Tecnoware EVO DSP TM, EVO DSP TT, EVO DSP TT 10-100kVA User Manual

Uninterruptible Power Supply
EVO DSP TM
10-30kVA
Important Notice
Thank you for purchasing TECNOWARE UPS.
This document provides instructions about safety, installation and handling of the UPS. It is necessary
to read the manual completely before working on this equipment.
Read the manual completely before working on this equipment!
Keep this manual near UPS for easy consultation!
Symbols
This symbol points out the instructions which are especially important.
This symbol points out the risk of electric shock if the following instruction is not obeyed.
This symbol points out the instructions, which may result in injury to the operator or damage to the equipment if not obeyed.
Copyright 2011 TECNOWARE s.r.l. All rights reserved. All trademarks are property of their respective owners.
TECNOWARE s.r.l. www.service.tecnoware.com
This manual has been printed and edited by TECNOWARE s.r.l. March 2011 edition - version 2.0
UPS EVO DSP TT 1 User’s Manual
Index
1 Safety ............................................................................................................ 4
2 Installation ...................................................................................................... 5
2.1 Transportation ............................................................................................... 5
2.2 Unpacking ..................................................................................................... 5
2.3 Storage ........................................................................................................ 5
2.4 Location and Connection of the UPS ..................................................................... 5
2.4.1 Environmental Requisites ...................................................................................... 5
2.4.2 Electrical Requisites ............................................................................................ 6
2.5 Connections ................................................................................................... 7
2.5.1 Internal Battery Connection ................................................................................... 8
2.5.2 Power Connections .............................................................................................. 9
2.5.2.1 Protective Earth (Ground) Connections ........................................................... 9
2.5.2.2 Input Connection ..................................................................................... 9
2.5.2.3 Separated Bypass Mains Input Connection (Optional) ......................................... 10
2.5.2.4 External Battery Connection ...................................................................... 10
2.5.2.5 Output Connection ................................................................................. 10
2.5.3 Communication Interfaces Connections .................................................................... 10
3 Operating Modes ............................................................................................. 11
3.1 Bypass Mode ................................................................................................ 12
3.2 Normal Mode ............................................................................................... 13
3.3 Battery Mode ............................................................................................... 13
4 Control and Monitoring ..................................................................................... 14
4.1 Front Panel ................................................................................................. 14
4.1.1 Keypad .......................................................................................................... 14
4.1.2 Mimic Panel .................................................................................................... 15
4.1.3 Liquid Crystal Display (LCD) and User Menu ............................................................... 16
4.1.4 Buzzer ........................................................................................................... 19
5 Operating Procedures ....................................................................................... 20
5.1 Commissioning ............................................................................................. 20
5.2 Decommissioning ........................................................................................... 20
5.3 Switching into Manual Bypass during Operation ...................................................... 21
5.4 Returning from Manual Bypass to UPS ................................................................. 21
5.5 Connection to a Generator ............................................................................... 21
6 Operating Procedures for Parallel System.............................................................. 22
6.1 Introduction ................................................................................................ 22
6.2 Procedure for Commissioning and Start Up (First Installation) .................................... 22
6.3 Procedure for Transferring to Static Bypass .......................................................... 25
6.4 Procedure for Transferring to (Maintenance) Manual Bypass ...................................... 25
6.5 Procedure for Switching OFF ............................................................................ 25
7 Features and Operating Limits ............................................................................ 26
7.1 Mains Limits for Normal mode ........................................................................... 26
7.2 Bypass Mains Limits for Bypass mode .................................................................. 26
7.3 Battery Test ................................................................................................ 26
7.4 Overload Behavior ......................................................................................... 27
7.5 Electronic Short Circuit Protection ..................................................................... 27
User’s Manual
2 UPS EVO DSP TT
8
Communication Interfaces ................................................................................. 28
8.1 RS232 Communication .................................................................................... 28
8.2 RS422 Communication .................................................................................... 28
8.3 Digital Inputs (UPS OFF and GEN ON) .................................................................. 29
8.4 Free Contact Communication ............................................................................ 29
9 Maintenance ................................................................................................... 30
9.1 Battery Fuses ............................................................................................... 30
9.2 Battery ....................................................................................................... 30
9.3 Fans .......................................................................................................... 30
9.4 Capacitors ................................................................................................... 30
10 Troubleshooting .............................................................................................. 31
11 Technical Specifications .................................................................................... 34
12 Internal Battery Location - Connection Instructions ................................................. 36
13 Internal Battery Location - Connection Diagram ...................................................... 38
UPS EVO DSP TT 3 User’s Manual
1 Safety
Information related to the safety of the UPS, loads and the user is summarized below. But the equipment should not be installed before reading this manual completely.
The equipment may only be installed and commissioned by authorized technical persons.
