Tecnibel CA250R5TA*, CA360R5TA*, CA480R5TA*, SPA250R5TA*, SPA360R5TA* Installation Manual

...
R 407 C
37.4163.194.0
INSTALLATION MANUAL
MANUALE D’INSTALLAZIONE
MANUEL D’INSTALLATION
MAGGIO 2001
Split system air conditioner
Climatiseurs split system
EG
I
F
CA250R5TA* CA360R5TA* CA480R5TA*
SPA250R5TA* SPA360R5TA* SPA480R5TA*
DSAV250R5TA* DSAV360R5TA* DSAV480R5TA*
CAV250R5TA* CAV360R5TA* CAV480R5TA*
SPAV250R5TA* SPAV360R5TA* SPAV480R5TA*
DSAV250R5TA* DSAV360R5TA* DSAV480R5TA*
R 22
Dear User
Thank you for selecting this product and we welcome you to the growing family of
satisfied products owners.
Like all products, it has been designed carefully and manufactured under strict quality
control.
We firmly believe that our products will give full satisfaction to users through proper
operation and maintenance.
Please read this manual, and be sure to keep it handy for your reference.
MODEL COMBINATIONS
CONTENTS
SEMI-CONCEALED MODEL
HEAT PUMP VERSION
INDOOR UNIT OUTDOOR UNIT CA250R5 GR250R5
GR250R7 CA360R5 GR360R7 CA480R5 GR480R7
CEILING-MOUNTED MODEL
HEAT PUMP VERSION
INDOOR UNIT OUTDOOR UNIT SPA250R5 GR250R5 SPAV250R5 GR250R7
SPA360R5
GR360R7
SPAV360R5 SPA480R5
GR480R7
SPAV480R5
CONCEALED DUCT MODEL
Combine indoor and outdoor units as listed above.
IMPORTANT: Please Read Before Starting
IMPORTANT: Precautions for new refrigerant R 407 C installation
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
1-1. Tools required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Type of copper Tube and Insulation Material 1-4. Additional materials required for Installation 1-5. Tubing Lenght 1-6. Operating Limits
2. INSTALLATION SITE SELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Indoor Unit Outdoor Unit 2-1. Air discharge chamber for top discharge 2-2. Installing the unit in heavy snow areas 2-3. Precautions for installation in heavy snow areas 2-4. Dimensions of snow/wind-proof ducting 2-5. Wind shield
3. HOW TO INSTALL THE INDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
4-WAY AIR DISCHARGE SEMI-CONCEALED TYPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
3-1. Suspending the Indoor Unit 3-2. Preparation for Suspending 3-3. Burying Inside the Ceiling 3-4. Installing the Drain Piping 3-5. Checking the Drainage
CEILING-MOUNTED TYPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
3-6. Suspending the Indoor Unit 3-7. Duct for fresh air 3-8. Installing the drain piping
CONCEALED-DUCT TYPE (DSAV Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
3-9. Required Minimun Space for Installation and Service 3-10. Suspending the Indoor Unit 3-11. Installing the Drain Piping 3-12. Increasing the Fan Speed 3-13. Checking the Drainage
4. HOW TO INSTALL THE OUTDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 17
4-1. Removing the Protective Spacer for Transportation 4-2. Installing the Outdoor Unit 4-3. Tubing Direction
EG
R
2 2
HEAT PUMP / COOLING ONLY VERSION
INDOOR UNIT OUTDOOR UNIT CAV250R5 GRV250L5/R5
GRV250L7/R7 CAV360R5 GRV360L7/R7 CAV480R5 GRV480L7/R7
R
4 0 7
C
HEAT PUMP / COOLING ONLY VERSION
INDOOR UNIT OUTDOOR UNIT SPAV250R5 GRV250L5/R5
GRV250L7/R7 SPAV360R5 GRV360L7/R7 SPAV480R5 GRV480L7/R7
HEAT PUMP / COOLING ONLY VERSION
INDOOR UNIT OUTDOOR UNIT DSAV250R5 GR250R5
GR250R7 DSAV360R5 GR360R7 DSAV480R5 GR480R7
1
HEAT PUMP VERSION
INDOOR UNIT OUTDOOR UNIT DSAV250R5 GR250R5
GR250R7 DSAV360R5 GR360R7 DSAV480R5 GR480R7
2
EG
5. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18
5-1. General Precautions on Wiring 5-2. Recommended Wire Lenght and Wire Diameter for Power Supply System 5-3. Wiring System Diagrams
