Technische Alternative CAN-MTx2-CO2, CAN-MTx2 Instruction Manual

www.ta.co.at
Manual version 1.18.1 English
CAN-MTx2
CAN-MTx2-CO2
CAN Monitor
Instruction manual
Table of contents
Version 1.18.1 EN
Safety requirements ............................................................................................................................5
Maintenance .............................................................................................................................................. 5
Disposal ...............................................................................................................................................6
Principles.............................................................................................................................................6
Installing and connecting the device ...................................................................................................7
Installing the device .................................................................................................................................. 7
Dimensions ........................................................................................................................................... 7
Power supply ............................................................................................................................................. 8
CAN bus connection ................................................................................................................................. 8
CAN bus cable selection and network topology ..................................................................................... 8
User manual - Technician / Expert .......................................................................................................9
Function overview display ........................................................................................................................ 9
Standard view ....................................................................................................................................... 9
Full screen view .................................................................................................................................. 10
Main menu ............................................................................................................................................... 11
Date / time / location .............................................................................................................................. 12
Inputs ....................................................................................................................................................... 13
Sensor correction ............................................................................................................................... 14
Average ............................................................................................................................................... 14
Sensor check for analogue sensors ................................................................................................. 14
Sensor error ................................................................................................................................... 15
Carbon dioxide and safety ................................................................................................................. 15
Messages from other X2 devices ..................................................................................................... 16
Internal CAN monitor messages ....................................................................................................... 17
CAN bus ................................................................................................................................................... 18
Datalogging......................................................................................................................................... 19
CAN settings ....................................................................................................................................... 20
CAN inputs .......................................................................................................................................... 20
CAN analogue outputs ....................................................................................................................... 21
Transmission condition ................................................................................................................ 21
CAN digital outputs ............................................................................................................................ 22
Designation .................................................................................................................................... 22
Transmission condition ................................................................................................................ 22
Active CAN nodes .............................................................................................................................. 23
General settings ...................................................................................................................................... 24
Language ............................................................................................................................................ 24
Brightness ........................................................................................................................................... 24
Display timeout ................................................................................................................................... 24
Simulation ........................................................................................................................................... 25
Access to menu .................................................................................................................................. 25
Currency .............................................................................................................................................. 25
User defined designations ................................................................................................................. 26
User .......................................................................................................................................................... 27
Current user ........................................................................................................................................ 27
Changing the password ..................................................................................................................... 28
List of permitted actions.................................................................................................................... 28
Version and serial number...................................................................................................................... 29
Data administration ................................................................................................................................ 30
Function data ...................................................................................................................................... 30
Load................................................................................................................................................ 31
Deleting, renaming and sending saved files ................................................................................ 32
Save... ............................................................................................................................................. 33
Firmware Load... ................................................................................................................................. 34
Function overview Load…/Delete... ................................................................................................... 34
Status .................................................................................................................................................. 35
Total reset ........................................................................................................................................... 35
Restart ................................................................................................................................................. 36
LED indicator light ................................................................................................................................... 36
LED status indicators at start ............................................................................................................ 36
Reset ........................................................................................................................................................ 37
Loading the firmware with the factory settings ............................................................................... 37
Calibration ............................................................................................................................................... 37
User manual - final user .................................................................................................................... 38
User levels ............................................................................................................................................... 39
Function overview ................................................................................................................................... 40
Standard view ..................................................................................................................................... 40
Full screen view .................................................................................................................................. 41
5
Safety requirements
These instructions are intended exclusively for authorised contractors. All installation and wiring work on the device must only be carried out in a zero
volt state. The opening, connection and commissioning of the device may only be carried
out by competent personnel. While doing so, they must observe all local safety requirements.
This device is state of the art and meets all necessary safety regulations. It may only be used in ac­cordance with the technical data and the safety requirements and regulations listed below. When us­ing the device, also observe the statutory and safety regulations apposite to the particular use. Any other use will automatically void all warranty rights.
The device must only be installed in a dry interior room. Solar thermal systems can become very hot. Consequently there is a risk of burns. Proceed with
caution when fitting temperature sensors.
For safety reasons, the outputs should only be left in manual mode when testing. In this operating
mode, no maximum temperatures or sensor functions are monitored.
Safe operation is no longer possible if the CAN monitor or connected equipment exhibits visual
damage, no longer functions or has been stored for lengthy periods in unsuitable conditions. If this is the case, disable the CAN monitor and equipment and secure against unintentional use.
