Technische Alternative UVR65 Programs, Installation, Electric Connection User Manual

Page 1
www.ta.co.at
UVR65
UNIVERSAL CONTROLLER
Version 1.01
Programs
Installation
Electric Connection
EnglishManual Version 1.01.5
Page 2
Page 3
Diese Anleitung ist im Internet auch in anderen Sprachen unter www.ta.co.at
verfügbar.
This instruction manual is available in English at www.ta.co.at
Ce manuel d’instructions est disponible en langue française sur le site Internet
www.ta.co.at
Questo manuale d’istruzioni è disponibile in italiano sul sito Internet
www.ta.co.at
Estas instrucciones de funcionamiento están disponibles en español, en Inter-
net www.ta.co.at.
Page 4
Table of contents
Safety requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Generally applicable rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
„Step by Step“ Setup guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Hydraulic diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Differential control – Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Program 0 – Simple solar system (factory settings) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Program 16 – Cylinder charge from a boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Program 32 – Burner request via cylinder sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Program 48 – Solar power system with 2 consumers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Program 64 – Solar power system with 2 solar panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Program 80 – Simple solar system and cylinder charge from a boiler . . . . . . . . . . . . . . . . 16
Program 96 – Buffer and hot water cylinder charging via solid fuel boiler . . . . . . . . . . . . . 17
Program 112 – 2 independent differential circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Program 128 – Burner request and solar system (or charging pump) . . . . . . . . . . . . . . . . . 19
Program 144 – Solar system with layered cylinder charging . . . . . . . . . . . . . . . . . . . . . . . . 20
Program 160 – Insertion of two boilers into a heating system . . . . . . . . . . . . . . . . . . . . . . 21
Program 176 – Solar system with 2 consumers and charging pump functionality . . . . . . . 22
Program 192 – Solar system with 2 consumers and charging pump (heating boiler) . . . . . 23
Program 208 – Solar system with 2 consumers and burner request . . . . . . . . . . . . . . . . . . 24
Program 224 – Solar system with 3 consumers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Program 240 – Solar system with 2 solar panels and 2 consumers . . . . . . . . . . . . . . . . . . 27
Program 256 – Solar power system with two solar panels (1 pump, 2 stop valves) . . . . . 28
Program 272 – Solar system with 2 collector panels and charging pump function . . . . . . 29
Program 288 – Solar system with 2 collector panels and burner request . . . . . . . . . . . . . . 30
Program 304 – Solar system with 2 collector panels + charging pump (boiler) . . . . . . . . . 31
Program 320 – Layered cylinder and charging pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Program 336 – Solar system with 2 consumers and layered cylinder charging . . . . . . . . . 33
Program 352 – Layered cylinder and burner request . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Program 368 – Layered cylinder and charging pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Program 384 – Layered cylinder with bypass functionality . . . . . . . . . . . . . . . . . . . . . . . . . 36
Program 400 – Solar system with 1 consumer and 2 charging pump functions . . . . . . . . . 37
Program 416 – 1 consumer, 2 charging pumps and burner request . . . . . . . . . . . . . . . . . . 38
Program 432 – Solar system, burner request, and one charging pump . . . . . . . . . . . . . . . . 39
Program 448 – Burner request and 2 charging pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Program 464 – Solar system with 2 consumers and bypass function . . . . . . . . . . . . . . . . . 43
Program 480 – 2 consumers and 3 charging pump functions . . . . . . . . . . . . . . . . . . . . . . . 44
Program 496 – 1 Consumer and 3 charging pump functions . . . . . . . . . . . . . . . . . . . . . . . 46
Program 512 – 3 independent differential circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Program 528 – 2 independent differential circuits & independent burner request . . . . . . . 48
Program 544 – Cascade: S1 -> S2 -> S3 -> S4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Program 560 – Cascade: S1 -> S2 / S3 -> S4 -> S5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Program 576 – Cascade: S4 -> S1 -> S2 + burner request . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Program 592 – 2 generators for two consumers + independent differential circuit . . . . . . 52
Program 608 – 2 generators for 2 consumers + burner request . . . . . . . . . . . . . . . . . . . . . 54
Program 624 – Solar system with one consumer and swimming pool . . . . . . . . . . . . . . . . 56
Program 640 – DHW preparation incl. circulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Program 656 – DHW preparation incl. circulation + burner request . . . . . . . . . . . . . . . . . . 58
Program 672 – 3 generators for 1 consumer + differential circuit + burner request . . . . . . 59
Page 5
Table of contents
Building drying – General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
External sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Programs – Building drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Program 688 – Only room drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Program 689 – Room drying and minimum temperature monitoring . . . . . . . . . . . . . . . . . 61
Program 690 – Room drying, minimum temperature monitoring, comfort ventilation . . . . 62
Program 691 – Room drying & comfort ventilation, minimal temp. monitoring for both . . . 62 Program 692 – Room drying, room temp. monitoring, comfort ventilation, for wine cellars 63
Setting up time programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Heating circuit control - Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Program 800 – Heating circuit with up to 2 heat sources . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Program 816 – Boiler circuit pump, mixer for return flow boosting . . . . . . . . . . . . . . . . . . 66
Program 832 – Solid fuel burner, buffer cylinder, heating circuit, additional heating req. . . 67
Program 896 – Automatic burner, cylinder, heating circuit, boiler request . . . . . . . . . . . . . 69
Program 912 – Automatic boiler, (combined) buffer, heating circuit, burner request . . . . . 71
Program 928 – Buffer, Cylinder, Heating circuit, boiler request . . . . . . . . . . . . . . . . . . . . . . 73
Program 944 – Solid fuel boiler, buffer, cylinder, heating circuit . . . . . . . . . . . . . . . . . . . . . 76
Program 960 – Boiler (or buffer), cylinder, 1 regulated & 1 unregulated heating circuit . . . 78
Programs 976/977/978 – Screed drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
Sensor installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Device installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Mixer connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Data line for DL-Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
CAN-Bus network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
CAN-Bus – Output values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Operation – Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
Device overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Example of menu view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Time/date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Operation – General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
Display (under Settings) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Data admin (under Settings) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Operation – Differential control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
System status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Page 6
Table of contents
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Technician level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Example for thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Schematic representation of thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Time/date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Datalogging settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Expert level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Programming settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Sensor menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Ext. sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Setting up external sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Blocking protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Run-on time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Blocking time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Control output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Absolute value control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Differential control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Event control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Stability problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Output mode, Correcting variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Control delay, control commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
System protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Excess temp. limiter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Collector cooling function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Start function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Solar priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Funct. check (Function check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Heat meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Step-by-step setup guide for heat metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Pasteurisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Drain-Back . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
CAN-/DL-Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Operation – Heating circuit control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Time prog. htg circ./DHW/Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
HC controller mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Time/Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
HC controller status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Technician level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Page 7
Table of contents
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Example for threshold values Max/Min/Diff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Further heating circuit parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Heating characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Heat curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Adjusting time programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Time/date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Datalogging settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Expert level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Programming settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Sensor menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Ext. sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Setting up external sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Blocking protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Run-on time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Blocking time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Control output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Absolute value control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Differential control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Event control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Stability problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Output mode, Correcting variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Control delay, control commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Shutdown conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Mixer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Funct. check (Function check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Heat meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Step-by-step setup guide for heat metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Pasteurisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
CAN-/DL-Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Datalogging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .170
Logged values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Datalogging without C.M.I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Datalogging with C.M.I. – Winsol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Datalogging with C.M.I. – Web-based . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Tips on troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
Technical support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .173
Information on the Eco-design Directive 2009/125/EG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .174
Page 8
8
Safety requirements
This device is state of the art and meets all necessary safety regulations. It may only be used
in accordance with the technical data and the safety requirements and regulations listed be-
low. When using the device, also observe the statutory and safety regulations apposite to the particular use. Any other use will automatically void all warranty rights.
• The device must only be installed in a dry interior room.
• It must be possible to isolate the controller from the mains using an omnipolar isolating facility (plug/socket or 2-pole isolator).
• Before starting installation or wiring work, the controller must be completely isolated from the mains and protected against reconnection. Never interchange the safety low voltage connections (e.g. sensor connections) with the 230 V connections. Destruction and life threatening voltages at the device and the connected sensors may occur.
• Solar thermal systems can become very hot. Consequently there is a risk of burns. Pro-
ceed with caution when fitting temperature sensors.
• For safety reasons, the outputs should only be left in manual mode when testing. In this operating mode, no maximum temperatures or sensor functions are monitored.
• Safe operation is no longer possible if the controller or connected equipment exhibits visual damage, no longer functions or has been stored for lengthy periods in unsuitable conditions. If this is the case, disable the controller and equipment and secure against unintentional use.
Maintenance
If treated and used correctly, the device will not require any maintenance. Use a cloth mois-
tened with mild alcohol (such as methylated spirits) to clean. Never use corrosive cleaning agents or solvents such as chloroethylene or trichloroethylene. No components relevant to long term accuracy are subject to loading if the device is used
correctly. Consequently long term drift is extremely low. The device therefore cannot be cal-
ibrated. Thus applying any compensation is impossible. The design characteristics of the device must not be changed during repairs. Spare parts must correspond to the original spare parts and must be used in accordance with the build version.
Disposal
• Devices no longer in use or beyond a state of repair must be disposed of in an environmentally responsible manner by an authorised collection point. They mus never be treated as ordinary household waste.
• We can undertake the environmentally responsible disposal of devices sold by the Technischen Alternative company upon request.
• Packaging material must be disposed of in an environmentally responsible manner.
• Incorrect disposal may result in considerable damage to the environment, as many of the materials used require professional handling.
All installation and wiring work on the controller must only be carried out in a zero volt state. The opening, connection and commissioning of the device may only be carried out by competent personnel. While doing so, they must observe all local safety requirements.
Page 9
9
Generally applicable rules
For the proper use of this device
The manufacturer’s warranty does not cover any indirect damage to the unit if the technician install-
ing the unit does not equip it with any additional electromagnetic modules (thermostat, possibly in
combination with a one-way valve) to protect the device from damage as a result of malfunction un-
der the following circumstances:
• Swimming pool system: If used with a high-performance collector and heat-sensitive compo-
nents (such as plastic lines), the supply line must have an excess temperature thermostat with
all of the necessary self-closing valves (closed when without current). The controller’s pump out-
put may provide these currents, if needed. As such, all heat-sensitive parts would be protected
from overheating if the system was idle, even if steam was to form due to stagnation. This tech-
nique is mandatory, especially in systems with heat exchangers, as a failure of the secondary pump might cause great damage to the plastic tubes.
• Conventional solar power systems with an external heat exchanger: in such systems, the sec-
ondary heat transfer medium is usually pure water. If the pump runs at temperatures below the freezing point because of controller malfunction, the heat exchanger and other components may
suffer frost damages. In this case, a thermostat must be installed on the supply line of the sec­ondary side after the heat exchanger to automatically stop the primary pump when the tempera-
ture falls below 5°C, regardless of the controller‘s output.
• When used for floor and wall heating: A safety thermostat must be used, just as with conven-
tional heating controllers. The heat circuit pump must be shut down if overheating occurs, regardless of the controller‘s output, to prevent indirect damage from excess temperatures.
Solar systems - tips for idle systems (stagnation):
Generally, stagnation is not problematic and cannot be ruled out if there is a power outage, for in-
stance. In the summertime, the controller’s storage limit may switch off the system repeatedly. Every
system must thus be intrinsically safe. If the expansion container is properly designed, this is en­sured. Tests have shown that the heat transfer medium (anti-freeze) is under less stress during stag-
nation than when it is just below the steam phase.
Data sheets of collector manufacturers list idle temperatures above 200°C. However, these temper-
atures generally only occur during operation with dry steam, i.e. if the heat exchange medium has completely turned to steam in the collector, or if the collector has been completely emptied due to steam. The damp steam then dries quickly and is no longer able to conduct heat. Hence, it can be assumed that these high temperature cannot occur at the measuring point of the collector sensor (when installed in the collector tube as usual), as the remaining thermal line would cool down the temperature via the metal connections between the absorber and the sensor.
Page 10
10
„Step by Step“ Setup guide
The following guide might give you instructions on setting up the device, but it is of utmost importance to read the entirety of the instruction manual – especially the chapters „Pro­grams“ and „Operation“.
Level
1
Choose a hydraulic diagram based on the sketches of system dia­grams. Mind the arrow diagram, as well as the the program exten-
sions „+1“, „+2“ and such, as far as they are specified in the diagram.
2
Choose a program based on its number. It may be feasible to use one or more program extension such as „+1“ or „+2“ to optimize your system‘s regulation.
3
Connect the sensors to the inputs, as well as pumps, valves etc. to the outputs according to the chosen program. If used, connect the data link (DL-Bus), the CAN-Bus and the control outputs.
4
Expert
Access the Expert level using the access code 64 and input your cho-
sen program‘s number under „Program settings“.
5
Technician
Setting up the priority allocation in the sub-menu Technician/Param­eters/Priority ranking.
6
Technician
Enter the necessary setting values max, min, diff according to the list of „necessary settings“ below your chosen program‘s diagram.
7
Technician Enter the time, date and summer time properties.
8
Technician If required, specify time programs under Time program.
9
Technician
Menu Manual Operation: the choices „Manual/ON“ and „Manual/OFF“ offer the possibility to set outputs to be turned permanently on or off in order to check their connection. It‘s crucial to set the outputs back to „Auto“ after you‘re done checking their functionality. If the chosen program uses control outputs or if they‘ve been set up manually, they can be set up to „Manual/ON“ (= 10V or 100% PWM) or „Manual/OFF“ (= 0V or 0% PWM). Alternatively, you can choose a specific voltage or PWM-percentage to be output. Don‘t forget to set the outputs back to Auto after checking their functionality.
10
Expert
Outputs can be crossed out, if so desired. Find the option under
Crossout.
11
Expert
If you‘re not using the standard type PT1000 temperature sensors, you must change your inputs‘ type of sensor in the Sensor menu.
12
Expert
If so desired, activate additional functions like starting function, cool-
ing function, heat meter etc.
13
Check the displayed sensor measurements on whether or not they‘re plausible. Disconnected or incorrectly parameterized sensors display a value of 9999,9°C.
Page 11
11
Hydraulic diagrams
• The following functions can be activated in addition to all programs: Pump run-on time, 0-10V or PWM outputs (if not already in use by the program), Sys-
tem function check, Heat meter, Pasteurisation (excl. building drying), Blocking protec­tion (excl. building drying).
• The following functions only make sense when a solar panel is used in your system.
Excess temperature limiter, Frost protection, Start function, Solar priority, Cooling function, Drainback function (only for drainback systems)
• The outputs A2, A3 and/or A5 can be logically connected (And/Or) to other outputs if they‘re not used by your chosen program. Find the corresponding settings under Expert level/Program settings/Assign unused outputs. Alternatively, you can simply control them with manual settings.
• A hold circuit (= burner request using one sensor, deactivation using another) predomi-
nantly reacts to the deactivation sensor. This that, if through disadvantageous sensor placement or choice of parameters, the conditions for both request and deactivation are met, the deactivation holds higher priority.
The hydraulic diagrams displayed in this booklet are practical sketches. They serve to ease the choice of the correct program, but don‘t replace or even describe the planning of your system‘s construction. As such, we can‘t guarantee your system‘s functionality if you imitate this booklet‘s hydraulic diagrams with your construction.
Page 12
12
Differential control – Programs
Program 0 – Simple solar system (factory settings)
S3 only used in programs +1
Program 0: Pump A1 runs if:
S1 is greater than threshold min1 w and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded threshold max1.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
All Programs +1: In addition, if S3 exceeds the threshold max2, pump A1 is deactivated. All Programs +4: Simple drain-back solar system with valve
This program may only be selected if the drain-back function (Expert level/Drain-back) is ac-
tivated. The basic settings are the same as with program 0:
A valve on output 3 prevents the heat transfer medium from flowing out of the solar panel during the day.
Once the filling time has elapsed, the valve connected to A3 is switched on. If the pump A1 is switched off due to the temperature difference, the valve A3 will remain
switched on for another 2 hours.
If the excess temp. limiter or frost protection are activated, the sun radiation value goes be-
low 50W/m2 (only if a radiation sensor is used) or if the low water level protection detects a low volume flow after the filling time, the valve is closed immediately.