6. HOW TO INSTALL THE REMOTE CONTROLLER (OPTIONAL PART) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
6-1. When Using a Wall Box for Flush Mounting 6-2. Basic Wiring Diagram 6-3. Wiring System Diagram for Group Control 6-4. Wiring System Digram for Multi-Remote Control 6-5. Meaning for Alarm Message
7. HOW TO INSTALL THE WIRELESS REMOTE CONTROLL UNIT (OPTIONAL PART) . . . . . . . . . . . . . . . . . . . . page 25
4-WAY AIR DISCHARGE SEMI-CONCEALED TYPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25
7-1. Indicator Section Installation 7-2. Operating Controler Installation
CEILING-MOUNTED TYPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
7-3. Indicator Section Installation 7-4. Operating Controller Installation 7-5. Electrical Wiring 7-6. Room temperature Sensor Setting 7-7. Address Switches 7-8. Setting the Model Code (only for Heat Pump models) 7-9. Test Run switch 7-10. Misoperation Alarm Indicators (only for Heat Pump models) 7-11. Wireless Remote controller Installation 7-12. How to install batteries (only for Heat Pump models)
8. HOW TO INSTALL THE WEEKLY TIMER (OPTIONAL CONTROLLER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 30
8-1. When Using a Wall Box for Flush Mounting 8-2. Wiring Diagram 8-3. Test Run Setting 8-4. Memory Back Up Function for Power Failure Compensation 8-5. State at Time of Power ON
9. HOW TO PROCESS TUBING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 32
9-1. Connecting Tubing Side 9-2. Connecting Tubing between Indoor and Outdoor Unit 9-3. Insulation of refrigerant Tubing 9-4. Taping the Tubes 9-5. Finishing the Installation
10. AIR PURGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 34
11. HOW TO INSTALL THE CEILING PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 36
4-WAY AIR DISCHARGE SEMI-CONCEALED TYPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 36
11-1. Before Installing the Ceiling Panel 11-2. Installing the Ceiling Panel 11-3. When Removing the Ceiling Panel for Servicing 11-4. Adjusting the Motor Flap
12. TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 38
12-1. Preparing for Test Run 12-2. PCB Setting 12-3. R.C. Address Setting Method 12-4. Automatic Address Setting Method 12-5. Test Run Procedure 12-6. Items to Check Prior to Test Run 12-7. The Main Alarms of Mis-wiring & Mis-setting 12-8. The Main Alarms of Unit Troubles 12-9. The Main Alarms of Power Supply Troubles
13. PUMP DOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 42
IMPORTANT
PLEASE READ BEFORE STARTING
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficienly.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state, and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
Outer diameter ø 6.35 ø 9.52 ø 12.7 ø 15.88 ø 19.05 ø 22.2 ø 25.4 ø 28.58 Wall thickness 0.8 0.8 0.8 1.0 1.0 1.2 1.0 1.0
3
EG
WARNING
• This symbol refers to a hazard or unsafe practice which can resuklt in severe personal injury or death.
IN CASE OF IMPROPER INSTALLATION
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instruction in this document.
When Transporting
Be careful when pocking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause driping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the aoutdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
When Connecting Refrigerant Tubing
• Executive enough ventilation in case refrigerant gases leak during operations. Be careful that the contact of the refrigerant gases with the flare will cause the generation of poisonous gases.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
CAUTION
• This symbol refers to a hazard or unsafe practice which can resuklt in personal injury or product or property damage.