Maintenance
If treated and used correctly, the device will not require any maintenance. Use a cloth moistened with mild alcohol (such as methylated spirits) to clean. Never use corrosive cleaning agents or solvents such as chloroethylene or trichloroethylene.
No components relevant to long term accuracy are subject to loading if the device is used correctly. Consequently long term drift is extremely low. The device therefore cannot be calibrated. Thus apply­ing any compensation is impossible.
The design characteristics of the device must not be changed during repairs. Spare parts must corre­spond to the original spare parts and must be used in accordance with the build version.
6
Disposal
Devices no longer in use or beyond a state of repair must be disposed of in an
environmentally responsible manner by an authorised collection point. They must never be treated as ordinary household waste.
We can undertake the environmentally responsible disposal of devices sold by
Technische Alternative upon request.
Packaging material must be disposed of in an environmentally responsible
manner.
Incorrect disposal may result in considerable damage to the environment, as many of the mate-
rials used require professional handling.
Standard delivery
CAN-MTx2 CAN monitor
SD memory card
Operating pen
Operating instructions
Installation material
Principles
The CAN-MTx2 CAN monitor is used as a control and display unit for the freely programmable con- trollers UVR16x2 and RSM610 as well as all other devices in the X2 series.
The CAN monitor has a combined temperature and humidity sensor built in and can therefore also be used as a room sensor.
The "Function overview" allows user friendly operation and display of X2 devices in the CAN bus net­work. The function overview is designed using the TA-Designer software and can comprise several pages.
As with the UVR16x2, it is operated via a 4.3" touchscreen. It is also possible for multiple CAN moni­tors in one CAN network to access the available X2 devices at the same time.
7
Installing and connecting the device
Installing the device
The device must only be installed in a dry interior room. For correct detection of the room tempera­ture, the CAN monitor must always be installed vertically.
Permissible ambient temperature: +5°C - +45°C Press the two locking clamps on the left and right and lift the cover. The control electronics are locat-
ed in the cover. Screw the base to the flat mounting surface using the supplied fastening materials, ideally with the
opening arranged over a mounting box fitted in the wall at eye level (approx. 1.6 m).
Dimensions
in mm
Operating pen
SD card
8
Power supply
The CAN monitor requires a 12 V power supply originating from a freely programmable controller (UVR16x2 or RSM610). No more than three devices (CAN monitor, CAN-I/O module etc.) can be sup­plied from each controller. With 4 or more devices in the CAN network, a 12 V power unit is required.
CAN bus connection
The screwless terminals for the CAN bus are located in the base of the CAN monitor. Pressing the small white button with a screwdriver unlocks the terminal and allows the connected lead to be in­serted or removed again. Spring contacts provide the electrical connection to the CAN monitor once it is fitted.
CAN bus cable selection and network topology
The principles of CAN bus cabling are described extensively in the manuals for the freely program­mable controllers. Therefore they are not included here in any detail, apart from the termination.
Each CAN network must be provided with a 120 Ω bus terminator at the first and last network node (termination with jumper). A CAN network therefore always has two terminators (one at each end). Spur lines and star-shaped CAN topologies are not permitted by the official specification.
The termination jumper for the CAN monitor is located on the back of the PCB and is visible when the upper part is removed from the base.
Terminated Not terminated
The CAN monitor is terminated if the jumper is set on the side labelled "term" (as shown above).
Release tabs
Spring contacts
9
User manual - Technician / Expert
If a function overview was loaded onto the CAN monitor, the display will show the function overview once it is connected to the CAN bus.
The function overview can be programmed as standard view or full screen view.
Function overview display
Standard view
Example: Start page with 4 links
From the start page (= first page), tapping takes you to the CAN monitor's main menu. If only technicians or experts are permitted to access the menu, then the relevant password must be
entered. If you press the background image for 3 seconds, 2 buttons appear which serve to access the version information and the general settings respectively.
You can go back to the page displayed previously by tapping .
V 1.01
MTX2-000000
10
Full screen view
In the full screen view, the upper status bar and the side buttons are hidden.
Example: Start page with 4 links
If you press the background image for 3 seconds, 4 buttons appear which enable access to the ver­sion information of the CAN monitor, the general settings or the date, time and location settings, and the main menu of the CAN monitor.