When the UPS is brought from a cold place to a warmer place, humidity in the air may cause condensation in the UPS. In this case, allow UPS to stand for two hours in the warmer place before beginning with the installation.
Even if no connection has been done, hazardous voltages may exist on connection terminals and inside the UPS. Do not touch these parts.
Connect the PE (Earth) ground connector before connecting any other cable.
Do not put the Battery fuses into the fuse holder before operating the equipment and seeing the “NORMAL” message on the LCD.
The connections shall be made with cables of appropriate cross-section in order to prevent the risk of fire. All cables shall be of insulated flexible type (tri-rated) and shall not be laid out on the walk path of persons. Cables crossing a path must be protected in accordance with local electrical and safety regulations.
Do not expose UPS to rain or liquids in general. Do not put any solid objects into any access/vent hole or space.
The equipment shall be operated in an environment, which is specified in “Location and Connection of the UPS” section of this manual.
Affix a label bearing the following expression, on the distribution panels feeding the UPS:
“Isolate the Uninterruptible Power Supply (UPS) before working on this circuit”.
Do not plug the communication cables in or out during lightening or electrical storms.
The equipment shall only be maintained and fixed by authorized technical persons.
In case of a fault situation (damaged cabinet or connections, penetration of foreign materials into the cabinet etc.) de-energize the UPS immediately and consult with Tecnoware Technical Service.
Used/dead batteries must be disposed of at an authorized waste disposal centre – local regulations may apply – batteries must not be put in a land fill.
Keep this manual nearby the UPS for easy consultation.
The equipment shall be packed properly during transportation.
The equipment is compliant with the European Community directives. Hence it is marked:
User’s Manual
4 UPS EVO DSP TT
2 Installation
2.1 Transportation
The UPS must remain in a vertical position throughout the transportation. Make sure that the floor can support the weight of the system – check with building engineer if not sure.
2.2 Unpacking
Equipment and batteries whose packaging is damaged during transportation shall be inspected by a qualified technical person before starting with the installation.
The procedure is as follows:
Remove the bands and the protective packaging from the UPS.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is recommended to keep the original package for future needs (e.g. further transportation or return to Service Department).
Check if the following are provided with the equipment:
Key of the cabinet door
Battery fuses (three pieces)
Test report
2.3 Storage
Recommended storage temperature, humidity and altitude values are listed in the “Technical Specifications” section.
If the batteries will be stored for longer than 2 months, they must be charged periodically. Charge period depends on the storage temperature. The relationship is as shown below:
Every 9 months if the temperature is below 20°C.
Every 6 months if the temperature is between 20°C and 30°C.
Every 3 months if the temperature is between 30°C and 40°C.
Every 2 months if the temperature is over 40°C.
2.4 Location and Connection of the UPS
2.4.1 Environmental Requisites
This product meets the safety requirements for devices to be operated in restricted access locations according to EN 60950-1 safety standard, which states that the owner should guarantee the following:
Access to the equipment can only be gained by service persons or by users who have been instructed about the reasons for the restrictions applied to the location and about any precautions that shall be taken.
UPS EVO DSP TT 5 User’s Manual
Bypass mains
Access is through the use of a tool or lock and key, or other means of security and is controlled by the authorized person responsible for the location.
Recommended operating temperature, humidity and altitude values are listed on the “Technical Specifications” section. Air conditioning may be required to provide these values.
Other requisites are:
The equipment and the batteries shall not be exposed to direct sunlight or placed near to a heat source.
Do not expose UPS to rain or any liquids in general. Do not introduce any solid objects.
Avoid dusty environments or areas where dust of conductive or corrosive materials is present.
Air outlets of the UPS are on sides, front and back. Leave at least 75 cm at the front and both sides and 50 cm at the back for maintenance and ventilation.
2.4.2 Electrical Requisites
The installation must comply with local national installation regulations.
The electrical distribution panels for the mains and separate Bypass mains inputs must have a protection and disconnection system. Disconnection devices used in these panels shall disconnect all line conductors and the neutral conductor simultaneously. The following table shows the recommended size of the mains and separate Bypass mains input protection devices (thermal, magnetic and differential) and the cable cross-sections for the linear loads.
UPS
Rating
Input
thermal
protection
input
thermal
protection
Input cable
cross-section
Bypass mains
input cable
cross-section
Battery cable
cross-section
Neutral
Cable Cross
section
Leakage
current
protection*
10 kVA 25 A 50 A 6 mm2 10 mm2 6 mm2 10 mm2 30 mA
15 kVA 25 A 80 A 6 mm2 10 mm2 6 mm2 10 mm2 30 mA
20 kVA 40 A 100 A 10 mm2 25 mm2 10 mm2 16 mm2 30 mA
30 kVA 63 A 160 A 16 mm2 35 mm2 16 mm2 35 mm2 30 mA
Input magnetic protection devices shall have D characteristic.