SPECIAL PRECAUTION
• ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When Wiring
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltage are used in this system. Carefully refer to the wiring diagram and these instruction when wiring. Improper connections and inadequate grounding can cause accidentaly injury or death.
Ground the unit following local electrical codes.
• Connect all witing tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
PRECAUTIONS FOR NEW REFRIGERANT R 407 C INSTALLATION
1. Care regarding piping
1-1. There is no need to change piping and tube wall thickness. Use refrigerant pipes of the same wall thickness as R22.
Type 0 1/2 H, H
Copper tube
* C 1220 type with JIS H 3300 designation (Copper Pipe and Copper Alloy Seamless Pipe)
1-2. Prevent impurities including water, dust and oxide
from coming into the pipe. Impurities can cause R407C refrigerant deterioration and compressor defects. Due to the different features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.
2. Make sure to refill the refrigerant in liquid form
2-1. Since R 407 C is a non-azeotrope, refilling the
refrigerant in gas form can lower performance and
cause defects of the unit.
2-2. Since refrigerant composition changes and
performance decreases when gas leaks, collect the remaining refrigerant and refill the required total amount of new refrigerant after fixing the leak.
3. Different tools
3-1. Tools specs have been changed due to the features
of R 407 C. Some of the R 22 tools cannot be used.
Vacuum pump
4
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not
supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Tourque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Suppled with Unit
See Table 1-1 to 1-3.
Table Type
1-1 4-Way AirDischarge Semi-Concealed 1-2 Ceiling-Mounted 1-3 Concealed-Duct
1-3. Type of Copper Tube and Insulation
Material
To purchase these material from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for 15.88 mm (5/8”) or
19.05 mm (3/4”) O.D. copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire size varies with the total length of witing. Refer to Section 5. Electrical Wiring for details.
EG
Gauge manifold
Vacuum pump
Outlet
Inlet
Liquid
Valve
Product name
Gauge manifold
Charge hose
Leak detector
Flaring oil
New
tools
Yes
Yes
Yes
Yes
Yes
R22 tools compatible with R407C
No
No
Yes
No
No
Remarks
Types of refrigerant and refrigerating machine oil, and pressure gauge are different.
To resist pressure and oil, material has been changed.
Use a conventional vacuum pump if it is equipped with a check valve. If it has no check valve, purchase and attach a vacuum pump adaptor.
Leak detector for CFC an HCFC which react to chlorine do not function because R407C contains no chlorine. Leak detector for R407C can be used for HFC134a.
Mineral oil (for example, suniso oil) can be used as R22 oil. Use synthetic fluid (for example, ether oil) as R407C oil.
* Using both R22 tools and new tools together can cause defects.
3-2. Use a R407C exclusive cylinder only.
Single-outlet valve
(with siphon tube). Liquid refrigerant can be refilled standing it up straight.
New refrigerant R407C cannot be used for existing models.
1. Compressor specs are different.
When refilling the R22 compressor with R407C, durability will significantly decrease since some of the materials used for compressor parts are different.
2. Existing piping cannot be used.
Completely cleaning out residual refrigerating machine oil is impossible, even by flushing.
3. Refrigerating machine oil differs.
Since R22 refrigerating machine oil is mineral oil, it does not dissolve in R407C. Therefore, refrigerating machine oil discharged from the compressor can cause compressor damage.
R22 refrigerating machine oil Mineral oil (suniso oil) R407C refrigerating machine oil Synthetic fluid (ether oil)
R 407 C
5
1-4. Additional Materials Required for
Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
CAUTION
• Check local electrical codes and regulations before obtainig wire. Also, check any specified instructions or limitations.
