Technische Alternative UVR16x2***-D, UVR16x2 Programming Manual

Page 1
Freely programmable
universal controller
Programming Part 1: General information
Version V1.18 EN
en
Page 2
Page 3
Table of contents
Principles ................................................................................................................................ 5
Planning basics ............................................................................................................................... 6
Designations ................................................................................................................................... 6
General information on programming parameters ........................................................................... 8
Date / time / location .............................................................................................................. 9
Power reserve ............................................................................................................................... 10
Value summary .................................................................................................................... 11
Inputs .................................................................................................................................... 12
Programming the parameters ........................................................................................................ 13
Sensor type and measured variable .......................................................................................... 13
Designation ............................................................................................................................... 15
Sensor correction ...................................................................................................................... 15
Average .................................................................................................................................... 15
Sensor check for analogue sensors .......................................................................................... 16
Sensor error ......................................................................................................................... 16
Assignment of the possible sensor types to the inputs .............................................................. 17
Resistance table for various sensor types ................................................................................. 17
Outputs ................................................................................................................................. 18
Programming the parameters ........................................................................................................ 19
Output type ............................................................................................................................... 19
Designation ............................................................................................................................... 23
Overview of outputs .................................................................................................................. 23
Output meter ............................................................................................................................. 24
Display of links .............................................................................................................................. 26
Blocking protection ........................................................................................................................ 27
Display on screen .......................................................................................................................... 28
Fixed values ......................................................................................................................... 29
Programming the parameters ........................................................................................................ 30
Fixed value type ........................................................................................................................ 30
Digital ....................................................................................................................................... 30
Analogue .................................................................................................................................. 31
Pulse ........................................................................................................................................ 32
Function quantity .................................................................................................................. 32
Designation ............................................................................................................................... 32
Restriction of change authority .................................................................................................. 32
Messages .............................................................................................................................. 33
CAN bus ................................................................................................................................ 34
Datalogging ................................................................................................................................... 35
CAN settings ................................................................................................................................. 36
CAN analogue inputs .................................................................................................................... 37
Node number ............................................................................................................................ 37
Designation ............................................................................................................................... 38
CAN bus timeout ....................................................................................................................... 38
Sensor check ............................................................................................................................ 38
Measured variable .................................................................................................................... 38
Value at timeout ........................................................................................................................ 39
Sensor correction ...................................................................................................................... 39
Sensor error .............................................................................................................................. 39
CAN digital inputs .......................................................................................................................... 40
CAN analogue outputs .................................................................................................................. 40
Designation and transmission condition ................................ .................................................... 41
Transmission condition ......................................................................................................... 41
CAN digital outputs ........................................................................................................................ 42
Designation and transmission condition ................................ .................................................... 42
Page 4
Active CAN nodes ......................................................................................................................... 43
DL bus ................................................................................................................................... 44
DL settings .................................................................................................................................... 44
DL input ........................................................................................................................................ 45
DL bus address and DL bus index ............................................................................................ 45
Designation .............................................................................................................................. 46
DL bus timeout ......................................................................................................................... 46
Sensor check ........................................................................................................................... 46
Measured variable ................................................................................................ .................... 46
Value at timeout ....................................................................................................................... 46
Sensor correction ................................................................ ..................................................... 47
Sensor error ............................................................................................................................. 47
DL digital inputs ........................................................................................................................ 47
Bus load of DL sensors ................................................................................................................. 47
DL output ...................................................................................................................................... 48
Designation and destination address ........................................................................................ 49
General settings ................................................................................................................... 50
Language ................................................................................................................................ . 50
Brightness ................................................................................................................................ 50
Display timeout ......................................................................................................................... 50
Simulation ................................................................................................................................ 51
Currency .................................................................................................................................. 51
Access to menu ........................................................................................................................ 51
User defined designations ........................................................................................................ 52
User ....................................................................................................................................... 53
Current user .................................................................................................................................. 53
Changing the password ................................................................................................................ 53
Version and serial number .................................................................................................. 55
Data administration ............................................................................................................. 56
Function data ................................................................................................................................ 56
Load… ..................................................................................................................................... 57
Deleting, renaming and sending saved files ............................................................................. 58
Delete file............................................................................................................................. 58
Rename file ......................................................................................................................... 58
Send file to selected nodes .................................................................................................. 58
Save… ..................................................................................................................................... 59
Firmware Load… .......................................................................................................................... 60
Function overview Load…/Delete… .............................................................................................. 60
Status ........................................................................................................................................... 61
Total reset ..................................................................................................................................... 61
Restart .......................................................................................................................................... 62
Reset ............................................................................................................................................ 62
Loading the firmware with the factory settings ............................................................................... 62
Calibration .................................................................................................................................... 63
System values ...................................................................................................................... 64
Function overview ............................................................................................................... 66
LED indicator light ................................................................ ................................ ............... 67
Technical data UVR16x2 (Relay versions) ......................................................................... 68
Technical data UVR16x2…-D (Triac versions) ................................................................... 69
The functions are described in Part 2.
Page 5
Principles
5
Principles
This manual is designed as a guide to programming directly on the device, but also provides important information about the elements required for programming with the TAPPS 2 programming software (functions, inputs and outputs, etc.).
Programming with TAPPS 2 is always recommended. It enables the programmer to draw (= program) all program operations in the form of a graphical flow chart and to define parameters for them accordingly.
Nevertheless it is important to know how to use the "programming mechanisms" on the device itself in order to be able to make changes on site.
Example with TAPPS 2:
Page 6
Principles
6
Planning basics
To ensure efficient programming, the following order must be observed:
1
A prerequisite for programming and defining parameters is an accurate hydraulic scheme.
2
Using that scheme, you must define what should be controlled and how.
3
Based on the required control functions, you must define the sensor positions and draw them on the scheme.
4
In the next step, all sensors and outputs are assigned the required input and output numbers.
As all the sensor inputs and outputs have different characteristics, it is not possible to simply number them consecutively. The input and output numbers must therefore be assigned as instructed in this manual.
5
After that, the functions are selected and their parameters are programmed.
Designations
All elements can be designated by selecting a predefined designation from various designation groups or from the user defined designations.
You can also assign a number from 1 to 16 to every designation. In the "General settings" menu, all user defined designations from the technician or expert level
can be created, changed or deleted globally.
Displayed in Expert mode only
Displayed in Technician or Expert mode only
Page 7
Principles
7
View with designations defined previously
An alphanumeric keyboard is provided for changing a designation or creating a new one.
Up to 100 different designations can be defined by the user. The maximum number of characters per designation is 24.
Designations defined previously are available for all elements (inputs, outputs, functions, fixed values, bus inputs and outputs).
Page 8
Principles
8
General information on programming parameters
for inputs, outputs, fixed values, functions, default settings, and CAN and DL inputs and outputs.
Every entry must be finished by selecting .
If you want to discard your entries, select .
Example:
Entering numeric values
A keypad is displayed for entering numeric values. Example: Entering the temperature "T.room standard" in the "Heating circuit" function.
