tecnoelettra ATS-I User Manual

P17/32 Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc
Tecnoelettra srl
Dal 1985
Tel.+39.0522.832004 – Fax.+39.0522.832012 P.17/32
Internet :www.tecnoelettra.it E
-
mail:info@tecnoelettra.it
USER MANUAL
ATS
-
I
REV1
P18/32 Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc
Tecnoelettra srl
Dal 1985
Tel.+39.0522.832004 – Fax.+39.0522.832012 P.18/32
Internet :www.tecnoelettra.it E
-
mail:info@tecnoelettra.it
Index
General description.........................................................................................................19
Electrical specifics...........................................................................................................19
Device operative logic .....................................................................................................20
Manual mode...............................................................................................................20
Automatic mode...........................................................................................................21
Alarms .........................................................................................................................21
Display.........................................................................................................................22
Automatic transfer switch procedure mains-generator, generator-mains......................24
Parameters Programmation.........................................................................................26
Phase detection special function..................................................................................27
Mechanical Sizing ...........................................................................................................28
Rear View........................................................................................................................29
Triple phase wiring diagram (230Vac, 400Vac, 440Vac).................................................30
Single phase wiring diagram (230Vac)............................................................................31
P19/32 Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc
Tecnoelettra srl
Dal 1985
Tel.+39.0522.832004 – Fax.+39.0522.832012 P.19/32
Internet :www.tecnoelettra.it E
-
mail:info@tecnoelettra.it
General description
ATS-I controller allows an automatic transfer switch commutation between mains and generator. In automatic mode, when faulty mains conditions are detected, the board sends a remote start signal to the engine; when generator is running, the phase sequence is checked, if voltage and frequency measurements are compatible with programmed values, the changeover switch is activated towards generator side. When mains voltage returns back, transfer switch returns on mains side and generator is stopped.
Electrical specifics
Supply voltage (isolated) 8 ÷ 30 Vdc
Voltage measurements
230Vac 1ph 230Vac 3ph 400Vac 3ph
440Vac 3ph Frequency measurements 45 ÷ 65 Hz Generator voltage range 0 ÷ 500 Vac Mains voltage range 0 ÷ 500 Vac Measurements precision ± 2% Input LA 10 ÷ 30 Vdc Input LM 10 ÷ 30 Vdc Input LR 0 ÷ 500 Vac Input LG 0 ÷ 500 Vac Output START GEN. 5A, 10 ÷ 30 Vdc Output TLR 5A, 230 Vac Output TLG 5A, 230 Vac Maximum reaction time for VF measurements 2 sec. Maximum phase detection delay 1 sec.
P20/32 Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc
Tecnoelettra srl
Dal 1985
Tel.+39.0522.832004 – Fax.+39.0522.832012 P.20/32
Internet :www.tecnoelettra.it E
-
mail:info@tecnoelettra.it
Device operative logic
There are two operative modes:
- Manual
- Automatic
At the startup, device selects automatically the correct operative mode in accordance with P13 parameter; “Aut/Man” key allows to change operative mode without restriction.
Front view:
Manual mode
In manual mode all system is controlled by ATS-I operative panel, on the left side of the display, a label shows the actual operative mode of the device (“ MAN “ or “ AUTO “). “Start Gen” button allows to start and stop the generator; in case of idle generator, when “Start Gen” button is pushed, a blinking key icon will appear near “MAN” indicator to signal a starting phase for generator; when running engine is detected, the key become permanent. To stop the engine “Start Gen” key must be pushed again ( key icon will disappear).
To switch contactor status from mains to genset, push “Generator” key: Generator icon will appear near frequency indicator, this icon blinks until feedback voltage is detected: from that moment, the icon becomes permanent. Push “Generator” key a second time to disconnect generator line without switching; push “Mains” key to switch contactor status from genset to mains, a icon will appear near frequency indicator, this icon blinks until feedback voltage is detected: from that moment, the icon becomes permanent. On display is possible to check mains line voltages, generator line voltages and frequency.
UP
Aut/Man
Generator
Start Gen
Select Mis
Down
LOCK
Mains
P21/32 Manuale ATS-I Tecnoelettra_IT-EN_rev1.doc
Tecnoelettra srl
Dal 1985
Tel.+39.0522.832004 – Fax.+39.0522.832012 P.21/32
Internet :www.tecnoelettra.it E
-
mail:info@tecnoelettra.it
To read mains voltages, push “Select Mis” key until “L” indication will appear on the left upper corner; at this point mains voltages will be showed on display. Push “Select Mis” again and “G” icon will appear; generator line voltages will replace mains measure. If generator is not running, “OFF” icon will appear which means unavailable genset measurements. The commutation is immediate (500ms delay from opening a contactor and closure the other) and a phase sequence check is performed each switching procedure. In manual mode, operative generator alarms are not detected, are available only indicators LA and LM. “M” letter on the right side means single-phase system.
Automatic mode
Automatic mode allows to manage engine and transfer switch completely by software logic, it’s not possible to start the generator or force switching through operative board, “AUTO” indication will appear on the low left corner. However with “Select Mis” is still possible to change displayed measurements from generator and mains. When controller commands switching on mains or generator, automatically values visible on display change in accordance. Each phase is checked separately, so a phase failure will start the automatic intervention procedure.
Alarms
If mains measurements are selected, in case of alarm will be possible to see one of these messages on the left side of the display :
- “LOW VOLT” line voltage below programmed threshold ( P3 parameter );
- “HIGH VOLT” line voltage over programmed threshold ( P4 parameter );
- “PH.SEQ.ERR” in case of wrong phase sequence;
Both alarms cause an automatic intervention procedure. Generator starting procedure begins after a programmable delay (P7 parameter).
With running generator, after another programmable timer ( P8 parameter), the controller checks voltage status measured on alternator and in case of anomaly, one of these alarms will be showed on display:
- “ERROR 1” if generator’s phase voltage is out of limits. ( P5, P6 parameters ).
- “ERROR 2” if generator’s frequency is out of limits. ( P12 parameter ).
- “ERROR 3” if generator fails to start.
If generator is working correctly, “ERROR 1” or “ERROR 2” alarms are showed if voltage or frequency values are out of limits for the duration of programmed time ( P15 parameter)
To reset an alarm on display must be used “Aut/Man” with locked keyboard ( “LOCK” key). The device returns on mains position and restarts commutation procedure towards generator. If generator alarm is active and mains voltage returns back, automatically the commutation will be switched on mains side.