TechnipFMC Smith Meter AccuLoad III Installation Manual

Page 1
Electronic Preset Delivery System
Smith Meter® AccuLoad® III with ALX Firmware
Installation Manual
ulletin MN06135 Issue/Rev 1.3 (6/17)
B
Page 2
Caution
The default or operating values used in this manual and in the program of the AccuLoad III are for factory testing only and should not be construed as default or operating values for your metering system. Each metering system is unique and each program parameter must be reviewed and programmed for that specific metering system application.
Disclaimer
FMC Technologies Measurement Solutions, Inc. hereby disclaims any and all responsibility for damages, including but not limited to consequential damages, arising out of or related to the inputting of incorrect or improper program or default values entered in connection with the AccuLoad III.
Page 3
Receipt of Equipment
When the equipment is received the outside packing case should be checked immediately for any shipping damage. If the packing c ase has been damaged, the local carrier s hould be not ified at once r egarding his l iability. Car efully remove the unit from its packing case and inspect for damaged or missing parts.
If damage has occurred during shipment or parts are missing, a written report should be submitted to the Customer Ser­vice Department, FMC Technologies Measurement Solutions, Inc., 1602 Wagner Avenue, Erie, Pennsylvania 165 10.
Prior to installation, the unit should be stored in its original packing case and protected from adverse weather conditions and abuse.
Caution:
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with this Instruction Manual, may cause interference to radio communications. It has not been tested to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operat­ed in a commercial en vironment. Operation of this equipment in a residential area is likely to cause inter­ference, in which case th e user, at his own expense, will b e required to take whateve r measures may be required to correct the interference.
Warning
These preset devices must be used with fail-safe backup equipment to prevent accidental runaway delivery of product. Failure to provide backup equipment could result in personal injury, property loss and equipment damage.
Warning
On initial po wer-up of a new unit or af ter installation of a new computer board, there ar e several alarms that wil l be triggered which cannot be cleared unt il the Ac cuLo ad is progr am med.
United States NIST Handbook 44 UR.3.5.1. and UR.3.5.2.
For compliance to United S tates NIST Handbook 44 UR.3.5. 1. an d UR. 3. 5.2., in v oices print ed us i ng a mechanical numeric-only printer (e.g., Smith Meter Load Printer) must contain in preprinted form the following information:
a. Volume corrected to 60 degrees F b. API/C of E _____________________ c. Temperature ____________________ d. Gross Volume ____________________
where the API/C of E, tem perature, and gross volume ma y be hand-written on th e ticket. Refer to Handbook 44, UR.3.5.1. and UR.3.5.2. for current requirements.
Page 4
This page intentionally left blank .
Page 5
Table of Contents
Section I - Introduction ................................................................................................................................................1
Receipt of Equipment ..............................................................................................................................................1
Warning and Precautions ........................................................................................................................................1
Weights and Measures Requirements ....................................................................................................................2
Section II - Pre-Inst al lat ion C onsid er at ions ................................................................................................................3
Mechanical ..............................................................................................................................................................3
Electrical ..................................................................................................................................................................3
Environmental .........................................................................................................................................................4
Section III - Installation ...............................................................................................................................................5
Mechanical ..............................................................................................................................................................5
Electrical ..................................................................................................................................................................5
Input Frequency x2 ..............................................................................................................................................6
Start-Up ...............................................................................................................................................................6
General Requirements ............................................................................................................................................6
Section IV - Diagrams .................................................................................................................................................7
Switch Settings ..................................................................................................................................................... 10
Analog Module Settings (JP1 on EAAI) ............................................................................................................... 11
Bi-State DC Inputs and Output Jumper Settings (JP1 on the BSE) .................................................................... 13
Pulse Inputs ......................................................................................................................................................... 15
Dual Pulse Inputs for Rev. 10.07 and Above Firmware (With Flow Controlled Additive) .................................... 18
Promass 80, 83, and 84 ....................................................................................................................................... 33
Wiring Terminals, 4-20mA and 1-5 Vdc Inputs/Outputs ...................................................................................... 49
Digital Inputs ........................................................................................................................................................ 50
Wiring Terminals, Digital Inputs ........................................................................................................................... 51
Digital Outputs ...................................................................................................................................................... 52
Wiring Terminals, Digital Outputs ........................................................................................................................ 53
Digital Inputs – AICB ............................................................................................................................................ 67
Optional AICB Board(s) (Additive Inputs/Outputs) ............................................................................................... 69
Communications (AICB Boards) .......................................................................................................................... 72
Jumper Locations ................................................................................................................................................. 72
Optional ComFlash Mass Storage Expansion Board .......................................................................................... 81
Section V - Maintenance ......................................................................................................................................... 83
Maintenance ......................................................................................................................................................... 83
Battery replacement procedure ............................................................................................................................ 83
Firmware updates ................................................................................................................................................ 84
Enclosure Maintenanc e ....................................................................................................................................... 84
Special Environments .......................................................................................................................................... 85
Section VII - Completing the Installation.................................................................................................................. 86
Explosion-proof housing closure .......................................................................................................................... 86
Sealing ................................................................................................................................................................. 87
Section VIII - Related Publications .......................................................................................................................... 88
Page 6
his page intentionally left bla nk.
T
Page 7

Section I – Introduction

This manual is to b e used for the installation of the AccuLoad III Electron ic Preset Controller w ith Accu­Load III f irmware. T he manual is d ivided into th e fol­lowing sections: Introduction, Pre-Installation Con­siderations, Installation, Diagrams, Maintenance, Completing the Installation, and Related Publica­tions.

Receipt of Equipment

When the equipment is received the outside pack­ing, case should be checked immediately for any shipping damage. If the packing case has been damaged, the local car rier shoul d be notif ied at o nce regarding his liabilit y. Carefully remove the unit from its packing case and inspe ct f or dam aged or m iss ing parts.
If damage has occur red during shipment or p ar ts are missing, a written re port should be submitted to the Customer Service Department, FMC Technologies Measurement Solutio ns, Inc., 1602 W agner Avenue, Erie, Pennsylvania 16510.
Before installation, the unit should be stored in its original packing case and protected from adverse weather conditions and abuse.