Part Name Figure Q’ty Remarks
Full-scale installation diagram 1 For determinig suspension bolt pitch
Flare insulator 2 For wide and narrow tubes
Installation gauge 1 For adjusting the unit position
Insulating tape 1 For wide tube flare nuts
Hose band 2 For Securing drain hose
Packing 1 For drain joint
Dran insulator 1 For drain joint
Drain hose 1 For drain hose joint
Sealing putty 1 For sealing recessed portion of power supply
Tube connector 1
For sizing up of narrow tube from 6.35 to 9.52 (only for 25 type)
Table 1-1. 4-Way Air Discharge Semi-Concealed
Table 1-2. Ceiling-Mounted
(White-for insulating)
Part Name Figure Q’ty Remarks
Special washer 4 For suspending indoor unit from ceiling
Drain insulator 1 For drain hose joint
Flare insulator 1 Set For drain narrow tube joints
Drain hose clamp
4 For drain hose joint 2 For rubber cap (in case of using left side drain pipe)
Insulating tape 2 For wide flare joint
Vinyl clamp 8 For ends of flare insulator
Sealing insulator
1 For sealing top face
1 For sealing rear face
Grommet 1 For power supply inlet
Full-scale installation diagram 1 For determining suspension bolt pitch
Sealing putty 1 For sealing recessed portion of power supply
Owner’s manual 1
Drain hose 1 For drain hose joint
Tube connector 1
For sizing up of narrow tube from 6.35 to 9.52 (only for 25 type)
White (heat-resisting)
T10
T3T5
EG
Special washer 8 For suspending indoor unit from ceiling
Flare Insulator 2 For wide and narrow tubes
Insulating Tape 1 For wide and narrow tubes flare nuts
Drain Insulator 1 For drain hose joint
Hose band 2 For securing drain hose
Packing 1 For drain joint
Drain hose 1
Sealing putty 1 For sealing recessed portion of power supply
Vinyl clamp 8 For flare insulator
Booster cable* 1 For increasing the fan speed
Tube connector 1
For sizing up of narrow tube from 6.35 to 9.52 (Only for 25 type)
6
Booster cable is housed inside the electrical component box.
1-5. Tubing Length
• Refrigerant tubing between the indoor and outdoor units shall be kept as short as possible
• The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the two units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H) as short as possible. Refer to Table 1-4 for the details.
Installation Example 1
INDOOR
UNIT
Tubing length (L)
OUTDOOR
UNIT
Elevation difference (H)
Table 1-3. Concealed-Duct
Table 1-4.
6.35 (1/4)
15.88 (5/8) 50
50
30
30
a) 45
3.0 3.2
Tubing size
Narrow tube mm(in.)
outer diameter
Wide tube mm (in.)
Limit of tubing length (m)
Outdoor unit is placed upper (m)
Limit of elevation difference between the two units
Outdoor unit is placed lower (m)
Max. allowable tubing length at shipment (m) Required additional refrigerant*
1
(g/m)
Refrigerant charged at shipment (kg)
9.52 (3/8)
19.05 (3/4) 50
50
30
30
b) 50
3.5 4.0
9.52 (3/8)
19.05 (3/4) 50
50
30
30
b) 50
4,5
Models
Tubing Data
No additional charge of compressor oil is necessary. *1 If total tubing length becomes 30 to 50 , charge additional refrigerant by a) 45 or b) 50 g/m.
EG
425 type
R22 R407C
436 type
R22 R407C
448 type
R22 R407C
1-6. Operating limits
Temperature Indoor air intake temp. Outdoor air intake temp.
Maximum 35°C DB / 25°C WB 43°C DB
Cooling
Minimum 18°C DB / 14°C WB – 5°C DB (–15°C DB*)
Maximum 27°C DB 21°C DB / 15.5°C WB
Heating
Minimum 15°C DB – 15°C WB
* R407C models only
Part Name Figure Q.ty Remarks
Ceiling-Mounted Type
DO:
• select an appropiate position from which every corner of the room can be uniformly cooled.
• select a location where the ceiling is strong enough to support the weight of the unit.
• select a location where tubing and drain pipe have the shortest run to the outside.
• allow room for operation and maintenance as well as unrestricted ai flow around the unit.
• install the unit within the maximum elevation difference (H) above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in table 1-4.
• allow room for mounting the remote controller about 1 moff the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.
7
NOTE
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 3 m.