*Load leakage currents are added to those generated by the UPS. If loads with high leakage currents are present, adjust this value accordingly. It is recommended to adjust the protective device after measuring the total leakage current with the UPS installed and operational with the intended load.
During transitory phases (power failure, return and voltage fluctuations) short leakage current peaks may occur. Make sure that the protection is not activated in such cases.
If the loads have a nonlinear characteristic, the current on the mains input, separate Bypass mains input may have a value that is 1.5-2 times the current phase value during operation. In this case, size the neutral cables and the input/output protection accordingly.
User’s Manual
6 UPS EVO DSP TT
According to EN 62040-1-2, the user shall place a warning label on the input distribution
A1
A2
F5 F1 F3 F2
F6
F4
X1
X2 X3 X4
A3
panel and the other primary power isolators, in order to prevent the risk of electric shock caused by a fault voltage on the UPS. The label shall carry the following wording:
ISOLATE THE UNINTERRUPTIBLE POWER SUPPLY (UPS) BEFORE WORKING ON THIS CIRCUIT
2.5 Connections
Connections shall be done by authorized technical staff only.
When the UPS is brought from a cold place to a warmer place, humidity of the air may condensate in it. In this case, wait for two hours before beginning with the installation.
UPS front side
The layout of the Communication Interface board, Parallel board, slot for SNMP Interface, circuit breakers and connection terminals, is shown below (for accessing open the UPS front door):
A1: Communication Interface board
A2: Parallel board (optional)
A3: Slot for SNMP Interface: SNMP (Simple Network Management
Protocol) Interface is optional.
ATTENTION: bring the 2 dip switches of A1 board to ON position before using SNMP Interface.
F1: Input mains circuit breaker
F2: Output circuit breaker
F3: Manual Bypass circuit breaker
F4: Static Bypass circuit breaker (optional)
F5: Battery circuit breaker
F6: Inrush circuit breaker
X1: Battery terminals (for connecting the batteries)
X2: Input terminals (for connecting AC Input mains)
X3: Bypass terminals (optional – for connecting AC Input mains for
Split Bypass)
X4: Output terminals (for connecting Output line)
UPS EVO DSP TT 7 User’s Manual
2.5.1 Internal Battery Connection
A
B
C
The models EVO DSP TM 10-30 KVA can be equipped with internal batteries. In such case these devices may have very hazardous voltages on the Battery terminals.
When the UPS has battery inside, before doing any operation please do the following points:
1. Remove the back UPS cover to access to the battery pack.
2. Connect the positive battery terminal A see the following figure).
3. Connect the positive battery terminal B (see the following figure).
4. Connect the positive battery terminal C (see the following figure).
5. Replace the back UPS cover.
PAY ATTENTION: RISK OF ELECTRICAL SHOCK – HIGH BATTERY VOLTAGE
A, B and C battery terminals are disconnected in factory to reduce the risk of electrical shock during shipment. After points 2, 3 and 4 the NOMINAL TOTAL BATTERY VOLTAGE is about 744 VDC (there are 62 batteries 12 VDC serial connected).
User’s Manual
Figure – A, B and C Battery terminals connections
8 UPS EVO DSP TT
2.5.2 Power Connections
The power screw terminals are located on the lower front side of the UPS. Refer to the names of each terminal to identify it during connection.
Connection terminals for all models with optional split Bypass
Battery terminals: use only to connect external battery.
Cables shall be passed through the hole under the connection terminals.
Make sure that all circuit breakers are “OFF”/“0” before starting with the installation.
Connections shall be done in the order below only.
2.5.2.1 Protective Earth (Ground) Connections
The device shall be earthed for a safe and reliable operation. Connect the PE ground connectors before connecting any other cable
Input Protective Earth connection terminal (PE) of the UPS shall be connected to ground with a low impedance connection.
PE terminals of the loads shall be connected to Output Protective Earth terminal of the UPS.
If there is an external battery cabinet present, it shall be grounded via Battery Protective Earth terminal of the UPS. Battery case must be earthed only. Do not connect any DC/battery point to PE earth.
2.5.2.2 Input Connection
Bring the circuit breaker on the distribution panel to “OFF”/“0” position before making the connections.
Connect the phases to input (X2) L1, L2 and L3 terminals. Connect neutral to N terminal of X2
A definite phase sequence is needed for the UPS to operate. If you encounter “INP SEQ FAIL” alarm message at start-up, stop and switch off the UPS, ensure the protection devices (breakers/isolators) on the input distribution panels are “OFF”/“0”, then interchange any two phases on the UPS input only.
UPS EVO DSP TT 9 User’s Manual
2.5.2.3 Separated Bypass Mains Input Connection (Optional)
Bring the circuit breaker on the distribution panel to “OFF” or “0” position before making the connections
Connect the Phase of Bypass Input mains to Bypass (X3) L1 terminal.