The current value is shown (example: 22.0 °C). The top line shows the entry range (example: 0.0 – 45.0 °C). You can make entries using either the correction keys (--, -, +, ++) or the numeric keys. The
correction keys "-" and "+" change the value of the first digit to the left of the decimal point; the keys "--" and "++" change the value of the second digit (the tens).
The arrow key shortens the value by one digit place; the key sets the value to zero.
Finish your entry with ; discard it with .
When in a submenu, select the button to return to the main menu.
Page 9
Date / time / location
9
Date / time / location
The "Date" and "Time" are shown in the status line at top right.
Tapping that status field takes you to the menu for the date, time and location details.
Example:
The system value parameters are displayed first.
Time zone – 01:00 means the time zone "UTC + 1 hour". UTC stands for "Universal Time
Coordinated", also known as GMT (= Greenwich Mean Time). Summertime – "Yes" if summertime is active. Automatic time change – If "Yes", the time will switch over automatically to summertime
according to the specifications of the European Union. Date – The current date (dd.mm.yy). Time – The current time
Page 10
Date / time / location
10
GPS latitude – Geographical latitude according to GPS (= global positioning system) GPS longitude – Geographical longitude according to GPS
The values for geographical latitude and longitude are used to determine the location-specific solar data. That data can be used in functions (e.g. shading function).
The factory default settings for the GPS data are for the location of Technische Alternative in Amaliendorf, Austria.
Next, the location-specific solar data is displayed.
Example:
Sunrise – Time Sunset – Time Solar altitude – Specified in ° as measured from the geometric horizon (0°),
zenith = 90°
Direction of the sun – Specified in ° as measured from the north (0°)
North = 0° East = 90° South = 180° West = 270°
Power reserve
In the event of power failure, the controller has a power reserve for about 3 days for the time and date.
Page 11
Summary of values
11
Value summary
This menu item shows the current values for inputs 1 – 16, the DL inputs and the analogue and digital CAN inputs.
The various values are displayed by tapping the group required.
Example: Inputs
Page 12
Inputs
12
Inputs
The controller has 16 inputs for analogue signals (measurements), digital signals (ON/OFF) or pulses.
When this item is selected in the main menu, the inputs are displayed together with their designation and their current measurement or status.
Example of a programmed system; input 1 is still unused:
Page 13
Inputs
13
Programming the parameters
Sensor type and measured variable
Once the required input is selected, the sensor type can be defined.
First, you must specify the basic type of input signal.
Digital Analogue Pulse
Digital
Select the measured variable:
Off / On No / Yes
Off / On (inverse) No / Yes (inverse)
Analogue
Select the measured variable:
Temperature
Select the sensor type: KTY (2 kΩ = formerly Technische Alternative's standard type),
PT 1000 (= current standard type), room sensors: RAS, RASPT, THEL thermocouple,
KTY (1 kΩ), PT 100, PT 500, Ni1000, Ni1000 TK5000
Solar radiation (sensor type: GBS01) Voltage (inputs 1-6 and 9-16: max. 3.3 V, inputs 7 and 8: max. 10V) Current (input 8 only: 4-20mA DC) Resistance Humidity (sensor type: RFS) Rain (sensor type: RES)
Also select the process variable for the measured variables Voltage, Current (input 8 only), Resistance:
Dimensionless Dimensionless (.1) Performance factor Dimensionless (.5) Temperature °C Global radiation Percent Absolute humidity
Pressure bar, mbar,
Pascal Litre Cubic metre Flow rate (l/min, l/h,
l/d, m³/min, m³/h,
m³/d)
Output
Voltage Amperage mA Amperage A Resistance Speed km/h Speed m/s Degree (angle)
Then you must use scaling to define the value range. Example Voltage/Global radiation:
0.00 V equates to 0 W/m², 10.00 V yields 1500 W/m².
Page 14
Inputs
14
Pulse input
Inputs 15 and 16 can capture pulses with max. 20 Hz and a pulse duration of at least 25 ms (S0 pulses).
Inputs 1 14 can capture pulses with max. 10 Hz and a pulse duration of at least 50 ms.
Select the measured variable
Wind speed A quotient must be entered for the "Wind speed" measured variable. This is the signal frequency at 1 km/h.
Example: The WIS01 wind sensor issues one pulse (=1Hz) per second at a wind speed of 20 km/h.
Therefore the frequency at 1 km/h equals 0.05 Hz.
Setting range: 0.01 – 1.00 Hz
Flow rate
A quotient must be entered for the "Flow rate" measured variable. This is the flow rate in litres per pulse.
Setting range: 0.1 – 100.0 l/pulse
Pulse
This measured variable is used as the input variable for the "Meter/Counter" function, as a pulse counter with "Pulses" as its unit.
User defined
For the "User defined" measured variable, both the quotient and the unit must be entered.
Setting range for quotient: 0.00001 – 1000.00000 units/pulse (5 decimal places) Units: l, kW, km, m, mm, m³. For l, mm and m³ the unit of time must be selected as well. For km and m the units of time are
predefined and cannot be changed. Example: For the "Energy meter" function, the unit "kW" can be used. In the example above,
0.00125 kWh/pulse was selected, which equates to 800 pulses /kWh.
Page 15
Inputs
15
Designation
Enter the input designation by selecting a predefined designation from various designation groups or from the user defined designations.
Sensor type Analogue / Temperature:
General Generator Consumer Line Climate User (user defined designations)
You can also assign a number from 1 to 16 to every designation.
Sensor correction
The option of sensor correction is available for the measured variables Temperature, Solar radiation, Humidity and Rain. The corrected value is utilised for all calculations and displays.
Example: Pt1000 temperature sensor
Average
This setting refers to the average of the measurements over time. Averaging over 0.3 seconds leads to extremely rapid reactions on the part of the display and the unit.
However, this can be expected to cause fluctuations of the value. A large average value leads to inertia and is only recommended for sensors for the heat meter. For simple measuring tasks, around 1 - 3 seconds should be selected. For hygienic domestic hot
water heating with the ultra-fast sensor, 0.3 - 0.5 seconds should be selected.
Page 16
Inputs
16
Sensor check for analogue sensors
When "Sensor check" is active (setting: "Yes"), a short circuit or a lead break will automatically generate an error message: A warning symbol is displayed in the upper status line, and the defective sensor is shown with a red border around it in the "Inputs" menu.
Example:
Sensor error
When "Sensor check" is active, Sensor error is available as an input variable for functions: status "No" for a sensor that is working correctly and "Yes" for a defect (short circuit or lead break). This allows the controller to react to the failure of a sensor, for example.
In System values / General, a sensor error for all inputs is available. If the Standard thresholds are selected, a short circuit will be indicated if the value falls below the
lower measurement limit and a lead break will be indicated if the value exceeds the upper measurement limit.
The Standard values for temperature sensors are -9999.9 °C for a short circuit and 9999.9 °C for a lead break. Those values are utilised in the internal calculations in the event of an error.
By selecting the thresholds and values appropriately, a fixed value can be specified for the controller in the event of sensor failure, in order to allow a function to continue operating in emergency mode.