This button takes you to the main menu of the controller. If only technicians or experts are permitted to access the menu, then the relevant password must be entered.
To go back to the start page of the function overview,
tap .
You can go back to the page displayed previously by tapping . .
11
Main menu
Inputs – The CAN-MT16x2 CAN monitor has a sensor for temperature and humidity
Messages – Sensor and network errors from the CAN-MTx2 are displayed here
CAN BUS – CAN settings, definition of CAN inputs and outputs
General settings – Setting of the language, display screen properties and definitions of user
defined designations
User – Setting of the user level, changing of passwords
Version – Information about the device version, serial number, the loaded function overview
and the loaded function data
Data admin – Loading and saving of function data and the function overview, loading of firm-
ware, total reset
Tap the "Home icon" to go to the Function overview.
12
Date / time / location
The "Date" and "Time" are shown in the status line at top right. As the CAN monitor does not have its own clock function, the time and date are taken from network
node 1 and cannot be changed in the CAN monitor. For this reason, at least one CAN bus device which has its own clock function must have the node number 1 (UVR16x2, UVR1611, RSM610, C.M.I.).
Tapping that status field takes you to the menu for the date, time and location details.
Display example:
Time zone – Specifies the time zone relative to UTC (= "Universal Time Coordinated", also
known as GMT (= Greenwich Mean Time)). In the example, the time zone is set to "UTC + 01:00".
Summertime – "Yes" if summertime is active.
Automatic time change – If "Yes", the time will switch over automatically to summertime
according to the specifications of the European Union.
Date – The current date (dd.mm.yy).
Time – The current time
13
GPS latitude – Geographical latitude according to GPS (= global positioning system)
GPS longitude – Geographical longitude according to GPS
The values for geographical latitude and longitude are used to determine the location-specific solar data. That data can be used in functions (e.g. shading function).
The factory default settings for the GPS data are for the location of Technische Alternative in Amaliendorf, Austria.
Sunrise – Time
Sunset – Time
Solar altitude – Specified in ° as measured from the geometric horizon (0°),
zenith = 90°
Direction of the sun – Specified in ° as measured from the north (0°)
North = 0° / East = 90° / South = 180° / West = 270°
Inputs
The CAN-MTx2 CAN monitor has a combined temperature, humidity and air pressure sensor built in. In addition, the CAN-MTx2-CO2 CAN monitor has a CO2 sensor. 5 values are displayed in the Inputs menu: temperature, relative humidity, dew point temperature, absolute air pressure (in mbar) and CO2 content (in ppm). These 5 values are already preset (as shown in the bottom graphic) at inputs 1 – 5. In CAN-MTx2 (without CO2 sensor), the fifth value is always 0.
14
Sensor correction
The option of sensor correction is available for the measured variables The corrected value is utilised for all calculations and displays.
Example:
Average
This setting refers to the average of the measurements over time. Averaging over 0.3 seconds leads to extremely rapid reactions on the part of the display and the unit.
However, this can be expected to cause fluctuations of the value. A high average value results in lagging and is only recommended for special applications. For simple measuring operations approx. 1-3 seconds should be selected.
Sensor check for analogue sensors
When "Sensor check" is active (setting: "Yes"), a short circuit or a lead break will automatically generate an error message: A warning symbol is displayed in the upper status line, and the defective sensor is shown with a red border around it in the "Inputs" menu.
Example:
Short-circuit of sensor 1
Standard value
15
Sensor error
When "Sensor check" is active, Sensor error is available as the source for digital CAN outputs: status "No" for a sensor that is working correctly and "Yes" for a defect (short circuit or lead break). This allows the controller to react to the failure of a sensor, for example.
In System values / General, a sensor error for all inputs is available. If the Standard thresholds are selected, a short circuit will be indicated if the value falls below the
lower measurement limit and a lead break will be indicated if the value exceeds the upper measurement limit.
The Standard values for temperature sensors are -9999.9 °C for a short circuit and 9999.9 °C for a lead break. Those values are utilised in the internal calculations in the event of an error.
By selecting the thresholds and values appropriately, a fixed value can be specified for the controller in the event of sensor failure, in order to allow a function to continue operating in emergency mode.
Example: If the temperature value falls below the threshold of 5.0 °C (= "Threshold value"), a value of
20.0 °C (= "Output value") is issued and displayed for that sensor (fixed hysteresis: 1.0 °C). At the same time the "Sensor error’ status is set to "Yes".