Warnings and Precautions

Before you begin please read all of the following warnings and cautions to reduce the risk of injury, equipment damage or malfunction.
Emergency Shutdown – The AccuLoad has an ex­tensive set of built-in safety features.
rdous Locations – The S and Q models are
Haza
approved for use in an explosive (Class I, Div. I, Groups C & D and Zone 1 Ex d ia, IIB Gb) atmos­phere but there are spec ific installation methods re­quired to produce a comprehensive explosion-proof system. This manual provides guidance for t he Ac­cuLoad installation only. In general, keeping the front cover bolted close in accordance with the in­structions in Section VII is the key to maintaining ex­plosion protection.
Any modification of the AccuLoad housing inval­idate the hazardous location rating of the Accu­Load.
Do not replace the bolts in the front cover except with those suppl ied by the manufac­ture. Using unapproved bo lts invalidates the explosion-proof rating of the enclosure.
Do not drill or machine the housing.
Do not attempt to replace the touchscreen or
glass except as part of the factory supplied assembly.
Electrostatic Discharge Precautions – The elec­tronic components in the AccuLoad are susceptible to damage by static d ischarge. To minimi ze the risk of damage, the follo wing precautions should be fol­lowed:
Before touching a circuit board with hands or tools, personnel/tools should be grounded using a wrist strap.
IMPORTANT: The AccuLoad s hould never be r elied upon to act as the prim ary safety system control for the flow valve and pump controls, i.e. emergency stop, overfill, ground protection, etc. These should always be handled b y separate systems specificall y designed for that application. For example, Safety systems specifically to meet SIL requirements. Any power control circuits from these external systems shall be wired in series ahead of the AccuLoad to remove power to the ancillary devices.
Hazardous Voltages – There are hazardous volt­ages involved in the inst allation and m aintenance of the AccuLoad and only qualified individuals should perform installation.
MN06135 Issue/Rev. 1.3 (6/17) 1
Avoid touching com ponents or trac es on the circuit boards and handle by the edg­es/mounting holes.
Circuit boards shou ld be kept in conductive bags when not installed.
ATEX / IEC Installations – There are special re­quirements for AT EX approved installations. Pl ease refer to Section III for a detailed list of the specific requirements.
RF Radiation - The AccuLoad generat es, uses, and can radiate radio frequency energy and, if not in­stalled and used in accordance with this Manual, may cause interferenc e to radio communications. It has not been tested t o comply with th e limits pursu­ant to Part 15 (CFR 47) of F CC Rules, as electron ic control equipm ent utili zed b y an i nd ust ria l complex is exempt from the rules.
Page 8
Section I – Introduction
Operation of this equipment in a residential area may cause interference, in which case the user, at his own expense, wil l be required to take whatever measures that m ay be required to correct the inter­ference. The AccuLoad h as been evaluated against the standard EN 61326-1: “Electrical equipm ent for measurement, control and laboratory use” and has been found to comply to the European Community EMC Directive 2014/30/EU.
Weights and Measures Requirements
The AccuLoad is a device marketed for a global market. Requirem ents var y depe nd ing o n th e r egion. It is a user requirement to verify that the AccuLoad is programmed and operated in a manner consistent with local codes and t hat proper notification (permit for use) or registratio n has been filed with the local authority or jurisdiction.
MN06135 Issue/Rev. 1.3 (6/17) 2
Page 9

Section II – Pre-Installation Considerations

Wire
Baud Rates
Feet
Meters

Mechanical

In addition to the following, all previous warnings and cautions should be reviewed before installation.
1. A solid base (ped estal or shelf) shou ld be use o support the explosion-proof AccuLoad III
t housing.
d
he DC signal wires must be multi-conductor
2. T shielded cab le of 18 t o 24 AW G minimum s trand copper.
Note: The following recommendations are based on our knowledge of the electrical codes. The local electrical codes should be reviewed to ensure that these recommendations follow the local code. Also installation manuals of all the equipment be­ing wired into the AccuLoad should be reviewed for trans mission distances and wire recommendations.
Weight: = 50 lb. (22.7 kg) ALIII-S Hardware Weight: = 125 lb. (57.5 kg) ALIII-Q Hardware
2. The location and the height of AccuLoad III should be selected to perm it eas y viewing of th di
splay and to pro vide convenient access to t he
keypad by all users.
3. Access for servicin g AccuLoad III is through the front cover. For ease of s ervice and removal of parts the cover mus t swing open more than 9 0° T
he explosion-proof AccuLoad III is hinged o
t
he left.
4. Conduit entry to the explosion-proof AccuLoa III is both through the bottom and top. The top entries are used for those units where the C
Grounding and overfill board is installed.
VACON
For the ALIII-S hardwar e there are three 1-1/4"
11.5 NPT conduit entranc es in the bott om of t uni
t and two 1" 11.5 NPT conduit entrances in
he
the top of the unit. For the ALIII-Q hardware there are two 1-1/4" 11.5 NPT c onduit en trances and five 1" 11.5 NPT conduit entrances in the bottom of the unit and one 1" 1 1.5 NPT conduit entrance in the top of the unit.
5. In warm climates , AccuLoad III should be sha d­ed from direct sunlight. The maximum external temperature of the AccuLoad III housing must not exceed 140°F (60°C) to ensure th at the in­ternal temperature limit is not exceeded.
Table 1. Typical Wire Sizes
e
.
n
d
I-
Equipment
Transmitters
Temp. Probes
Density & Pressure
Transmitters
EIA-232
Communications
EIA-485
Communications
T
able 2. Maximum Cable Length and Baud Rate
Number &
Gauge of
4 / 18 Ga. 4 / 20 Ga.
4 / 22 Ga.
3 / 24 Ga. 9533
4 / 24 Ga. 9842
Belden Number or Equivalent
9418 8404
8729
OR
9940
(EIA-232)
Baud Rate Feet Meters
38,400 250 75 19,200 500 150
9,600 1,000 305 4,800 2,000 610 2,400 4,000 1,220 1,200 4,000 1,220

Electrical

1. All DC wiring must be routed into AccuLoad III
MN06135 Issue/Rev. 1.3 (6/17) 3
through the c onduit entries located in the b ottom of the housing. Do not route DC and AC wiring through the same conduit entry.
T
able 3. Maximum Cable Length and Baud Rate
(EIA-485)
1,200 to 38,400 4,000 1,220
te: For Et hernet communications, refer to standard IT
No
practices for connecting any AccuLoad using routers, hubs, switches, etc.
Page 10
Section II – Pre-Installation Considerations
3. All AC wiring must be routed into AccuLoad III through the conduit entr ies loc ated in the bottom of the housing. Connec tors s ized for a m ax imum of 14-gauge wire, consult the local electrical codes for the minim um AC wire si ze required for your application. Do not ro ute AC and DC wiring through the same conduit entry.
4. All AC wiring should be stranded copper and must comply with federal, state and local codes and specifications.
5. Two separate AC circ uits m ust be pro vided fr om the breaker panel. One circuit will supp ly isolat­ed power to the AccuLoad III electronics (in­strument power). The second circuit will supply power to the external devices.
6. For proper operation the AccuLoad III must earth grounded. The grounding point should be as close to th e u ni t as pos sible. To e ns ur e proper earth ground:
a) The resistance between the ground lug in
the AccuLoad III and the grounding point must not exceed 2 Ω.
b) The proper grounding point is a ½ " to ¾" di-
ameter copper stake that extends into the water table. Where this is not practical, a ground plane may be used.
Note: E lectrical conduit, piping, and structural steel are
considered proper grounding points for equipment
not using electronics.
be
Environmental
Models ALIII-S-XP and ALIII-Q-XP
The enclosures of Explosion / Flame proof models are manufactured f rom aluminum alloy, and are de­signed to be operated in n ormal environmental con­ditions free of corrosive agents.
In areas including but n ot limited to environment ally corrosive atmospheres, special considerations for additional environm ental pr otections shal l be made if installing into near shore areas that are subject to wind borne salt sea water s pray and subject to pos­sible continuous ac cumulations of wetted salt water on the equipment. The recommended protection is
exclusion of the environment by placing the equip­ment into secondar y protected environm ent such as a kiosk or a control room. If exclusion of the envi-
ronment is not pos sible, then extra means m ust be taken to maintain the equipment integrity, this in­cludes frequent cleaning and inspection intervals. See Section IV for additional information.
In areas where the ambient temperature is very high, it is recommended that the equipment be in­stalled under a canopy / sun shield to limit direct sunlight radiation.
In areas of high humidity (tropical) or with varying temperature swings, it is recommended to place TechnipFMC P/N 647 001 443 or similar desiccant packs inside of the enclosures, and to maintain these while in service.
c) No other devices, excep t AccuLoad IIIs and
ancillary equipment such as load printers, should be connected to any point in the grounding circuit.
7. If external relay permissives are used in series with AccuLoad III relays, an RC network must pl
aced in parallel with the permissive to pr event a false turn-on of t he AccuLoad III relays. Rec­ommended RC network = 0.1 UF capacitor and a 680 resistor (Electrocube part number RG 2031-11).
8. Interposing relays m ust be insta lled bet ween th p controller, alarm ing device, and the Accu-
pum Load III permissive sense relays.
MN06135 Issue/Rev. 1.3 (6/17) 4
be
e
Page 11

Section III – Installation

Mechanical

See Pre-installation Considerations.