All Programs +1:
In addition, if S3 exceeds the threshold max2, pump A1 is deactivated.
necessary settings:
max1 max2 min1 diff1
... limit CYL S2 ... see all programs +1 ... activation temp. coll. S1 ... coll. S1 - CYL S2
àA1
àA1 àA1
necessary settings:
max1 max2 min1 diff1
... limit CYL S2 ... see programs 1 or 5 ... see program 0 ... coll S1 - CYL S2
Page 13
13
Program 16 – Cylinder charge from a boiler
S3 only for program +1
Program 16: The pump A1 runs, if:
S1 is greater than threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded threshold max1.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
All Programs +1: Additionally, if S3 exceeds the threshold max2, pump A1 is deactivated.
Program 32 – Burner request via cylinder sensors
Program 32:
Output A3 switches on, if S2 falls below the threshold min3. Output A3 switches off (dominantly), if S1 exceeds the threshold max3.
A3 (on) = S2 < min3 A3 (off) = S1 > max3
All Programs +1:
The burner request (A3) is made only via S2.
Output A3 switches on, if S2 falls below the threshold min3. Output A3 switches off (dominantly), if S2 exceeds the threshold max3.
A3 (on) = S2 < min3 A3 (off) = S2 > max3
necessary settings:
max1 max2 min1 diff1
... limit CYL S2 ... see all programs +1 ... activation temp. boiler S1 ... boiler S1 - CYL S2
àA1
àA1 àA1
necessary settings
min3 max3
... burner req. off CYL S1 ... burner req. on CYL S2
àA3 àA3
Page 14
14
Program 48 – Solar power system with 2 consumers
Program 48: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max2.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2
All programs +1:
Instead of two pumps, one pump and a three-way valve are used. Without priority allocation, cylinder 2 is filled by default.
All programs +2: Additionally, if S4 exceeds the threshold max3, pump A1 is switched off.
All programs +4:
Both solar circuits have separate activation thresholds measured via S1. Output A1 retains min1, and A2 activates via min2.
The Priority ranking between CYL1 and CYL2 can be set in the menu Settings/Technician level/Parameters/Priority ranking. Additionally, a solar priority function can be set up in the menu Settings/Expert level/Solar priority (see „Solar Priority“ for more details).
necessary settings: max1
max2 max3 min1 min2 diff1 diff2
... limit CYL1 S2 ... limit CYL2 S3 ... see all programs +2 ... activation temp. coll. S1 ... see all programs +4 ... coll. S1 - CYL1 S2 ... coll. S1 - CYL2 S3
à
A1
à
A2
à
A1, A2
à
A1
à
A2
Excess temperature limiter:
... activate for S1 and A1+A2
A1 ... common pump A2 ...
Valve (A2/NO receives voltage when filling CYL2)
Page 15
15
Program 64 – Solar power system with 2 solar panels
Program 64: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
Pump A2 runs, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1 A2 = S2 > (S3 + diff1) & S2 > min2 & S3 < max1
All programs +1:
If the difference between the solar panel sensors S1 and S2 exceeds the difference diff3, the circuit with the colder solar panel is deactivated. This should, in most cases, prevent heat from being lost on the colder solar panel as a result of temperatures mixing.
All programs +2: Additionally, if S4 exceeds the threshold max2, pumps A1 and A2 are deactivated.
All programs +4:
Instead of two pumps, one pump A1 and a three-way valve A2 are used. If both solar circuits are activated, circuit 2 is prioritized.
WARNING: This program is not intended for systems with two solar panels fields, since the usage of a three-way valve always leaves one solar panel field idle. Note: The additional application of the priority circuit „All programs +1“ is recommended.
necessary settings:
max1 max2 min1 min2 diff1
diff3
... limit CYL S3 ... see all programs +2 ... activation temp. coll. 1 S1 ... activation temp. coll. 2 S2 ... coll.1 S1 - CYL S3 ... coll.2 S2 - CYL S3 ... see all programs +1
àA1, A2
àA1 àA2 àA1 àA2
Excess temperature limiter 2: ...activate for S2 and A2
A1 ... common pump A2 ... valve
Page 16
16
Program 80 – Simple solar system and cylinder charge from a boiler
Program 80: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Charging pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2
All programs +1:
Pump A1 runs, if:
S1 exceeds threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
necessary settings:
max1 max2 max3 min1 min2 diff1 diff2
... limit CYL S2 ... limit CYL S4 ... see all programs +4 ... activation temp. coll. S1 ... activation temp. boiler S3 ... coll. S1 - CYL S2 ... boiler. S3 - CYL S4
à
A1
à
A2
à
A1
à
A2
à
A1
à
A2
necessary settings
max1 max2 max3 min1 min2 diff1 diff2
... limit CYL S2 ... limit CYL S2 ... see all programs +4 ... activation temp. coll. S1 ... activation temp. boiler S3 ... coll. S1 - CYL S2 ... boiler S3 - CYL S2
à
A1
à
A2
à
A1
à
A2
à
A1
à
A2
Page 17
17
The charging pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S2 by the difference diff2
• and S2 has not exceeded the threshold max2.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2
All programs +2:
If sensor S2 has reached the threshold max1 (or if S4 has reached the threshold max3 in con- junction with All Programs +4), pump A2 is activated and pump A1 keeps running. This pro-
vides a cooling function with the boiler without causing idle temperatures in the solar panel.
All programs +4: Additionally, if S4 exceeds the threshold max3, pump A1 is switched off.
All programs +8: If the re-cooling function (all programs +2) is activated, A3 runs concurrently.
Program 96 – Buffer and hot water cylinder charging via solid fuel boiler
Program 96: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2 S4
• and S4 has not exceeded max2.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2
necessary settings
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S4 ... see all programs +2 ... activation temp. boiler S1 ... activation temp. CYL1 S3 ... see all programs +2 ... boiler S1 - CYL1 S2 ... CYL1 S3 - CYL2 S4 ... see all programs +1, +2
àA1 àA2
àA1 àA2
àA1 àA2
Page 18
18
All programs +1:
Additionally, the charging pump A2 is also regulated via the heater boiler temperature S1. Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff3
• and S4 has not exceeded max2
• or S3 is greater than threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded max2.
A2 = (S1 > (S4 + diff3) & S1 > min1 & S4 < max2)
or
(S3 > (S4 + diff2) & S3 > min2 & S4 < max2)
All programs +2: Pump A3 runs, if:
S5 exceeds the threshold min3 • and S5 is greater than S6 by the difference diff3
• and S6 has not exceeded the threshold max3.
A3 = S5 > (S6 + diff3) & S5 > min3 & S6 < max3
Program 112 – 2 independent differential circuits
Example: solar system with return rise
Program 112: Pump A1runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The output A2 is activated, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2
necessary settings:
max1 max2 min1 min2 diff1 diff2
... limit CYL S2 ... limit return flow S4 ... activation temp. coll. S1 ... activation temp. CYL top S3 ... coll. S1 - CYL S2 ... CYL S3 - return flow S4
à A1 à A2 à A1 à A2 à A1 à A2
Page 19
19
Program 128 – Burner request and solar system (or charging pump)
Program 128: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Output A3 is activated, if S4 falls below the threshold min3. Output A3 is deactivated (dominantly), if S3 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A3 (on) = S4 <min3 A3 (off) = S3 > max3
All programs +1: The burner request (A3) is regulated only via S4. Output A3 switches on, if S4 falls below the threshold min3. Output A3 switches off (dominantly), if S4 exceeds the threshold max3.
A3 (on) = S4 < min3 A3 (off) = S4 > max3
All programs +2:
Additionally, pump A1 switches between sensors S4 and S2, if the difference diff2 is reached (for applications such as a boiler-buffer-cylinder system).
Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1,
or
S4 has exceeded the threshold min2 • and S4 is greater than S2 by the difference diff2
• and S2 has not exceeded the threshold max1.
A1 = (S1 > (S2 + diff1) & S1 > min1 & S2 < max1)
or
(S4 > (S2 + diff2) & S4 > min2 & S2 < max1)
necessary settings:
max1 max3 min1 min2 min3 diff1 diff2
... limit CYL S2 ... burner req. off CYL S3 ... activation temp. coll. S1 ... see all programs +2 ... burner req. on CYL S4 ... coll. S1 - CYL S2 ... see all programs +2
à A1 à A3 à A1
à A3 à A1
Page 20
20
Program 144 – Solar system with layered cylinder charging
Layered systems are only practical if the speed control is activated (Absolute value control system: Mode „Normal“ and sensor input S1)
Program 144: The solar pumps A1 run, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The three-way valve A2 switches upwards if:
S3 exceeds the threshold min2or, if S3 falls below min2, S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S3 > min2 or S3 > (S4 + diff2)) & S4 < max2
Program 145:
If S4 has reached the threshold max2, the rapid warm-up phase is completed and the speed control is blocked, which achieves optimal efficiency.
If Control Output A4 is activated, the analogue level for maximum speed will be output. Con-
trol Output A5 is not affected and continues regulating.
necessary settings
max1 max2 min1 min2 diff1 diff2
... limit CYL S2 ... limit CYL S4 ... activation temp. coll. S1 ... activation temp. HE S3 ... coll. S1 - CYL S2 ... HE S3 - CYL S4
à A1 à A2 à A1 à A2 à A1 à A2
Page 21
21
Program 160 – Insertion of two boilers into a heating system
Program 160: The charging pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded max1.
The charging pump A2 runs, if:
S5 exceeds the threshold min2 • and S5 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
Output A3 is activated, if S4 falls below the threshold min3. Output A3 is deactivated (dominantly), if S3 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S5 > (S3 + diff2) & S5 > min2 & S3 < max2 A3 (on) = S4 < min3 A3 (off) = S3 > max3
All programs +1: The burner request (A3) is regulated using only S4.
A3 (on) = S4 < min3 A3 (off) = S4 >max3 (dominant)
All programs +2: A3 activation is only permitted, if A1 is deactivated. All programs +4 (only practical in conjunction with „all programs +1“): Pump A2 runs, if:
S5 exceeds the threshold min2 • and S5 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
A2 = S5 > (S4 + diff2) & S5 > min2 & S4 < max2
All programs +8 (additional sensor S6): If S6 exceeds the threshold max1 (no longer on S2), A3 (burner request) is deactivated. The sensor S6 is to be fitted to the flue tube or can be
replaced with flue-gas thermostat.
necessary settings
max1 max2 max3 min1 min2 min3 diff1 diff2
... limit CYL S2 ... limit CYL S3 ... burner req. off CYL S3 ... activation temp. boiler S1 ... activation temp. boiler S5 ... burner req. on CYL S4 ... boiler S1 - CYL S2 ... boiler S5 - CYL S3
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2
Page 22
22
Program 176 – Solar system with 2 consumers and charging pump functionality
Program 176: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S5 exceeds the threshold min2 • and S5 is greater than S4 by the difference diff3
• and S4 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2 A3 = S5 > (S4 + diff3) & S5 > min2 & S4 < max3
All programs +1: Instead of the two pumps A1 and A2, one pump A1 and a three-way valve A2 are used.
Without priority allocation, cylinder 2 is filled by default.
All programs +2: If both cylinders have reached their maximum temperatures due to the so-
lar system, pump A3 is activated (re-cooling function). All programs +4: Both solar circuits have separate activation thresholds at S1:
Output A1 retains min1, and A2 is regulated via min3.
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S3 ... limit CYL1 S4 ... activation temp. coll. S1 ... activation temp. CYL2 S5 ... see all programs +4 ... coll. S1 - CYL1 S2 ... coll. S1 - CYL2 S3 ... SP2 S5 - CYL1 S4
à A1 à A2 à A3 à A1, A2 à A3
à A1 à A2 à A3
Excess temperature limiter: ... activate for S1 and A1+A2
A1 ... mutual pump A2 ... valve (A2/NO receives voltage when filling CYL2)
Page 23
23
All programs +8: The limitation of cylinder CYL1 is regulated via the independent sensor S6 and the threshold max1 (no maximum threshold S2!).
The Priority Ranking between CYL1 and CYL2 is parameterized in the menu Settings/Tech- nician level/Parameters/Priority ranking. Additionally, a solar priority function can be set up in the menu Settings/Expert level/Solar priority (more information in the chapter „Solar Pri-
ority“).
Program 192 – Solar system with 2 consumers and charging pump (heating boiler)
Program 192: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S4 exceeds the threshold min2 • and S4 is greater than S3 by the difference diff3
• and S3 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2 A3 = S4 > (S3 + diff3) & S4 > min2 & S3 < max3
All programs +1: Instead of the two pumps A1 and A2, on pump A1 and a three-way valve A2 are used. Without priority allocation, cylinder 2 is charged by default.
necessary settings
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S3 ... limit CYL2 S3 ... activation temp. coll. S1 ... activation temp. boiler S4 ... see all programs +4 ... coll. S1 – CYL1 S2 ... coll. S1 – CYL2 S3 ... boiler S4 – CYL2 S3
à A1 à A2 à A3 à A1, A2 à A3
à A1 à A2 à A3
Excess temperature limiter:
... activate for S1 and A1+A2
A1... mutual pump A2 ... Valve (A2/NO receives voltage when charging CYL2)
Page 24
24
All programs +2: If both cylinders have reached their maximum temperatures due to the so-
lar system, pump A3 is activated (re-cooling function). All programs +4: Both solar circuits have separate activation thresholds at S1:
Output A1 retains min1 and A2 regulates via min3. The Priority Ranking between CYL1 and CYL2 can be parameterized in the menu Settings/
Technician level/Parameters/Priority ranking. Additionally, a solar priority function can be
set up in the menu Settings/Expert level/Solar priority (further details in chapter „Solar Pri-
ority“).
Program 208 – Solar system with 2 consumers and burner request
Program 208: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
Output A3 is activated, if S5 falls below the threshold min3. Output A3 is deactivated (dominant), if S4 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2 A3 (on) = S5 < min3 A3 (off) = S4 > max3
All programs +1: Instead of the two pumps A1 and A2, one pump A1 and a three-way valve A2 are used. Without priority allocation cylinder 2 is filled by default..
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2
... limit CYL1 S2 ... limit CYL2 S3 ... burner req. off CYL2 S4 ... activation temp. coll. S1 ... see all programs +4 ... burner req. on CYL2 S5 ... coll. S1 - CYL1 S2 ... coll. S1 - CYL2 S3
à A1 à A2 à A3 à A1, A2
à A3 à A1 à A2
Excess temperature limiter: ... activate for S1 and A1+A2
A1... mutual pump A2... Valve (A2/NO receives voltage when charging CYL2)
Page 25
25
All programs +2: The burner request (A3) is only regulated via sensor S5.
A3 (on) = S5 < min3 A3 (off) = S5 > max3 (dominant)
All programs +4: Both solar circuits have separate activation thresholds at S1: Output A1 retains min1 and A2 is regulated via min2.
All programs +8: If at least one of the two solar circuits is active, the burner request is blocked. If both solar circuits are inactive, the burner request is unblocked after a 5 minute delay.
The Priority Ranking between CYL1 and CYL2 can be parameterized in the menu Settings/ Technician level/Parameters/Priority ranking. Additionally, a solar priority function can be
set up in the menu Settings/Expert level/Solar priority (further details in chapter „Solar Pri-
ority“).
Program 224 – Solar system with 3 consumers
necessary setting
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S3 ... limit CYL3 S4 ... activation temp. coll. S1 ... see all programs +8 ... see all programs +8 ... coll. S1 - CYL1 S2 ... coll. S1 - CYL2 S3 ... coll. S1 - CYL3 S4
à A1 à A2 à A3 à A1, A2, A3
à A1 à A2 à A3
Excess temperature limiter: ... activate for S1 and A1+A2+A3
Page 26
26
Program 224: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
Pump A3 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff3
• and S4 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2 A3 = S1 > (S4 + diff3) & S1 > min1 & S4 < max3
Program 225: Instead of the two pumps A1 and A2, one pump A1 and a three-way valve A2 are used (pump-valve-system between CYL1 and CYL2).
Program 226: Instead of the two pumps A1 and A3, one pump A1 and a three-way valve A3 are used (pump-valve-system between CYL1 and CYL3).
Program 227: All three cylinders are charged via one pump (A1) and two serially connected three-way valves (A2, A3). If both valves are without voltage, CYL1 is being charged.
