installation ...................................................................... 9
6.1 Installation ............................................................................. 9
7 First Start Up .............................................................................. 10
8 Functioning ................................................................................ 11
8.1 Turning ON and OFF ................................................................. 11
8.2 Low Battery and Automatic Restart ............................................... 11
8.3 Load Testing .......................................................................... 12
8.4 Static Bypass ......................................................................... 12
8.5 Operation in Warning and Fault Status ........................................... 13
9 Communication Interfaces .............................................................. 13
10 Technical Characteristics ................................................................ 14
11 Maintenance ............................................................................... 16
11.1 UPS Cleaning ......................................................................... 16
11.2 Battery ................................................................................ 16
11.3 Operator Safety ...................................................................... 16
12 Troubleshooting ........................................................................... 17
Conformity to the European Directives ................................................... 18
Product Disposal ............................................................................... 18
Lead Batteries ................................................................................. 18
November 2018 – version 1.1
Indice
Manuale Utente – Italiano .................................................................... 19
Avvisi di Sicurezza ............................................................................ 19
1 Introduzione ............................................................................... 20
2 Caratteristiche Generali ................................................................. 21
3 Ricevimento e Collocazione ............................................................. 21
4 Modi di Funzionamento .................................................................. 22
4.1 Modo NORMALE ....................................................................... 23
4.2 Modo BATTERIA ...................................................................... 23
4.3 Modo BYPASS ......................................................................... 23
4.4 Modo STAND-BY ...................................................................... 24
5 Descrizione Esterna ....................................................................... 24
5.1 Pannello Frontale .................................................................... 24
5.1.1 Pannello Led ............................................................................. 25
5.1.2 Pulsanti ................................................................................... 26
5.1.3 Allarme Acustico ........................................................................ 26
5.2 Pannello Posteriore .................................................................. 26
6 Installazione Elettrica .................................................................... 27
6.1 Installazione .......................................................................... 27
7 Prima Accensione ......................................................................... 28
8 Funzionamento ............................................................................ 29
8.1 Accensione e Spegnimento ......................................................... 29
8.2 Fine Autonomia e Riaccensione Automatica ..................................... 29
8.3 Controllo del Carico ................................................................. 30
8.4 Bypass Statico ........................................................................ 30
8.5 Segnalazioni di Allarme ............................................................. 31
9 Interfaccia di Comunicazione ........................................................... 31
10 Caratteristiche Tecniche................................................................. 32
11 Manutenzione .............................................................................. 34
11.1 Pulizia dell’UPS ...................................................................... 34
11.2 Batterie ............................................................................... 34
11.3 Sicurezza dell’Operatore ........................................................... 34
12 Anomalie ed Interventi ................................................................... 35
Conformità alle Direttive Europee ......................................................... 36
Smaltimento del Prodotto ................................................................... 36
Batterie al Piombo ............................................................................ 36
Edizione November 2018 – versione 1.1
ENGLISH
UPS EVO DSP PLUS 1 User’s manual
User’s Manual - English
Safety Warnings
Read this manual carefully and completely before installing and using the EVO DSP PLUS
Uninterruptible Power Supply, which, from here after, will also be referred to as UPS.
The UPS must be used only by properly trained personnel. To ensure correct and safe
operations, it is necessary that operators and maintenance personnel observe the general safety Standards as well as the specific instructions included in this manual.
Risk of electric shock: do not remove the cover. The UPS contains internal parts which are at a
high Voltage and are potentially dangerous, capable of causing injury or death by electric shock.
There are no internal parts in the UPS which are user serviceable. Any repair or maintenance
work must be performed exclusively by qualified technical personnel authorized by producer. The producer declines any responsibility if this warning is disregarded.
The electric installation has to be done by qualified personnel. Follow all the Safety Standards
(CEI Standards in Italy or IEEE elsewhere) for the Input/Output connections and for the right section of Input/Output cables.
It is compulsory to ground the UPS according to Safety Standards. Risk of electric shock at the Output lines when the UPS is ON. Risk of electric shock at the Output lines while the unit is connected to the AC utility line. For respect of the Safety Standards is necessary the presence of a differential circuit breaker
between UPS Output lines and the loads.
We recommend to use a dedicate AC power line for the UPS. Do not obstruct ventilation slots or holes and do not rest any object on top of the UPS. Do not insert objects or pour liquids in the ventilation holes. Install the UPS indoors, in a protected, clean and moisture-free environment. Do not expose to the direct sun light. Do not keep liquids, flammable gases or corrosive substances near the UPS.
ENGLISH
User’s manual 2 UPS EVO DSP PLUS
1 Introduction
The EVO DSP PLUS (UPS means Uninterruptible Power Supply) is the result of constant technological research aimed at obtaining the best performance at the lowest cost.
UPS EVO DSP PLUS is an advanced ON-LINE UPS built specifically to protect your computer from any irregularities in the AC line (for example blackouts, brownouts, over voltages, micro-interruptions), which often cause damage to hardware and software.