Electrical

ATEX & IEC EX - Approved Units
(a) Cable Entry must be in accordance to IEC
60079-1 section 13 :
For systems utili zing ca ble glands , the glan d and/or thread adaptor m ust be Ex certified. The cable end must be securely installed and, depending on the cable type, be properly protected from mechanical dam­age. Requirements o utlined in Section 10.4 of IEC 60079-14 shall be followed.
(b) Cable Entry must be in accordance to IEC
60079-1 section 13 :
For systems utilizing c onduit, an Ex cer tified sealing device must be immediately at the entrance of the enc los ure. Any unused entr y must be suitably blocked with an Ex d IIB certified plug. Requirem ents outlined i n Sec­tion 10.5 of IEC 60079-14 shall be followed.
(c) Installation:
General Installation to b e in ac cordanc e with IEC 60079-14, wiring system to be in ac­cordance with section 9.
(d) Flame Pa th Di me nsi ons:
AccuLoad Joint Dimensions: Flanged joint widths are 19.05 mm minimum and gaps are
0.051 mm maxim um. Flameproof joints sh all be maintained as outl ined in section 1 0.4 or IEC 60079-14.
(e) Cover Fasteners:
AccuLoad Special Fasten ers: Cover Bolts – steel grade 12.9, M8 x 1.25.
(f) Cautions and Warnings:
Caution: To prevent ignition of hazardous atmospheres, discon nect from supply circ uit before opening, keep tightly closed when circuits are in operation.
Warning: Contai ns internal batt ery-powered circuit, to prevent ignition of hazardous at­mospheres, do not open enclosure unless area is known to be non-hazardous.

General Requirements

It is imperative that the electrical installat ion be per­formed by a com petent i ndi vidual t hat is fam iliar with associated risks involved with the i nstal lation, opera­tion, and maintenance, of electrical equipment in hazardous (classif ied) loca tions. T his in dividua l m ust possess knowledge of local, national electrical codes, and/or ordinances c oncerned with hazardous location safety requirements. It is recommended (may be required i n some jurisdicti ons) that the final installation should be verified / inspec ted by the au­thority having jurisdiction before placing the equip­ment into service.
Electrical installat ions in hazardous areas have fea­tures specifically des igned to m ake them suitable for use in such locations and it is the oper ator’s res pon­sibility to maintain the in tegrity of those special fea­tures.
The operator must ensure that electrical equipment is:
a. Installed and operated correctly b. Monitored on a regular basis c. Maintained with due regard to safety d. Follow all requirements of National Electrical
Code for the country of installation.
e. A
C Circuits must be isolated from DC circuits and brought into the unit through their respec­tive conduit openings.
f. Be sure all connections on the terminal blocks
are tight.
ll shields must be connected to terminals 3,
g. A
13, 14, or 15 on terminal block TB4 on the EAAI Board or terminal 3 and 4 on terminal block TB6 on the KDC Board, or terminals 9 and 10 on
TB14 on the BSE Board.
ll exposed shields must be properly insulated
A to prevent short circuits to other terminals or to the chassis. The shield at the device (e.g., tem­perature device, transmitter, etc.) must be cut back to the insulation and taped off. All shields should be continuous. If splices are required, they must be soldered and properly insulated. If other communicating devices are used with the AccuLoad III, refer to the manual for that unit for shielding information. Shields for other com­municating equipment should not be te r minated in the AccuLoad III.
MN06135 Issue/Rev. 1.3 (6/17) 5
Page 12
Section III – Installation
Note: Shields must not be termina ted at the groun d lugs.
h. S
ufficient slack should be provided for the wir­ing in the AccuLoad III to permit easy removal of the boards. With sufficient slack, the terminal blocks can be removed and laid back out of t way so that the boards can be replaced without removing individual wires.
here is a ground lug provided in the unit. The
i. T
wire from the lug should be connected to t
roper grounding point. See Pre-Installation
p Considerations, page 2.
j. T
ypical electrical installation diagrams are pro­vided in the following sections to show the Ac­cuLoad III and ancillary equipment. Before wir­ing the ancillary equipment, refer to its installa­tion manual.
he
he
Installing and Removing the Analog I/O Module
C
aution: Turn off the power at the unit prior to installing
or removing the Analog I/O Module. Failure to do so will damage modules.
Care should be taken when installing or removing the Analog I/O modules so as not to damage the board or the module. To install the module, line up the alignment pins with the socket and push down on the module. Once it is seated, screw in the mounting screw until tight. Do not over-tighten the screw. To remove the modules from the board, loos­en the mounting screw and pull up on the module.
nput Frequency x2
I
If the application requir es a pulse rate that is higher than the meter is capable of putting out, the Accu­Load III can multiply the incoming pulses times 2. This option is activated by switches located on the PIB boards. The PIB b oar d s are loc at ed on t he EA AI and the BSE boards.
F
igure 2. Connector and Switches on PIB Board
The default setting from the factory is “tim es 1.” The switch is closed (ON). To m ultiply the incom ing puls­es times 2, push the switch of the incoming pulse channel to the open (OFF) position. The switches are located on the PIB boards, as shown in Figure 2. The PIB board that is loc ated on the EAAI board is for pulse inputs 1 t hrough 6. The PIB board that is located on the BSE board is for pulse inputs 7 through 12.
te: The switches correspond to the pulse input channels (i.e.,
No
Meter Pulse In #1 is equal to Switch #1.) See Table 6 for corre­sponding Pulse Input channels.
Start-Up
When the wiring is completed and verified, power may be applied to the unit. T he displa ys shoul d light, indicating that the AccuLo a d III is r ead y for Start-Up. Please reference the Operator Reference Manual.
igure 1. Analog Modules
F
MN06135 Issue/Rev. 1.3 (6/17) 6
Page 13