If priority allocation is active, as set up in the menu Settings/Technician level/Parameters/ Priority ranking, both valves A2 and A3 are never active simultaneously: When charging CYL2, only pump A1 and valve A2 are active; when charging CYL3, only pump A1 and valve
A3 are active.
All programs +4: If all cylinders have reached their maximum temperatures, charging of
CYL2 continues regardless of max2.
All programs +8: All solar circuits have separate activation thresholds at S1: Output A1 retains min1, but A2 switches at min2 and A3 at min3.
The Priority Ranking between CYL1, CYL2 and CYL3 can be parameterized in the menu Set- tings/Technician level/Parameters/Priority ranking. Additionally, a solar priority function can be set up in the menu Settings/Expert level/Solar priority (further details in chapter „So-
lar Priority“).
A1... mutual pump A2... Valve (A2/NO receives voltage when charging CYL2)
A1... mutual pump A3... Valve (A3/NO receives voltage when charging CYL3)
A1 ... mutual pump A2 ... valve (A2/NO receives voltage when charging cylinder CYL2) A3 ... valve (A3/NO receives voltage when charging cylinder CYL3)
Page 27
27
Program 240 – Solar system with 2 solar panels and 2 consumers
Program 240: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1
or, together with valve A3
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
Pump A2 runs, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1
or, together with valve A3
S2 exceeds the threshold min2 • and S2 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
The valve A3 switches dependent on the chosen (solar) priority. Without priority allocations, CYL2 will be charged by default.
A1, A2 ... pumps A3
... switch-over valve (A3/S receives voltage when charging CYL2)
necessary settings:
max1 max2 min1 min2 diff1
diff2
diff3
... limit CYL1 S3 ... limit CYL2 S4 ... activation temp. coll.1 S1 ... activation temp. coll. 2 S2 ... coll. 1 S1 - CYL1 S3 ... coll. 2 S2 - CYL1 S3 ... coll. 1 S1 - CYL2 S4 ... coll. 2 S2 - CYL2 S4 ... see all programs +1
à A1, A2 à A1, A2, A3 à A1 à A2 à A1 à A2 à A1, A3 à A2, A3
Excess temperature limiter 2: ... activate for S2 and A2
A1 = S1 > (S3 + diff) & S1 > min1 & S3 < max1 & (A3 = off)
or S1 > (S4 + diff2) & S1 > min1 & S4 < max2 & (A3 = on)
A2 = S2 > (S3 + diff1) & S2 > min2 & S3 < max1 & (A3 = off)
or S2 > (S4 + diff2) & S2 > min2 & S4 < max2 & (A3 = on)
A3 = dependent on chosen priority
Page 28
28
All programs +1: If the difference between the solar panel sensors S1 and S2 exceeds the difference diff3, the colder panel‘s circuit will be deactivated. This prevents heat from being lost on the colder panel when temperatures are mixed.
WARNING: In this program, the priority settings do not refer to the pumps, but rather their respective cylinders. The Priority Ranking between CYL1 and CYL2 can be parameterized in
the menu Settings/Technician level/Parameters/Priority ranking. Additionally, a solar prior-
ity function can be set up in the menu Settings/Expert level/Solar priority (further details in chapter „Solar Priority“).
Program 256 – Solar power system with two solar panels (1 pump, 2 stop valves)
Program 256: Pump A1 runs, if:
• Valve A2 is activated • or valve A3 is activated.
Valve A2 is activated, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
Valve A3 is activated, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max1.
A1 = (A2 = on) or (A3 = off) A2 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1 A3 = S2 > (S3 + diff2) & S2 > min2 & S3 < max1
All programs +1: If the difference between the solar panel sensors S1 and S2 exceeds the difference diff3, the colder panel‘s circuit is deactivated. This prevents heat from being lost on the colder panel when temperatures are mixed.
All programs +2: Additionally, if S4 exceeds the threshold max2, the outputs A1, A2 and A3 are deactivated.
necessary settings:
max1 max2 min1 min2 diff1 diff2 diff3
... limit CYL S3 ... see all programs +2 ... activation temp. coll. 1 S1 ... activation temp. coll. 2 S2 ... coll.1 S1 - CYL S3 ... coll.2 S2 - CYL S3 ... see all programs +1
à A1, A2, A3
à A1, A2 à A1, A3 à A1, A2 à A1, A3
Excess temperature limiter 2: ... activate for S2 and A1
Page 29
29
Program 272 – Solar system with 2 collector panels and charging pump function
Program 272: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
Pump A2 runs, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
The charging pump A3 runs, if:
S5 exceeds the threshold min3 • and S5 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1 A2 = S2 > (S3 + diff1) & S2 > min2 & S3 < max1 A3 = S5 > (S4 + diff2) & S5 > min3 & S4 < max2
All programs +1: If the difference between the solar panel sensors S1 and S2 exceeds the difference diff3 the colder panel‘s circuit is deactivated. This prevents heat from being lost on the colder panel when temperatures are mixed.
All programs +2: Instead of the two pumps A1 and A2, one pump A1 and a three-way valve A2 are used. Without priority allocation, collector 2 will be preferred.
WARNING: This program is not intended for systems with two solar panels fields, since the
usage of a three-way valve always leaves one solar panel field idle. Note: The additional application of the priority circuit „All programs +1“ is recommended.
necessary settings:
max1 max2 min1 min2 min3 diff1
diff2 diff3
... limit CYL1 S3 ... limit CYL2 S4 ... activation temp. coll. 1 S1 ... activation temp. coll. 2 S2 ... activation temp. CYL1 S5 ... coll.1 S1 - CYL1 S3 ... coll.2 S2 - CYL1 S3 ... CYL1 S5 - CYL2 S4 ... see all programs +1
à A1, A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Excess temperature limiter 2: ... activate for S2 and A2
Page 30
30
Program 288 – Solar system with 2 collector panels and burner request
Program 288: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
Pump A2 runs, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
Output A3 is activated, if S5 falls below threshold min3. Output A3 is deactivated (dominant), if S4 exceeds the threshold max3.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1 A2 = S2 > (S3 + diff1) & S2 > min2 & S3 < max1 A3 (on) = S5 < min3 A3 (off) = S4 > max3
All programs +1: If the difference between the two solar panel sensors S1 and S2 exceeds the difference diff3, the colder panel‘s circuit is deactivated. This prevents heat from being lost on the colder panel when temperatures are mixed.
All programs +2: The burner request (A3) is regulated only via S5.
A3 (on) = S5 < min3 A3 (off) = S5 > max3 (dominant)
All programs +4: Instead of the pumps A1 and A2, one pump A1 and a three-way valve A2 are used. Without priority allocation, solar panel 2 will be preferred.
WARNING: This program is not intended for systems with two solar panels fields, since the usage of a three-way valve always leaves one solar panel field idle.
Note: The additional application of the priority circuit „All programs +1“ is recommended.
necessary settings:
max1 max3 min1 min2 min3 diff1
diff3
... limit CYL S3 ... burner req. off CYL S4 ... activation temp. coll.1 S1 ... activation temp. coll.2 S2 ... burner req. on CYL S5 ... coll. 1 S1 - CYL S3 ... coll. 2 S2 - CYL S3 ... see all programs +1
à A1, A2 à A3 à A1 à A2 à A3 à A1 à A2
Excess temperature limiter 2: ... activate for S2 and A2
Page 31
31
Program 304 – Solar system with 2 collector panels + charging pump (boiler)
Program 304: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
Pump A2 runs, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
The charging pump A3 runs, if:
S4 exceeds the threshold min3 • and S4 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1 A2 = S2 > (S3 + diff1) & S2 > min2 & S3 < max1 A3 = S4 > (S3 + diff2) & S4 > min3 & S3 < max2
All programs +1: If the difference between the two solar panel sensors S1 and S2 exceeds the difference diff3, the colder panel‘s circuit is deactivated. This prevents heat from being lost on the colder panel when temperatures are mixed.
All programs +2: Instead of the pumps A1 and A2, one pump A1 and a three-way valve A2 are used. Without priority allocation, solar panel 2 will be preferred.
WARNING: This program is not intended for systems with two solar panels fields, since the usage of a three-way valve always leaves one solar panel field idle.
Note: The additional application of the priority circuit „All programs +1“ is recommended.
necessary settings:
max1 max2 min1 min2 min3 diff1
diff2 diff3
... limit CYL S3 ... limit CYL S3 ... activation temp. coll.1 S1 ... activation temp. coll.2 S2 ... activation temp. boiler S4 ... coll.1 S1 - CYL S3 ... coll.2 S2 - CYL S3 ... boiler S4 - CYL S3 ... see all programs +1
à A1, A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Excess temperature limiter 2: ... activate for S2 and A2
Page 32
32
Program 320 – Layered cylinder and charging pump
Only practical with speed control activated! (Absolute value control: mode „Normal“ and sensor input S1)
Program 320: Solar pumps A1 run, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The three-way valve A2 switches upwards, if:
S5 exceeds the threshold min2, • or, if S5 falls below min2, S5 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S6 exceeds the threshold min3 • and S6 is greater than S2 by the difference diff3
• and S2 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2
A3 = S6 > (S2 + diff3) & S6 > min3 & S2 < max3
All programs +1: If S4 has reached the threshold max2, the rapid warm-up phase is complet-
ed and the speed control is blocked, which achieves optimal efficiency.
If control Output A4 is activated, the analogue level for maximum speed will be output. Con-
trol Output A5 is not affected and continues regulating. All programs +8 (independent charging pump A3): charging pump A3 runs, if:
S6 exceeds the threshold min3 • and S6 is greater than S3 by the difference diff3
• and S3 has not exceeded the threshold max3.
A3 = S6 > (S3 + diff3) & S6 > min3 & S3 < max3
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL S2 ... limit CYL S4 ... limit CYL S2 ... activation temp. coll. S1 ... activation temp. HE S5 ... activation temp. boiler S6 ... coll. S1 - CYL S2 ... HE S5 - CYL S4 ... boiler S6 - CYL S2
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Page 33
33
Program 336 – Solar system with 2 consumers and layered cylinder charging
Layered system only practical with speed control activated! (Absolute value control: mode „Normal“ and sensor input S1)
Program 336: The solar pumps A1 run, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The solar pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
The three-way valve A3 switches upwards, if:
S5 exceeds the threshold min3 or, if S5 falls below the threshold min3, S5 is greater than S4 by the difference
• and S4 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2
A3 = (S5 > min3 or S5 > (S4 + diff3)) & S4 < max3
All programs +2: If S4 has reached the threshold max3, the rapid warm-up phase is complet-
ed and the speed control is blocked, which achieves optimal efficiency.
If control Output A4 is activated, the analogue level for maximum speed will be output. Con-
trol Output A5 is not affected and continues regulating.
All programs +4: Both solar circuits receive separate activation thresholds S1: Output A1 re-
tains min1 and A2 is regulated via min2. The Priority Ranking between CYL1 and CYL2 can be parameterized in the menu Settings/
Technician level/Parameters/Priority ranking. Additionally, a solar priority function can be
set up in the menu Settings/Expert level/Solar priority (further details in chapter „Solar Pri-
ority“).
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S3 ... limit CYL1 S4 ... activation temp. coll S1 ... see all programs +4 ... activation temp. HE S5 ... coll. S1 - CYL1 S2 ... coll. S1 - CYL2 S3 ... HE S5 - CYL1 S4
à A1 à A2 à A3 à A1, A2
à A3 à A1 à A2 à A3
Excess temperature limiter: ... activate for S1 and A1+A2
Page 34
34
Program 352 – Layered cylinder and burner request
Layered system only practical with speed control activated! (Absolute value control: mode „Normal“ and sensor input S1)
Program 352: Pumps A1 run, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The three-way valve A2 switches upwards, if:
S5 exceeds the threshold min2or, if S5 falls below min2, S5 is greater than S4 by the difference diff2.
• and S4 has not exceeded the threshold max2.
Output A3 is activated, if S4 falls below min3. Output A3 is deactivated (dominantly), if S3 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2
A3 (on) = S4 < min3 A3 (off) = S3 > max3
All programs +1: All programs +1: If S4 has reached the threshold max2, the rapid warm-up phase is completed and the speed control is blocked, which achieves optimal efficiency.
If control Output A4 is activated, the analogue level for maximum speed will be output. Con-
trol Output A5 is not affected and continues regulating. All programs +4: The burner request (A3) is only regulated via S4.
A3 (on) = S4 < min3 A3 (off) = S4 > max3 (dominant)
All programs +8: If the solar circuit is active, the burner request is blocked. If the solar circuit is inactive, the burner request is unblocked after a 5 minute delay..
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2
... limit CYL S2 ... limit CYL S4 ... burner req. off CYL S3 ... activation temp. coll. S1 ... activation temp. HE S5 ... burner req. on CYL S4 ... coll. S1 - CYL S2 ... HE S5 - CYL S4
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2
Page 35
35
Program 368 – Layered cylinder and charging pump
Layered system only practical with speed control activated! (Absolute value control: mode „Normal“ and sensor input S1)
Program 368: Pumps A1 run, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The three-way valve A2 switches upwards, if:
S5 exceeds the threshold min2or, if S5 falls below min2, S5 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S4 exceeds the threshold min3 • and S4 is greater than S3 by the difference diff3
• and S3 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2
A3 = S4 > (S3 + diff3) & S4 > min3 & S3 < max3
+ All programs +1: If S4 has reached the threshold max2, the rapid warm-up phase is com-
pleted and the speed control is blocked, which achieves optimal efficiency.
If control Output A4 is activated, the analogue level for maximum speed will be output. Con-
trol Output A5 is not affected and continues regulating.
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL1 S4 ... limit CYL2 S3 ... activation temp. coll. S1 ... activation temp. HE S5 ... activation temp. CYL1 S4 ... coll. S1 - CYL1 S2 ... HE S5 - CYL1 S4 ... CYL1 S4 - CYL2 S3
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Page 36
36
Program 384 – Layered cylinder with bypass functionality
Layered system only practical with speed control activated! (Absolute value control: mode „Normal“ and sensor input S1)
Program 384: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The three-way valve A2 switches upwards, if:
S5 exceeds the threshold min2 or, if S5 falls below the threshold min2, S5 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
Pump A3 runs, if:
S3 is greater than S2 by the difference diff3 and pump A1 is running.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2
A3 = S3 > (S2 + diff3) & (A1 = on)
All programs +1: If S4 has reached the threshold max2, the rapid warm-up phase is complet-
ed and the speed control is blocked, which achieves optimal efficiency.
If control Output A4 is activated, the analogue level for maximum speed will be output. Con-
trol Output A5 is not affected and continues regulating.
To prevent frost damages to the heat exchanger, a frost protection function should be acti-
vated for sensor S3 and output A3.
necessary settings:
max1 max2 min1 min2 diff1 diff2 diff3
... limit CYL S2 ... limit CYL S4 ... activation. coll. S1 ... activation. HE1 S5 ... coll. S1 - CYL S2 ... HE S5 - CYL S4 ... solar flow S3 - CYL S2
à A1 à A2 à A1 à A2 à A1 à A2 à A3
Page 37
37
Program 400 – Solar system with 1 consumer and 2 charging pump functions
Program 400: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S5 by the difference diff3
• and S5 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2 A3 = S3 > (S5 + diff3) & S3 > min2 & S5 < max3
All programs +1: Instead of the two pumps A2 and A3, one pump A2 and a three-way valve A3 are used. Without priority allocation, cylinder 3 is charged by default.
All programs +2: Separate activation thresholds for the charging pump circuits.
Output A2 retains min2 and A3 is regulated via min3. The Priority Ranking between CYL1 and CYL2 can be set in the menu Settings/Technician
level/Parameters/Priority ranking.
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S4 ... limit CYL3 S5 ... activation temp. coll. S1 ... activation temp. CYL1 S3 ... see all programs +2 ... coll. S1 - CYL1 S2 ... CYL1 S3 - CYL2 S4 ... CYL1 S3 - CYL3 S5
à A1 à A2 à A3 à A1 à A2, A3
à A1 à A2 à A3
A2 ... mutual pump A3 ... valve (A3/NO receives voltage when charging cylinder CYL3
Page 38
38
Program 416 – 1 consumer, 2 charging pumps and burner request Priority allocation between SP1 and SP2 possible
Program 416: The charging pump A1 runs, if:
• S4 exceeds the threshold min1 • and S4 is greater than S1 by the difference diff1
and S1 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S4 exceeds the threshold min1 • and S4 is greater than S2 by the difference diff2
• and S2 has not exceeded the threshold max2.