All that is possible because EVO DSP PLUS is a Double-Conversion ON-LINE UPS.
Under normal AC line condition EVO DSP PLUS provides an automatic Output Voltage regulation from the Rectifier and Inverter blocks and filters out frequently occurring electrical disturbances (high Voltage transients, spikes, interferences, etc.), thus protecting the devices connected to its outlets. During a power failure, EVO DSP PLUS continues supplying adequate AC power (with a true sine wave) to all connected devices through its internal batteries and by its DC/AC converter (Inverter).
EVO DSP PLUS protects the devices from accidental overload or Inverter fault by an Automatic Bypass that directly connects the AC Input line with its outlets.
Read this manual carefully before using the EVO DSP PLUS; it includes important safety warnings and useful advices for correct use and installation.
EVO DSP PLUS is constantly being developed and improved: consequently, your unit may differ somewhat from the description contained in this manual.
This manual includes the following models:
UPS EVO DSP PLUS 1.0 MM
In this manual EVO DSP PLUS will simply be referred to as UPS. EVO DSP PLUS models are made from a single unit that contains the electronics parts and the batteries.
ENGLISH
UPS EVO DSP PLUS 3 User’s manual
2 General Characteristics
EVO DSP PLUS has all the advanced features which guarantee maximum reliability and safety:
Double-Conversion ON-LINE Transformerless technology Sinusoidal wave generated by an IGBT Inverter Output Voltage regulation 2% Protection from overload and short circuits Automatic Bypass to protect from accidental overload or Inverter fault Start-up even under Mains OFF conditions Automatic protection when Battery is low Automatic restart, following an automatic shut-down due to Low Battery, once AC utility power comes
back on
Automatic Input Frequency (50 or 60 Hz) Led panel for visualization of the path of energy flow Acoustic signals of various kinds indicating alarm situations Available settings of all the UPS parameters by user through front panel pushbuttons. High efficiency Maximum reliability Smart design and easy to use
3 Receipt and site selection
Carefully remove the UPS from its packaging, and carry out a meticulous inspection. We recommend keeping the original packaging in a secure place, in case you need to send the UPS for maintenance purposes. In case of transport damage, notify the carrier and dealer immediately.
We recommend paying attention to the below points in order to choose a correct placement for your UPS:
The UPS is designed to operate in a protected environment (e.g. offices). We therefore recommend
installing it in a place with very little or no humidity, dust or smoke.
When the UPS is brought from a cold place to a warmer place, humidity in the air may cause condensation
in the UPS. In this case, allow UPS to stand for two hours in the warmer place before beginning with the installation.
In all circumstances, see the Technical Characteristics chapter for environmental specifications and
check that the selected area meets these criteria.
During normal operation the UPS discharges a minimal amount of heat. So it is necessary to leave at least
10 cm of unobstructed space all around the UPS in order to keep it properly ventilated.
Do not obstruct ventilation holes. Do not insert objects or pour liquids in the ventilation holes. Do not rest any object on top of the UPS. Do not keep liquids, flammable gases or corrosive substances near the unit. Install the UPS on a properly tiled floor. Avoid the installation on a floor that is not tiled flat.
ENGLISH
User’s manual 4 UPS EVO DSP PLUS
4 Operating Modes
Figure 1 – Operating modes
BATTERY MODE
NORMAL MODE
BYPASS MODE
ENGLISH
UPS EVO DSP PLUS 5 User’s manual
4.1 NORMAL Mode
The UPS typically works in Normal mode: Input mains power is available and its amplitude is within specifications. Please refer to figure 1.
After the filter has eliminated any high Frequency interference present on the mains, the AC Input line is rectified and conditioned in the Rectifier block (AC/DC conversion); the continuous power now enters into the Inverter block and is then reconverted into alternated power (DC/AC conversion), overcoming the Automatic Bypass and feeding the load after an extra filtration. At the same time the UPS recharges the batteries through the Battery Charger block.
The Normal mode is identified by:
The Led panel LED1, LED4, LED 7 are on (see fig. 3)
4.2 BATTERY Mode
During operation in Normal mode, if the UPS finds the Mains OFF condition (due to a Blackout or Overvoltage/Brownout), it then switches into Battery mode. In this case, the batteries supply the required Output power thanks to the DC/AC conversion carried out by the Inverter. The UPS switches back to Normal mode a few seconds after AC Input power is restored or Voltage comes back to internal specifications. Please refer to figure 1.
The Battery mode is identified by:
The Led panel LED2, LED4, LED 7 are on (see fig. 3) An acoustic signal every 4 seconds.
4.3 BYPASS Mode
In Bypass mode, the AC Input line is directly connected with the UPS outlets by an Automatic Bypass.
As indicated in figure 1, in Bypass mode the UPS recharges the batteries.
During Normal mode, the UPS switches automatically to Bypass mode as a consequence of accidental overload or Inverter fault thus protecting the supplied devices.