Example: If the temperature value falls below the threshold of -40 °C (= "Threshold value"), a value of
0.0 °C (= "Output value") is issued and displayed for that sensor (fixed hysteresis: 1.0 °C). At the same time the "Sensor error’ status is set to "Yes".
The short circuit threshold must be defined below the lead break threshold.
Example: Sensor 12 has fallen below
-40 °C, so 0 °C is issued as the measurement, and a sensor error is displayed at the same time.
Short-circuit of sensor 1 Standard value
Page 17
Inputs
17
Assignment of the possible sensor types to the inputs
PT1000, KTY (2 kΩ),
KTY (1 kΩ), PT100,
PT500, Ni1000, Ni1000
TK5000
Digital
(ON/OFF)
THEL, GBS01, RFS,
RES01
Voltage
0 – 3.3 V DC
Voltage
0 – 10V DC
Current
4 – 20 mA
Resistance
1 – 100 kΩ
Pulses
max 10 Hz
Pulses (S0)
max. 20 Hz
Inputs
1 - 6
x x x x x x
Input 7
x x x x x x x
Input 8
x x x x x x x x
Inputs
9 - 14
x x x x x x
Input 15
x x x x x x x
Input 16
x x x x x x x
In the case of voltage measurements on inputs 1-6 and 9-16 (max. 3.3V), note that the internal resistance of the voltage source must not exceed 100 ohms otherwise the accuracy will be less than that specified in the technical data.
Voltage measurements on inputs 7 and 8: The controller's input impedance is 30 kΩ. Make sure that the voltage never exceeds 10.5 V as this would have an extremely negative effect on the other inputs.
Resistance measurement: If the process variable is set to "Dimensionless", measurement is only possible up to 30 kΩ. If the process variable is set to "Resistance" and the resistances being measured are >15 kΩ, the averaging time should be increased as the values will fluctuate slightly.
Resistance table for various sensor types
Temp. [°C]
0
10
20
25
30
40
50
60
70
80
90
100
PT1000 [Ω]
1000
1039
1078
1097
1117
1155
1194
1232
1271
1309
1347
1385
KTY [Ω] (2 kΩ)
1630
1772
1922
2000
2080
2245
2417
2597
2785
2980
3182
3392
KTY [Ω] (1 kΩ)
815
886
961
1000
1040
1122
1209
1299
1392
1490
1591
1696
PT100 [Ω]
100
104
108
110
112
116
119
123
127
131
135
139
PT500 [Ω]
500
520
539
549
558
578
597
616
635
654
674
693
Ni1000 [Ω]
1000
1056
1112
1141
1171
1230
1291
1353
1417
1483
1549
1618
Ni1000 [Ω] TK5000
1000
1045
1091
1114
1138
1186
1235
1285
1337
1390
1444
1500
The standard type used by Technische Alternative is PT1000.
KTY (2 kΩ) was the factory-fitted standard type until 2010/2011. PT100, PT500: As these sensors are more susceptible to external interference, their sensor leads
must be screened and the Average time should be increased. Nevertheless the accuracy specified in the technical data for PT1000 sensors cannot be guaranteed.
Page 18
Outputs
18
Outputs
The controller has 16 outputs.
Tapping the outputs display in the upper status line takes you to the "Outputs" menu. Undefined outputs are hidden.
When selected, the outputs are displayed together with their designation and their current status (see chapter "Display on screen").
Example:
Page 19
Outputs
19
Programming the parameters
Once the required output is selected, the output type can be defined.
First, you must specify the basic output type.
Output type
The following different output types exist, although they are not available for selection for all outputs:
Switching output Output pair 0 - 10 V PWM
Outputs 1/2, 3/4, 6/7, 8/9, 10/11, 12/13 and 14/15 as an output pair
These outputs can be used as single switching outputs or as an output pair together with the following switching output (e.g. to control a mixer drive).
Caution The output pairs 1/2 and 6/7 must only be used in the relay version of the UVR16x2.
The output pairs 1/2, 3/4, 6/7, 8/9 and 10/11 are available as standard. The output pairs 12/13 and 14/15 require the use of auxiliary relays (relay modules).
The mixer runtime must be entered for every output pair.
If a mixer runtime of 0 is entered, the output pair will not be utilised.
Output pairs are shown in the status line with a "+" between the output numbers. Example: Outputs 8+9 and 10+11 have been programmed as output pairs
If two different functions act on the two outputs in the output pair simultaneously, the output with the lower number ("OPEN" command) will be activated.
Exception: the "Message" function – if the simultaneous command comes from this function, the output with the higher number ("CLOSE" command) will be activated.
Page 20
Outputs
20
All switching outputs
A start delay and a run-on time can be defined for all switching outputs.
All outputs
Manual mode can be restricted to certain user groups (User, Technician, Expert) for all outputs.
Outputs 12 to 16 as analogue outputs
These outputs provide a voltage between 0 and 10 V, e.g. for output-dependent control of burners (burner modulation) or speed control of electronic pumps.
The output can be issued either as a voltage (0 10 V) or as a PWM signal. They can be controlled by the PID function, or by other functions. The "Scaling" provides the option
of matching the analogue value of the source (with or without decimal place) to the control range of the device being controlled.
In PWM (pulse width modulation) mode, a square wave signal is created with a voltage level of about
10 V and a frequency of 1 kHz with a variable duty factor (0 - 100 %). If multiple functions (analogue values) act simultaneously on one analogue output, the higher
value is output.
For cases where an analogue output is activated by a digital command, an output voltage of 0.00 V and 10.00 V (or 0.0 % – 100.0 % for PWM) can be defined. Digital commands are dominant over links with an analogue value.
The activation of the analogue output via "Dominant off" and "Digital on" is possible by means of the following digital signals:
Example: Output value 5.00 V
Example: Output value 10.00 V
Dominant off (from messages)
Dominant on (from messages)
Manual Off
Manual On
Digital on
Anti-blocking protection
Page 21
Outputs
21
Output status of the analogue outputs
For the output status you can define whether the ON status should be issued above or below an adjustable threshold.
Example: If the analogue output is over 3.00 V, the output status switches from OFF to ON.
Depending on the technical attributes of the pump being controlled, it may thus be possible to set the output status to be ON only when the pump is actually running.
If you want an analogue output (A12 – A16) to be switched together with a switching output, it can only be done by means of appropriate programming.
Example: As soon as the output status of the analogue output switches to ON, that ON command is forwarded to the switching output via the logic function.
analogue output
switching output
Page 22
Outputs
22
Display in the Outputs menu
The display in the menu shows the operating state of the analogue output. The output status can be changed by selecting it.
Auto: Output issued according to the
source and scaling
Manual: Adjustable value Manual/OFF: Output issued according
to "Dominant off" setting
Manual/ON: Output issued according to "Digital on" setting
Examples of different scalings Correcting variable of PID function: Mode 0-10 V, correcting variable 0 should correspond to 0 V,
correcting variable 100 should correspond to 10 V:
Temperature value, e.g. from an analogue function: Mode PWM, the temperature 0 °C should correspond to 0 %, 100.0 °C should correspond to 100 %:
The temperature is transferred in 1/10 °C without the decimal point.