Output A3 is activated, if S4 falls below the threshold min3. Output A3 is deactivated (dominantly), if S3 exceeds the threshold max3.
A1 = S4 > (S1 + diff1) & S4 > min1 & S1 < max1
A2 = S4 > (S2 + diff2) & S4 > min1 & S2 < max2
A3 (on) = S4 < min A3 (off) = S3 > max3
All programs +1: Instead of the two pumps A1 and A2, one pump A1 and a three-way valve A2 are used. Without priority allocation, cylinder 2 is charged by default.
All programs +2: Additionally, charging pump A1 is activated, if the temperature of cylinder S1 (CYL1) falls below the boiler flow temperature S5 by the difference diff3.
Additionally, charging pump A2 is activated, if the temperature of cylinder S2 (CYL2) falls be-
low the boiler flow temperature S5 by the difference diff3.
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S1 ... limit CYL2 S2 ... burner req. off CYL3 S3 ... activation temp. CYL3 S4 ... see all programs +2 and +8 ... burner req. on CYL3 S4 ... CYL3 S4 - CYL1 S1 ... CYL3 S4 - CYL2 S2 ... see all programs +2
à A1 à A2 à A3 à A1, A2
à A3 à A1 à A2
A1... mutual pump A2... valve (A2/NO receives voltage when charging cylinder CYL2
Page 39
39
Pump A1 runs, if:
S4 exceeds the threshold min1 • and S4 is greater than S1 by the difference diff1
• and S1 has not exceeded the threshold max1.
or
S5 exceeds the threshold min2 • and S5 is greater than S1 by the difference diff3
• and S1 has not exceeded the threshold max1.
Pump A2 runs, if:
S4 exceeds the threshold min1 • and S4 is greater than S2 by the difference diff2
• and S2 has not exceeded the threshold max2.
or
S5 exceeds the threshold min2 • and S5 is greater than S2 by the difference diff3
• and S2 has not exceeded the threshold max2.
All programs +4: The burner request (A3) is only regulated via S4.
A3 (on) = S4 < min3 A3 (off) = S4 > max3 (dominantly)
All programs +8: (Not usable in conjunction with +2) Both charging pump circuits have separate activation thresholds at S4: Output A1 retains min1 and A2 is regulated via min2. The Priority Ranking between CYL1 and CYL2 can be set in the menu Settings/Technician
level/Parameters/Priority ranking. Program 432 – Solar system, burner request, and one charging pump
A1 = (S4 > (S1 + diff1) & S4 > min1 & S1 < max1)
or (S5 > (S1 + diff3) & S5 > min2 & S1 < max1)
A2 = (S4 > (S2 + diff2) & S4 > min1 & S2 < max2)
or (S5 > (S2 + diff3) & S5 > min2 & S2 < max2)
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2
... limit CYL S2 ... limit CYL S4 ... burner req. off S S4 ... activation temp. coll. S1 ... activation temp. boiler S3 ... burner req. on CYL S5 ... coll. S1 - CYL S2 ... boiler S3 - CYL S4
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2
Page 40
40
Program 432: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
Output A3 is activated, if S5 falls below the threshold min3. Output A3 is deactivated (dominantly), if S4 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2 A3 (on) = S5 < min3 A3 (off) = S4 > max3
All programs +1
Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S2 by the difference diff2
• and S2 has not exceeded the threshold max2.
Output A3 is activated, if S5 falls below the threshold min3. Output A3 is deactivated (dominantly), if S4 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2 A3 (on) = S5 < min3 A3 (off) = S4 > max3
All programs +2: The burner request (A3) is only regulated via S5.
A3 (on) = S5 < min3 A3 (off) = S5 > max3 (dominant)
All programs +4: If the sensor S2 has reached the threshold max1, pump A2 is activated and pump A1 continues operation. This achieves a „cooling function“ with the boiler/heating without idle temperatures at the solar panel.
All programs +8: Activity of the solar circuit blocks the burner request. If the solar circuit is deactivated, the burner request is unblocked after a 5 minute delay.
required settings:
max1 max2 max3 min1 min2 min3 diff1 diff2
... limit CYL S2 ... limit CYL S2 ... burner req. off CYL S4 ... activation temp. coll. S1 ... activation temp. boiler S3 ... burner req. on CYL S5 ... coll. S1 - CYL S2 ... boiler S3 - CYL S2
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2
Page 41
41
Program 448 – Burner request and 2 charging pumps
Program 448: The charging pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded max1.
The charging pump A2 runs, if:
S5 exceeds the threshold min2 • and S5 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
Output A3 is activated, if S5 falls below the threshold min3. Output A3 is deactivated (dominantly), if S4 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S5 > (S3 + diff2) & S5 > min2 & S3 < max2 A3 (on) = S5 < min3 A3 (off) = S4 > max3
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S3 ... burner req. off CYL1 S4 ... activation temp. boiler S1 ... activation temp. CYL1 S5 ... burner req. on CYL1 S5 ... boiler S1 - CYL1 S2 ... CYL1 S5 - CYL2 S3 ... see all programs +2
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2
Page 42
42
All programs +1:
The charging pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff1
• and S4 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S5 exceeds the threshold min2 • and S5 is greater than S3 by the difference diff2
• and S3 has not exceeded the difference max2.
Output A3 is activated, if S5 falls below the threshold min3. Output A3 is deactivated (dominantly), if S4 exceeds the threshold max3.
A1 = S1 > (S4 + diff1) & S1 > min1 & S4 < max1 A2 = S5 > (S3 + diff2) & S5 > min2 & S3 < max2 A3 (on) = S5 < min3 A3 (off) = S4 > max3
All programs +2: Additionally, the charging pump A2 is activated if the cylinder temperature S3 (CYL2) falls below the boiler temperature S1 by the difference diff3.
The charging pump A2 runs, if:
S5 exceeds the threshold min2 • and S5 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
or
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff3
• and S3 has not exceeded the threshold max2.
A2 = (S5 > (S3 + diff2) & S5 > min2 & S3 < max2)
or
(S1 > (S3 + diff3) & S1 > min1 & S3 < max2)
All programs +4: The burner request (A3) is regulated only via sensor S5.
A3 (on) = S5 < min3 A3 (off) = S5 > max3 (dominant)
All programs +8: The burner request (A3) is regulated only via sensor S4.
A3 (on) = S4 < min3 A3 (off) = S4 > max3 (dominant)
Combining additions +4 and +8 is not permitted. An attempt to set this up (P460) will result in the program number resetting to +4 (P452).
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S4 ... limit CYL2 S3 ... burner req. off CYL1 S4 ... activation temp. boiler S1 ... activation temp. CYL1 S5 ... burner req. on CYL1 S5 ... boiler S1 - CYL1 S4 ... CYL1 S5 - CYL2 S3 ... see all programs +2
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2
Page 43
43
Program 464 – Solar system with 2 consumers and bypass function
Program 464: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
or S1 is greater than S3 by the difference diff1.
• and both temperature thresholds (S2 > max1 and S3 > max2) are not exceeded at once.
Pump A2 runs, if:
S4 exceeds the threshold min2 • and S4 is greater than S2 by the difference diff2
• and S2 has not exceeded the threshold max1.
Pump A3 runs, if:
S4 exceeds the threshold min2 • and S4 is greater than S3 by the difference diff3
• and S3 has not exceeded the threshold max2.
A1 = (S1 > (S2 + diff1) or S1 > (S3 + diff1)) & S1 > min1
& (S2 < max1 or S3 < max2)
A2 = S4 > (S2 + diff2) & S4 > min2 & S2 < max1 A3 = S4 > (S3 + diff3) & S4 > min2 & S3 < max2
All programs +1: Instead of both charging pumps A2 and A3, on pump A2 and a three-way valve A3 are used. Valve A3/NO receives voltage when charging CYL2.
Speed control: Both control outputs are set to full speed once max1 has been reached.
All programs +2: Separate activation thresholds at S4 for the secondary solar circuit: Output A2 retains min2 and A3 is regulated via min3.
necessary settings:
max1 max2 min1 min2 min3 diff1
diff2 diff3
... limit CYL1 S2 ... limit CYL2 S3 ... activation temp. coll. S1 ... activation temp. solar flow S4 ... see all programs +2 ... coll. S1 - CYL1 S2 ... coll. S1 - CYL2 S3 ... solar flow S4 - CYL1 S2 ... solar flow S4 - CYL2 S3
à A1, A2 à A1, A3 à A1 à A2, A3
à A1 à A1 à A2 à A3
Page 44
44
All programs +4: The two secondary pumps A2 and A3 are only permitted to run if the pri-
mary pump A1 runs in automatic mode. The Priority Ranking between CYL1 and CYL2 can be set in the menu Settings/Technician
level/Parameters/Priority ranking. Additionally, a solar priority function can be set up in the menu Settings/Expert level/Solar priority (see „Solar Priority“ for more details).
Program 480 – 2 consumers and 3 charging pump functions
Program 480: The charging pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded max1.
The charging pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S2 by the difference diff2
• and S2 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S5 exceeds the threshold min3 • and S5 is greater than S4 by the difference diff3
• and S4 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2 A3 = S5 > (S4 + diff3) & S5 > min3 & S4 < max3
necessary settings: max1
max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL1 S2 ... limit CYL2 S4 ... activation temp. heat source. S1 ... activation temp. boiler S3 ... activation temp. CYL1 S5 ... heat source S1 - CYL1 S2 ... boiler S3 - CYL1 S2 ... CYL1 S5 - CYL2 S4
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Page 45
45
All programs +1:
Charging pump A3 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff3
• and S4 has not exceeded the threshold max3
or
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff3
• and S4 has not exceeded the threshold max3
or
S5 exceeds the threshold min3 • and S5 is greater than S4 by the difference diff3
• and S4 has not exceeded the threshold max3.
A3 = (S1 > (S4 + diff3) & S1 > min1 & S4 < max3)
or
(S3 > (S4 + diff3) & S3 > min2 & S4 < max3)
or
(S5 > (S4 + diff3) & S5 > min3 & S4 < max3)
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL1 S2 ... limit CYL2 S4 ... activation temp. heat source S1 ... activation temp. boiler S3 ... activation temp. CYL1 S5 ... heat source S1 - CYL1 S2 ... boiler S3 - CYL1 S2 ... heat source S1 - CYL2 S4 ... boiler S3 - CYL2 S4 ... CYL1 S5 - CYL2 S4
à A1 à A2 à A3 à A1, A3 à A2, A3 à A3 à A1 à A2 à A3 à A3 à A3
Page 46
46
Program 496 – 1 Consumer and 3 charging pump functions
Program 496: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S2 by the difference diff2
• and S2 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S4 exceeds the threshold min3 • and S4 is greater than S2 by the difference diff3
• and S2 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S2 + diff2) & S3 > min2 & S2 < max2 A3 = S4 > (S2 + diff3) & S4 > min3 & S2 < max3
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL S2 ... limit CYL S2 ... limit CYL S2 ... activation temp. coll. S1 ... activation temp. heat source S3 ... activation temp. boiler S4 ... coll. S1 - CYL S2 ... heat source S3 - CYL S2 ... boiler S4 - CYL S2
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Page 47
47
Program 512 – 3 independent differential circuits
Program 512: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
Pump A3 runs, if:
S5 exceeds the threshold min3 • and S5 is greater than S6 by the difference diff3
• and S6 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2 A3 = S5 > (S6 + diff3) & S5 > min3 & S6 < max3
All programs +1: If sensor S2 has reached the threshold max1, pump A2 is activated and pump A1 keeps running. This provides a cooling function with the boiler without causing idle temperatures in the solar panel.
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S4 ... limit CYL3 S6 ... activation temp. coll. 1 S1 ... activation temp. coll. 2 S3 ... activation temp. coll. 3 S5 ... coll. 1 S1 - CYL1 S2 ... coll. 2 S3 - CYL2 S4 ... coll. 3 S5 - CYL3 S6
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Page 48
48
Program 528 – 2 independent differential circuits & independent burner request
Program 528: Pump A1runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
Output A3 is activated, if S6 falls below the threshold min3. Output A3 is deactivated (dominantly), if S5 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2 A3 (on) = S6 < min3 A3 (off) = S5 > max3
All programs +1: The burner request (A3) is regulated only via sensor S6 (deactivation dom-
inant).
A3 (on) = S6 < min3 A3 (off) = S6 > max3
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2
... limit CYL1 S2 ... limit CYL2 S4 ... burner req. off CYL3 S5 ... activation temp. coll.1 S1 ... activation temp. coll.2 S3 ... burner req. on CYL3 S6 ... coll. 1 S1 - CYL1 S2 ... coll. 2 S3 - CYL2 S4
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2
Page 49
49
Program 544 – Cascade: S1 -> S2 -> S3 -> S4
Program 544: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S3 exceeds the threshold min3 • and S3 is greater than S4 by the difference diff3
• and S4 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S2 > (S3 + diff2) & S2 > min2 & S3 < max2 A3 = S3 > (S4 + diff3) & S3 > min3 & S4 < max3
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S3 ... limit CYL3 S4 ... activation temp. coll. S1 ... activation temp. CYL1 S2 ... activation temp. CYL2 S3 ... coll. S1 - CYL1 S2 ... CYL1 S2 - CYL2 S3 ... CYL2 S3 - CYL3 S4
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Page 50
50
Program 560 – Cascade: S1 -> S2 / S3 -> S4 -> S5
Program 560: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S4 exceeds the threshold min3 • and S4 is greater than S5 by the difference diff3
• and S5 has not exceeded the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2 A3 = S4 > (S5 + diff3) & S4 > min3 & S5 < max3
All programs +1: Pump A3 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S5 by the difference diff3
• and S5 has not exceeded the threshold max3
or
S4 exceeds the threshold min3 • and S4 is greater than S5 by the difference diff3
• and S5 has not exceeded the threshold max3.
A3 = (S3 > (S5 + diff3) & S3 > min2 & S5 < max3)
or
(S4 > (S5 + diff3) & S4 > min3 & S5 < max3)
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2 diff3
... limit CYL1 S2 ... limit CYL2 S4 ... limit CYL3 S5 ... activation temp. coll. S1 ... activation temp. CYL1 S3 ... activation temp. CYL2 S4 ... coll. S1 - CYL1 S2 ... CYL1 S3 - CYL2 S4 ... CYL2 S4 - CYL3 S5
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2 à A3
Page 51
51
Program 576 – Cascade: S4 -> S1 -> S2 + burner request
Program 576: The charging pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
The charging pump A2 runs, if:
S4 exceeds the threshold min2 • and S4 is greater than S1 by the difference diff2
• and S1 has not exceeded the threshold max2.
Output A3 is activated, if S4 falls below the threshold min3. Output A3 is deactivated (dominantly), if S3 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S4 > (S1 + diff2) & S4 > min2 & S1 < max2 A3 (on) = S4 < min3 A3 (off) = S3 > max3
All programs +1: The burner request (A3) is regulated only via S4 (deactivation dominant).
A3 (on) = S4 < min3 A3 (off) = S4 > max3
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2
... limit CYL3 S2 ... limit CYL2 S1 ... burner req. off CYL1 S3 ... activation temp. CYL2 S1 ... activation temp. CYL1 S4 ... burner req. on CYL1 S4 ... CYL2 S1 - CYL3 S2 ... CYL1 S4 - CYL2 S1
à A1 à A2 à A3 à A1 à A2 à A3 à A1 à A2
Page 52
52
Program 592 – 2 generators for two consumers + independent differential circuit
No diagram available
Program 592: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1
or
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
or
S2 exceeds the threshold min2 • and S2 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S5 exceeds the threshold min3 • and S5 is greater than S6 by the difference diff3
• and S6 has not exceeded the threshold max3.
