Tecnoware EVO TM 6.0, EVO TM 8.0, EVO TM 10.0, EVO TM 12.0, EVO TM 15.0 User Manual

EVO TM
Uninterruptible Power Supply
EVO TM 6.0 (6 KVA)
EVO TM 8.0 (8 KVA)
EVO TM 10.0 (10 KVA)
EVO TM 12.0 (12 KVA)
EVO TM 15.0 (15 KVA)
User’s manual 1 UPS EVO TM
TABLE OF CONTENTS
TABLE OF CONTENTS ......................................................................................................... 1
1.
SAFETY WARNINGS ................................................................................................. 2
2.
INTRODUCTION....................................................................................................... 3
3.
GENERAL CHARACTERISTICS .................................................................................... 4
4.
RECEIPT AND SITE SELECTION.................................................................................. 5
5.
OPERATING MODES ................................................................................................. 5
6.
EXTERNAL DESCRIPTION.......................................................................................... 7
7.
ELECTRICAL INSTALLATION .....................................................................................11
8.
FIRST START UP.....................................................................................................13
9.
FUNCTIONING........................................................................................................14
10. COMPUTER INTERFACE............................................................................................15
11. TECHNICAL CHARACTERISTICS ................................................................................16
12. RECOMMENDATIONS FOR CORRECT USE ...................................................................17
13. TROUBLESHOOTING ...............................................................................................19
14. PICTURES..............................................................................................................21
 Copyright 2007 TECNOWARE s.r.l. All rights reserved. All trademark are property of their respective owners.
TECNOWARE s.r.l. www.service.tecnoware.com
This manual has been printed and edited by TECNOWARE s.r.l.
December 2007 Edition, version 4.0
UPS EVO TM 2 User’s manual
1. SAFETY WARNINGS
Read this manual carefully and completely before installing and using the TECNOWARE EVO TM Uninterruptible Power Supply, which, from here after, will also be referred to as UPS.
The UPS must be used only by properly trained personnel. To ensure correct and safe operations, it is necessary that operators and maintenance personnel observe the general safety Standards as well as the specific instructions included in this manual.
Risk of electric shock: do not remove the cover. The UPS contains internal parts which are at a high voltage and are potentially dangerous, capable of causing injury or death by electric shock.
There are no internal parts in the UPS which are user serviceable. Any repair or maintenance work must be performed exclusively by qualified technical personnel authorized by TECNOWARE. TECNOWARE declines any responsibility if this warning is disregarded.
The electric installation, has to be done by qualified personnel. Follow all the Safety Standards (CEI Standards in Italy) for the IN/OUT connections and for the right section of IN/OUT cables. We recommend to use a dedicated AC input/output power Line for the UPS.
It is compulsory to ground the UPS according to safety Standards.
Risk of electric shock at the output socket when the UPS is ON.
Risk of electric shock at the output socket while the unit is connected to the AC utility line.
For respect of the safety norms is necessary the presence of a differential switch after of the UPS output.
We recommend to use a dedicate AC input/output power Line for the UPS.
Do not obstruct ventilation slots or holes and do not rest any object on top of the UPS.
Do not insert objects or pour liquids in the ventilation holes.
Install the UPS indoors, in a protected, clean and moisture-free environment.
Do not expose to the direct sun light.
Do not keep liquids, flammable gases or corrosive substances near the UPS.
User’s manual 3 UPS EVO TM
2. INTRODUCTION
UPS EVO TM
The UPS EVO TM (Uninterruptible Power Supplies) are the result of constant technological research aimed at obtaining the best performance at the lowest cost.
The EVO TM units are advanced ON-LINE UPS built specifically to protect your computer from any irregularities in the AC line (for example blackouts, brownouts, over voltages, micro­interruptions) which often cause damage to hardware and software.
All that is possible because EVO TM is a Double-Conversion ON-LINE UPS.