4-Way Semi-Concealed Type
Ceiling
Wall
25 cm min.
Air discharge
Side view
Air intake
30 cm min.
25 cm min.
NOTE
The rear of the indoor unit can be installed flush against the wall.
Front view
1 m
1 m
1 m
1 m
1 m
AVOID:
• heat source, exhaust fans, etc. (Fig. 2-1).
• damp, humid or uneven locations.
DO:
• choose a place as cool as possible.
• choose a place that well ventilated and autside air temperature does not exceed maximum 45 °c constantly.
• allow enough room around the unit for air intake/exhaust and possible maintenance. (Fig. 2-2).
• provide a solid base; about 15 cm above ground level to reduce humidity and possible water damage in unit and drecrease service life. (Fig. 2-3).
• use lug bolts or equal to bolt down unit, reducing vibration and noise.
OUTDOOR UNIT
Air in
Air in
Min. 15 cm
Air discharge
Anchor bolts (4 pieces)
Model Min. (cm)
425 type 10 436, 448 type 20
Fig. 2-3
Hot air
Out­door unit
Exhaust fan
Heat source
Fig. 2-1
Fig. 2-2
Min. 1 cm
Min. 1 cm
Min. 2 m
Ground
Min. 2 m
Obstacle
Air dis­charge
Min. 50 cm
Obstacle above
Table 2-1 Dimension
A
2. INSTALLATION SITE SELECTION
AVOID:
• areas where leakage of flammable gas may be expected.
• places where large amounts of oil mist exist.
• direct sunlight.
• location where nearby heat sources may affect performance of the unit.
• locations where nearby external air may enter the room directly. This may cause “sweating” in the air discharge ports, causing them to spray or drip.
• location where the remote controller will be splashed with water or affected by dampness or humidity.
• installing the remote controller behind curtains or furniture.
INDOOR UNIT
EG
8
Min. 1 m Min. 1 m Min. 1 m Min. 1 m
Min. 20 cm
Min. 35 cm
Min. 35 cm
Min. 30 cm
Min. 30 cm
Air discharge chamber
Min. 1.5 m
Min. 30 cm
Min. 35 m
Min. 20 cm
In case of multiple installations
Unit spacing if air discharge chamber is not used. Unit spacing when air dscharge chamber is used.
* If you would like to make the separation smaller on the air discharge side, use an air discharge chamber. * Your can install any number of units side-by-side.
* Only up to 3 units can be install side-by-side under the above conditions. the next group must be spaced at least 30 cm away from the first group.
2-1. Air Discharge Chamber for Top
Discharge
Be sure to install the air discharge chamber in the field when:
• it is difficult to keep a space of min. 50 cm between the air discharge outlet and the obstacle.
• The air discharge outlet is facing to the sidewalk and discharged hot air annoys the passers.
Refer to Fig. 2-4.
2-2. Installing the Unit in Heavy Snow
Areas
In positions with strong wind, snow-proof ducting should likewise be fitted and direct exposure to the wind should be avoided as much as possible. Countermeasures against snow and wind in regions with snow and strong wind, the following problems may occur when the outdoor unit is not provided with a platform and snow-proof ducting.
a) The outdoor fan may not run and damage of the
unit may be caused. b) There may be no air flow. c) The tubing may freeze and burst. d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
2-3. Precautions for Installation in Heavy
Snow Areas
1) The platform should be higher than the max, snow
depth. (Fig. 2-5).
2) The two fixing feet of the outdoor unit should be
used for the platform, and the platform should be
installed beneath the air intake side of outdoor
unit.
3) The platform foundation must be firmer and the
unit must be secured with anchor bolts.
4) In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent
the unit from being blown over.
Air discharge
Fig. 2-4
In regions with snow fall, the outdoor unit should be provided with a platform and snow-proof duct.