Burner output, e.g. from the functions DHW demand or Maintenance: Mode 0-10 V, burner output of
0.0 % should correspond to 0 V, 100.0 % should correspond to 10 V: The percentage is transferred in 1/10 % without the decimal point.
Page 23
Outputs
23
Designation
Enter the output designation by selecting a predefined designation from various designation groups or from the user defined designations.
General Climate User (user defined designations)
You can also assign a number from 1 to 16 to every designation.
Overview of outputs
Switching output
Triac
Switching output
N/O relay
Switching output
N/O + N/C relay Switching output
Potential-free
N/O + N/C relay
Output pair for
mixer, etc.
0-10 V or PWM
Output 1
x x
2
x x
3
x x
4
x x
5
x
6
x x
7
x x
8
x x
9
x x
10
x x
11
x x
12
x x
x
13
x x
x
14
x x
x
15
x x
x
16
x
x
Switching outputs and
output pairs 12 – 16 only possible with additional PCBs
Output pairs
1/2 and 6/7
only possible for relay
versions
Page 24
Outputs
24
Output meter
Selecting this icon allows you to see the hours run and pulses (times switched on) for every output.
Example: For output 1, the meter reading since 01/01/2014 can be viewed.
If you tap the button, you will be asked whether you want to delete the total meter readings and the "Previous day" readings for the hours run meter and the pulse counter. The "Today" and "Last run" and "Current run" readings will not be deleted.
Answer by tapping either the tick (= Yes) or the cross (= No). After the deletion, the current date will be displayed.
The meter shows the total hours run, the hours run the previous day and today, and the previous runtime and the current runtime.
If you tap the button, you will be asked whether you want to delete the hours run counted today. This will not delete the "Last run" and "Current run".
Page 25
Outputs
25
Below the hours run, the pulses (how many times switched on) can be viewed.
The meter shows the total number of pulses (times switched on), the number of pulses on the previous day and the number today.
If you tap the button, you will be asked whether you want to delete the pulses counted today.
CAUTION: The meter readings are saved to the internal memory every hour. Therefore, in the
event of a power failure, no more than 1 hour of metering can be lost.
When loading function data, you will be asked whether you want to apply the saved meter
readings (see manual "Programming Part 1: General information").
Meter reset
If you tap a "Delete" button, you will be asked whether you want to delete the total meter readings or today's meter reading.
Answer the confirmation prompt by tapping either the tick (= Yes) or the cross (= No). After the deletion of the total meter readings, the current date will be displayed.
Page 26
Outputs
26
Display of links
When you select this icon, the output's links to the functions will be displayed.
Example:
In this example, output 1 is controlled by two functions, and it has just been switched on by function 29 (Solar1).
Tapping a function takes you directly to the menu for that function.
Page 27
Outputs
27
Blocking protection
Circulating pumps which do not run for a long period (e.g. heating circuit pump during the summer) often encounter start-up problems as a result of corrosion. This problem can be avoided by starting the pump periodically for 30 seconds.
The Blocking protection menu item added after output 16 allows you to specify a time and all the outputs to receive blocking protection.
Example:
The outputs selected in the Output assignment will be switched on for 30 seconds on Tuesday and Friday at 4:30 p.m. if the output has not been active since the last controller start or since blocking protection was last initiated.
The outputs 3, 4, 6 and 7 were selected.
The controller does not switch on all the outputs at the same time, but instead begins with one output, switches to the next after 30 seconds, and so on.
Page 28
Outputs
28
Display on screen
Example of a system already programmed:
The switched-on outputs are highlighted in green. Outputs in manual mode are marked with a hand symbol under the output number.
Example: Outputs switched dominant (by the "Message" function):
Outputs 1, 4 and 5 are
switched on
Outputs 3 and 4 are
in manual mode
Output 2 has been
switched to dominant on
(red border)
Output 5 has been
switched to dominant
off (red border)
Indicates that a
message is active.
Page 29
Fixed values
29
Fixed values
In this menu you can define up to 64 fixed values, which can be used as input variables for functions, for example.
When this item is selected in the main menu, the fixed values already defined are displayed together with their designation and their current value or status.
Example:
Page 30
Fixed values
30
Programming the parameters
Example: Fixed value 1
Fixed value type
Once the required fixed value is selected, the fixed value type can be defined.
Digital Analogue Pulse
Digital
Select the measured variable:
Off / On No / Yes
Select whether the status can be changed via a selection box or simply by a click.
Changing a digital fixed value
Tapping a button with a light background allows you to change the fixed value either via a selection box or by tapping ("Click"). If the status does not appear on a light background, that status cannot be
changed from the logged-in user level. Example: Changeover from ON to OFF via a selection box
Page 31
Fixed values
31
Analogue
Select from a wide range of units and dimensions
After assigning the designation, you must define the permitted limits and the current fixed value. The value can be adjusted in the menu within those limits.
Example:
Changing an analogue fixed value
Tapping a button with a light background allows you to change the fixed value via a keypad. If the value does not appear on a light background, that status cannot be changed from the logged-in user level.
Example:
Page 32
Fixed values
32
Pulse
A fixed value of this type allows short pulses to be generated by tapping it in the menu “Fixed values”.
Example:
A pulse can also be triggered in the menu of the fixed value by tapping.
Function quantity
Select the function quantity: When activated, either an ON pulse (from OFF to ON) or an OFF pulse (from ON to OFF) will be generated, depending on the selection made here.
Designation
Enter the fixed value designation by selecting a predefined designation or one of the user defined designations.
You can also assign a number from 1 to 16 to every designation.
Restriction of change authority
For all fixed values, you can set the user level from which the fixed value can be changed:
Page 33
Messages
33
Messages
This menu item displays activated messages.
Example: Message 21 is active.
If there is at least one active message, a warning symbol will appear in the upper status line. If the message has been hidden, the pop-up window for the message can be displayed by tapping the
warning symbol.
More detailed information about the messages is provided in the manual Programming / Part 2: Functions, Message chapter".
Page 34
CAN bus
34
CAN bus
The CAN network allows communication between CAN bus devices. When analogue or digital values are sent via CAN outputs, other CAN bus devices can utilise those values as CAN inputs.
This menu contains all of the information and settings needed to set up a CANopen network. Up to 62 CAN bus devices can be operated in one network.
Every CAN bus device must be given its own node number in the network. The cable topology of a CAN bus network is described in the installation instructions.
Page 35
CAN bus
35
Datalogging
This menu is not visible in the User mode.
This menu is used to define the parameters for CAN datalogging of analogue and digital values.
CAN datalogging requires at least version 1.13 on the C.M.I. datalogger.
CAN datalogging is only possible with the C.M.I. datalogger. In contrast to data recording via the DL bus, the data to be logged via the CAN-bus can be freely selected. There is no constant data output. When requested by a C.M.I., the controller saves the current values to a logging buffer and locks it to prevent it from being overwritten (when requests are received from another C.M.I.) until the data is read out and the logging buffer has been enabled again.