The Bypass mode is identified by:
The Led panel LED3, LED4, LED 7 are on (see fig. 3)
During Bypass mode, loads are fed directly from AC Input line. Therefore no protection against AC Input line disturbances or interruptions is present.
ENGLISH
User’s manual 6 UPS EVO DSP PLUS
4.4 STAND-BY Mode
If the UPS is in Stand-by mode, it is “inactive”. In Stand-by mode the Inverter is off and there is not Output power but the UPS is not completely off: indeed the UPS recharges the batteries regularly.
If the OFF button is pressed when the UPS is in Normal mode, the UPS switches in Stand-by mode.
If the UPS is in Stand-by mode and the AC Input line is removed from UPS, then the UPS switches completely off.
The Stand-by mode is identified by:
The Led panel LED4, LED 7 are on (see fig. 3).
5 EXTERNAL DESCRIPTION
5.1 Front Panel
The front panel informs the user about operating status, alarm conditions and measurements. It also provides access to controls and configuration parameters.
Front panel shown below consists of two parts:
1. LED panel provides complete information about the UPS status and existing alarms, Load and Battery level.
2. 1 push buttons enables the user to turn ON/OFF the UPS.
Figure 2 – Front panel
ENGLISH
UPS EVO DSP PLUS 7 User’s manual
5.1.1 LED Panel
Please refer to figure 3.
LED1: Line MODE LED2: Battery MODE LED3: Bypass MODE LED4: Power ON LED5: Warning or Fault
LED6: LOAD LEVEL
LED7: BATTERY LEVEL
Figure 3 – Led Panel
1
13
4
13
2
13
3
13
1
13
1
13
5
13
ENGLISH
User’s manual 8 UPS EVO DSP PLUS
5.1.2 Buttons
Functions of the buttons are given below:
Button
Function
ON/OFF
Turn ON the UPS: press and hold ON/OFF. If UPS is off, all led will flash few second, then the
UPS will turned ON.
Turn OFF the UPS: press and hold ON/OFF. If the UPS in on, it will go off or go standby charging if the utility is available
5.1.3 Acoustic Alarm
UPS status
Acoustic Alarm
Battery Mode
Beeping once every 4 seconds
Low Battery
Beeping once every second
Overload
Beeping twice every second
Fault Mode
Beeping continuously
5.2 Rear Side
Figure 4 – Rear Side
1. Computer Interface (USB connector): it is the communication USB port.
2. Grounded AC Input power cord: to connect the UPS to the AC utility line.
3. Input Circuit Breaker: it goes off in Overload or short-circuit condition; push the external button of the
Circuit Breaker to reactivate it.
4. Grounded Output Receptacles: IEC C13 type; to supply critical loads.
EVO DSP PLUS 1.0 MM
2
13
3
13 13
1
4
13
ENGLISH
UPS EVO DSP PLUS 9 User’s manual
6 Electrical Installation
The electrical installation has to be done by qualified personnel. Follow all the Safety Standards (CEI Standards in Italy or IEEE elsewhere) for the Input/Output connections and for the right selection of Input/Output cables.
For safety we recommend using external circuit breakers between Input mains and UPS AC Input line and between UPS Output lines and the loads. The circuit breakers should be qualified with leakage current protective function (leakage current < 30 mA).
For the Input/Output connections use ONLY the included power cables or cables with the same power ratings.
The producer declines any responsibility if this warning is disregarded.
The EVO DSP PLUS models are made of a single unit design that contains the electronic parts and batteries.
Before starting the installation procedure, be sure that:
1. The AC Input Voltage for the UPS has been removed.
2. The UPS is completely OFF.
6.1 Installation
We advise you to follow the steps below explained:
1. Through the included power cable connect the UPS Input socket to the AC line outlet (see figure 4). It is
mandatory to ground the AC line outlet according to the Safety Standards. Carefully check the grounding
of AC line outlet.
2. Connect the devices to be supplied to the UPS outputs. Be sure all the devices have the main switch in OFF
position.
It is compulsory to ground the UPS according to the Safety Standards.
The case of the UPS is internally connected to the ground terminal (GND) of the IN/OUT terminals, in order to guarantee safety to the user. To guarantee safety it is necessary to be sure that the local electric plant is supplied with GROUND (in compliance with the Safety Standards), and that a valid connection is guaranteed between the GROUND of the UPS and the GROUND of the local electric plant.
Any interruption of the GROUND conductor is absolutely prohibited.
Risk of electric shock at the Output lines if the UPS is ON, even when the UPS is not connected to AC utility line.
Risk of electric shock at the Output lines while the unit is connected to the AC utility line.
Risk of electric shock: do not remove the cover. The UPS contains internal parts which are at a high Voltage and are potentially dangerous, capable of causing injury or death by electric shock.
There are no internal parts in the UPS which are user serviceable. Any repair or maintenance work must be performed exclusively by qualified technical personnel authorized by the producer. The producer declines any responsibility if this warning is disregarded.
Disregard for these warnings may lead to a risk of electric shock to operators.