Without snow-
proof ducting
(Low platform)
With snow-proof
ducting
(High platform)
Fig. 2-5
Fig. 2-6
Air Intake
Platform (foundation)
Higher than the maximum snow depth
Duct
About 1/2 of the unit height
Air Intake
Duct
Outdoor Unit
Example of Installation
Duct
Duct
Outdoor Unit
Min. 100 300
Min. 100 300 Unit: mm
2-4. Dimensions of Snow/Wind-proof
Ducting and Refrigerant Tubing Space for Installation
EG
9
4-WAY AIR DISCHARGE SEMI-CONCEALED TYPE
EG
3-1. Suspending the Indoor Unit
This unit uses a drain pump. Use a carpenter’s level to check that the unit is level.
3-2. Preparation for Suspending
(1) Fix the suspension bolts securely in the ceiling using
the method shown in the drawings (Figs. 3-1 / 3-2 / 3-3), by attaching them to the ceiling support structure, or by any other method that insures that the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the
ceiling.
Model A B
425 type 820 730
436, 448 type 1110 1020
3) Determine the pitch of the suspension bolts using the provided full-scale installation diagram. The diagram and table (Fig. 3-3 and Table 3-3) show the relationship between the position of the suspension fitting, the unit, and the panel.
Model ABCDE
425 type 150 200 255 298 125
436, 448 type 165 235 285 328 125
Hole-in-anchor Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8’’) (field supply)
A (ceiling opening dimension)
B (suspension bolt itch)
Electrical component box
Refrigerant tubing side
Drain hose side
Refrigerant tubing joint (narrow tube side)
Refrigerant tubing joint (wide tube side)
Drain inspection port
Suspension lug
Power supply inlet
Unit: mm
820 (ceiling opening dimension)
590 (suspension bolt pitch)
Fig. 3-1
Fig. 3-3
Fig. 3-2
3. HOW TO INSTALL THE INDOOR UNIT
Table 3-1
Table 3-2
Unit: mm
Unit: mm
2-5. Wind Shield for “SHL”, “SCL” Model
It is recommended to install wind shields for cooling operation in low outdoor temperature condition. (Fig. 2-8).
General
When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air temperature in winter), wind shield must be installed on the outdoor unit.
This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.
For outer dimensions of wind shield, please see Fig. 2-9.
IMPORTANT
Fig. 2-8
Wind shield (air discharge side)
Front
3 - ø60 hole
8 - ø6 hole
450 100250250
1116
132
567
131
300
592
3 -
ø40 hole
6 -
ø6 hole
25054924
132
57013
596
554
13125025027
554
For 436,448 type
For 425 type
Fig. 2-9
Recommended outer dimensions of wind shield (field supply).
10
EG
3-3. Burying inside the Ceiling
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts using the provided full­scale installation diagram. (Fig. 3-4).
Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring into positiion for connection to the unit before placing the unit inside the ceiling.
(2) The length of suspension bolt must be so that the
distance between the bottom of the bolt and the bottom of the ceiling is more than 60 mm as shown in Fig. 3-4.
(3) Thread the 2 hexagonal nuts and washers (field supply)
onto the 4 suspension bolts as shown in Fig. 3-5. Use 2 sets of nuts and washers (upper and lower), so
that the unit with not fall off the suspension lugs.
(4) Remove the protective cardboard used to protect the
fan parts during transport.
(5) Adjust the distance between the unit and surface of
the ceiling (48 mm) using the supplied installation gauge. (Fig. 3-4).
3-4. Installing the Drain Piping
(1) Prepare a standard hard (PVC) pipe (O.D. 32 mm) for
the drain and use the accessory drain hose and hose band to prevent water leaks.
The PVC pipe must be purchase separately. The transparent part allows you to check drainage.
(Fig. 3-6).
Full-scale installation drawiong
(provided)
Transparent part for checking drainage
Hose band (supplied)
Hard PVC pipe pipe (not supplied)
Drain hose (supplied)
Packing (supplied)
Nuts and washers
(2 sets)
Suspension bolt
Suspension lug
Uppper
Lower
More than 60 mm
48 mm
Fig. 3-4
Fig. 3-5
CAUTION
• Tighten the hose band firmly after the supplied drain hose has been inserted to touch the ends of both of the connection pipes, as shown in Fig. 3-7.