The settings required on the C.M.I. for datalogging via CAN bus are described in the C.M.I.'s online help.
Digital and analogue values – Each controller has 2 data records that it can use to output up to 26 digital values and 32 analogue values, which are defined in the "CAN bus/Datalogging" menu of the UVR 16x2. The sources for the logged values can be inputs, outputs, function output variables, fixed values, system values, and DL and CAN bus inputs. Each data record comprises 16 analogue and 13 digital values as well as 2 heat meters:
Digital
Analogue
Heat meters
Data record 1
1 – 13
1 – 16
1 – 2
Data record 2
14 – 26
17 – 32
3 – 4
If, for example, a digital value is to be stored in data record 2, then it must be defined as digital value 14 or higher.
Digital inputs must be defined in the range of digital values.
Heat meters
Up to 4 heat meters can be logged per controller. The "output" and "total meter reading" output variables of the heat meters are automatically
included in the data record according to their function number (heat meters 1 and 2 in data record 1, heat meters 3 and 4 in data record 2).
N.B.: When the datalogger configuration is loaded into the Winsol setup (2nd page), the UVR16x2 controller will appear as "UVR1611".
Page 36
CAN bus
36
CAN settings
Node
Define a unique CAN node number for the device (setting range: 1 – 62). The device with node number 1 provides the time stamp for all other CAN bus devices.
Designation
Every controller can be given its own designation.
Bus rate
The standard bus rate of the CAN network is 50 kbit/s (50 kBd), which is specified for most CAN bus devices.
Important: All devices in the CAN bus network must have the same transfer rate in order to
be able to communicate with each other.
The bus rate can be set to between 5 and 500 kbit/s, with lower bus rates allowing longer cable networks.
Bus rate [kbit/s]
Maximum permissible total bus length [m]
5
10000
10
5000
20
2500
50 (standard)
1000
125
400
250
200
500
100
In the event of a total reset from the "Data admin" menu, the settings for the node number and bus rate are retained.
Page 37
CAN bus
37
CAN analogue inputs
Up to 64 CAN analogue inputs can be programmed. They are defined by specifying the transmission node number and the number of the transmission node's CAN output.
Node number
After the node number of the transmission node is entered, the other settings can be specified. The number of a CAN analogue output is taken from the device with that node number and applied here.
Example: On CAN analogue input 1, the output number applied is that of CAN analogue output 1 from the device with node number 2.
Page 38
CAN bus
38
Designation
Every CAN input can be given its own designation. The designation can be selected from various designation groups or can be user defined, as for the other controller inputs.
Example:
CAN bus timeout
Define the timeout time for the CAN input (minimum value: 5 minutes).
As long as the information continues to be read from the CAN bus, the network error for the CAN input will be "No".
If the value has not been updated for longer than the set timeout, the network error changes from "No" to "Yes". You can then define whether the controller should issue the last value transmitted or a definable substitute value (only when the measured variable is set to User).
The network error can be selected as the source of a function input variable, which allows the controller to react appropriately to a failure of the CAN bus or transmission node.
In System values / General, a network error for all CAN inputs is available.
Sensor check
If you set "Sensor check" to "Yes", the sensor error of the sensor supplying the CAN input is available as an input variable for a function.
Measured variable
If "Measured variable" is set to "Automatic", the unit of measurement specified by the transmission node will be applied in the controller.
If you select "User", you can select a unit of your own, a sensor correction and, if sensor check is active, a monitoring function.
Every CAN input is assigned its own unit, which can differ from the unit used by the transmission node. A range of units is available to choose from.
This setting is only displayed if "Measured variable" is set to "User".
Page 39
CAN bus
39
Value at timeout
This setting is only displayed if "Measured variable" is set to "User". If the timeout time is exceeded, you can define here whether the controller should issue the last value
transmitted ("Unchanged") or a definable substitute value.
Sensor correction
This setting is only displayed if "Measured variable" is set to "User". The value of the CAN input can be corrected by applying a fixed value.
Sensor error
This setting is only displayed if sensor check is active and "Measured variable" is set to "User". When "Sensor check" is active, the sensor error of a CAN input is available as an input variable for
functions: status "No" for a sensor that is working correctly and "Yes" for a defect (short circuit or lead break). This allows the controller to react to the failure of a sensor, for example.
If the Standard thresholds are selected, a short circuit will be indicated if the value falls below the measurement limit and a lead break will be indicated if the value exceeds the measurement limit.
The Standard values for temperature sensors are -9999.9 °C for a short circuit and 9999.9 °C for a lead break. Those values are utilised in the internal calculations in the event of an error.
By selecting the thresholds and values for short circuit and lead break appropriately, a fixed value can be specified for the controller in the event of sensor failure at the transmission node, in order to allow a function to continue operating in emergency mode (fixed hysteresis: 1.0 °C).
The short circuit threshold must be defined below the lead break threshold. In System values / General, a sensor error for all inputs, CAN inputs and DL inputs is available.
Page 40
CAN bus
40
CAN digital inputs
Up to 64 CAN digital inputs can be programmed. They are defined by specifying the transmission node number and the number of the transmission node's CAN output.
Their parameters are programmed in almost exactly the same way as for the CAN analogue inputs. Under Measured variable / User the Display for the CAN digital input can be changed from Off / On
to No / Yes and you can define whether the controller should issue the last status transmitted ("Unchanged") or a definable substitute status when the timeout time is exceeded.
CAN analogue outputs
Up to 32 CAN analogue outputs can be programmed. They are defined by specifying the source in the controller.
Specify the source in the controller which supplies the value for the CAN output.
Inputs Outputs Functions
Fixed values System values DL bus
Example: Source, Input 1
Page 41
CAN bus
41
Designation and transmission condition
Every CAN analogue output can be given its own designation. The designation can be selected from various designation groups or can be user defined, as for the inputs.
Example:
Transmission condition
Example:
If change > 1.0 K
If the current value has changed by more than 1.0 K compared to the last transmitted value, a new transmission is made. The unit used by the source is applied to the output value (minimum setting: 0.1 K).
Blocking time 10 s
If the value changes by more than 1.0 K within 10 seconds of the last transmission, the value is nevertheless only transmitted again after 10 seconds (minimum setting: 1 sec.).
Interval time 5 m
The value is transmitted every 5 minutes even if it has not changed by more than 1.0 K since the last transmission (minimum setting: 1 minute).
Page 42
CAN bus
42
CAN digital outputs
Up to 32 CAN digital outputs can be programmed. They are defined by specifying the source in the controller.
Their parameters are programmed in exactly the same way as for the CAN analogue outputs except for the transmission conditions.
Designation and transmission condition
Every CAN digital output can be given its own designation. The designation can be selected from various designation groups or can be user defined, as for the inputs.
Example:
Transmission condition
Example:
If change Yes/No
Transmission of the value if a status change occurs
Blocking time 10 s
If the value changes within 10 seconds of the last transmission, the value is nevertheless only transmitted again after 10 seconds (minimum setting: 1 sec.).