A1= S1 > (S3 + diff1) & S1 > min1 & S3 < max1
or
S2 > (S3 + diff1) & S2 > min2 & S3 < max1
A2 = S1 > (S4 + diff2) & S1 > min1 & S4 < max2
or
S2 > (S4 + diff2) & S2 > min2 & S4 < max2
A3 = S5 > (S6 + diff3) & S5 > min3 & S6 < max3
necessary settings:
max1 max2 max3 min1 min2 min3 diff1
diff2
diff3
... limit CYL1 S3 ... limit CYL2 S4 ... limit CYL3 S6 ... activation temp. boiler 1 S1 ... activation temp. boiler 2 S2 ... activation temp. coll. S5 ... boiler 1 S1 - CYL1 S3 ... boiler 2 S2 - CYL1 S3 ... boiler 1 S1 - CYL2 S4 ... boiler 2 S2 - CYL2 S4 ... coll. S5 - CYL3 S6
à A1 à A2 à A3 à A1, A2 à A1, A2 à A3 à A1 à A1 à A2 à A2 à A3
Page 53
53
Program 593:
Program 593: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
or
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff1
• and S4 has not exceeded the threshold max2.
Pump A2 runs, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max1.
or
S2 exceeds the threshold min2 • and S2 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
The charging pump A3 runs, if:
S5 exceeds the threshold min3 • and S5 is greater than S6 by the difference diff3
• and S6 has not exceeded the threshold max3.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1
or
S1 > (S4 + diff1) & S1 > min1 & S4 < max2
A2 = S2 > (S3 + diff2) & S2 > min2 & S3 < max1
or
S2 > (S4 + diff2) & S2 > min2 & S4 < max2
A3 = S5 > (S6 + diff3) & S5 > min3 & S6 < max3
necessary settings:
max1 max2 max3 min1 min2 min3 diff1
diff2
diff3
... limit CYL1 S3 ... limit CYL2 S4 ... limit CYL3 S6 ... activation temp. boiler 1 S1 ... activation temp. boiler 2 S2 ... activation temp. coll. S5 ... boiler 1 S1 - CYL1 S3 ... boiler 1 S1 - CYL2 S4 ... boiler 2 S2 - CYL1 S3 ... boiler 2 S2 - CYL2 S4 ... coll. S5 - CYL3 S6
à A1, A2 à A1, A2 à A3 à A1 à A2 à A3 à A1 à A1 à A2 à A2 à A3
Page 54
54
Program 608 – 2 generators for 2 consumers + burner request
No diagram available
Program 608: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
or
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
or
S2 exceeds the threshold min2 • and S2 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
Output A3 is activated, if S6 falls below the threshold min3. Output A3 is deactivated (dominantly), if S5 exceeds the threshold max3.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1
or
S2 > (S3 + diff1) & S2 > min2 & S3 < max1
A2 = S1 > (S4 + diff2) & S1 > min1 & S4 < max2
or
S2 > (S4 + diff2) & S2 > min2 & S4 < max2
A3 (on) = S6 < min3 A3 (off) = S5 > max3
Program 609: The burner request (A3) is regulated only via sensor S6.
A3 (on) = S6 < min3 A3 (off) = S6 > max3 (dominant)
Program 610: Like P608, but the request (A3) is regulated via sensors S2 and S5.
A3 (on) = S2 < min3 A3 (off) = S5 > max3 (dominant)
Program 611: Like P608, but the request (A3) is regulated only via sensor S2.
A3 (on) = S2 < min3 A3 (off) = S2 > max3 (dominant)
Program 612: Like P608, but the request (A3) is regulated via sensors S4 and S5.
A3 (on) = S4 < min3 A3 (off) = S5 > max3 (dominant)
Program 613: Like P608, but the request (A3) is regulated only via sensor S4.
A3 (on) = S4 < min3 A3 (off) = S4 > max3 (dominant)
necessary settings:
max1 max2 max3 min1 min2 min3 diff1
diff2
... limit CYL1 S3 ... limit CYL2 S4 ... burner req. off S5 ... activ. temp. boiler 1 S1 ... activ. temp. boiler 2 S2 ... burner req. on S6 ... boiler1 S1 - CYL1 S3 ... boiler2 S2 - CYL1 S3 ... boiler1 S1 - CYL2 S4 ... boiler2 S2 - CYL2 S4
à A1 à A2 à A3 à A1, A2 à A1, A2 à A3 à A1 à A1 à A2 à A2
Page 55
55
All programs +8:
Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff1
• and S3 has not exceeded the threshold max1.
or
S1 exceeds the threshold min1 • and S1 is greater than S4 by the difference diff1
• and S4 has not exceeded the threshold max2.
Pump A2 runs, if:
S2 exceeds the threshold min2 • and S2 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max1.
or
S2 exceeds the threshold min2 • and S2 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
A1 = S1 > (S3 + diff1) & S1 > min1 & S3 < max1
or
S1 > (S4 + diff1) & S1 > min1 & S4 < max2
A2 = S2 > (S3 + diff2) & S2 > min2 & S3 < max1
or
S2 > (S4 + diff2) & S2 > min2 & S4 < max2
necessary settings:
max1 max2 max3 min1 min2 min3 diff1
diff2
... limit CYL1 S3 ... limit CYL2 S4 ... burner req. off S5 ... activ. temp. boiler 1 S1 ... activ. temp. boiler 2 S2 ... burner req. on S6 ... boiler 1 S1 - CYL1 S3 ... boiler 1 S1 - CYL2 S4 ... boiler 2 S2 - CYL1 S3 ... boiler 2 S2 - CYL2 S4
à A1, A2 à A1, A2 à A3 à A1 à A2 à A3 à A1 à A1 à A2 à A2
Page 56
56
Program 624 – Solar system with one consumer and swimming pool
Program 624: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S3 by the difference diff2
• and S3 has not exceeded the threshold max2.
Filter pump A3 runs, if:
A3 is enabled via an Or time program
or pump A2 is running in automatic mode.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1 A2 = S1 > (S3 + diff2) & S1 > min1 & S3 < max2
A3 = (A3 = time program on) or (A2 = automatic on)
All programs +1: Instead of the two pumps A1 and A2, one pump A1 and a three-way valve A2 are used.
Without priority allocation, cylinder 2 is filled by default.
All programs +2: Additionally: If sensor S4 exceeds the threshold max3, then pump A1 is de-
activated. All programs +4: Both solar circuits receive separate activation thresholds at S1.
Output A1 retains min1 and A2 is regulated via min2. The Priority Ranking between CYL1 and CYL2 can be set in the menu Settings/Technician
level/Parameters/Priority ranking. Additionally, a solar priority function can be set up in the menu Settings/Expert level/Solar priority (see „Solar Priority“ for more details).
necessary settings:
max1 max2 max3 min1 min2 diff1 diff2
... limit CYL1 S2 ... limit CYL2 S3 ... see all programs +2 ... activation temp. coll. S1 ... see all programs +4 ... coll. S1 - CYL1 S2 ... coll. S1 - CYL2 S3
à A1 à A2
à A1, A2
à A1 à A2
Excess temperature limiter: ... activate for S1 and A1+A2
A1... mutual pump A2... valve (A2/NO receives voltage when charging cylinder CYL2)
Page 57
57
Program 640 – DHW preparation incl. circulation
Only practical with speed control activated! (Absolute value control: mode „Inverted“ input S5, Differential v.c. mode „Normal“ sensors S3 and S5)
WARNING: The excess collector temperature limiter is activated for A1 by default. This must be changed to A3 or deactivated entirely.
Program 640: Pump A1 runs, if:
• the flow switch (FlS) S6 detects a flow. The nominal value for the speed control (abso-
lute value control) of pump A1 is specified for sensor S5.
Pump A2 runs, if:
S3 exceeds the threshold min2 • and S3 is greater than S4 by the difference diff2
• and S4 has not exceeded the threshold max2.
Pump A3 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
A1 = flow switch (S6) = ON A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2 A3 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
All programs +1: Pump A2 is only activated, if S6 is ON, in addition to basic regulation. All programs +4: Pump A1 runs, if:
• the flow switch S6 detects a flow or pump A2 is activated.
A1 = A2 or flow switch S6 = EIN
necessary settings:
max1 max2 min1 min2 diff1 diff2
... limit CYL S2 ... limit circ. return S4 ... activation temp. coll. S1 ... activation temp. CYL S3 ... coll. S1 - CYL S2 ... CYL S3 - circ.return. S4
à A3 à A2 à A3 à A2 à A3 à A2
Excess temperature limiter: ... activate for S1 and A3
Page 58
58
Program 656 – DHW preparation incl. circulation + burner request
Only practical with speed control activated! (Absolute value control: mode „Inverted“ input S1, Differential v.c. mode „Normal“ sensors S3 and S1)
Program 656: Pump A1 runs, if:
• Flow switch S5 detects flow. The nominal value for the speed control (absolute value control) of pump A1 is specified for S1.
Pump A2 runs, if:
S3 exceeds the threshold min1 • and S3 is greater than S4 by the difference diff1
• and S4 has not exceeded the threshold max1.
Output A3 is activated, if S3 falls below the threshold min3. Output A3 is deactivated (dominantly), if S2 exceeds the threshold max3.
A1 = flow switch (S5) = ON
A2 = S3 > (S4 + diff1) & S3 > min1 & S4 < max1
A3 (on) = S3 < min3 A3 (off) = S2 > max3
All programs +1: Circulation pump A2 is only activated, if flow switch S5 is ON (A1 = ON), in addition to basic regulation.
All programs +2: The burner request (A3) is regulated using only sensor S3.
A3 (on) = S3 < min3 A3 (off) = S3 > max3 (dominant)
All programs +4: Pump A1 runs, if:
• Flow switch S5 or pump A2 is active.
A1 = A2 or flow switch S5 = ON
necessary settings:
max1 max2 min1 min3 diff1
... limit circulation return S4 ... burner req. off CYL S2 ... activation temp. CYL S3 ... burner req. off CYL S3 ... CYL S3 - circ. return S4
à A2 à A3 à A2 à A3 à A2
Page 59
59
Program 672 – 3 generators for 1 consumer + differential circuit + burner request
No diagram available
Program 672: Pump A1 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S2 by the difference diff1
• and S2 has not exceeded the threshold max1.
Pump A2 runs, if:
S1 exceeds the threshold min1 • and S1 is greater than S5 by the difference diff2
• and S5 has not exceeded the threshold max2.
or
S3 exceeds the threshold min2 • and S3 is greater than S5 by the difference diff2
• and S5 has not exceeded the threshold max2.
or
S4 is greater than S5 by the difference diff2
• and S5 has not exceeded the threshold max2.
Output A3 is activated, if S6 falls below the threshold min3. Output A3 is deactivated (dominantly), if S5 exceeds the threshold max3.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S1 > (S5 + diff2) & S1 > min1 & S5 < max2
or
S3 > (S5 + diff2) & S3 > min2 & S5 < max2
or
S4 > (S5 + diff2) & S5 < max2
A3 (on) = S6 < min3 A3 (off) = S5 > max3
Program 673: The burner request (A3) is regulated using only sensor S6.
A3 (on) = S6 < min3 A3 (off) = S6 > max3 (dominant)
Program 674: The burner request (A3) is regulated using only sensor S5.
A3 (on) = S5 < min3 A3 (off) = S5 > max3 (dominant)
necessary settings:
max1 max2 max3 min1 min2 min3 diff1 diff2
... limit CYL1 S2 ... limit CYL2 S5 ... burner req. off CYL2 S5 ... activation temp. boiler 1 S1 ... activation temp. boiler 2 S3 ... burner req. on CYL2 S6 ... boiler 1 S1 - CYL1 S2 ... boiler 1 S1 - CYL2 S5 ... boiler 2 S3 - CYL2 S5 ... boiler 3 S4 - CYL2 S5
à A1 à A2 à A3 à A1, A2 à A2 à A3 à A1 à A2 à A2 à A2
Page 60
60
Building drying – General Information
A special application of the universal controller UVR65 is the energy-saving and cost-effective drying of basements and other building parts via regulation of ventilation. The special functionality of the
sensor RFS-DL (measurement of absolute humidity) enables the comparison of the values for abso-
lute humidity indoors and outdoors to turn a fan on or off.
Two humidity sensors 01/RFS-DL are required.
Basics
• The direction of the fan must have it blowing from outdoors to the inside
If the fan blows from indoors to the outside, you risk warm and humid air streaming in from adja-
cent building parts, which humidifies the room even more, rather than drying it.
• A supply fan suffices in most cases
The exhaust air is pushed out through leaks in the building. Airtight buildings must have an over-
flow opening added. If a supply fan and an exhaust fan are used, the throughput of the exhaust fan must never exceed that of the supply fan.
• The ventilated building/room must be as airtight as possible.
In order to prevent an unwanted influx of humid air through natural circulation, windows and doors should remain closed.
• In order to keep the resulting cooling of ventilated rooms within reasonable limits (especially in
cold seasons), timer-controlled interval operation is useful. An additional temperature monitor-
ing can be implemented.
• The exterior humidity sensor must be protected from direct insolation and rain. If necessary, it must be physically shielded from such dangers to its functionality.
External sensors
The humidity sensors RFS-DL aren‘t usual sensors and must be con-
nected to the Dataline (DL-Bus). The chapter „Electrical connection“ explains the Dataline in further detail.
The humidity sensors are automatically parameterized as External
Sensors (Expert level) if a building drying program is input. This in-
cludes address and index of the sensors, but adjusting the exterior
sensor‘s address to 2 on the sensor itself is still necessary (as de-
scribed above).
Goals:
• Lowering of humidity through targeted ventilation with dry air
• Improvement of air quality and odor with frequent ventilation
• Replacement of energy-inefficient dehumidification devices
The RFS-DL intended to measure outdoors must have its DL-Bus address adjusted. Dip-switch 1 must be set to ON. This changes the sensor‘s address to 2.
Page 61
61
Choosing a building drying program automatically binds inputs and external sensors according to the table below to reduce the amount of necessary manual setup. These settings can of course be changed, if so desired.
Programs – Building drying
Program 688 – Only room drying
A room‘s humidity is to be reduced. As soon as the absolute humidity outdoors falls below the hu-
midity indoors, a fan is activated. The fan runs, if
• the absolute humidity outdoors falls below the absolute humidity indoors and
• the optional interval operation („timer“) is active and
• the relative humidity indoors exceeds the minimal humidity min1.
A1 = S5 > min1 & S1 > (S2 + diff1)
No time programs can be set up for this program.
Program 689 – Room drying and minimum temperature monitoring
A room‘s humidity is to be reduced. If it becomes too cold in the ventilated room, the fan is deacti-
vated. The fans runs, if
• the absolute humidity outdoors falls below the absolute humidity indoors and
• the room temperature is high enough (to prevent excessive cooling in cold seasons) and
• the optional interval operation („timer“) is active and
• the relative humidity indoors exceeds the minimum humidity min1
A1 = S5 > min1 & S1 > (S2 + diff1) & S3 > min3
No time programs can be set up for this program.
Input Ext. Sensor Value
S1 E1 Absolute humidity indoors
S2 E2 Absolute humidity outdoors
S3 E3 Temp. indoors
S4 E4 Temp. outdoors
S5 E5 Relative humidity indoors
S6 E6 Relative humidity outdoors
necessary settings:
factory setting
min1 diff1
... minimum relative humidity indoors ... minimum difference in humidity indoors/outdoors
62/60% 1,0/0,5 g/m
3
necessary settings:
factory setting
min1 diff1 min3
... minimum relative humidity indoors ... minimum difference in humidity indoors/outdoors ... minimum temperature indoors
62/60% 1,0/0,5 g/m
3
10/9 °C
Page 62
62
Program 690 – Room drying, minimum temperature monitoring, comfort ventilation
A room‘s humidity is to be reduced. If it becomes too cold in the ventilated room, the fan is deacti-
vated. In order to guarantee a certain degree of air quality, the fan is activated despite exterior humidity or
if the room temperature falls below a set minimum. The fan is activated via one or more time pro-
grams, preferably in the cool morning hours, to achieve the „comfort ventilation“. The fan runs for room drying purposes, if
• the absolute humidity outdoors falls below the absolute humidity indoors and
• the temperature is high enough (to prevent excessive cooling in cold seasons) and
• the optional interval operation („timer“) is active and
• the relative humidity indoors exceeds the minimum humidity min1.
The fan runs for comfort ventilation purposes daily, according to time programs.
A1 = S5 > min1 & S1 > (S2 + diff1) & S3 > min3 || TW(1-3)
This program has the time programs 1-3 affecting A1. Time program 1 has factory settings for 6:00­6:30 daily.