• Do not use an adhesive when connecting the supplied hose. Reasons:
1. It may cause water to leak from the connection. Sin­ce the connection is slippery just after the adhesive has been applied, the pipes easily slip off.
2. The pipes cannot be removed when maintenaces is needed.
• Do not bend the supplied drain hose 90° or more. The hose may slip off.
• Align the hose bands with the ends of the hoses. Ti­ghten the hose bands firmly. PLease make sure that the stopper is not covered by the hose band, as shown in Fig. 3-7.
CAUTION
• Tighten the hose clamps so their locking nuts face upward (Fig. 3-6).
(2) After checking the drainage, wrap the supplied packing
and drain pipe insulator around the pipe. (Fig. 3-8.)
NOTE
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
Fig. 3-6
Fig. 3-7
Drain insulator (supplied)
Air bleeder
Fig. 3-8
Fig. 3-9
Stopper
Hose band
Supplied drain hose
Drain pipe (not supplied)
Connection pipe
Hose band
Align the hose band with the end of the pipe
Align the hose band with the end of the pipe
11
EG
3-5. Checking the Drainage
After wiring and piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (L, N terminal) inside the electrical component box. (2) Remove the tube cover and through the opening, slowly pour about 1,200 cc of water into the drain pan to check drainage. (3) Short the check pin (CN5 withe) on the indoor control main board and operate the drain pump. Check the water flow and see
if there is any leakage.
CAUTION
Be careful since the fan will start when you short the pin on the in­door control board.
(4) When drain checking is finished, open the check pin
(CN5 white) and remount the tube cover.
CAUTION
To mount the tube co-
ver, use 4 x 8 tapping screws. Do not use long screws as they may puncture the drain pan and cause water leakage.
4 x 8 mm tapping screw
Tube cover
Front face
Rear
Full-scale diagram
Hole-in-anchor Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8’’) (field supply)
Fig. 3-13
CEILING-MOUNTED TYPE 3-6. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the ceiling
at the spot where you want to install the indoor unit. Use a pencil to mark the drill holes. (Fig. 3-14).
NOTE
Since the diagram is made of paper, it may shrink or stretch slightly because of high temperature or humidity. For this reason, before drilling the holes maintain the correct dimensions between the markings.
(2) Drill holes at the 4 points indicated on the fullscale
diagram.
(3) Depending on the ceiling type:
a) Insert suspension bolts as shown in Fig. 3-15.
or
b) Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-16.
Fig. 3-14
Fig. 3-15
CAUTION
Do not install an air bleeder, as this may cause water to spray from the drain tube outlet. (Fig. 3-9)
If it is neccesary to increase the height of the drain pipe somewhat, the portion directly after the connection port can be raised a maximum of 25 cm. Do not raise it any higher than 25 cm, as this could result in water leaks. (Fig. 3-10)
Do not install pipe with an upward gradient from the connection port. It will cause the drain water to flow backwards and leak when the unit is stopped. (Fig. 3-11)
Do not apply force to the piping on the unit side when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its connection to the unit. Fasten the pipe to a wall, frame, or other support as close to the unit as possible. (Fig. 3-12)
Be sure to provide insulation for any drain piping installed indoors.
30 cm or less (as short as possible)
25 cm or less
Upward gradient
Support
pieces
Fig. 3-10
Fig. 3-11
Fig. 3-12
12
EG
Ceiling tiles
Ceiling support
A
A
unit
Fixture
Ceiling surface
Within
50 mm
WARNING
It is important that you use extreme care in supporting the indoor unit from the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the ceiling unit, test the strength of each attached suspension bolt.
(4) Screw in the suspensions bolts, allowing them to
protrude from the ceiling as shown in Fig. 3-16. The distance od each exposed bolt must be of equal length within 50 mm. (Fig. 3-17)
(5) Before suspending the indoor unit; remove the 2 or 3
screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 3-18. Then remove both side panels sliding them along the unit toward the front after removing the two screws which fix them. (Fig. 3-19).