Interval time 5 m
The value is transmitted every 5 minutes even if it has not changed since the last transmission (minimum setting: 1 minute).
Page 43
CAN bus
43
Active CAN nodes
Tapping the button displays the active CAN nodes in the CAN bus network. "Status" displays the controller's CAN bus status. Following a controller start the status changes automatically, according to a predefined process, from init. preop(erational) operat(ional). Only then is it possible to communicate with other CAN bus devices.
This view shows an RSM610 with node number 32 in the CAN bus network. Tapping a CAN bus device of the X2 series takes you to the menu of the device. Other CAN bus devices and the C.M.I. will be displayed, but it is not possible to access their menus. To return to the menu of your own controller, tap the controller in this overview.
Updating the view
Page 44
DL bus
44
DL bus
The DL bus acts as a bus cable for various sensors and/or for datalogging by C.M.I. or D-LOGG. The DL bus is a bidirectional data link and is only compatible with products from Technische
Alternative. The DL bus network operates independently of the CAN bus network. This menu contains all of the information and settings needed to set up a DL bus network.
The cable topology of a DL bus network is described in the controller's installation instructions.
DL settings
You can use this button to activate or deactivate data output for datalogging via the DL bus and for display on the RAS-PLUS room sensor. The C.M.I. can be used for DL datalogging. Only the input and output values and the 2 heat meters are included in the data output; the values of the
network inputs are not included.
Page 45
DL bus
45
DL input
Sensor values from DL bus sensors are transferred via a DL input. Up to 32 DL inputs can be programmed.
Example: Programming the parameters of DL input 1
Select: Analogue or digital
DL bus address and DL bus index
Every DL sensor must have its own DL bus address. Setting the address of a DL sensor is described in the sensor's datasheet.
Most DL sensors can measure various different values (e.g. flow rate and temperatures). Every value measured must be given its own index number. The applicable index number can be found in the DL sensor's datasheet.
Page 46
DL bus
46
Designation
Every DL input can be given its own designation. The designation can be selected from various designation groups or can be user defined, as for the other controller inputs.
Example:
DL bus timeout
As long as the information continues to be read from the DL bus, the network error for the DL input will be "No".
If the controller scans the DL sensor value three times and no value is transmitted, the network error changes from "No" to "Yes". You can then define whether the controller should issue the last value transmitted or a definable substitute value (only when the measured variable is set to User).
The network error can also be selected as the source of a function input variable, which allows the controller to react appropriately to a failure of the DL bus or DL sensor.
In System values / General, a network error for all DL inputs is available.
Sensor check
If you set "Sensor check" to "Yes", the sensor error of the sensor supplying the DL input is
available as an input variable for a function.
Measured variable
If "Measured variable" is set to "Automatic", the unit of measurement specified by the DL sensor will be applied in the controller.
If you select "User", you can select a unit of your own, a sensor correction and, if sensor check is active, a monitoring function.
Every DL input is assigned a unit, which can differ from the unit used by the DL sensor. A wide range of units is available to choose from.
This setting is only displayed if "Measured variable" is set to "User".
Value at timeout
This setting is only displayed if "Measured variable" is set to "User". If a timeout is set, you can define here whether the controller should issue the last value transmitted
("Unchanged") or a definable substitute value.
Page 47
DL bus
47
Sensor correction
This setting is only displayed if "Measured variable" is set to "User". The value of the DL input can be corrected by applying a fixed differential value.
Sensor error
This setting is only displayed if sensor check is active and "Measured variable" is set to "User". When "Sensor check" is active, the sensor error of a DL input is available as an input variable for
functions: status "No" for a sensor that is working correctly and "Yes" for a defect (short circuit or lead break). This allows the controller to react to the failure of a sensor, for example.
If the Standard thresholds are selected, a short circuit will be indicated if the value falls below the measurement limit and a lead break will be indicated if the value exceeds the measurement limit.
The Standard values for temperature sensors are -9999.9 °C for a short circuit and 9999.9 °C for a lead break. Those values are utilised in the internal calculations in the event of an error.
By selecting the thresholds and values for short circuit and lead break appropriately, a fixed value can be specified for the controller in the event of sensor failure at the transmission node, in order to allow a function to continue operating in emergency mode (fixed hysteresis: 1.0 °C).
The short circuit threshold must be defined below the lead break threshold. In System values / General, a sensor error for all inputs, CAN inputs and DL inputs is available.
DL digital inputs
The DL bus is configured for the transfer of digital values as well as analogue. However, there is not yet any use for this at present.
The parameters are programmed in almost exactly the same way as for the DL analogue inputs. Under Measured variable / User the Display for the DL digital input can be changed to No / Yes.
Bus load of DL sensors
A 2-pole cable provides both the power supply and the signal transfer for DL sensors. An additional power supply by means of an external power supply unit (such as with the CAN bus) is not possible.
As the DL sensors have a relatively high power demand, the "bus load" must be considered: The UVR16x2 controller supplies 100 % of the bus load. The bus loads of the DL sensors are listed in
the technical data of each DL sensor. Example: The DL sensor FTS4-50DL has a bus load of 25 %. Consequently up to four FTS4-50DL
sensors can be connected to the DL bus.
Page 48
DL bus
48
DL output
Analogue and digital values can be transmitted to the DL bus network via a DL output. For example, a
digital command to activate an O2-DL O2 sensor can be output. Example: Programming the parameters of DL output 1
Specify the source in the controller which supplies the value for the DL output.
Inputs Outputs Functions Fixed values System values CAN bus analogue CAN bus digital
Example: Digital value; source: the result of a logic function
Page 49
DL bus
49
Designation and destination address
Specify the designation and the destination address of the DL sensor to be activated. Provision has been made for the specification of an index number, but there is not yet any DL bus
device which requires that specification. For the activation of the O2 sensor, the index therefore has no effect and can be ignored. Examples:
Page 50
General settings
50
General settings
Displayed in Expert mode only
This menu allows settings to be made which then take effect for all other menus and displays.
Language
Select the display language
Brightness
Select the brightness of the display to match the surroundings (setting range: 5.0 100.0 %
Display timeout
The display will be switched off if the user does not do anything for the period of time set here. Tapping the touchscreen surface re-activates the display (setting range: 5 seconds to 30 minutes)
Displayed in Technician or Expert mode only
Page 51
General settings
51
Simulation
Option of activating the simulation mode (only possible in Expert mode):
No averaging of the outside temperature in heating circuit control. All temperature inputs are measured as PT1000 sensors, even if a different sensor type is
defined.
The RAS features of room sensors are ignored.
Select from: OFF
Analogue Simulation with the EWS16x2 development set CAN SIM board – Simulation with SIM-BOARD-USB-UVR16x2 for
simulation in a system
The simulation mode is ended automatically when you exit the Expert level.
Currency
Select the currency for yield metering
Access to menu
Definition of the user levels from which access to the main menu is permitted.