The short circuit threshold must be defined below the lead break threshold.
Example: The temperature sensor has fall­en below 5.0 °C, so 20.0 °C is issued as the measurement, and a sensor error is dis­played at the same time.
Note: In the event of temperature sensor failure, the humidity and dew point will be calculated incor­rectly.
Carbon dioxide and safety
Carbon dioxide is a non-toxic and non-flammable gas. However, in higher concentrations it can be life threatening.
For mechanically ventilated rooms, the Austrian Federal Ministry of Agriculture, Forestry, Environment and Water Management requires a target value below 800 ppm and a maximum value of 1400 ppm.
CO2 requirements for mechanically ventilated interior rooms
(Source: Kohlenstoffdioxid als Lüftungsparameter [Carbon Dioxide as a Ventilation Parameter], August 2011, authors: BOOS,
DAMBERGER, HUTTER, KUNDI, MOSHAMMER, TAPPLER, TWRDIK, WALLNER)
Target range: Individual values < 800 ppm
Minimum specification: Maximum moving hourly average < 1000 ppm
Minimum specification: All individual values in the evaluation period < 1400 ppm
16
Messages from other x2 devices
Depending on the setting in the x2 device, messages from other x2 devices can be displayed on the CAN monitor with a pop-up window, a changed status LED and/or a warning tone.
The pop-up window works in the same way as on the display of the UVR16x2 controller.
Example: Message type "Error"; warning tone activated After the message has been triggered and the cause of the fault has been removed, the following dis-
play appears (red):
If the pop-up window has been hidden, it can be shown again by tapping the warning symbol in the status bar on the left.
More information about generating messages can be found in the programming manuals for the x2­devices.
Warning symbol on the left
Message type
Message name
Hide message = Hide the message window
only visible for "Fault"
message type
Message window
Delete message (only
possible once the
cause of the message
ceased)
Time
17
Internal CAN monitor messages
The "Messages" menu displays messages that are caused by sensor or CAN bus errors in the CAN­MTx2.
Message from other x2 devices are not displayed here.
Example: Fault on input 1
If at least one internal message is active, the warning symbol will appear in the upper status line on the right. If the message window has been hidden, it can be shown again by tapping the warning symbol in the status bar.
18
CAN bus
The CAN network allows communication between CAN bus devices. When analogue or digital values are sent via CAN outputs, other CAN bus devices can utilise those values as CAN inputs.
Up to 62 CAN bus devices can be operated in one network. Every CAN bus device must be given its own node number in the network. The cable topology of a CAN bus network is described in the installation instructions.
19
Datalogging
This menu cannot be selected in the User mode.
This menu is used to define the parameters for CAN datalogging of analogue and digital values.
CAN datalogging requires at least version 1.25 on the C.M.I. datalogger and a Winsol version of at least 2.06.
CAN datalogging is only possible with the C.M.I. datalogger. The data to be logged can be freely selected. Es erfolgt keine ständige Datenausgabe. There is no constant data output. When requested by a C.M.I., the controller saves the current values to a logging buffer and locks it to prevent it from being overwritten (when requests are received from another C.M.I.) until the data is read out and the logging buffer has been enabled again.
The settings required on the C.M.I. for datalogging via CAN bus are described in the C.M.I.'s online help.
Each CAN-MTx2 can issue a maximum of 64 digital and 64 analogue values that are defined in the menu "CAN bus/datalogging" of the CAN-MTx2.
The sources for the logged values can be inputs and CAN bus inputs.
20
CAN settings
Node
Define a unique CAN node number for the device (setting range: 1 – 62). The factory-set node number of the CAN-MTx2 is 50.
Designation
Every device can be given its own designation.
Bus rate
The standard bus rate of the CAN network is 50 kbit/s (50 kBd), which is specified for most CAN bus devices.
Important: All devices in the CAN bus network must have the same transfer rate in order to be
able to communicate with each other.
The bus rate can be set to between 5 and 500 kbit/s, with lower bus rates allowing longer cable net­works (see installation instructions of the controllers).
CAN inputs
As CAN inputs are of no practical use in the CAN monitor, this sub-menu is not described in this man­ual.
21
CAN analogue outputs
The 5 analogue inputs are already linked to the first five CAN analogue outputs. In CAN-MTx2 (without CO2 sensor), the fifth value is always 0.