Section IV– Diagrams

igure 3. AccuLoad III-Q Dimensions
F
MN06135 Issue/Rev. 1.3 (6/17) 7
Page 14
Section IV – Diagrams
Figure 4. AccuLoad III-S Dimensions
MN06135 Issue/Rev. 1.3 (6/17) 8
Page 15
Section IV – Diagrams
1 – In
4 – Out
7 – Out
10 – Out
13 – In
16 – Out
25 – Out
2 – In
5 – Out****
8 – Out
11 – In
14 – Out
23 – In*
3 – In
6 – In***
9 – Out
12 – Out
15 – In
24 – In**
Figure 5. KDC Layout
Configurable jum per locations are heav ily circled on the d iagram above. It is im portant to note that a ll but one of these jumpers, J22, are f ac tory defaults and sho ul d n o t be configured by the user. The pr oper settings are pr ov id­ed below so if one of thes e is accidentally chang ed, it can be returned to its original position. J22 is the jumper used to zero the passcode s and security input acc ess level (151-157). Jumpers are conf igured using the plugs that fit over the jumper pr ongs. A jumper with no prongs plu gged, or with one prong plugged, is OUT. A jumper with both prongs plugged is IN.
Note: Should Program Mode be inaccessible after changing PROMs, or if the operator loses or forgets t he acc ess cod e, set J 22 to In, then power up. Entry to the program mode is provided. Check passcodes and remove jumper J22 when finished.
* Jumper 23 if removed indicates there is not a BSE board in the System (ALIII-S Hardware) ** Jumper 24 if removed indicates there is only one display (ALIII-S Hardware) *** For units shipped prior to October 2001: J6 must be in the “in" position for Optrex Model DMF5003N. For units shipped after October 2001: J6 must be in the “out" position for Model MTG-2406 displays. **** For units shipped prior to August 2005: J5 must be in the “out” position. After August 2005 and for all units with Rev. B displays, the Jumper J5 must be in the “in” position.
MN06135 Issue/Rev. 1.3 (6/17) 9
Page 16
Section IV – Diagrams
Ribbon Cable
Switch Settings
A new 8 pin DIP switch will be available for use (SW  SW1-8). The switch will be utilized as follows: SW1-1 force firmware upgrade (powers up waiting for firmware upgrade)
SW1-2 SW1-3 OFF OFF use programmed IP address ON OFF use 192.168.0.1 OFF ON use 10.0.0.1 ON ON use DHCP
Figure 6. EAAI Layout
The user-configurabl e jum per on the E AAI bo ard is ind icated b y a circle and arr ow in the d iagram abo ve. Se e the table on the following page f or an explan ation of analo g m odule settings . This jumper has been c onfig ured f or the modules that were s hi ppe d with the unit. Changes should only be m ade if d if f er ent modules are added or del eted. Modules must be installed with inputs first, followed by outputs.
MN06135 Issue/Rev. 1.3 (6/17) 10
Page 17
Section IV – Diagrams
Analog Module Settings (JP1 on EAAI)
6 Inputs, 0 Outputs
5 Inputs, 1 Output
4 Inputs, 2 Outputs
3 Inputs, 3 Outputs
Table 4. Analog Module Settings
2 Inputs, 4 Outputs
1 Input, 5 Outputs
0 Inputs, 6 Outputs
MN06135 Issue/Rev. 1.3 (6/17) 11
Page 18
Section IV – Diagrams
Figure 7. BSE Layout
Note: JP1 3 through 6 define the number of BIOB inputs. JP1 1 and 2 are not used.
MN06135 Issue/Rev. 1.3 (6/17) 12
Page 19
Section IV – Diagrams
Bi-State DC Inputs and Output Jumper Settings (JP1 on the BSE)
8 Inputs, 0 Outputs
7 Inputs, 1 Output
6 Inputs, 2 Outputs
5 Inputs, 3 Outputs
4 Inputs, 4 Outputs
Table 5. Bi-State Inputs and Outputs
3 Inputs, 5 Outputs
2 Input, 6 Outputs
1 Inputs, 7 Outputs
0 Inputs, 8 Outputs
MN06135 Issue/Rev. 1.3 (6/17) 13
Page 20
Section IV – Diagrams
Figure 8. KDC/EAAI/PIB/B SE Boards
MN06135 Issue/Rev. 1.3 (6/17) 14
Page 21
Section IV – Diagrams
EAAI PIB
+
-
+
-
+
-
+
-
-
+
-
+
Pulse In #1
Pulse In #2
Pulse In #4
Pulse In #3
Pulse In #6
Pulse In #5
3
12
11
7
10
9
8
5 6
4
1 2
PT1
Board
OFF = X2
On = X1
2 6543S11
8
Pulse In #10
­Pulse In #11
Pulse In #12
-
+
+
-
12
11
10
9
Pulse In #9
Pulse In #8
Pulse In #7
BSE PIB
ON
3
+
+
+
-
-
5
7
6
4
-
+
1 2
PT1
2
On = X1 OFF = X2
S1
5 63 4
ON
1
Board
Figure 9. PIB Boards
Note: AccuLoad III-S hardware has one PIB board.
PIB Update
Refer to MN06113
Note: If AccuLoad III Rev. 10.12 or higher is being used and the reverse fl ow is implemented; PIB board Rev. 3 or above must be used.
Pulse Inputs
6-Product Meters (AccuLoad III-Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 Single Pulse Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 Single Pulse Dual Pulse Dual/Integrity
MN06135 Issue/Rev. 1.3 (6/17) 15
Meter #1A Meter #2A Meter # 3A Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Meter # 3A Meter #2A Meter #2B Meter # 3B
N/A N/A N/A N/A N/A N/A
Meter #4A Meter #5A Meter #6A Injector/Dens. Injector/Dens. Injector/Dens. Meter #4A Meter #4B Meter #6A Meter #5A Meter #5B Meter #6B
N/A N/A N/A N/A N/A N/A
5-Product Meters (AccuLoad III-Q Hardware)
Meter #1A Meter #2A Meter # 3A Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Meter # 3A Meter #2A Meter #2B Meter # 3B
N/A N/A N/A N/A N/A N/A
Meter #4A Meter #5A Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #4A Meter #4B Injector/Dens. Meter #5A Meter #5B Injector/Dens.
N/A N/A N/A N/A N/A N/A
Page 22
Section IV – Diagrams
4-Product Meters (AccuLoad III-Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 Single Pulse Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 Single Pulse Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 Single Pulse Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 Single Pulse Dual Pulse Dual/Integrity
Meter #1A Meter #2A Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Injector/Dens. Meter #2A Meter #2B Injector/Dens. Meter #1A Meter #1B Meter #1A Bar Meter #2A Meter #2B Meter #2A Bar
Meter #3A Meter #4A Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #3A Meter #3B Injector/Dens. Meter #4A Meter #4B Injector/Dens. Meter #3A Meter #3B Meter #3A Bar Meter #4A Meter #4B Meter #4A Bar
3-Product Meters (AccuLoad III-Q Hardware)
Meter #1A Meter #2A Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Injector/Dens. Meter #2A Meter #2B Injector/Dens. Meter #1A Meter #1B Meter #1A Bar Meter #2A Meter #2B Meter #2A Bar
Meter #3A Injector Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #3A Meter #3B Injector/Dens. Reserved Reserved Injector/Dens. Meter #3A Meter #3B Meter #3A Bar Injector/Dens. Injector/Dens. Injector/Dens.