Program 691 – Room drying & comfort ventilation, minimal temp. monitoring for both
A room‘s humidity is to be reduced. To ensure a certain level of air quality, the fan is activated despite exterior humidity. The fan is activated via one or more time programs, preferably in the cool morning hours. If the set minimum room temperature is underrun, the comfort ventilation is deactivated as well.
The fan runs for room drying purposes, if
• the absolute humidity outdoors falls below the absolute humidity indoors and
• the temperature is high enough (to prevent excessive cooling in cold seasons) and
• the optional interval operation („timer“) is active and
• the relative humidity indoors exceeds the minimum humidity min1.
The fan runs for comfort ventilation purposes daily, according to time programs, as long as the room temperature is high enough.
A1 = S5 > min1 & S1 > (S2 + diff1) & S3 > min3 || (TW(1-3) & S3 > min 3)
This program has the time programs 1-3 affecting A1. However, if the minimum room temperature is underrun, time program 1 will be blocked (TW1 has factory settings for 6:00-6:30 daily).
necessary settings:
factory setting
min1 diff1 min3
... minimum relative humidity indoors ... minimum difference in humidity indoors/outdoors ... minimum temperature indoors
62/60% 1,0/0,5 g/m
3
10/9 °C
necessary settings:
factory setting
min1 diff1 min3
... minimum relative humidity indoors ... minimum difference in humidity indoors/outdoors ... minimum temperature indoors
62/60% 1,0/0,5 g/m
3
10/9 °C
Page 63
63
Program 692 – Room drying, room temp. monitoring, comfort ventilation, for wine cellars
A wine cellar‘s humidity is to be lowered. To ensure a certain level of air quality, the fan is activated despite exterior humidity. The fan is activated via one or more time windows, preferably in the cool morning hours.
The fan runs for room drying purposes, if
• the absolute humidity outdoors falls below the absolute humidity indoors and
• the relative humidity indoors exceeds 60% (for example) and
• the room temperature exceeds the desired temperature (example: 10°C) and
• the optional interval operation („timer“) is active and
• die maximum temperature indoors max1 has not been exceeded.
The fan runs for comfort ventilation purposes daily, according to the time programs, without regard to other settings (example: 10:00 bis 10:30). Up to 3 time programs can be set up.
The time programs 1-3 affect A1 (TW1 has factory settings for 6:00-6:30 daily)
A1 = (S5 > min1 & S1 > (S2 + diff1) & S3 > min3 & S3 < max1) || TW(1-3)
All building drying programs +8 (additional dehumidifier)
Additional parameters:
min2 (Factory settings = 72/70% minimum relative humidity indoors) Priority ventilation (Factory settings = False)
A3 = S5 > min2 (activation dehumidifier)
Setting up time programs
Setting up a building drying program that features time programs will cause the option „Time program Bldg drying“ to appear in the main menu, used to parameter.
Three time programs are available, each with three adjustable time frames. A time programs can be bound to any days of the week. These bindings count for all of the time program‘s time frames.
The chosen time program (and its assigned days of the week) have a black background. To change a time frame, the wheel must be turned until the desired value is framed in bold. Pushing the wheel down opens a window to adjust the frame‘s time.
necessary settings:
factory setting
min1 diff1 min3 max1
... minimum relative humidity indoors ... minimum difference in humidity indoors/outdoors ... minimum temperature indoors ... maximum temperature indoors
62/60% 1,0/0,5 g/m
3
10/9 °C 14/13 °C
Page 64
64
Heating circuit control - Programs
All heating circuit programs (except program groups 816 and 976 as well as other stated exceptions) require the following settings:
Program 800 – Heating circuit with up to 2 heat sources
A1 = S4 > min1 & (Heating circuit = active)
A2/A3 = Mixer
If no room sensor is in use, the room influence in the menu point Expert level/Mixer must be set to 0.0%.
Overview Technician level:
Time/Date Menu Parameters Mode (preferably Auto) Basic parameters
Time programs Heat curve Expert level: Set flow temp. at +10°C and at -20°C
or Slope
Menu Programming settings
Program (number) Flow temperature min and max Room sensor present (Y/N) Frost protection conditions Use S4 (only P800 - 802) Time program set values (Y/N)
Menus Shutdown conditions & Mixer Mixer selection (only P832 and above)
S1... Room sensor A1... Heating circuit pump S2... Temperature outdoors A2... Mixer OPEN S3... Heating circuit flow A3... Mixer CLOSE S4... Cylinder top S5... Boiler
Page 65
65
Program 800: Activation of heating circuit pump A1, if sensor S4 has exceeded the thresh­old min1. If sensor S4 is not in use, then the corresponding program setting must be adjust-
ed accordingly.
All programs +1: Like program 800, but the heating circuit pump A1 is also enabled via sen-
sor S5 and the minimum threshold min2 (2 generators for the heating circuit).
A1 = ((S4 > min) or (S5 > min2)) & (heating = active)
All programs +2: Like program 800, but the set flow temperature is output via control output A4 (e.g. for burner modulation).
Example: The set flow temperature of 55°C is output via control output A4 as 5,5 Volt. How­ever, the voltage being output does not fall below the threshold min1. If the pump is deacti-
vated via a shutdown condition (menu Shutdown conditions), then the control output will output 0,5V. If it is deactivated by the shutdown condition S4 < min1, voltage equal to the set flow temperature (as calculated by the controller) will be output, however not below the threshold min1.
The menu Technician level/Parameters features several adjustment settings under the point Modulation:
Offset-value for the set flow temp., range of -50,0K to +50,0K. (FS = 0,0K) Inverse output Yes/No, FS = No Min. output range of 0.00V - 10.00V, FS = 0.00V Max. output range of 0.00V - 10.00V, FS = 10.00V
All programs +4: Like program 800, but the mixer control is output via control output A5 (for
mixers with 0-10V-regulation). The menu Technician level/Parameters features adjustment settings under the point
0-10V mixer:
Inverse output Yes/No, FS = NO Min. output range of 0.00V - 10.00V, FS = 0.00V Max. output range of 0.00V - 10.00V, FS = 10.00V
Scaling: 0°C = 0.0 V
100°C = 10.0 V
Page 66
66
Program 816 – Boiler circuit pump, mixer for return flow boosting
Program 816: Boiler circuit pump A1 is enabled, if S1 exceeds the threshold min1 and S4 is
greater than S2 by the difference diff1 and S2 has not exceeded the threshold max1.
A1 = S1 > min1 & S1 > (S2 + diff1) & S2 < max1
Program 817: Like program 816, however with additional 10V burner request via sensors S4 and S2 at the control output A4.
A1 = S1 > min1 & S1 > (S2 + diff1) & S2 < max1
A4 on = S4 < min3
A4 off = S2 > max3
The menu Technician level/Parameters features a setting to change the control output from
inverse no to inverse yes. The setting inverse yes has the control output generating 0 Volts, if the threshold min3 is underrun and 10 Volts, if the threshold max3 is exceeded.
Program 818: Like program 816, but with additional 10 V burner request via sensors S4 and S5 at the control output A5.
A1 = S1 > min1 & S1 > (S2 + diff1) & S2 < max1
A5 on = S4 < min3
A5 off = S5 > max3
The menu Technician level/Parameters features a setting to change the control output from
inverse no to inverse yes. The settings inverse yes has the control output generating 0 Volts, if the threshold min3 is underrun and 10 Volts, if the threshold max3 is exceeded.
min3 ... A4 on (10V) S4 (FS = 60°C) max3 ... A4 off (0V) S2 (FS = 75°C)
min3 ... A5 on (10V) S4 (FS = 60°C) max3 ... A5 off (0V) S5 (FS = 75°C)
Page 67
67
Program 832 – Solid fuel burner, buffer cylinder, heating circuit, additional heating req.
Program 832: Enabling of the heating circuit pump A1 via boiler temp. and buffer temp., reg-
ulation of buffer charging pump A2, burner request related to buffer.
A1 = (S4 > min1 or S6 > min2) & (Heating = active)
A2 = S4 > min1 & S4 > S5 + diff1
A3 on = S6 < min3
A3 off = S6 > max3
A4/A5 = Mixer
S1 ... Room sensor A1 ... Heating circuit pump
S2 ... Temperature outdoors A2 ... Buffer charging pump
S3 ... Heating circuit flow A3 ... Heating request
S4 ... Boiler A4 ... Mixer OPEN
S5 ... Buffer bottom A5 ... Mixer CLOSE
S6 ... Buffer top
min1 ... Activation threshold S4 à A1, A2
min2 ... Activation threshold S6 à A1
diff1 ... boiler S4 - buffer S5 à A2
diff3 ... Buffer S6 - Set. flow. t. à A3
min3 ... Heating req. on S6 à A3
max3 ... Heating req. off S6 à A3
Page 68
68
Program 833: The burner is regulated only via S5.
A3 on = S5 < min3
A3 off = S5 > max3
Program 834: Separate activation and deactivation thresholds via sensors S5 and S6.
A3 on = S6 < min3
A3 off = S5 > max3
Program 835: Activation and deactivation thresholds are related to the set flow tempera-
ture.
A3 on = S6 < Set flow temp. + diff3 & Heating active
A3 off = S6 > Set flow temp. + diff3
Program 836: Separate activation and deactivation thresholds for the heating request. Both thresholds are related to the set flow temperature.
A3 on = S6 < Set flow temp. + diff3 & Heating active
A3 off = S5 > Set flow temp. + diff3
Program 837: The heating request is related to the set flow temperature.
A3 on = S6 < Set flow temp. + diff3 & Heating active
A3 off = S6 > max3
Program 838: Separate activation and deactivation thresholds for the heating request. The heating request is related to the set flow temperature, the deactivation threshold is regulated via S5.
A3 on = S6 < Set flow temperature + diff3 & Heating active
A3 off = S5 > max3
All programs +8: The heating request is only permissible, if the solid fuel burner is cold.
A3 (+8) = S4 < min1 & Conditions for A3 of other programs
All programs +16: The heating circuit pump A1 is regulated only via the buffer temperature S6 and not via the boiler temperature S4.
A1 = S6 > min2 & Heating = active
Page 69
69
Program 896 – Automatic burner, cylinder, heating circuit, boiler request
Basic functionality (P896): No buffer, cylinder charging pump = A2, Boiler request = A3.
For a modulating boiler operation without a mixer it‘s feasible to set the thresholds min1 and min2 to 5°C (= no functionality) and to activate the pump shutdown condition Set flow temp. in the menu Shutdown conditions.
Sensors Outputs
S1 ... Room sensor A1 ... Heating circuit pump S2 ... Temperature outdoors A2 ... Cylinder charging pump S3 ... Heating circuit flow A3 ... Boiler request S4 ... Boiler A4 ... Mixer OPEN S5 ... Cylinder bottom A5 ... Mixer CLOSE S6 ... Cylinder top
Boiler request A3
S4 < max2
and
S6 à min3/max3
and
Time programs
or
Heating active and S4 < min2
or
Heating active and S4 < Set flow temp. + diff2
necessary parameter settings:
min1 ... Activation threshold S4 àA1+A2 min3 ... Heating request on S6 àA3 min2 ... Basic temperature S4 àA3 max3 ... Heating request off S6 àA3 max1 ... Limit cylinder S6 àA2 diff1 ... Burner S4 - cylinder S6 àA2 max2 ... Limit boiler S4 àA3 diff2 ... Burner S4 < set flow t. àA3
Page 70
70
Program 896:
A1 = S4 > min1 & Heating = active
A2 = S4 > min1 & S4 > S6 + diff1 & S6 < max1
A3 = [(S6àmin3/max3 & TP
Req. DHW
) or ((S4 < min2 or S4 < Set flow temp + diff2) &
(Heating = active))] & S4 < max2
All programs +1: Cylinder priority
A1 (+1) = only if [(S6 < max1) & TP
Req. DHW
] is false
Together with „All programs +2“:
A1 (+3) = only if [(S5 < max1) & TP
Req. DHW
] is false
All programs +2: Separate sensors for activation and deactivation threshold of the DHW request
A2 = S4 > min1 & S4 > S5 + diff1 & (S5 < max1)
A3 on = {(S6 < min3 & TP
Req. DHW
) or [(S4 < min2 or S4 < Set flow temp + diff2) &
Heating = active ]} & S4 < max2
A3 off = {(S5 > max3 & [(S4 > min2 & S4 > Set flow temp + diff2) & Heating = active]}
or S4 >max2
All programs +4: Like program 896, however limit max1 at S6 only active, if heating = active.
A2 = S4 > min1 & S4 > S6 + diff1 & (S6 < max1 & Heating = active)
All programs +8: Like program 896, however the burner request is only related to the de-
mand of the heating circuit and the cylinder charging rather than to a comparison with the boiler temperature.
A3 on = [(S6 < min3 & TP
Req. DHW
) or (Heating = active)] & (S4 < max2)
A3 off = (S6 > max3 & Heating = inactive) or S4 > max2
Time programs are not possible for the heating circuit A1 and the DHW request A3. The time program TP
Req. DHW
only affects the request A3 and not the charging pump.
Page 71
71
Program 912 – Automatic boiler, (combined) buffer, heating circuit, burner request
Basic functionality (P912): The combined buffer is held to a certain temperature by the au-
tomatic burner. Buffer charging pump A2, burner request A3, Mixer regulation A4+A5.
A1 = S5 > min2 & (Heating = active)
A2 = S4 > min1 & S4 > S5 + diff1 & S5 < max1
A3 on = [(S6 < min3 & TP
Req. DHW
) or (S5 < set flow temp + diff3 & (Heating = active))]
& TP
Req. Burner
& S4 < max2
A3 off = [S6 > max3 & (S5 > set flow temp + diff3 & (Heating = active))] or S4 > max2
Sensors Outputs
S1 ... Room sensor A1 ... Heating circuit pump S2 ... Temperature outside A2 ... Buffer charging pump S3 ... Heating circuit flow A3 ... Burner request S4 ... boiler A4 ... Mixer OPEN S5 ... Buffer top A5 ... Mixer CLOSE S6 ... Buffer bottom
Burner request A3
S4 < max2
and
Time programs
and
S6 à min3/max3
or
Heating active and S5 < Set flow temp + diff3
necessary parameter settings
min1 ... activation threshold S4 à A2 max1 ... limit buffer S5 à A2 min2 ... activation threshold S5 à A1 max2 ... limit boiler S4 à A3 min3 ... Heating request on S6 à A3 max3 ... Heating request off S6 (S5) à A3 diff1 ... Burner S4 - CYL bot. S5 à A2 diff3 ... CYL bottom S5 < set flow t. à A3
Page 72
72
Program 913: Separate deactivation threshold for the burner request at S5 and S6 (hold cir-
cuit).
A3 on = S6 < min3 & S4 < max2 & TP
Req. DHW
& TP
Req. burner
A3 off = S5 > max3 or S4 > max2
Program 914:
Hold circuit with difference to the set flow temperature.
A1 = S6 > min2 & (Heating = active)
A3 on = [(S6 < min3 & TP
Req. DHW
) or (S6 < set flow temp + diff3 & Heating = active)] &
TP
Req. burner
& S4 < max2
A3 off = [S6 > max3 & (S5 > set flow temp + diff3 & Heating = active)] or S4 > max2
Program 915: Burner request unrelated to the heating circuit.
A1 = S6 > min2 & (Heating = active)
A2 = S4 > min1 & S4 > S5 + diff1 & S5 < max1
A3 = S5 à min3/max3 & TP
Req. burner
& S4 < max2
All programs +4: The buffer charging pump A2 is activated along with the burner request (in-
tended for condensing boilers with a minimum circulating water level).
A2 = Conditions for A2 or A3 of the corresponding program
Time programs for heating circuit A1, DHW request A3 and burner request A3 possible.
Burner request A3
ON:
S4 < max2
and
Time programs
and
S6 < min3
or
Heating active & S6 < set flow temp + diff3
Burner request A3
OFF:
S4 > max2
or
S6 > max3
and
Heating active & S5 > set flow temp + diff3
Page 73
73
Program 928 – Buffer, Cylinder, Heating circuit, boiler request
Basic functionality (P928): Regulation of the heating circuit pump A1, cylinder charging pump A2, burner request A3.