As there are no other analogue values available as the source for CAN analogue outputs, no instruc­tions are given here for programming other CAN analogue outputs.
Transmission condition
Example:
If change > 1.0 K
If the current value has changed by more than 1.0 K compared to the last transmitted value, a new transmission is made. The unit used by the source is applied to the output value (minimum setting: 0.1 K).
Blocking time 10 s
If the value changes by more than 1.0 K within 10 seconds of the last transmission, the value is nevertheless only transmitted again after 10 seconds (minimum setting: 1 sec.).
Interval time 5 m
The value is transmitted every 5 minutes even if it has not changed by more than 1.0 K since the last transmission (minimum setting: 1 minute).
22
CAN digital outputs
They are defined by specifying the source in the CAN monitor. Example: Source "Sensor error inputs"
Designation
Every CAN digital output can be given its own designation. The designation can be selected from var­ious designation groups or can be user defined.
Example:
Transmission condition
Example:
If change Yes/No
Transmission of the value if a status change occurs
Blocking time 10 s
If the value changes within 10 seconds of the last transmission, the value is nevertheless only transmitted again after 10 seconds (minimum setting: 1 sec.).
Interval time 5 m
The value is transmitted every 5 minutes even if it has not changed since the last transmission (minimum setting: 1 minute).
23
Active CAN nodes
Tapping the button displays the active CAN nodes in the CAN bus network. "Status" displays the CAN bus status of the CAN monitor. After starting, the status changes automati-
cally, according to a predefined process, from init. preop(erational) operat(ional). Only then is it possible to communicate with other CAN bus devices.
Tapping a CAN bus device of the X2 series takes you to the menu of the device. Other CAN bus devices and the C.M.I. will be displayed, but it is not possible to access their menus. To return to the menu of the CAN monitor, tap the CAN monitor in this overview.
Updating the view
24
General settings
Displayed in Expert mode only
This menu allows settings to be made which then take effect for all other menus and displays.
Language
Select the display language
Brightness
Select the brightness of the display to match the surroundings (setting range: 5.0 100.0 %
Display timeout
The display will be switched off if the user does not do anything for the period of time set here. Tap­ping the touchscreen surface re-activates the display (setting range: 5 seconds to 30 minutes). For the CAN monitor this time should be set to no more than 3 minutes, as otherwise the increasing inter­nal warming will cause the sensor's measurements to be incorrect.
Displayed in Technician or Ex­pert mode only
25
Simulation
No application possibility for the CAN-MTx2
Access to menu
Definition of the user level from which access to the CAN monitor's main menu is permitted.
If only technicians or experts are permitted to access the menu, then the relevant password must be
entered when selecting the main menu from the start page of the function overview ( button).
When the CAN monitor is restarted, either the function overview is displayed (if loaded) or, in the case of restricted access, the keyboard for the password.
Currency
No application possibility for the CAN-MTx2
26
User defined designations
In this menu, you can enter, change or delete user defined designations for all elements of the CAN monitor. This menu can only be selected from within the Technician or Expert level.
View with designations defined previously
An alphanumeric keyboard is provided for changing a designation or creating a new one.
Up to 100 different designations can be defined by the user. The maximum number of characters per designation is 24.
Designations defined previously are available for all elements.
27
User
Current user
Select whether the user is an Expert, Technician or User. To enter the Technician or Expert level a password must be entered, which can be set by the pro-
grammer.
Following a restart, the CAN monitor is always in the User level.
28
Changing the password
An Expert can change the passwords for Technician and Expert. A Technician can only change the Technician password.
There are no restrictions regarding the length of the password or the type of characters that can be used.
To change a password, you must first en­ter the old password.
List of permitted actions
User
Displays and permitted actions
User
Function overview with options for control
Access to main menu only if enabled for "User" in the "General settings"
Inputs: display only, no access to the parameters
Messages: display of active messages
CAN bus: no access to the parameters
General settings: language, brightness and display timeout can be altered
User: change of user (with password entry)
Technician
All of the above plus:
Access to main menu only if enabled for Technician or User in the "General set-
tings"
Changes to the parameters for inputs
General settings: Changes to user defined designations and creation of new
ones
All settings in the CAN bus menu
Data administration actions
Expert
All actions and all displays are accessible.
Automatic changeover
Normally, the CAN monitor automatically switches back to user mode 30 minutes after login as an expert or technician.