2-Product Meters (AccuLoad III-Q Hardware)
Meter #1A Meter #2A Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Injector/Dens. Meter #2A Meter #2B Injector/Dens. Meter #1A Meter #1B Meter #1A Bar Meter #2A Meter #2B Meter #2A Bar
Injector Injector Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Injector Injector Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Injector Injector Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens.
1-Product Meter (AccuLoad III-Q Hardware)
Meter #1A Reserved Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Reserved Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Meter #1A Bar Injector/Dens. Injector/Dens. Injector/Dens.
Injector Injector Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Injector Injector Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Injector Injector Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens.
MN06135 Issue/Rev. 1.3 (6/17) 16
Page 23
Section IV – Diagrams
6-Product Meters (AccuLoad III-S Hardware Rev. 10.08 and above firmware
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse N/A N/A N/A N/A N/A N/A
Meter #1A Meter #2A Meter #3A Meter #4A. Meter #5A. Meter #6A
Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse N/A Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse N/A Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Single Pulse Dual Pulse Dual/Integrity
N/A N/A N/A N/A N/A N/A
5-Product Meters (AccuLoad III-S Hardware Rev. 10.08 and above firmware
Meter #1A Meter #2A Meter #3A Meter #4A. Meter #5A. Injector/Dens.
N/A
N/A N/A N/A N/A N/A N/A
4-Product Meters (AccuLoad III-S Hardware Rev. 10.08 and above firmware
Meter #1A Meter #2A Meter #3A Meter #4A. Injector/Dens. Injector/Dens.
N/A
N/A N/A N/A N/A N/A N/A
3-Product Meters (AccuLoad III-S Hardware)
Meter #1A Meter #2A Meter #3A Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Meter #3A Meter #2A Meter #2B Meter #3B
N/A N/A N/A N/A N/A N/A
2-Product Meters (AccuLoad III-S Hardware)
Meter #1A Meter #2A Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Injector/Dens. Meter #2A Meter #2B Injector/Dens. Meter #1A Meter #1B Meter #1A Bar Meter #2A Meter #2B Meter #2A Bar
1-Product Meter (AccuLoad III-S Hardware)
Meter #1A Reserved Injector/Dens. Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Reserved Injector/Dens. Injector/Dens. Injector/Dens. Meter #1A Meter #1B Meter #1A Bar Injector/Dens. Injector/Dens. Injector/Dens.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Table 6. Pulse Inputs
Note: When using dual pulse and not the A Bar inputs for transmitter security, the pulse inputs for the A Bar assignment will be not used
MN06135 Issue/Rev. 1.3 (6/17) 17
Page 24
Section IV – Diagrams
Dual/Integrity
Dual Pulse
Dual Pulse Inputs for Rev. 10.07 and Above Firmware (With Flow Controlled Additive)
5 Product Meters with 1 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Dual/Integrity
Dual Pulse Meter #1A Meter #1B Meter #3A Meter #2A Meter #2B Meter #3B Dual/Integrity NA NA NA NA NA NA
Dual Pulse
Dual Pulse Dual/Integrity NA NA NA NA NA NA
Dual Pulse Dual/Integrity NA NA NA NA NA NA
Dual Pulse Meter #1A Meter #1B Meter #3A Meter #2A Meter #2B Meter #3B Dual/Integrity
Dual Pulse FC Inj #1A FC Inj #1B FC Inj #3A FC Inj #2A FC Inj #2B FC Inj #3B Dual/Integrity
Dual/Integrity
Dual Pulse FC Inj #1A FC Inj #1B Injector/Dens FC Inj #2A FC Inj #2B Injector/Dens Dual/Integrity NA NA NA NA NA NA
Meter #1A Meter #1B Meter #3A Meter #2A Meter #2B Meter #3B
NA NA NA NA NA NA
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12
Meter #4A Meter #4B FC Inj #1A Meter #5A Meter #5B FC Inj #1B
NA NA NA NA NA NA
4 Product Meters with 2 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12
Meter #4A Meter #4B FC Inj #2A FC Inj #1A FC Inj #1B FC Inj #2B
NA NA NA NA NA NA
4 Product Meters with 1 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Meter #1A Meter #1B Meter #3A Meter #2A Meter #2B Meter #3B
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12
Meter #4A Meter #4B Injector/Dens FC Inj #1A FC Inj #1B Injector/Dens
3 Product Meters with 3 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
NA NA NA NA NA NA
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12
NA NA NA NA NA NA
3 Product Meters with 2 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Meter #1A Meter #1B Meter #3A Meter #2A Meter #2B Meter #3B
NA NA NA NA NA NA
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12
MN06135 Issue/Rev. 1.3 (6/17) 18
Page 25
Section IV – Diagrams
3 Product Meters with 1 Flow Controlled Additive (AccuLoad III – Q Hardware)
Dual Pulse Dual/Integrity Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 Dual Pulse
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6 Meter #1A Meter #1B Injector/Dens Meter #2A Meter #2B Injector/Dens Meter #1A Meter #1B Meter #1 Bar Meter #2A Meter #2B Meter #2 Bar
Meter #3A Meter #3B Injector/Dens FC Inj #1A FC Inj #1B Injector/Dens
Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Dual/Integrity
Meter #3A Meter #3B Meter #3 Bar FC Inj #1A FC Inj #1B FC Inj #1 Bar
2 Product Meters with 4 Flow Controlled Additive (AccuLoad III – Q Hardware)
Meter #1A Meter #1B FC Inj #1A Meter #2A Meter #2B FC Inj #1B
NA NA NA NA NA NA
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12
FC Inj #2A FC Inj #2B FC Inj #4A FC Inj #3A FC Inj #3B FC Inj #4B
NA NA NA NA NA NA
2 Product Meters with 3 Flow Controlled Additive (AccuLoad III – Q Hardware)
Meter #1A Meter #1B FC Inj #1A Meter #2A Meter #2B FC Inj #1B
NA NA NA NA NA NA
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12
FC Inj #2A FC Inj #2B Injector/Dens FC Inj #3A FC Inj #3B Injector/Dens
NA NA NA NA NA NA
2 Product Meters with 2 Flow Controlled Additive (AccuLoad III – Q Hardware)
Meter #1A Meter #1B Injector/Dens Meter #2A Meter #2B Injector/Dens Meter #1A Meter #1B Meter #1 Bar Meter #2A Meter #2B Meter #2 Bar
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 FC Inj #1A FC Inj #1B Injector/Dens FC Inj #2A FC Inj #2B Injector/Dens FC Inj #1A FC Inj #1B FC Inj #1 Bar FC Inj #2A FC Inj #2B FC Inj #2 Bar
2 Product Meters with 1 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Dual/Integrity
MN06135 Issue/Rev. 1.3 (6/17) 19
Meter #1A Meter #1B Injector/Dens Meter #2A Meter #2B Injector/Dens Meter #1A Meter #1B Meter #1 Bar Meter #2A Meter #2B Meter #2 Bar