Under normal AC line condition UPS EVO TM provides an automatic output voltage regulation from the Rectifier and Inverter blocks and filters out frequently occurring electrical disturbances (high voltage transients, spikes, interferences, etc.), thus protecting the devices connected to its outlets. During a power failure, UPS EVO TM continues supplying adequate AC power (with a true sine wave) to all connected devices through its internal batteries and by its DC/AC converter (Inverter).
UPS EVO TM protects the devices from accidental overload or Inverter fault by an AUTOMATIC BYPASS that directly connects the AC input line with its outlets.
The EVO TM models are factory-equipped with a RS-232 interface which may be used for notify to a computer a power failure or a low battery condition: this allows automatic data backup during an extended blackout with the most common operating systems (Windows, Novell, Linux, etc). Thanks to Interface RS232, UPS EVO TM can communicate the several made measurements (input and output voltage, batteries, absorption, frequency…), and can also be programmed in order to start-up or shutdown automatically at fixed times.
WARNING
Read this manual carefully before using an UPS EVO TM; it includes important safety warnings and useful advices for correct use and installation.
EVO TM is constantly being developed and improved: consequently, your unit may differ somewhat from the description contained in this manual.
This manual includes the follows models of the EVO TM series:
EVO TM 10.0
EVO TM 6.0 EVO TM 12.0
EVO TM 8.0 EVO TM 15.0
In this manual, which covers all 5 models, EVO TM will simply be referred to as UPS.
UPS EVO TM 4 User’s manual
3. GENERAL CHARACTERISTICS
UPS EVO TM has all the modern features which guarantee maximum reliability and safety:
Double-Conversion ON-LINE technology
Sinusoidal wave generated by an IGBT INVERTER
Output voltage regulation ±1%
Protection from overload and short circuits
Automatic BYPASS to protect from accidental overload or Inverter fault
Start-up even under MAINS OFF conditions
Automatic protection when battery is low
Automatic restart, following an automatic shut-down due to low battery, once AC
utility power comes back on.
Selectable input frequency (50/60 Hz)
Display LCD for visualization of the input and output voltage measurements,
batteries voltage, percentage of power used, percentage of load, frequency and operating temperature.
Visual warnings through led, indicating low battery, overload and fault conditions
Dry Contact board (optional)
SNMP Adapter (optional)
EPO (Emergency Power OFF)
Remote ON/OFF
Acoustic signals of various kinds indicating alarm situations
Communication with the computer through RS-232
Available extended autonomy by adding external Battery Boxes
High efficiency
Maximum reliability
Smart design and easy to use.
User’s manual 5 UPS EVO TM
4. RECEIPT AND SITE SELECTION
Carefully remove the UPS from its packaging, and carry out a meticulous inspection. We recommend keeping the original packaging in case you need to send the UPS for maintenance purposes. In case of transport damage, notify the carrier and dealer immediately. We recommend keeping the original packaging in a secure place, in case you need to ship the UPS for maintenance purposes.
We recommend to pay attention to the below points in order to choose a correct placement for your UPS:
The UPS is designed to operate in a protected environment (e.g. offices). We therefore recommend installing it in a place with very little or no humidity, dust or smoke.
In all circumstances, see the TECHNICAL CHARACTERISTICS chapter for environmental specifications and check that the selected area meets these criteria.
During normal operation UPS EVO TM discharges a minimal amount of heat. So it is necessary to leave at least 10 cm of unobstructed space all around the UPS in order to keep it properly ventilated.
Do not obstruct ventilation holes.
Do not insert objects or pour liquids in the ventilation holes.
Do not rest any object on top of the UPS.
Do not keep liquids, flammable gases or corrosive substances near the unit.
Install UPS EVO TM on a properly tiled floor. Avoid the installation on a floor that is not
tiled flat.
5. OPERATING MODES
The operation modes are: LINE MODE, BATTERIES mode and BYPASS mode.
For details see figure 1.
LINE MODE
UPS EVO TM typically works in LINE mode, input mains power is available and its amplitude is within specifications.
