Tecnologic ‘K’ Series
UK Quick Programming Guide – K38/39 & K49
This guide should be used alongside the full engineering manual, appropriate to the instrument being
used, where more detailed information can be found.
Programming the Instrument
Tecnologic controllers are supplied with default programmable settings that may be suitable for your
application. However we recommend that you go through the programming process, as incorrect
programming could compromise its performance.
Programming level pass numbers:
1381 – Basic menu without 10 second time out
1400 – Advanced menu without 10 second time out
** Minus 1000 to the pass number to add t ime out f un ct ion **
Note: To reset instrument to factory default settings, press P for 5 seconds and dial in -481.
Press P to confirm
Key
P button used for entering or moving to the next parameter.
Up & down buttons used for increasing or decreasing values.
U button is used for navigation between menus.
Holding down for 1 second will take you back one step.
Holding down for 2 seconds will take you out of configuration.
Unit 1 Farnborough Business Centre, Eelmoor Road, Farnborough, GU14 7XA
T: 01252 377600 F: 01252 377601 E: sales@tecnologicuk.co.uk
Navigating the basic level programming guide
This is a blueprint guide for changing all the parameter settings on the instrument
within the 381 menu.
Note: Some parameters will disappear and/or additional parameters will appear depending on
settings selected. If the advanced menu is required use the 1400 pass code & select appropriate
menu using the ‘U’ key. Please refer to the main manual for more details.
Power up unit. tEST will flash
Press & hold .
Dial in ‘1381’ & press P to
confirm.
With power to unit press P for 5
seconds.
‘Pass’ is displayed along with ‘0’
Use and arrow to
select required setting
within chosen parameter.
Press P to confirm.
Unit then accepts the chosen
setting and moves on to next
parameter in menu. (Repeat
above for all required parameters)
To exit programming press and
hold U to return to displayed
temperature.
press P to move onto
next one.
Unit will display first parameter in
Auto tuning for PID
parameters
Proportional band value
(°C)
Min. adjustable set
point value
Max. adjustable set
point value
Min. adjustable alarm 1
value
Max. adjustable alarm 1
value
Alarm 1 hysteresis
(differential)
Independent timer
function
Programmer function at
start-up
*Please note that o3F or/and o4F will only show dependent on model.
** If set AL2t, L, H etc will be repeated as with alarm 1
*** Parameter will not appear on all models.