A1 = S6 > min1 & (Heating = active)
A2 = S6 > min1 & S6 > S4 + diff1 & S4 < max1 & TP
Req. DHW
A3 on = S6 < min3 A3 off = S6 > max3
Sensors Outputs
S1 ... Room sensor A1 ... Heating circuit pump S2 ... Temperature outdoors A2 ... Cylinder charging pump S3 ... Heating circuit flow A3 ... Heating request S4 ... Cylinder bottom A4 ... Mixer OPEN S5 ... Buffer bottom A5 ... Mixer CLOSE S6 ... Buffer top
Heating request A3
ON
S6 < min3
OFF
S6 > max3
necessary parameter settings:
min1 ... Activation threshold S6 à A1, A2 min3 ... Heating request ON S6 à A3 max1 ... Limit cylinder S4 à A2 max3 ... burner request OFF S6 à A3 diff1 ... Buffer S6 - cylinder S4 à A2
Page 74
74
Program 929: Like program 928, deactivation threshold of the burner request at S5 (holding circuit).
A2 = S6 > min1 & S6 > S4 + diff1 & S4 < max1 & ZP
Req. DHW
A3 on = S6 < min3 A3 off, = S5 > max3
Program 930:
Burner request related to set flow temperature and sensor S5.
A2 = S6 > min1 & S6 > S4 + diff1 & S4 < max1
A3 = (S5 à min3/max3 & TP
Req. DHW
) or (S6 < set flow temp + diff3 & Heating active)
Program 931: Like program 930, however with regard to the cylinder temperature S4.
A2 = S6 > min1 & S6 > S4 + diff1 & S4 < max1
A3 = (S4 à min3/max3 & TP
Req. DHW
) or (S6 < set flow temp + diff3 & Heating active)
Program 932: Separate sensors for activation and deactivation thresholds of the burner re-
quest related to set flow temperature (holding circuit).
A2 = S6 > min1 & S6 > S4 + diff1 & S4 < max1 & TP
Req. DHW
A3 on = S6 < (set flow temp + diff3 & Heating active) A3 off = S5 > set flow temp + diff3)
Program 933: Like program 932 but with regard to the cylinder temperature and the status of the cylinder charging pump (holding circuit).
A3 on = [S4 < min3 & TP
Req. DHW
& (S6 < min1 or S6 < S4 + diff1)]
or
(S6 < set flow temp + diff3 & Heating active)
A3 off = S5 > set flow temp + diff3 & S4 > max3
Program 934: Like program 932, but A2 (DHW) is prioritized over A1.
A1 = (S6 > min1 & (Heating = active)) & S4 > max1
A3 on = S6 < (set flow temp + diff3 & Heating active)
A3 off = S5 > set flow temp + diff3
Program 935: Like program 933, but A2 (DHW) is prioritized over A1.
A1 = (S6 > min1 & (Heating = active)) & S4 > max1
A3 on = [S4 < min3 & TP
Req. DHW
& (S6 < min1 or S6 < S4 + diff1)] or (S6 < set flow temp + diff3 & Heating = active)
A3 off = S5 > set flow temp + diff3 & S4 > max3
Page 75
75
All programs +8: Second energy source next to the buffer with sensor S5. All conditions at S6 also count for S5. The higher temperature comes into effect. However all conditions only at S5 remain unchanged.
Example: program 936 (= 928 + 8)
A1 = (S6 > min1 or S5 > min1) & (Heating = active)
A2 = (S6 > min1 or S5 > min1) & (S6 > S4 + diff1 or S5 > S4 + diff1) & S4 < max1
A3 on = S6 < min3 and S5 < min3 A3 off = S6 > max3 or S5 > max3
Example: program 937 (= 929 + 8)
A1 = (S6 > min1 or S5 > min1) & (Heating = active)
A2 = (S6 > min1 or S5 > min1) & (S6 > S4 + diff1 or S5 > S4 + diff1) & S4 < max1
A3 on = S6 < min3 and S5 < min3 A3 off = S5 > max3
Note regarding Time programs: Time programs possible for A1, A2 and A3.
The programs 928, 929, 932 and 934 (and all programs +8) have the time program Req. DHW affecting the cylinder charging pump A2.
The program 930, 931, 933 and 935 (and all programs +8) have the time program Req. DHW affecting the heating request pump A3 for the preparation of DHW (only thresholds min3/ max3).
Page 76
76
Program 944 – Solid fuel boiler, buffer, cylinder, heating circuit
Basic functions (P944): Clearance for the heating circuit pump A1, if either the boiler‘s or
the buffer‘s temperature has exceeded its respective minimum threshold , regulation of the cylinder charging pump A2, mixer regulation A4+A5, regulation of the buffer charging pump A3. The room sensor at EXT1 is intended to be an RAS+DL (not included).
A1 = (S4 > min1 or S6 > min2) & (Heating = active)
A2 = (S6 > min2 & S6 > S1 + diff2 & S1 < max2) & TP
Req. DHW
A3 = S4 > min1 & S4 > S5 + diff1 & S5 < max1
Sensors Outputs
S1 ... Cylinder bottom A1 ... Heating circuit pump S2 ... Temperature outdoors A2 ... Cylinder charging pump S3 ... Heating circuit flow A3 ... Buffer charging pump S4 ... Boiler A4 ... Mixer OPEN S5 ... Buffer bottom A5 ... Mixer CLOSE S6 ... Buffer top EXT1 Room sensor RAS+DL
necessary parameter settings:
min1 ... Activation threshold S4 à A1, A3 max2 ... Limit cylinder S1 à A2 min2 ... Activation threshold S6 à A1, A2 diff1 ... Boiler S4 - buffer S5 à A3 max1 ... Limit buffer S5 à A3 diff2 ... Buffer S6 - cylinder S1 à A2
Page 77
77
All programs +1: The cylinder is charged in regard to both the boiler‘s and the buffer‘s tem-
perature.
A2 = [(S4 > min1 & S4 > S1 + diff2) or (S6 > min2 & S6 > S1 + diff2) & S1 < max2] & TP
Req. DHW
all programs +2: The heating circuit pump A1 is activated only via the buffer temperature S6 and not via the burner temperature S4.
A1 = S6 > min2 & (Heating = active)
all programs +4: Cylinder priority – Heating circuit A1 is blocked, if the boiler charge A2 goes active.
A1 = A1-Conditions according to program & A2 inactive
Time programs possible for heating circuit A1 and cylinder charge (DHW request) A2.
Page 78
78
Program 960 – Boiler (or buffer), cylinder, 1 regulated & 1 unregulated heating circuit
Basic functionality (P960): Regulation of the heating circuit pumps A1, A2, and the cylinder
charging pump A3, mixer regulation for the first heating circuit A4+A5; regulation of the sec-
ond heating circuit can be achieved via speed control for A2.
A1 = S4 > min1 & (Heating = active)
A2 = (S4 > min1 & S4 > S5 + diff1 & S5 < max1) & (Heating = active) & TP
HC2
A3 = (S4 > min1 & S4 > S6 + diff2 & S6 < max2) & TP
Req. DHW
Sensors Outputs
S1 ... Room sensor A1 ... Heating circuit pump 1 S2 ... Temperature outdoors A2 ... Heating circuit pump 2 S3 ... Flow heating circuit 1 A3 ... Cylinder charging pump S4 ... Boiler A4 ... Mixer OPEN S5 ... Return heating circuit 2 A5 ... Mixer CLOSE S6 ... Cylinder bottom
necessary parameter settings:
min1 ... Activation threshold S4 à A1, A2, A3 diff2 ... Difference S4 - S6 à A3 max1 ... Limit S5 à A2 max2 ... Limit S6 à A3
min3 max3
... hold circuit (S4/S6) (programs +2, +4)
à A3
diff1 ... Difference S4 - S5 à A2
Page 79
79
Program 962: Combined buffer instead of the boiler and the cylinder. As such, output A3 is used for the heating demand via S4.
A3 on = S4 < min3 A3 off = S4 > max3
Program 964: Like program 962, but with the deactivation threshold of the heating request at S6 in the buffer (hold circuit)
A3 on = S4 < min3 A3 off = S6 > max3
All programs +1: The pump shutdown conditions of heating circuit 1 do not affect output A2.
A2 = (S4 > min1 & S4 > S5 + diff1 & S5 < max1) & TP
HC2
Programs 976/977/978 – Screed drying
This group of programs enables the drying of screed without having to change the connec-
tions of inputs and outputs, since all heating circuit programs use A1 for a heating pump and S3 as the flow sensor.
The mixer is regulated via the outputs A2+A3, A4+A5 or only the control output A4 (0-10 V mixer), depending on the program.
S3 ... Flow
A1 ... Heating pump A2 + A3 ... Mixer program 976 A4 + A5 ... Mixer program 977 A4 ... Mixer program 978
(0-10 V mixer)
necessary settings :
Technician level/parameters
Number of stages, range 1-64
Cycle time, range of 1 second to 3 days
Set temperature per stage, range 0.0 - 100,0°C
Buttons: Start, Next stage, Reset
Indicators: Remaining runtime stage, Total remaining runtime
Expert level
Menu Shutdown conditions: Mixer action
Menu Mixer: Mixer run time, control speed
Page 80
80
Installation instructions
Sensor installation
Correct arrangement and installation of the sensors is extremely important for correct func­tioning of the system. To this end, also ensure that they are completely inserted in their sen-
sor wells. The cable fittings provided serve as strain relief. When used outdoors, no water must be allowed to penetrate the sensor wells (risk of frost).
Fundamentally, sensors should not be exposed to moisture (such as condensation) since this can diffuse through the cast resin and damage the sensor. If this happens, heating the sensor to 90 °C for an hour may help. When using sensor wells in stainless steel cylinders or swimming pools, particular attention must be given to their corrosion resistance.
Collector sensor: Either insert into a pipe which is brazed or riveted directly to the absorber and protrudes from the collector housing or insert a tee into the flow manifold
of the outermost collector into which the sensor well, together with the brass cable fit-
ting (= protection against moisture), can be inserted; then insert the sensor. To protect against lightning damage, the junction box has a surge protection (voltage dependent resistor) which is clamped in parallel between the sensor and the extension cable.
Boiler sensor (boiler flow): This sensor is either inserted into a sensor well in the boiler or fitted to the flow line as close to the boiler as possible.
DHW cylinder sensor: The sensor required for the solar thermal system should be used
with a sensor well for finned tube heat exchangers just above the exchanger or, if inte-
grated smooth tube heat exchangers are used, in the lower third of the exchanger or the exchanger’s return outlet so that the sensor well protrudes into the heat exchanger tube. The sensor monitoring the heating of the DHW cylinder by the boiler is installed at a level corresponding to the amount of domestic hot water required during the heating season. The supplied cable fitting acts as strain relief. Installation below the associated coil or heat exchanger is not permissible under any circumstances.
Buffer sensor: The sensor required for the solar thermal system is fitted in the lower sec-
tion of the cylinder just above the solar indirect coil using the sensor well supplied. The supplied cable fitting acts as strain relief. As the reference sensor for the heating system
hydraulics, it is recommended to insert the sensor into the sensor well between the cen­ter and upper third of the buffer cylinder, or positioned against the cylinder wall under-
neath the insulation.
Pool sensor (swimming pool): Fit a T-piece into the suction line immediately on the pool outlet and insert the sensor with a sensor well. In the process, ensure the material used is corrosion-resistant. A further option would be to fit the sensor as a contact sensor with appropriate thermal insulation against ambient influences..
Contact sensor: Use scroll springs, pipe clips, etc.to attach the contact sensor to the respective line. Ensure the material used is suitable (corrosion, temperature resistance,
etc.). Then insulate the sensor thoroughly so that the pipe temperature is captured accu-
rately and ambient temperatures cannot falsify the result.
Page 81
81
DHW sensor: A rapid reaction to changes in the water volume is extremely important when using the controller in systems that generate domestic hot water by means of an external heat exchanger and variable speed pump (freshwater module). Therefore fit the DHW sensor directly on the heat exchanger outlet. This ultra-quick sensor (special accessory, type MSP ...) should protrude into the output with the aid of a tee sealed in with an O-ring. The heat exchanger should be installed upright with the DHW outlet at the top.
Radiation sensor: The parallel collector orientation is important in order to obtain a mea-
surement that corresponds to the collector position. Consequently it should be secured to the sheet steel covering or adjacent to the collector on an extension of the mounting rail. To this end, the sensor casing has a blind hole that can be opened at any time. The sensor is also available as a wireless version.
Room sensor: This sensor is intended for installation in the living space (reference
room). Do not install the room sensor near a heat source or window. By simply replug-
ging a jumper inside the sensor, each room sensor can also be used exclusively as a remote adjuster (no room temperature influence). It is only suitable for operation in dry rooms. The sensor is also available as a wireless version.
Outdoors temperature sensor: This sensor is installed on the coldest wall (usually fac-
ing north) some two meters above the ground.Avoid temperature influences from nearby air shafts, open windows, cable ways, etc. It must not be subjected to direct insolation.
Sensor lines
All of the sensor lines with a cross-section of 0.5mm2 can be extended up to 50m. With this
length of line and a Pt1000 temperature sensor, the measurement error is approx. +1K. Lon-
ger lines or a lower measurement error require an appropriately larger cross-section. In order
to prevent measurement fluctuations, the sensor cables must not be subject to negative ex-
ternal influences to ensure fault-free signal transmission. When using non-screened cables, sensor cables and 230V network cables must be laid in separate cable channels and at a minimum distance of 5 cm. If screened cables are used, the screen must be connected to the sensor earth.
Page 82
82
Device installation
CAUTION! Always disconnect the mains plug before opening the casing!
Only work inside the controller with the power cable disconnected.
Unscrew the screws on the front and lift the cover.
The electronics are located in the cover. The connection to the terminals in the lower section of the enclosure is made by contact pins when the cover is put in place. The lower section can be wall mounted through the slots provided (with the cable entries in the side facing down) or mounted on a top-hat rail (TS35 support rail as defined by the EN50022 standard).
Mounting dimensions (in mm)
Page 83
83
Measurement drawing of casing (in mm)
Electrical connection
Caution: This must only be carried out by a qualified electrician in accordance with the rele-
vant local regulations. The sensor lines may not be fed through the same cable channel as the supply voltage. The maximum load of all switching outputs A1-A3 equals 2.5A. All of the outputs are fused along with the equipment at 3.15A. If filter pumps are directly connected, mind their rating plate. The fuse protection can be increased to max. 5A (medium-lag). The strip terminal PE must be used for all protective conductors.
Note: The system has to be grounded properly and furnished with surge arresters to protect
it from damage due to lightening. Sensor failures due to storms and static electricity are usu-
ally the result of faulty construction. All sensor ground wires are internally looped and can be exchanged as needed.
Page 84
84
Mixer drive and pumps for PWM or 0-10V signals
Programs which use outputs A4 + A5 to regulate a three-point mixer via an auxiliary relay
leave no control outputs to generate PWM or 0-10V signals for pumps. All heating circuit pro-
grams beginning at 832 are affected. If pumps requiring PWM or 0-10V signals are in use, then they must be set to heating mode
(PWM 1). In this mode, the pump runs at full speed if it receives no control signal. Alterna-
tively, pumps requiring no control signal can be used.
If a mixer using 0-10V signals via control output A4 is in use, control output A5 is free to gen- erate PWM or 0-10V signals for a pump. Most 0-10V mixers require external 24V supply volt-
age, which must be supplied using an external main supply unit. The choice of the used mixer type is made in the menu point Expert level/Mixer.
Special connections
Control outputs A4 and A5 (0-10V / PWM)
These outputs are intended for the speed control of electronic pumps, to control the burner output (0-10V or PWM) for switching tasks with an auxiliary relay (e.g. HIREL-22) in certain programs. They can be operated via respective menu functions parallel to the outputs A1 to A3, if they are not in use by the used program.
Sensor input S6
Compared to the other inputs, input S6 has the special feature of being able to record fast signal changes of the type supplied by volume flow encoders (type VIG...) and wind sensors (type WIS01).
The data lina (DL-Bus)
The bi-directional data link (DL-Bus) was developed for the UVR-controller series and is only compatible with products of the Technische Alternative company. Any cable with a
cross section of 0.75 mm² can be used for the data link (e.g. twin-strand) with a maxi-
mum length of 30 m. For longer cables, we recommend the use of a screened cable. If screened cables are used, the screen must be connected to the sensor earth.
CAN-Bus
The CAN-Bus serves the purpose of accessing the UVR65 controller from other devices (and vice-versa) and for C.M.I. data logging. The basics of CAN-Bus connections are described in further detail in the coming pages.