For programming or test purposes, this automatic changeover can be switched off. To do so, an expert selects "Change expert password", first enters the old password, then enters nothing (not "0" either) and confirms this with the tick.
The same can be done for the Technician password.
29
Version and serial number
The display shows the serial number, internal production data and the names of the current function data and function overview.
MTX2-000000
V 1.01
30
Data administration
Only visible in Technician or Expert mode
You can perform the following actions in this menu:
Save, load or delete function data
Load firmware
Load or delete a function overview
Display the status of the data transfer
Function data
This menu is used for loading function data and for backing up the settings of the CAN monitor (=function data) on the SD card ("Save").
A total reset deletes all settings and resets the CAN monitor to its condition when delivered from the factory.
Display the current function data with the time of loading
31
Load...
Function data can be loaded from the SD card onto the CAN monitor or other X2 devices. More than one set of function data can be saved on the SD card.
The data transfer is only possible after a technician or expert password has been entered for the tar­get device.
After selecting the function data required (*.dat file), you will be prompted to specify how the meter readings and the heat meter's calibration values should be treated.
This prompt is irrelevant when loading function data onto the CAN monitor.
You can choose from the following actions:
Retain
The meter readings and calibration values in the controller will be applied.
Example of use: After programming is changed using TAPPS
Reset
The meter readings and calibration values will be reset to zero.
Load function data
The meter readings and calibration values applied will be taken from the function data being loaded onto the controller.
Example of use: Replacement of a controller. The function data is taken from the old controller and its meter readings are to be loaded onto the new controller.
Tapping loads the new function data; cancels the action.
Once the function data is loaded, the controller returns to the User level.
32
Deleting, renaming and sending saved files
In order to rename or delete a saved file, tap the plus icon. The following options then appear for se­lection:
Delete file Rename file Send file to selected nodes Return from this selection by tapping the plus icon again.
Delete file
A confirmation prompt appears, which you can confirm by tapping .
Tapping cancels the action.
Rename file
The file name can be changed using a keyboard (Umlauts are not possible). The file name may have up to 63 characters.
Send file to selected nodes
This allows you to send function data to other CAN bus subscribers with X2 technology (e.g. RSM610, CANEZ2, CAN-I/O45).
Select the node number and then tap .
33
Save...
The current function data of the CAN monitor can be backed up on the SD card. You can give the function data a name of your own. More than one set of function data can be saved. Example:
In this example there are already several sets of function data saved on the SD card.
If you want to save the function data under a new name, tap the button. You can then enter a new name and save the file
(umlauts cannot be entered). The file name may have up to 63 characters.
Tap the plus icon to load function data from a different X2 device onto the CAN monitor SD card.
When the button expands, tap the green arrow.
Now a node query appears and it is possible to enter a new file name.
34
Firmware Load...
Firmware (= operating system, file *.bin) can be loaded from the SD card onto the CAN monitor or other X2 devices on the CAN bus (exception: UVR16x2). More than one operating system version may be saved on the SD card.
The data transfer is only possible after a technician or expert password has been entered for the tar­get device. As when loading function data, the saved firmware files can be deleted, renamed or loaded onto other X2 devices.
Delete file Rename file Send file to selected nodes Return from this selection by tapping the icon again.
Function overview Load…/Delete...
The function overview (*.x2d file, TA­Designer minimum version: 1.15) can be
loaded onto the device from the SD card or deleted in the device. Multiple files can be saved to the SD card.
When you select the file a confirmation prompt will appear, as the function over­view currently on the device will be over­written.
"Delete..." deletes the function overview saved on the device. When you select the file a confirmation prompt will appear.
Answer the confirmation prompt by tapping either (= Yes) or (= No).
35
Status
This indicates whether a data administration transfer of data from the SD card to the CAN monitor or vice versa was successful or not.
This status display does not apply to data transfers from another controller, a C.M.I. or another CAN monitor.
Total reset
A total reset deletes all settings and resets the CAN monitor to its condition when delivered from the factory. The settings for the CAN node number and the CAN bus rate are retained.
After tapping the screen you will be asked to confirm that you want a total reset to be carried out.
Answer by tapping either (= Yes) or (= No).
36
Restart
At the end of the "Data admin" menu, there is an option to restart the moni­tor following a confirmation prompt, without disconnecting the monitor from the network.