(6) Preparation for suspending the indoor unit. The
suspension method varies depending on whether the unit is next to the ceiling or not. (Fig. 3-20 and 3-21).
(7) Suspend the indoor unit as follows.
(a) mount a washer and two hexagonal nuts on each suspension bolt as shown in Fig. 3-22.
Fig. 3-16
Fig. 3-17
Pul out the Air­Intake grille pushing claws of the hinges
Hinge
Screw
Latch
Air-intake grille
Suspension bolt (field supply)
Ceiling surface Washer (supplied)
Double nut (field supply)
Fixture
unit
Slide toward front side
Sode panel
Ceiling surface
Nut (field supply)
Suspension bolt
Washer
(supplied)
Approx.
25 mm
Slide
Fig. 3-18
Suspension bolt (field supply)
Washer (supplied)
Washer (field supply)
Double nut (field supply)
unit
Fig. 3-19
Fig. 3-20
Fig. 3-21
Fig. 3-22
Fig. 3-23
Fig. 3-24
(b) Lift the indoor unit, and place it on the washer throught the notches, so as to fix it in place.(Fig. 3-23)
(c) Tighten the two hexagonal nuts on each suspension bolt to suspend the indoor unit as shown in Fig. 3-24.
NOTE
A ceiling surface is not always level. Please confirm that the indoor unit is evenly suspended. For the installation to be correct, leave a clearance of about 10 mm between the ceiling panel and the ceiling surface and fill the gap with an appropriate insulation or filler material.
(8) If the tubing and wiring have to pass towards the rear
of the unit, make holes in the wall. (Fig. 3-25)
(9) Measure the thickness of the wall from the inside to
the outside and cut PVC pipe at a slight angle to fit. Insert the PVC pipe in the wall. (Fig. 3-26)
NOTE
The hole should be made at a slight downxard slant to the outside.
13
3-7. Duct for Fresh Air
There is a duct connection port (knock-out hole) at the right­rear on the Panel Top of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by knocking out and connect the duct to the idoor unit throught the connection port. (Fig. 3-27)
If connection at the right-rear on the Panel Top is not appropriate, another duct connection port can be made by cutting an opening on the left side of the Rear Panel of the indoor unit as shown in Fig. 3-28.
3-8. Installing the Drain Piping
Prepare a standar PVC pipe for the drain and connect it to the indoor unit drain pipe with the supplied hose clamps to prevent water leaks.
CAUTION
Tighten the drain pipe clamps so that the locking nuts are facing upwards. (If tightened with the locking nuts facing downwards, it may cause water leakage).
Do not use an adhesive when connecting the drain hose (supplied) to the drain connection (main unit, PVC pipe).
Connect the drain piping so that it slopes downward from the unit to the outside. (Fig. 3-29)
Never allow traps to occur in the course of the piping.
Insulate any piping inside the room to prevent dripping.
Use the supplied drain pipe to connect the drain pipe with the
drain outlet of the indoor unit.
After connecting the drain pipe securely, wrap the supplied drain pipe insulator around the pipe, seal the gap at the drain socket with the supplied black insulation tape, then secure it with clamps. (Fig. 3-30)
After the drain piping, pour water into the drain pan to check that the water drains smoothly.
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any spe­cified instruction or li­mitations.
Duct connection port (Knock-out hole)
Panel Top
Right side
Right side
Cut this portion
Fig. 3-27
Fig. 3-28
Fig. 3-29
Fig. 3-30
ABC
425 110 100 100
110 100 150
436
448
Min. 1/100
Good
Not good
Drain hose (supplied)
Drain pipe camp (supplied)
Hard PVC pipe (not supplied)
Vinyl clamp (supplied)
Packing (supplied)
EG
Fig. 3-25
Fig. 3-26
Indoor side
Outdoor side
PVC pipe (localy purchased)
INSIDE OUTSIDE
PVC pipe
Slight angle
Cut at slight angle
Wall
Loading...
+ 30 hidden pages