Page 85
85
Terminal diagram
View of the lower casing section with terminals:
Mains connection
Power is supplied through a power supply unit integrated into the device. The mains connection must therefore be 230 V 50 Hz. This is also the voltage conducted by the output relay. The integral power supply unit also supplies power to the CAN bus.
Mains:
L... Phase conductor
N... Neutral conductor
PE... Earth conductor
Outputs:
C... Root (A3)
A1 & A2... NO contact
NC... N/C contact
N... Neutral conductor
Page 86
86
Sensor leads
Sensor terminal diagram
Sensors are always connected across the relevant sensor terminal (S1 – S6) and sensor earth (GND).
There is an earth strip in the base. A connection to the GND terminal must be laid using this strip be-
fore the sensors are connected. In order to prevent measurement fluctuations and ensure perfect signal transmission, sensor leads
must not be subject to external negative influences through 230 V cables. Never run sensor leads together with mains voltage cables in the same conduit.
When using non-screened cables, route sensor leads and 230 V cables either in separate cable con-
duits or with a minimum distance of 5 cm. If screened cables are used, the screen must be connected to the sensor earth (GND). All sensor leads with a cross-section of 0.5 mm2 can be extended to up to 50 meters. With this lead
length and a PT1000 temperature sensor, the measuring error is approximately +1 K. A correspond-
ingly larger cross-section is required for longer leads or a lesser measuring error. The connection between the sensor and the extension can be made by pushing heat shrink tubing
(trimmed to 4 cm) over one core and twisting the bare wire ends. Solder the connection if one of the wire ends has been tin-plated.
Then push the heat shrink tubing over the connection and heat up carefully (e.g. with a lighter) until it sits tightly over the connection.
Page 87
87
Outputs
Terminal diagram, switching outputs
The maximum current load of the outputs is noted in the chapter Technical data.
Terminal diagram for analogue outputs (0-10V / PWM)
The connections A4 & A5 are the positive pole, the GND connection is the negative pole.
Page 88
88
Mixer connection
When using a three-point mixer, a connection between the root C and the phase conductor L must be established.
This connection plan only applies to program groups 800 and 816.
Output A3 serves to close, Output A2 serves to open the mixer.
Alternatively, the auxiliary relay HIREL-22 can be used to connect a mixer to the analogue outputs A4
and A5. This is the case in all heating circuit programs except program groups 800 and 816. The ter-
minal diagram for this variant follow on the next page.
Mains:
L... Phase conductor
N... Neutral conductor
Outputs:
C... Root
NO N/O contact
NC... N/C contact
N... Neutral conductor
Page 89
89
Connection auxiliary relay HIREL-22
Connection of a three-way mixer to the analogue outputs A4 and A5
The auxiliary relay is not to be mounted in the device itself, as it has its own casing. This connection plan only applies to program groups 832 and above.
Page 90
90
Data line for DL-Bus
The DL-Bus consists of just 2 wires: DL and GND (sensor earth). The DL-Bus itself supplies the nec-
essary power for the DL-Bus sensors. Cables can be routed with a star topology but also in serial formation (from one device to the next). Any cable with a cross-section of 0.75 mm² up to 30 m in length can be used as data cable. For longer
cables, we recommend the use of a screened cable. If screened cables are used, the screen must be connected to GND Long cable conduits routed closely next to each other for mains and data cables result in faults being
induced into the data cables from the mains. We therefore recommend a minimum clearance of 20 cm between two cable conduits or the use of screened cables.
Use separate, screened cables when capturing data from two controllers with a single datalogger. Never run the data cable together with a CAN-Bus cable in the same conduit.
Terminal diagram for DL-Bus
Bus load of DL sensors
A 2-pole cable provides both the power supply and the signal transfer from DL-Bus sensors. An ad-
ditional power supply by means of an external power supply unit (such as with the CAN-Bus) is not
possible directly, but some DL-Bus devices can have their bus load reduced via an external 12V sup-
ply (only if explicitly stated). Take the „BUS load“ into consideration as sensors have a relatively high current demand: The controller UVR65 supplies a maximum bus load of 100%. The bus loads of the electronic sensors
are listed in the technical data of the relevant sensors. Example: The electronic sensor FTS4-50DL has a BUS load of 25 %. Consequently up to four FTS4-
50DL can be connected to the DL BUS.
Page 91
91
CAN-Bus network
Terminal CAN-Bus line
Guidelines for the topology of a CAN network
Technical principles
The CAN BUS comprises the cables CAN-High, CAN-Low, GND and one +12 V supply cable for
bus components without their own power sup-
ply. The combined total load of all devices with 12 V and 24 V supply must not exceed 6 W.
Design CAN networks in a linear fashion and set a terminator at each network termination. This is ensured by the termination of the end devices.
In the case of larger networks (covering sever­al buildings), problems can occur through elec-
tromagnetic interference and potential differences.
To avoid or to the greatest extent manage such problems, take the following measures:
• Cable screening
The BUS cable screen must be connected well at every node to provide continuity. For larger networks we recommend including the screen in the equipotential bonding, in line with the examples shown.
• Equipotential bonding
The lowest possible ohm connection to the earth potential is particularly important. Where cables enter buildings, ensure that the cable entries are in the same location where possible and that all are connected to the same equipotential bonding system (Single-entry-point principle). The purpose is to create potentials that are as similar as possible, in order to achieve the smallest possible potential difference to adjacent lines in case one line suffers a voltage surge (lightning strike). Also ensure a corresponding clearance between the cable and lightning protection systems. The equipotential bonding also has positive properties to counteract interferences emitted from linked cables..
Page 92
92
• Avoiding earth loops
If a bus cable is routed between several buildings, ensure that earth loops are avoided. The reason for this is that buildings actually have different potentials compared to the earth potential.An earth loop is created when connecting one cable screen in each building directly with the equipotential bonding system. In other words, a current flows from the higher to the lower potential. For example, if lightning strikes near one of the buildings, the potential of that building will briefly be raised by several kV. In this case, the equalizing current flows to earth via the bus screen and causes an extreme electromagnetic input which can result in the destruction of the bus components..
Lightning protection
Efficient lighting protection is highly dependent on good building earthing that meets the relevant regulations.
An external lightning protection system offers protection against a direct lightning strike. In order to protect against voltage surges in the 230 V mains supply cable (indirect lightning strike),
appropriate lightning conductors and surge arresters compliant with local regulations must be fitted in the upstream distribution systems.
In order to protect the individual components of a CAN network against indirect lightning strike, we recommend the use of surge arresters specifically developed for BUS systems.
Beispiel: CAN bus surge arresters CAN-UES from Technische Alternative
Gas discharge arrester for indirect earthing EPCOS N81-A90X
Examples of different network variants
Key to symbols:
„Small“ network (within one building)
Max. cable length: 1000 m at 50 kbit/s The screen must be continued at each network node and be connected to the device earth (GND).
The screen earthing or GND must only be implemented indirectly via a gas discharge arrester. Ensure that no unintentional direct connection of earth or screen and the earth potential is created (e.g. via sensors and the earthed pipework).
... device with its own power supply (RSM610, UVR16x2, UVR1611, UVR65)
... device is supplied by the CAN-Bus (CAN-I/O 45, CAN-MTx2, ...)
... terminated (end devices) ... open termination
... gas discharge arrester for indirect earthing
Page 93
93
Cable selection and network topology
Screened twisted pairs have proven useful in CANopen networks. These are cables with twisted
pairs of conductors and a shared external screen. Such cables are relatively resistant to EMC inter-
ference and can still carry 50 kbit/s for up to 1000 m. The CANopen recommendations (CiA DR 303-
1) for cable cross-sections are given in the table below.
The maximum cable length also depends on the number of nodes [n] linked with the BUS cable and the cable cross-section [mm2].
Bus rate
In the CAN BUS / CAN settings menu of the UVR65, the BUS rate can be set to between 5 and 500 kbit/s, whereby lower BUS rates enable longer cable networks.. However in this case, the cable cross­section must be increased accordingly.
The standard BUS rate of the CAN network is 50 kbit/s (50 kBaud), which is specified for many CAN BUS devices.
Important: All devices in the CAN BUS network must have the same transfer rate in order to be able to communicate with each other.
Recommendations
A 2x2-pole, screened twisted pair (twist CAN-L with CAN-H or +12 V with GND) with a cable cross­section of at least 0.5 mm² and a conductor-to-conductor capacity of no more than 60 pF/m and a
nominal impedance of 120 ohms. The standard BUS speed of the UVR65 is 50 kbit/s. This recom-
mendation corresponds, for example, to cable type Unitronic®-BUS CAN 2x2x0.5 supplied by Lapp Kabel for permanent installation in buildings or conduits. Theoretically this would enable a BUS length of approx. 500 m to guarantee reliable transmission.
For direct routing underground, earth cable 2x2x0.5 mm² supplied by HELUKABEL, part no. 804269, or earth cable 2x2x0.75 mm² supplied by Faber Kabel, part no. 101465, would be suitable.
Bus length
[m]
Resistance in terms
of length [mΩ/m]
Cross-section
[mm2]
0...40 70 0,25...0,34
40...300 < 60 0,34...0,60
300...600 < 40 0,50...0,60
600...1000 < 26 0,75...0,80
Cable cross-section
[mm2]
Maximum length [m]
n=32 n=63 0,25 200 170 0,50 360 310 0,75 550 470
Bus rate [kbit/s] Maximum permissible total bus length [m]
5 10.000 10 5.000 20 2.500 50 (standard) 1.000 125 400 250 200 500 100
Page 94
94
Wiring
A CAN BUS network should never have a star topology. Rather, the correct topology is a line from the
first device (with terminator) to the second, third and so forth. The last bus device has the termina-
tion jumper again.
Example: Connection of three network nodes (NWN) with a 2x2-pole cable and termination of the ter-
minal network nodes (network inside one building)
Each CAN network is to be provided with a 120 ohm BUS terminator at the first and last network sub-
scriber (= termination). This is achieved with a plug-in jumper at the back of the controller. Each CAN network therefore always has two terminators (one at each end). Branch cables or a star topology are not permissible for CAN wiring.
Page 95
95
CAN-Bus – Output values
The controller sends the same set of data to the CAN-Bus, in the form of analogue and digital values. If a value can‘t be sent (for example: value of an external sensor that isn‘t connected) the output will read zero.
1
Only relevant for data logging purposes – When regularly accessed via CAN-Bus, zero will be output.
Output Value
Analogue 1 Measurement sensor S1 Analogue 2 Measurement sensor S2 Analogue 3 Measurement sensor S3 Analogue 4 Measurement sensor S4 Analogue 5 Measurement sensor S5 Analogue 6 Measurement sensor S6 Analogue 7 Measurement external sensor 1 Analogue 8 Measurement external sensor 2 Analogue 9 Measurement external sensor 3 Analogue 10 Measurement external sensor 4 Analogue 11 Measurement external sensor 5 Analogue 12 Measurement external sensor 6 Analogue 13 Measurement external sensor 7 Analogue 14 Measurement external sensor 8 Analogue 15 Measurement external sensor 9 Analogue 16 Actuating variable sent to control output A4 Analogue 17 Actuating variable sent to control output A5 Analogue 18 Current yield of heat meter 1 Analogue 19
Meter reading of heat meter 1 (kWh)
1
Analogue 20 Current yield of heat meter 2 Analogue 21
Meter reading of heat meter 1 (kWh)
1
Analogue 22 Current yield of heat meter 3 Analogue 23
Meter reading of heat meter 1 (kWh)
1
Analogue 24 Status heating circuit control (only for heating circuit programs) Analogue 25 Set flow temperature (only for heating circuit programs) Analogue 26 Request set flow temperature (only for heating circuit programs) Analogue 27 Request DHW (only for heating circuit programs 896 and 912) Digital 1 Output status A1 Digital 2 Output status A2 Digital 3 Output status A3 Digital 4 Output status A4 Digital 5 Output status A5 Digital 6 Status function control Digital 7 Status frost protection
Page 96
96
Operation – Basics
Device overview
The display (1) on the front shows information about sensor measurements, menu position, parameters and such.
The bar (2) on the right side of the display moves along with the vertical position in the cur-
rently opened menu (= scroll bar).
The wheel (3) to the right of the menu serves to navigate through menus. Twisting it clock-
wise navigates downwards in a menu, twisting it counter-clockwise navigates upwards.
Pushing the wheel (3) down opens the currently selected menu/enables changing the cur-
rently selected value/parameter. (= Enter button) Pushing the button (4) left of the wheel leaves the current menu. (= Back button) Pushing the „Enter button“ (3) or the „Back button“ (4) is related to the value/menu point
that‘s framed. The three LEDs (5) above one another, on the right side of the display, are indicators for the
status of the outputs. A green LED indicates an active output. The single LED (6) between the display and the wheel indicates the status of the device and
the system. Green flashing indicates a booting up of the device. Constant green light indi­cates normal operation. Orange indicates a „Message“, e.g. an active excess collector tem-
perature limiter. Red indicates an „Error“ such as the loss of any signal from a DL-sensor. If
a message or error is present, the menu System status (bottom of the Overview) offers fur-
ther details. At a short push of the Reset button (7), the device reboots. To carry out a total reset of the
device, push the button until the status LED stops rapidly flashing orange and begins slowly flashing in red.
Page 97
97
Example of menu view
1 Title of the current menu 2 Sub-title (not selectable) 3 Scroll bar (indicates vertical menu position) 4 Selected menu point (framed)
Pushing down the wheel („Enter“) opens the following window to input/adjust values:
1 Chosen parameter 2 Range of adjustment 3 Chosen value (framed) 4 Confirm/cancel changes
Main menu
Overview
Measurements, system status etc.
Settings
Adjustments to regulation, display settings, data administration
User
Administrate users and their passwords
Version
Infos about your device
Overview
Time/date
Range: 00:00-24:00 Pushing the wheel activates adjustment of the hours. The frame
becomes thicker when selecting such a button. Confirm your ad-
justments by pushing the wheel (Enter) or by hitting the button (Back).
Same goes for the adjustment of the minutes.
Select the tick to confirm changes, select the cross to abort. The selected option is highlighted with a thicker frame. Pushing the back-button also aborts adjustments.
Page 98
98
Operation – General
Note: The abbreviation „FS“ as in „Factory settings“ is used frequently.
Display (under Settings)
Data admin (under Settings)
The „function data“ refers to a collection of data such as parameters, chosen program and such, not to actual programming like with freely programmable devices.
Display Timeout
Time after which the display‘s background lighting turns off if the device is idle. (FS = 30 seconds)
Contrast
Screen contrast in percent. (FS = 50.0%)
Function data
Load function data from the SD card
Save current function data to the SD card
Carry out total reset (device is reset to factory settings,
with the exception of CAN-Bus settings)
Name of the current function data loaded into the device (no data has been loaded in the example)
Firmware
Load Firmware from the SD card
Status
Status of the loading of function data
Restart your device (not a reset of settings)
Page 99
99
User
The 3 different user levels have different kinds of rights to access and modify data.
Version
*Keep this information at the ready when contacting technical support!
User level Rights
User
No password
Overview: Change time and date
View: Inputs, control outputs, system status, chosen pro-
gram, Adjust: Time programs
Settings:
Data admin: Load and save function data, view current func-
tion data, load Firmware, view system status
Display: All settings User: Change user level (with corresponding passwords)
Version: View version information, serial number, date of man-
ufacturer and internal ID
Technician
Standard password: 32
All rights of the User level, additionally: Settings: Access to the Technician level
Data admin: Carry out total reset and Restart User: Change Technician password, switch to User level, switch to Expert level (with password)
Expert
Standard password: 64
The Expert has access to all menu points and all settings.
Version* Firmware version of your device*
Serial number*
Date of manufacturer
Hardware (cover)
Rev Revision number
Current function
data
Name of the currently loaded function data, time and date of loading
Internal ID Used to access menus if the pass-
words have been forgotten.
Page 100
100
Operation – Differential control
Main Menu
This instruction manual shows menus with expert level access.
Overview
• Time/Date
• Inputs
• Status control output
• System status
• Chosen program
Settings
• Technician level (e.g. parameter menu)
• Expert level (basic system settings)
• Data admin
User
• Choice between user/technician/expert level
• Change passwords of the different user levels
Version
• See chapter Operation - General
Loading...