LED indicator light
LED status indicators at start
Indicator light
Explanation
Steady red light
The CAN monitor is booting (= start routine after switching on, resetting or updating) or
Steady orange light
Hardware is initialising after booting up
Flashing green light
After hardware initialisation, the CAN monitor waits about 30 seconds to receive all the information necessary for operation (sensor values, network inputs)
Steady green light
Normal operation of the CAN monitor
LED indicator light
37
Reset
Pressing the reset button on the front of the CAN monitor briefly (with a narrow-tip pen) and releasing it before the beep ends will restart the CAN monitor (= reset).
Loading the firmware with the factory settings
In special cases, it may be necessary to restore the CAN moni­tor's firmware to its condition when delivered from the factory. A total reset is carried out at the same time.
Pressing the reset button on the front of the CAN monitor (with a narrow-tip pen) when switching it on will initiate loading of the original firmware at the time of delivery.
The button must be pressed until the beep stops.
Calibration
If the touch-sensitive points on the touchscreen no longer align with the background graphics, making it difficult to operate the CAN monitor, you can re-adjust the touchscreen using "Calibration". You can start calibration by pressing the touchscreen surface when the TA logo is displayed after the monitor is started. The following display appears for five seconds after the monitor is started (the seconds will count down):
Touching the screen within that time will start the calibration procedure.
To calibrate, you must touch all 9 target points separately one after the other.
You then have the option of a total reset or continuing to the main menu of the CAN monitor.
Reset button
Touch the screen for calibration
5 sec
38
User manual - final user
The CAN-MTx2 CAN monitor is used as a control and display unit for the freely programmable con­trollers UVR16x2 and RSM610 as well as all other devices in the X2 series.
The CAN monitor has a combined temperature and humidity sensor built in and can therefore also be used as a room sensor.
The wide variety of systems means that a single instruction manual for all application scenarios is not possible. You should therefore always seek instructions from your heating system installer.
The programmer can create a "Function overview" for user operation. This function overview may include all X2 devices in the CAN bus network. In the function overview, you can check all important measurements and change settings in selected functions which are important to you as the user.
In this manual, we explain how to select the function overview. For further information about func­tions and modifying values, see the operating manuals of the freely programmable controllers (UVR16x2, RSM610).
Note: Your personal system will normally vary from the examples in the manuals.
39
User levels
To prevent incorrect operation of the controller, three different user groups can log onto the controller: User, Technician or Expert. Access by Technicians and Experts requires a password.
User
Displays and permitted actions
User
Function overview with options for control
Access to main menu only if enabled for "User" in the "General settings"
Inputs: display only, no access to the parameters
Messages: display of active messages
CAN bus: no access to the parameters
General settings: language, brightness and display timeout can be altered
User: change of user (with password entry)
Technician
All of the above plus:
Access to main menu only if enabled for Technician or User in the "General set-
tings"
Changes to the parameters for inputs
General settings: Changes to user defined designations and creation of new
ones
All settings in the CAN bus menu
Data administration actions
Expert
All actions and all displays are accessible.
The CAN monitor is operated via a 4.3" touchscreen. For greater ease of use, an operating pen is pro­vided.
View of CAN-MTx2
You can use the pen to tap operating fields on the screen and to scroll through the view displayed in the main menu.
Stylus
40
Function overview
The function overview is freely designed by the programmer and can therefore look different on every system. It can be displayed with the aid of graphics or simply as a table.
Values selected by the programmer can be changed either by all users, by Experts only or by Experts and Technicians. Many values (e.g. sensor values) can generally never be changed.
If multiple UVR16x2 controllers or other X2 devices in the system are linked by CAN bus, the function overview can also be programmed to display the values of other devices.
The function overview can comprise several pages, in which case a Link (= link on the screen linking to another page) is required for switching to a different page. The appearance of links can be freely designed by the programmer. Access to some pages may be restricted to certain user groups (with or without password entry).
The function overview can be programmed with the first page showing an overview of the following pages with links to those pages.
Touching the relevant link takes you to the display on the required page. If a function overview was loaded onto the CAN monitor, the display will show the function overview
once it is connected to the CAN bus.
From the main menu, you can access the function overview by tapping the button.
The function overview can be programmed as standard view or full screen view.
Standard view
Example:
Start page with 4 links
You can go back to the page displayed previously by tapping .