If only technicians or experts are permitted to access the menu, then the relevant password must
be entered when selecting the main menu from the start page of the function overview ( button). When the controller is restarted, either the function overview (if loaded) or, in the case of restricted
access, the keyboard for the password is displayed.
Page 52
General settings
52
User defined designations
In this menu, you can enter, change or delete user defined designations for all elements of the controller. This menu can only be selected from within the Technician or Expert level.
View with designations defined previously
An alphanumeric keyboard is provided for changing a designation or creating a new one.
Up to 100 different designations can be defined by the user. The maximum number of characters per designation is 24.
Designations defined previously are available for all elements (inputs, outputs, functions, fixed values, bus inputs and outputs).
Page 53
User
53
User
Current user
Select whether the user is an Expert, Technician or User. To enter the Technician or Expert level a password must be entered, which can be set by the
programmer.
When function data is loaded from the Expert or Technician level, the controller returns to the User level and applies the programmed passwords.
When the controller is started, the controller is always in the User level.
Changing the password
An Expert can change the passwords for Technician and Expert. A Technician can only change the Technician password.
There are no restrictions regarding the length of the password or the type of characters that can be used.
To change a password, you must first enter the old password.
Page 54
User
54
List of permitted actions
User
Displays and permitted actions
User
Function overview with options for control Access to main menu only if enabled for "User" in the "General settings" Summary of values Inputs: display only, no access to the parameters Outputs: changes to the output status of the outputs enabled for User, display
of hours run, no access to the parameters
Fixed values: changes to the value or status of the fixed values enabled for
User, no access to the parameters Functions: display of the function status, no access to the parameters Messages: display of active messages, hiding and deleting messages CAN and DL bus: no access to the parameters Default settings: language, brightness and display timeout can be altered User: change of user (with password entry) System values: setting the date, time, location data, display of System values
Technician
All of the above plus:
Access to main menu only if enabled for Technician or User in the "General
settings" Changes to the parameters for inputs (except for type and measured variable),
no creation of new ones Changes to the parameters for outputs (except for type; status only if enabled
for User or Technician), no creation of new ones Changes to the parameters for fixed values (except for type and measured
variable; value and status only if enabled for User or Technician), no creation of
new ones Changes to user defined designations and creation of new ones Functions: changes to user defined input variables and parameters; output
variables are visible All settings in the CAN and DL bus menus Data administration actions
Expert
All actions and all displays are accessible.
Automatic changeover
Normally the controller will change over automatically from the Expert or Technician mode back to the User mode 30 minutes after the last operating action.
For programming or test purposes, this automatic changeover can be switched off. To do so, an expert selects "Change expert password", first enters the old password, then enters nothing (not "0" either) and confirms this with the tick.
The same can be done for the Technician password. When new programming is loaded, the controller returns to the User level and the Expert password
set by the programmer will apply.
Page 55
Version
55
Version and serial number
This menu item displays the operating system version (firmware).
The display then shows the serial number, internal production data and the names of the current function data and function overview.
The serial number is also visible on the controller's rating plate (upper side panel).
Page 56
Data administration
56
Data administration
Only visible in Technician or Expert mode
You can perform the following actions in this menu:
Save, load or delete function data Load firmware Load or delete a function overview Display the status of the data transfer
Restart the controller
Function data
Display the current function data with the time of loading
Page 57
Data administration
57
Load…
Function data can be loaded from the SD card onto the controller. Multiple function data can be saved to the SD card.
After selecting the function data required (*.dat file), you will be prompted to specify how the meter readings and the heat meter's calibration values should be treated.
You can choose from the following actions:
Retain
The meter readings and calibration values in the controller will be applied.
Example of use: After programming is changed using TAPPS
Reset
The meter readings and calibration values will be reset to zero.
Load function data
The meter readings and calibration values applied will be taken from the function data being loaded onto the controller.
Example of use: Replacement of a controller. The function data is taken from the old controller and its meter readings are to be loaded onto the new controller.
Tapping loads the new function data; cancels the action.
Once the function data is loaded, the controller returns to the User level.
Page 58
Data administration
58
Deleting, renaming and sending saved files
In order to rename or delete a saved file, tap the file icon. The following options then appear for selection:
Delete file Rename file Send file to selected nodes Return from this selection by tapping the file icon again.
Delete file
A confirmation prompt appears, which you can confirm by tapping .
Tapping cancels the action.
Rename file
The file name can be changed using a keyboard (Umlauts are not possible). The file name may have up to 63 characters.
Send file to selected nodes
This allows you to send function data to other CAN bus subscribers with X2 technology (e.g. RSM610, CANEZ2, CAN-I/O45).
Select the node number and then tap .
Page 59
Data administration
59
Save…
The current function data can be saved to the SD card. You can give the function data a name of your own. More than one set of function data can be saved. Example:
In this example there are already several sets of function data saved on the SD card.
If you want to save the function under a new name, tap . You can then enter a new name and save the file (umlauts cannot be entered). The file name may have up to 63 characters.
Page 60
Data administration
60
Firmware Load…
Firmware (= operating system, file *.bin) can be loaded from the SD card onto the controller or other X2 devices on the CAN bus. More than one operating system version may be saved on the SD card.
As when loading function data, the saved firmware files can be deleted, renamed or loaded onto other X2 devices.
Delete file Rename file Send file to selected nodes Return from this selection by tapping the file icon again.
Function overview Load…/Delete…
The function overview (*.x2d file, TA­Designer minimum version: 1.15) can
be loaded onto the device from the SD card or deleted in the device. Multiple files can be saved to the SD card.
When you select the file a confirmation prompt will appear, as the function overview currently on the device will be overwritten.
"Delete..." deletes the function overview saved on the device. When you select the file a confirmation prompt will appear.
Answer the confirmation prompt by tapping either (= Yes) or (= No).
Page 61
Data administration
61
Status
This indicates whether a data administration transfer of data from the SD card to the controller or vice versa was successful or not.
This status display does not apply to data transfers from another controller, a C.M.I. or a CAN monitor.
Total reset
A total reset can only be carried out from the Technician or Expert level and requires confirmation when prompted.
A total reset deletes the function modules, the parameter settings of all inputs and outputs, bus inputs and outputs, fixed values and system values.
The settings for the CAN node number and the CAN bus rate are retained. After tapping the screen you will be asked to confirm that you want a total reset to be carried out.
Answer by tapping either (= Yes) or (= No). A total reset can also be carried out by pressing the user interface when the TA logo is displayed
as the controller is starting up. At the end of the five seconds for starting calibration, a confirmation prompt appears.
Here you can select the required procedure or go to the controller's main menu by tapping .
Page 62
Data administration
62
Restart
At the end of the "Data admin" menu, there is an option to restart the controller following a confirmation prompt, without disconnecting the controller from the network.
Reset
Pressing the reset button on the front of the controller briefly (with a narrow-tip pen) and releasing it before the beep ends will restart the controller (= reset).
Loading the firmware with the factory settings
In special cases, it may be necessary to restore the controller's firmware to its condition when delivered from the factory. A total reset is carried out at the same time.