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 FC Inj #1A FC Inj #1B Injector/Dens Reserved Reserved Injector/Dens
FC Inj #1A FC Inj #1B FC Inj #1 Bar Injector/Dens Injector/Dens Injector/Dens
Page 26
Section IV – Diagrams
1 Product Meters with 4 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Dual/Integrity
Meter #1A Meter #1B FC Inj #2A FC Inj #1A FC Inj 1 B PC Inj #2B
NA NA NA NA NA NA
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 FC Inj #3A PC Inj #3B Injector/Dens FC Inj #4A FC Inj #4B Injector/Dens
NA NA NA NA NA NA
1 Product Meters with 3 Flow Controlled Additive (AccuLoad III – Q Hardware)
Meter #1A Meter #1B Injector/Dens FC Inj #1A FC Inj 1 B Injector/Dens Meter #1A Meter #1B Meter #1 Bar FC Inj #1A FC Inj 1 B FC Inj #1 Bar
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 FC Inj #2A PC Inj #2B Injector/Dens FC Inj #3A FC Inj #3B Injector/Dens FC Inj #2A PC Inj #2B PC Inj #2 Bar FC Inj #3A FC Inj #3B FC Inj #3 Bar
1 Product Meters with 2 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Dual/Integrity
Meter #1A Meter #1B Injector/Dens FC Inj #1A FC Inj 1 B Injector/Dens Meter #1A Meter #1B Meter #1 Bar FC Inj #1A FC Inj 1 B FC Inj#1 Bar
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12 FC Inj #2A PC Inj #2B Injector/Dens Reserved Reserved Injector/Dens FC Inj #2A PC Inj #2B PC Inj #2 Bar Injector/Dens Injector/Dens Injector/Dens
MN06135 Issue/Rev. 1.3 (6/17) 20
Page 27
Section IV – Diagrams
1 Product Meters with 1 Flow Controlled Additive (AccuLoad III – Q Hardware)
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Input #7 Input #8 Input #9 Input #10 Input #11 Input #12
Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Meter #1A Meter #1B Injector/Dens FC Inj A FC Inj 1 B Injector/Dens Meter #1A Meter #1B Meter #1 Bar FC Inj A FC Inj 1 B FC Inj Bar
Injector Injector Injector/Dens Injector/Dens Injector/Dens Injector/Dens Injector Injector Injector/Dens Injector/Dens Injector/Dens Injector/Dens
2 Product Meters with 1 Flow Controlled Additive (AccuLoad III – S Hardware)
Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Input #1 Input #2 Input #3 Input #4 Input #5 Input #6
Dual Pulse Dual/Integrity
Dual Pulse Security phase shift requirements between the A and B pulses: The AccuLoad will interpret a valid quadrature signal (90˚ phase shift between A and B pulses) if t1, t2, t3, and t4
are all greater than or equal to 25usec in the following diagram:
Meter #1A Meter #1B FC Inj #1A Meter #2A Meter #2B FC Inj #1 B
NA NA NA NA NA NA
1 Product Meter with 2 Flow Controlled Additive (AccuLoad III – S Hardware)
Meter #1A Meter #1B Injector/Dens. FC Inj A FC Inj 1 B Injector/Dens. Meter #1A Meter #1B Meter #1 Bar FC Inj A FC Inj 1 B FC Inj Bar
1 Product Meter with 1 Flow Controlled Additive (AccuLoad III – S Hardware)
Meter #1A Meter #1B Injector/Dens. FC Inj A FC Inj 1 B Injector/Dens. Meter #1A Meter #1B Meter #1 Bar FC Inj A FC Inj 1 B FC Inj Bar
MN06135 Issue/Rev. 1.3 (6/17) 21
Page 28
Section IV – Diagrams
Figure 10. Wiring Diagram, Prime 4 Meter Single Pulse
Note: Wiring between transmitter and AccuLoad should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shields to terminals 3, 13, 14, or 15 of Terminal Block 4.
Prime 4 Wire Codes:
Black: Common Red: Input Power White: Signal A Output Yellow: Signal B Output
MN06135 Issue/Rev. 1.3 (6/17) 22
Page 29
Section IV – Diagrams
Figure 11. Wiring Diagram, Prime 4 Meters Dual Pulse
Note: Drawing is shown with dual meters and each meter being shown wired as a dual pulse input. When not using the dual pulse input, see figure 10.
Note: Wiring between transmitter and AccuLoad should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shi elds to terminals 3, 13, 14, or 15 of Terminal Block 4.
Prime 4 Wire Codes:
Black: Common Red: Input Power White: Signal A Output Yellow: Signal B Output
MN06135 Issue/Rev. 1.3 (6/17) 23
Page 30
Section IV – Diagrams
Figure 12. Wiring Diagram, Genesis Meter Single Pulse
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shi elds to terminals 3, 13, 14, or 15 of Terminal Block 4.
Genesis Terminal Connections:
1: Input Power 2: Signal A Output 3: Signal B Output 4: Electronics Ground 5: Not used 6: Not used 7: Not used 8: Not used
MN06135 Issue/Rev. 1.3 (6/17) 24
Page 31
Section IV – Diagrams
Figure 13. Wiring Diagram, Genesis Meter Dual Pulse
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shields to terminals 3, 13, 14, or 15 of Terminal Block 4.
Genesis Terminal Connections:
1: Input Power 2: Signal A Output 3: Signal B Output 4: Electronics Ground 5: Not used 6: Not used 7: Not used 8: Not used
MN06135 Issue/Rev. 1.3 (6/17) 25
Page 32
Section IV – Diagrams
F
igure 14. Wiring Diagram, UPT Transmitter Single Pulse
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shi elds to terminals 3, 13, 14, or 15 of Terminal Block 4.
UPT Terminal Connections:
1: Electronics Ground
2: Input Power 3: Signal B Output
¯ Output
4: B 5: Signal A Output
¯ Output
6: A 7: Shield 8: Verification Pulse Output 9: Inverted Verification Pu lse 10: Not Used
MN06135 Issue/Rev. 1.3 (6/17) 26
Page 33
Section IV – Diagrams
Figure 15. Wiring Diagram, UPT Transmitter Dual Pulse
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shi elds to terminals 3, 13, 14, or 15 of Terminal Block 4.
UPT Terminal Connections:
1: Electronics Ground
2: Input Power 3: Signal B Output
¯ Output
4: B 5: Signal A Output
¯ Output
6: A 7: Shield 8: Verification Pulse Output 9: Inverted Verification Pulse Output 10: Not Used
MN06135 Issue/Rev. 1.3 (6/17) 27
Page 34
Section IV – Diagrams
Figure 16. Wiring Diagram, PEX-P Transmitter Single Pulse
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shi elds to terminals 3, 13, 14, or 15 of Terminal Block 4.
PEXP Wire Codes:
Black: Signal Red: Input Power White: Common
MN06135 Issue/Rev. 1.3 (6/17) 28
Page 35
Section IV – Diagrams
Figure 17. Wiring Diagram, PPS Transmitters Single Pulse
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shields to terminals 3, 13, 14, or 15 of Terminal Block 4.
PPST Terminal Connections
1: Common 2: Input Power 3: Signal B Output 4: B¯ Output 5: Signal A Output 6: A¯ Output
MN06135 Issue/Rev. 1.3 (6/17) 29
Page 36