To go to the start page of the function overview, tap .
From the start page (= first page), tapping takes you to the CAN monitor's main menu. If only technicians or experts are permitted to access the menu, then the relevant password must be entered.
41
If you press the background image for 3 seconds, 2 buttons appear which serve to access the version information and the general settings respectively.
You can go back to the page displayed previously by tapping .
Full screen view
In the full screen view, the upper status bar and the side buttons are hidden.
Example:
Start page with 4 links
V 1.01
MTX2-000000
42
If you press the background image for 3 seconds, 4 buttons appear which enable access to the ver­sion information of the CAN monitor, the general settings or the date, time and location settings, and the main menu of the CAN monitor.
This button takes you to the main menu of the CAN monitor. If only technicians or experts are permitted to access the menu, then the relevant password must be entered.
To go back to the start page of the function overview,
tap .
You can go back to the page displayed previously by tapping . .
For more details about functions and modifying values, see the operating manuals of the freely programmable controllers (UVR16x2, RSM610).
Subject to technical modifications © 2018
V 1.01
MTX2-000000
43
EU Declaration of conformity
Document- Nr. / Date:
TA17030 / 02/02/2017
Company / Manufacturer:
Technische Alternative RT GmbH
Address:
A- 3872 Amaliendorf, Langestraße 124
This declaration of conformity is issued under the sole responsibility of the manufacturer.
Product name:
CAN-MTx2, CAN-MTx2-CO2
Product brand:
Technische Alternative RT GmbH
Product description:
CAN Monitor
The object of the declaration described above is in conformity with Directives:
2014/35/EU
Low voltage standard
2014/30/EU
Electromagnetic compatibility
2011/65/EU
RoHS Restriction of the use of certain hazardous substances
2009/125/EC
Eco-design directive
Employed standards:
EN 60730-1: 2011
Automatic electrical controls for household and similar use – Part 1: General requirements
EN 61000-6-3: 2007 +A1: 2011 + AC2012
Electromagnetic compatibility (EMC) - Part 6-3: Generic standards ­Emission standard for residential, commercial and light-industrial envi­ronments
EN 61000-6-2: 2005 + AC2005
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards ­Immunity for industrial environments
EN 50581: 2012
Technical documentation for the assessment of electrical and electron­ic products with respect to the restriction of hazardous substances
Position of CE - label: On packaging, manual and type label
Issuer:
Technische Alternative RT GmbH A- 3872 Amaliendorf, Langestraße 124
This declaration is submitted by
Dipl.-Ing. Andreas Schneider, General manager, 02/02/2017
This declaration certifies the agreement with the named standards, contains however no warranty of characteristics.
The security advices of included product documents are to be considered.
Guarantee conditions
Note: The following guarantee conditions do not limit the legal right to a warranty, but rather expand
your rights as a consumer.
1. Technische Alternative RT GmbH provides a two-year guarantee from the date of purchase for
all the devices and parts which it sells. Defects must be reported immediately upon detection and within the guarantee period. Technical support can supply the correct solution for almost every known problem. In this respect, contacting us immediately will help to avoid unneces­sary expense and effort in troubleshooting.
2. The guarantee includes free repair (but not the cost of on-site fault finding, removal, refitting
and shipping) due to operational and material defects which impair operation. In the event that a repair is not economical in the opinion of Technische Alternative for reasons of cost, the goods will be replaced.
3. Not included is damage resulting from the effects of a voltage surge or abnormal ambient
conditions. Likewise, no liability can be accepted if the device defect is due to: transport dam­age for which we are not responsible, incorrect assembly and installation, incorrect use, failure to observe the operating and installation instructions or incorrect maintenance.
4. The guarantee will become void if repairs or actions are carried out by people who are not au-
thorised to perform them or have not been so authorised by us or if our devices are operated with spare parts, auxiliary parts or accessories that are not considered to be original parts.
5. The defective parts must be returned to our factory with a copy of the proof of purchase and a
precise fault description. Processing is accelerated if an RMA number is requested via our homepage www.ta.co.at.The defect must be clarified with our technical support beforehand.
6. Services provided under guarantee result neither in an extension of the guarantee period nor in
a commencement of a new guarantee period. The guarantee period for fitted parts ends with the guarantee period of the whole device.
7. Further or other claims, especially those for compensation for damage other than to the de-
vice itself, insofar as a liability is not legally required, are excluded.