Pressing the reset button on the front of the controller (with a narrow-tip pen) when switching it on will start the loading of the original firmware at the time of delivery.
The button must be pressed until the beep stops.
Reset button
Page 63
Data administration
63
Calibration
If the touch-sensitive points on the touchscreen no longer align with the background graphics, making it difficult to operate the controller, you can re-adjust the touchscreen using "Calibration". You can start calibration by pressing the touchscreen surface when the TA logo is displayed after the controller is started. The following display appears for five seconds after the controller is started (the seconds will count down):
Touching the screen within that time will start the calibration procedure. To calibrate, you must touch all 9 target points separately one after the other.
You then have the option of a total reset or continuing to the main menu of the controller (see following description).
Touch the screen for calibration
5 sec
Page 64
System values
64
System values
This menu displays the status of system values that are available for selection as the source for function input variables and CAN and DL outputs.
The system values are divided into 4 groups:
General system values
When programmed accordingly, these system values allow monitoring of the controller system.
Controller start Sensor error inputs Sensor error CAN
Sensor error DL Network error CAN Network error DL
Controller start generates a 20 second pulse 40 seconds after the device is switched on or reset, and is used for monitoring the controller starts (e.g. after power failures) in the datalogging feature. The interval time in datalogging should be set to 10 seconds for these starts.
The sensor errors and network errors are global digital values (No/Yes) which are not connected to the error status of a specific sensor or network input. If any one of the sensors or network inputs has an error, the status of the corresponding group changes from No to Yes.
Page 65
System values
65
Time system values
Date system values
Second (seconds of the current time)
Day
Minute (minutes of the current time)
Month
Hour (hour of the current time)
Year (without the century)
Second pulse
Day of the week (starting with Monday)
Minute pulse
Calendar week
Hour pulse
Day of the year
Summertime (digital value OFF/ON)
Day pulse
Time (hh:mm)
Month pulse
Year pulse
Week pulse
The pulse values generate a single pulse per time unit.
Sun system values
Sunrise (time) Sunset (time) Minutes until sunrise (on the same day, does not go beyond midnight) Minutes since sunrise Minutes until sunset Minutes since sunset (on the same day, does not go beyond midnight) Solar altitude (see Shading function) Direction of the sun (see Shading function) Solar altitude > 0° (digital value yes/no)
Page 66
Function overview
66
Function overview
The function overview will only be displayed with controller version V1.04 or higher.
Programming of the function overview is done using the "TA-Designer" software and is described in that software's help file.
If multiple UVR16x2 controllers or X2 devices in the system are linked by CAN BUS, values from these other devices can be displayed as well.
Tapping the "Home" icon opens the function overview. This overview is designed to provide the user with a simple way of controlling and monitoring the system.
The function overview can be displayed with the aid of graphics or simply as a table. Examples:
Selecting this button on the start page takes you back to the controller menu.
Page 67
LED indicator light
67
LED indicator light
The indicator light can indicate a variety of statuses by means of three colours.
Indications at controller start
Indicator light
Explanation
Steady red light
The controller is booting up (= start routine after switching on, resetting or updating) or
Steady orange light
Hardware is initialising after booting up
Flashing green light
After hardware initialisation, the controller waits about 30 seconds to receive all the information necessary for a function (sensor values, network inputs)
Steady green light
Normal operation of the controller
An active message can be displayed by a change in the LED indicator light. This can be set in the Parameter menu of the "Message" function.
Page 68
68
Technical data UVR16x2 (Relay versions)
All inputs
Temperature sensors of type PT1000, KTY (2 kΩ/25 °C), KTY (1 kΩ/25 °C), PT100, PT500, Ni1000, Ni1000TK5000 and room
sensors RAS or RASPT, radiation sensor GBS01, thermocouple THEL, humidity sensor RFS, rain sensor RES01, pulses max. 10 Hz (e.g. for flow rate transducer VSG), voltage up to 3.3 V DC, resistance (1-100 kΩ), and as a digital input
Input 7
Also voltage 0-10 V DC
Input 8
Also current loop 4-20 mA DC, voltage 0-10 V DC
Inputs 15, 16
Also pulse input up to 20 Hz, for flow rate transducer VSG or S0 signals, for example
Outputs 1 - 4, 6 - 11
Relay outputs, partially with N/C and N/O contacts
Output 5
Relay changeover contact – potential-free
Outputs 12 - 16
Analogue outputs 0-10 V (max. 20 mA) or PWM (10 V/1 kHz), or expansion option as switching outputs with auxiliary relay modules
Output 16
Additional attribute: stabilised voltage output for supply of external sensors
Max. bus load (DL bus)
100 % CAN bus
Standard data rate 50 kbit/s, adjustable from 5 to 500 kbit/s
12 V / 24 V DC
Power supply for external devices, max. 6 W in total
Differential temperatures
With separate start and stop differential Threshold values
With separate start and stop differential or fixed hysteresis
Temperature measuring range
PT100, PT500, PT1000: -200 °C to +850 °C with a resolution of 0.1 K All other temperature sensors: -49.9 °C to +249.9 °C with a resolution of 0.1 K
Temperature accuracy
Typ. 0.4 K, max. ±1 K within a range of 0 - 100 °C for PT1000 sensors
Accuracy of resistance measurement
Max. 1.6 % at 100 kΩ (measured variable: resistance, process variable: resistance)
Voltage accuracy
Typ.1 %, max. 5 % of maximum input measuring range
Output 0-10V accuracy (A12-A15)
Max. -2% to +6% Max. breaking capacity
Relay outputs: 230 V / 3 A each
Connection
100 - 230 V, 50 - 60 Hz, (outputs A1 – A11 and device are fused jointly with 6.3 A (fast))
Supply cable
3x 1 mm² H05VV-F to EN 60730-1 (cable with standard plug included in the standard sensor pack)
Power consumption
3.0 – 4.5 W, subject to the number of active switching outputs
IP rating
IP40
Protection class
II – double insulated
Permissible ambient temperature
+5 to +45 °C
Page 69
69
Technical data UVR16x2-D (Triac versions)
Differences in the original properties compared with relay version:
Output 1, 2, 6, 7
Triac outputs
Outputs 3, 4, 8-11
Relay outputs, partially with N/C and N/O contacts
Output 5
Relay changeover contact – potential-free
Outputs 12 - 16
Analogue outputs 0-10 V (max. 20 mA), PWM (10 V/1 kHz) or expansion option as switching outputs with auxiliary relay modules
Output 16
Additional attribute: stabilised voltage output for supply of external sensors
Subject to technical modifications © 2016
Page 70
Page 71
Page 72
Legal notice
This operating manual is protected by copyright. Use outside the copyright requires the consent of Technische Alternative elektronische Steuerungsgerätegesellschaft m. b. H. This applies in particular to reproductions, translations and electronic media.
elektronische Steuerungsgerätegesellschaft m. b. H. A-3872 Amaliendorf Langestrasse 124, Austria Tel +43 (0)2862 53635 Fax +43 (0)2862 53635 7 Email: mail@ta.co.at --- www.ta.co.at --- © 2016