Section IV – Diagrams
Figure 18. Wiring Diagram, PPS Dual Pulse Transmitter
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shields to terminals 3, 13, 14, or 15 of Terminal Block 4.
PPST Terminal Connections:
1: Common
2: Input Power 3: Signal B Output
¯ Output
4: B 5: Signal A Output
¯ Output
6: A
MN06135 Issue/Rev. 1.3 (6/17) 30
Page 37
Section IV – Diagrams
Figure 19. Wiring Diagram, Turbine Meters with PA-6 Preamps Single Pulse
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shields to terminals 3, 13, 14, or 15 of Terminal Block 4.
PA-6 Terminal Connections
1: Common 3: Signal Output 5: Input Power
MN06135 Issue/Rev. 1.3 (6/17) 31
Page 38
Section IV – Diagrams
Figure 20. Wiring Diagram, Dual Pulse Turbine Meters with PA-6 Preamps
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected able utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shields to terminals 3, 13, 14, or 15 of Terminal Block 4.
PA-6 Terminal Connections (Boss #2)
1: Common 3: Signal A Output 5: Input Power
PA-6 Terminal Connections (Boss #1)
1: Common 3: Signal B Output 5: Input Power
MN06135 Issue/Rev. 1.3 (6/17) 32
Page 39
Section IV – Diagrams
Transmitter/Sensor
Modeling
+ Terminal
- Terminal
80XXX
-X-XXX-X-X-X-X-X-X-X-A
242580XXX
-X-XXX-X-X-X-X-X-X-X-D
242580XXX
-X-XXX-X-X-X-X-X-X-X-S
242580XXX
-X-XXX-X-X-X-X-X-X-X-T
24
25
80XXX
-X-XXX-X-X-X-X-X-X-X-8
22
23
83XXX
-X-XXX-X-X-X-X-X-X-X-A
242583XXX
-X-XXX-X-X-X-X-X-X-X-B
242583XXX
-X-XXX-X-X-X-X-X-X-X-S
242583XXX
-X-XXX-X-X-X-X-X-X-X-T
24
25
83XXX
-X-XXX-X-X-X-X-X-X-X-C
24
25
83XXX
-X-XXX-X-X-X-X-X-X-X-D
242583XXX
-X-XXX-X-X-X-X-X-X-X-N
222383XXX
-X-XXX-X-X-X-X-X-X-X-P
222383XXX
-X-XXX-X-X-X-X-X-X-X-2
24
25
83XXX
-X-XXX-X-X-X-X-X-X-X-4
24
25
83XXX
-X-XXX-X-X-X-X-X-X-X-5
242584XXX
-X-XXX-X-X-X-X-X-X-X-S
242584XXX
-X-XXX-X-X-X-X-X-X-X-T
242584XXX
-X-XXX-X-X-X-X-X-X-X-N
222384XXX
-X-XXX-X-X-X-X-X-X-X-D
242584XXX
-X-XXX-X-X-X-X-X-X-X-2
24
25
Transmitter/Sensor
Modeling
+ Terminal
- Terminal
83XXX
-X-XXX-X-X-X-X-X-X-X-M
22, 24
23, 25 84XXX
-X-XXX-X-X-X-X-X-X-X-M
22, 24
23, 25 84XXX
-X-XXX-X-X-X-X-X-X-X-1
22, 24
23, 25
Promass 80, 83, and 84 Coriolis Meters
When connecting the Pro mass 84 (does not apply to the Promass 80 or 83 mode ls) to an AccuLoad, it is im­portant that the “Line Monitoring” function on the Promass 84 be disabled. This is because the pulse input circuitry of the AccuLoad requires the input puls e “off” voltage to be les s than one volt (and the “on” v oltage to be greater than 5 volts). If the “Line M onitoring” on the Promas s 84 is enabled, t he “off” voltage of the p ulses will be great er than one volt an d there fore will not be c ounted by the Acculoa d. T here ar e thr ee jumpers on eac h of t he fr equen­cy output submodules on t he I/O board t hat enab le/di sable th e “Lin e Monitor ing” function. The fac tory defau lt is to enable “Line Mo nitoring”. Follow the steps from sectio n 6.4.2 of the Pro line Promass 84 Op erating Instruction – Bulletin MN0M032 to enable/disable this function.
Table 7. Promass Modeling for Single Pulse Wiring
Table 8. Promass Modeling for Dual Pulse Wiring
Note: In dual pulse mode, Output 1 (24/25) leads Output 2 (22/23) when flowing in the forward direction.
MN06135 Issue/Rev. 1.3 (6/17) 33
Page 40
Section IV – Diagrams
Figure 21. Wiring Diagram, Promass 80, 83, and 84 Single Pulse
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect s hi elds to terminals 3, 13, 14, or 15 of Terminal Block 4.
Promass Wire Codes: Terminal 22/24: + Terminal 23/25: -
Note: The pulse input circuitry on the PIB has 1.6k of current limiting resistance “built-in” so that an external pull-up resistor is not required when an open collector output device is connected as shown.
MN06135 Issue/Rev. 1.3 (6/17) 34
Page 41
Section IV – Diagrams
Figure 22. Wiring Diagram, Promass 83 and 84 Dual Pulse
Caution: For clarity, shields not shown. Connect shi elds to terminals 3, 13, 14, or 15 of Terminal Block 4.
Promass Wire Codes:
Terminal 22: Output 2+ Terminal 23: Output 2­Terminal 24: Output 1+ Terminal 25: Output 1-
Note: The pulse input circuitry on the PIB has 1.6k of current limiting resistance “built-in” so that an external pull-up resistor is not required when an open collector output device is connected as shown.
MN06135 Issue/Rev. 1.3 (6/17) 35
Page 42
Section IV – Diagrams
Figure 22B. Wiring Diagram, GPST Dual Pulse Transmitter + 24 Vdc with Open Collector Output with Common Ground
Figure 22C. Wiring Diagram, GPST Dual Pulse Transmitter + 12 Vdc with Open Collector Output with Common Ground Converter P2412 see MN06117
MN06135 Issue/Rev. 1.3 (6/17) 36
.
Page 43
Section IV – Diagrams
Figure 23. Wiring Diagram, Open Collector Output
Note: Wiring between transmitter and Accuload should be done with a shielded cable per each transmitter. If selected cable utilizes twisted pairs, do not run more than one signal in a twisted pair.
Caution: For clarity, shields not shown. Connect shi elds to terminals 3, 13, 14, or 15 of Terminal Block 4. Note: This diagram assumes that each output’s collector and emitter are isolated.
MN06135 Issue/Rev. 1.3 (6/17) 37
Page 44
Section IV – Diagrams
METERED INJECTOR
PIB
+V SIG COMM
Typical Metered Injector Additive Meter
+24Vdc
Input
R
P.S.
GND
+V
Figure 24. Metered Injector to PIB Wiring Diagram
Caution: For clarity, shields not shown. Connect shields to terminals 3, 13, 14, or 15 of Terminal Block 4.
MN06135 Issue/Rev. 1.3 (6/17) 38
Page 45
Section IV – Diagrams
Figure 25. Wiring Diagram, Four Additive Meters
This diagram is valid only when using one or two product meters. For other setups refer to the table on pulse inputs for available wiring connections.
Caution: For clarity, shields not shown. Connect shi elds to terminals 3, 13, 14, or 15 of Terminal Block 4.
MN06135 Issue/Rev. 1.3 (6/17) 39
Page 46
Section IV – Diagrams
Voltage
Sense
Voltage
Sense
Voltage
Sense
Voltage
Sense
AccuLoad III
Valve Feedback Switches
#1
#2
#3
#4
Arm #1
Input #___
Input #___
Input #___
Input #___
N or L2
L1
Figure 26. Typical Block Valve Feedback Wiring
MN06135 Issue/Rev. 1.3 (6/17) 40
Page 47
Section IV – Diagrams
Voltage
Sense
Voltage
Sense
Voltage
Sense
Voltage
Sense
AccuLoad III
Injector Feedback Switches
#1
#2
#3
#4
Arm #1
Input #___
Input #___
Input #___