After the filter has eliminated any high frequency interferences present on the mains, the input line Is rectified and conditioned in the RECTIFIER board (AC/DC conversion); the continuous power now enters into the INVERTER board and is then reconverted in alternated power (DC/AC conversion), overcoming the AUTOMATIC BYPASS and feeding the load after an extra filtration. At the same time UPS EVO TM recharges the batteries through the BATTERY CHARGER block. Please refer to figures 2A/2B, that describes the UPS front panel, the LINE MODE is identified by:
Led LINE and UPS are on
UPS EVO TM 6 User’s manual
BATTERY MODE
During operation in the LINE MODE, if the UPS finds the MAINS OFF condition (due to a blackout or overvoltage/brownout), it then switches into BATTERY mode. In this case, the batteries supplies the required output power thanks to the DC/AC conversion carried out by the INVERTER. UPS EVO TM switches back to LINE MODE a few seconds after AC input power is restored or voltage comes back to internal specifications.
The BATTERY mode is identified by:
Led LINE off and led UPS on.
The UPS emits an acoustic signal approximately every 2 seconds, in order to indicate
the BATTERY MODE
The acoustic signal will be automatically de-activated after 90 seconds.
BYPASS MODE
In BYPASS mode, the AC input line is directly connected with the UPS outlets by an AUTOMATIC BYPASS.
As it is indicated in figure 1, in BYPASS mode the UPS recharge however the batteries.
UPS EVO TM uses the BYPASS mode during the start-up phase; furthermore the UPS
switches automatically to BYPASS mode as a consequence of accidental overload or Inverter fault thus protecting the supplied devices.
The BYPASS mode is identified by:
BYPASS Led and LINE led are lit.
When EVO TM functions in BYPASS mode it can be considered as “not active”, since the INVERTER block is not active.
EVO TM is considered “active” when the INVERTER block is on (LINE mode and BATTERY mode).
To activate or de-activate UPS EVO TM use the INV ON/OFF button on the front panel.
WARNING
When UPS EVO TM works in BYPASS mode there isn’t output power if the input power is OFF.
User’s manual 7 UPS EVO TM
6. EXTERNAL DESCRIPTION
FRONT PANEL
On the front panel there is an LCD display, 3 buttons and some led which indicate the various operating and alarm conditions. Please refer to figure 1, describing the UPS several operation modes (LINE MODE, BATTERY mode and BYPASS mode) and to the figures 2A/2B we give a short description of the frontal panel elements.
LCD Display
At the top of the frontal panel is present a two rows LCD display showing the UPS functioning state and the UPS measurements values. After approximately 2 minutes without pressing any of the frontal panel buttons the display back-lighting turns off. To relight it press SELECTION button.
ON Button
By pressing the “ON” button the inverter is activated and will supply the output power within 20 second.
OFF Button
By pressing the “OFF” button for approximately 3 seconds the inverter is deactivated and the UPS switches in BYPASS mode.
SELECTION Button
Using the button, represented by two vertical arrows, is possible to change the slide visualized on the LCD display. Every time the button is pressed the slide changes in according to the sequence described in Table 1 (the display shows the actual screen number visualized by a fractional number 2/8, 5/8, etc).
Table 1: Indications of LCD display LCD
Display show
Description
TECNOWARE
EVO TM XXX
Welcome message
STATUS
AC:IN BAT:OK
State of the system (*refer following note)
INPUT VOLTAGE
220 V 2/8
INPUT VOLTAGE
OUTPUT VOLTAGE
220 V 3/8
OUTPUT VOLTAGE
INPUT FREQUENCY 50 HZ 4/8
INPUT FREQUENCY
OUTPUT FREQUENCY
50 HZ 5/8
OUTPUT FREQUENCY
BATTERY VOLTAGE
220V 6/8
BATTERY VOLTAGE
CURRENT LOAD
100% 7/8
CURRENT LOAD (%)
TEMPERATURE
33° 8/8
INTERNAL TEMPERATURE
Loading...