Connect the Neutral to N terminal of X3.
2.5.2.4 External Battery Connection
Do not put the Battery fuses into the fuse holder (F5) before operating the equipment and seeing the “NORMAL” message on the LCD.
Devices with internal batteries may have dangerous voltages on the Battery terminals
To connect external batteries, do the following:
Switch the circuit breaker of the external batteries to “OFF”/“0” position.
Connect the (-) pole of the external batteries to the Battery (-) terminal,
Connect the (+) pole of the external batteries to the Battery (+) terminal,
Connect the midpoint of the external batteries to the Battery (N) terminal.
Danger of explosion and fire if batteries of the wrong type are used.
2.5.2.5 Output Connection
To enable the short circuit protection feature of the UPS, each load shall be fed over a separate circuit breaker chosen according to the load current. This may provide quick disconnection of the short circuited load and operation continuity of the other loads. To obtain maximum protection, the rating of each individual load circuit breaker shall have the minimum value, which is enough to carry the full load current continuously.
Rated apparent and active power of the loads shall be less than the UPS power ratings.
Connect the loads to output (X4) L1 and N terminals. Do not use L2 and L3 terminals.
2.5.3 Communication Interfaces Connections
Related information is given in “Communication Interfaces” section.
User’s Manual
10 UPS EVO DSP TT
3 Operating Modes
Static
Bypass
F3
F1
F6
F5
F2
Inverter
Rectifier
B
attery
Static
Bypass
F3
F1
F6
F5
F2
Inverter
Rectifier
Inrush circuit
B
attery
F4
Flow path:
Battery mode
There are three operating modes, which differ in the path of the energy flow.
UPS block diagrams and the energy flow path in each operating mode is shown below:
INPUT
3 Phases + Neutral
OUTPUT
1 Phase + Neutral
BYPASS INPUT
1 Phase +
INPUT
3 Phases + Neutral
Inrush circuit
OUTPUT
1 Phase + Neutral
Normal mode
Bypass mode
Figure – Block diagram and energy flow paths
(up: without Separate Bypass mains Input – down: with Separate Bypass mains Input)
UPS EVO DSP TT 11 User’s Manual
When UPS has no separate Bypass mains input, Bypass line is also fed from the mains input. Thus, if such a device is in question, mains input shall be comprehended when the Bypass mains input is referred in the following sections of the manual.
UPS behavior at the start-up is different from the usual operation. The UPS can only operate in Bypass mode during start-up. So, in order for the UPS to start-up, frequency/waveform/RMS value of the Bypass mains voltage shall be in acceptable limits and Bypass shall be enabled.
After start-up, the following applies:
Operating mode depends on the priority, Inverter, Rectifier and Bypass preferences made by the user and mains, separate Bypass mains and battery voltages.
Priority and Inverter, Rectifier and Bypass preferences can be set by using the “COMMANDS” menu and “EXTENDED CMNDS” submenu.
If operation in any of these modes is impossible, output voltage will not be present. In this case, loads will not be fed, and “VSECFLR” alarm message is shown on the LCD instead of operating mode.
3.1 Bypass Mode
Devices without separate Bypass mains input, energy is drawn from the mains. In devices with separate Bypass mains input, energy is drawn from the separate Bypass mains.
Loads are fed via static Bypass line.
Output voltage has the same amplitude, frequency and waveform as the input voltage.
Current drawn by the loads are only limited by the thermal/magnetic breakers over the energy flow path.
Voltage, frequency and waveform of the Bypass supply shall be within their tolerance limits, and Bypass shall be enabled for the UPS to operate in this mode.
When the upper provisions are met, the UPS works in Bypass mode in the following conditions:
During the start-up;
If the Bypass priority is selected;
If the Inverter is disabled or blocked;
In case of a prolonged Overload.
ECO Mode
You can save energy by selecting the Bypass priority. Efficiency in Bypass mode is higher than the efficiency in Normal mode. If the Bypass priority is selected, the UPS will operate in Bypass mode whenever the frequency/waveform/RMS value of Bypass mains voltage is within their tolerance limits. If the Bypass voltage goes beyond these limits, the UPS switches into normal operation.
Bypass mode does not provide perfect stability in frequency/waveform/RMS value of the output voltage like in Normal mode. Thus, the use of this mode should be carefully executed according to the level of protection required by the application.
Bypass mode does not provide electronic short circuit protection like in Normal mode. If a short circuit occurs on the output during Bypass operation, the thermal/magnetic protection will act and all loads will be de energized – load will be stopped.
Prolonged overloads may cause the thermal/magnetic protection to act. In this case, all loads will be de energized – load output will be stopped.
User’s Manual
12 UPS EVO DSP TT
Loading...
+ 30 hidden pages