Tecnologic K series, K38, K39, K49 Quick Programming Manual

Tecnologic ‘K’ Series
UK Quick Programming Guide – K38/39 & K49
This guide should be used alongside the full engineering manual, appropriate to the instrument being
used, where more detailed information can be found.
Tecnologic controllers are supplied with default programmable settings that may be suitable for your application. However we recommend that you go through the programming process, as incorrect programming could compromise its performance.
Programming level pass numbers:
1381 – Basic menu without 10 second time out
1400 – Advanced menu without 10 second time out
** Minus 1000 to the pass number to add t ime out f un ct ion **
Note: To reset instrument to factory default settings, press P for 5 seconds and dial in -481. Press P to confirm
Key
P button used for entering or moving to the next parameter.
Up & down buttons used for increasing or decreasing values.
U button is used for navigation between menus. Holding down for 1 second will take you back one step.
Holding down for 2 seconds will take you out of configuration.
P
U
Unit 1 Farnborough Business Centre, Eelmoor Road, Farnborough, GU14 7XA
T: 01252 377600 F: 01252 377601 E: sales@tecnologicuk.co.uk
Navigating the basic level programming guide
This is a blueprint guide for changing all the parameter settings on the instrument within the 381 menu.
Note: Some parameters will disappear and/or additional parameters will appear depending on settings selected. If the advanced menu is required use the 1400 pass code & select appropriate menu using the ‘U’ key. Please refer to the main manual for more details.
Start/ Configure.
Power up unit. tEST will flash
Press & hold . Dial in ‘1381’ & press P to confirm.
With power to unit press P for 5
seconds. ‘Pass’ is displayed along with ‘0’
Use and arrow to select required setting within chosen parameter. Press P to confirm.
Unit then accepts the chosen
setting and moves on to next parameter in menu. (Repeat above for all required parameters)
To exit programming press and
hold U to return to displayed temperature.
To skip a parameter
press P to move onto next one.
Unit will display first parameter in
menu, i.e. SEnS
381 Parameter menu
Display
Parameter name/
description
Manual
ref.
SEnS
Sensor/ input type
[2]
dP
Decimal point position
[3]
unit
Engineering Unit
[6]
o1F
Output function 1
[12]
o2F*
Output function 2
[15]
cont
Control type
[52]
Auto
Auto tuning for PID parameters
[53]
Pb
Proportional band value (°C)
[58]
int
Integral time (sec)
[59]
dEr
Derivative time (sec)
[60]
Fuoc
Fuzzy overshoot control
[61]
H.Act
Heating output actuator
[62]
SPLL
Min. adjustable set point value
[73]
SPHL
Max. adjustable set point value
[74]
SP1
Control set point
[75]
AL1t
Alarm 1 type/function
[24]
AL1L
Min. adjustable alarm 1 value
[26]
AL1H
Max. adjustable alarm 1 value
[27]
AL1
Alarm 1 set point value
[28]
HAL1
Alarm 1 hysteresis (differential)
[29]
AL2t**
Alarm 2 type/function
[32]
t.F
Independent timer function
[84]
Pr.F
Programmer function at start-up
[89]
AdE***
Bargraph deviation
[118]
*Please note that o3F or/and o4F will only show dependent on model. ** If set AL2t, L, H etc will be repeated as with alarm 1
*** Parameter will not appear on all models.