Input #___
N or L2
L1
Figure 27. Typical Additi ve Feed back Wiring
MN06135 Issue/Rev. 1.3 (6/17) 41
Page 48
Section IV – Diagrams
Figure 28. Electric Motor-Operated Block Valve/Pump Control
MN06135 Issue/Rev. 1.3 (6/17) 42
Page 49
Section IV – Diagrams
R2A R2B R2C R2D R2N
R1A
R1B
R1C
R1D
R1N
Notes:
1.This figure shows wiring for a typical pump and alarm contact array for multipl
e
A
ccuLoad III-controlled load arms if the pump and alarm control options are used.
2.R1A through R1N represent the contacts of the customer-supplied relay (R1)
on
th
e output of the AccuLoad III pump permissive contacts.
3.R2A through R2N represent the contacts of the customer-supplied relay (R2)
on
the
output of the AccuLoad III alarm permissive contacts.
4. An interposing relay must be used between the pump controller and the Acc
uLoad
III p
ump contacts.
Pump Controller
L1
N
B1B1
Figure 29. AccuLoad III Pump and Alarm Contacts
MN06135 Issue/Rev. 1.3 (6/17) 43
Page 50
Section IV – Diagrams
Figure 30. Wiring Schematic, Hi gh Speed Prover Output (Open Collector Opto Coupler)
Caution: For clarity, shields not shown. Connect shields to terminals 3, 13, 14, or 15 of Terminal Block 4.
MN06135 Issue/Rev. 1.3 (6/17) 44
Page 51
Section IV – Diagrams
RTD +
SIG +
SIG -
RTD -
Ground (TB6)
AccuLoad III - EAAI
Red Red
Black Black
Terminal Block TB5
1 2
3 4
10
RTD -
SIG -
SIG +
RTD +
8
7
6
5
Probe Meter #2
Resistance Temperature
Black
Black
Red Red
Probe Meter #1
Resistance Temperature
SIG -
RTD -
RTD +
SIG +
11
12
9
10
Black Black
Resistance Temperature
Probe Meter #3
Red
Red
RTD -
RTD +
SIG +
SIG -
8
13 14
7
Probe Meter #4
Resistance Temperature
Black
Black
Red
Red
Terminal Block as noted
Ground (TB6)
9
TB6 TB5 TB5 TB6
TB6
5
RTD +
SIG -
RTD -
SIG +
TB5 TB6
TB5
16
6
15
TB5
SIG +
RTD -
SIG -
TB6
TB5
RTD +
TB6
17
4
18
3
Red
Black Black
Resistance Temperature
Probe Meter #5
Red
Red
Probe Meter #6
Resistance Temperature
Black
Black
Red
Figure 31. Resistance (RTD) Input
Note: If using two twisted pairs of wires, RTD+ and RTD– should be wired with one twisted pair. Sig+ and Sig– should be wired with another twisted pair.
Used for temperature input from a platinum RTD. This input requires a four-wire connection to a platinum sensor with the following specification:
1. 100
2. 0.00385
MN06135 Issue/Rev. 1.3 (6/17) 45
@ 0 Degrees Celsius.
Ω ⁄ Ω ⁄
Deg. C., DIN 43760, BS1904, or IPTS 1948 Temperature Coefficient.
Page 52
IN X+
IN X-
AccuLoad III - EAAI
AC Power
Supply
L1
Terminal Block TB2
Remote Stop or
Remote Start
(Momentary Contact)
L2 or
Neutral
Figure 32. AC Remote Start and Stop
Section IV – Diagrams
Figure 33. DC Remote Start and Stop
MN06135 Issue/Rev. 1.3 (6/17) 46
Page 53
RTD +
SIG X +
SIG X -
RTD -
Ground (TB4)
AccuLoad III - EAAI
4-20mA
Transmitting Device
Vin
GND
Terminal Block TB5
External
Power
RTD +
SIG X +
SIG X -
RTD -
Ground (TB4)
AccuLoad III - EAAI
4-20mA
Transmitting Device
Vin
GND
Terminal Block TB5
Figure 34. 4-20mA Inputs (Active)
Section IV – Diagrams
Figure 35. 4-20mA Inputs (Passive)
The 4-20mA inputs are isolated from the processor and main power and can be programm ed f or the f u nction requ ired by the application. The analog inputs are also scaleable through the I/O Configuration Menu of the unit. The inputs should be wired with shielded twisted pairs of wires of 18 to 24 gauge.
MN06135 Issue/Rev. 1.3 (6/17) 47
Page 54
Section IV – Diagrams
RTD +
SIG X +
SIG X -
RTD -
Ground (TB4)
AccuLoad III - EAAI
1-5 Vdc
Transmitting Device
Vin
No Connection
No Connection
Terminal Block TB5
RTD +
SIG X +
SIG X -
RTD -
Ground (TB4)
AccuLoad III - EAAI
No Connection
No Connection
4-20mA
Receiving Device
Terminal Block TB5
Figure 36. 4-20mA Outputs
The 4-20mA outputs are isolated from the processor and main power and can be program med for the function required by the applicati on. T he analog outpu ts are als o s caleable thr ough t he I/O Configurat ion Men u of t he unit. The outputs should be wired with shielded twisted pairs of wires of 18 to 24 gauge.
Figure 37. 1-5 Vdc Input
The 1-5 Vdc inputs are isolated f rom the processor and main power and can be programm ed for the function required by the applicati on. The inputs are scalabl e through the I/O Conf iguration Menu of the unit. The inputs should be wired with shielded twisted pairs of wires of 18 to 24 gauge.
MN06135 Issue/Rev. 1.3 (6/17) 48
Page 55
Section IV – Diagrams
AM #1 + 2
EAAI
TB5
AM #2 + 6
EAAI
TB5
AM #4 + 13
EAAI
TB5
AM #5 + 15
EAAI
TB5
RTD +
SIG X + SIG X -
RTD -
Ground (TB4)
AccuLoad III - EAAI
1-5 Vdc
Receiving Device
Vin
No Connection
No Connection
Vout
Terminal Block TB5
Figure 38. 1-5 Vdc Output
The 1-5 Vdc outputs are is olated from the processor and m ain power and can be programmed for the f unction required by the applic ation. The outputs are also scal eable through the I/O Configurat ion Menu of the unit. The outputs should be wired with shielded twisted pairs of wires of 18 to 20 gauge.
Wiring Terminals, 4-20mA and 1-5 Vdc Inputs/Outputs
Module Number Connection Terminal Number Board Terminal Block
AM #1 - 3 EAAI TB5 AM #1 Shield 3, 13, 14, or 15 EAAI TB4
AM #2 - 7 EAAI TB5 AM #2 Shield 3, 13, 14, or 15 EAAI TB4 AM #3 + 10 EAAI TB5 AM #3 - 11 EAAI TB5 AM #3 Shield 3, 13, 14, or 15 EAAI TB4
AM #4 - 14 EAAI TB5 AM #4 Shield 3, 13, 14, or 15 EAAI TB4
AM #5 - 16 EAAI TB5 AM #5 Shield 3, 13, 14, or 15 EAAI TB4 AM #6 + 17 EAAI TB5
Table 9. Analog Terminal Connection
AM #6 - 18 EAAI TB5 AM #6 Shield 3, 13, 14, or 15 EAAI TB4
MN06135 Issue/Rev. 1.3 (6/17) 49
Page 56
Section IV – Diagrams
IN X+
IN X-
AccuLoad III - EAAI
AC Power
Supply
Input Device
V+
V-
Terminal Block TB2
Digital Inputs
The AccuLoad III is c apa ble of pr ovid ing f ourt een D C d igita l in puts and n ine AC d igita l inp uts (s tan dar d). T he in puts can be program m ed as to f unct ion t hroug h the c onfi gur ation d irec tor y. Ei ght of the DC digit al in puts are bi -stat e and can be used as either in puts or outputs depending on how the y are pr ogramm ed and wire d. (See Tab les 8 and 10 for digital inputs terminal connections. For optional AICB inputs, see Table 18.)
Figure 39. DC Inputs
Figure 40. AC Inputs
MN06135 Issue/Rev. 1.3 (6/17) 50
Page 57
Section IV – Diagrams
Wiring Terminals, Digital Inputs
Input # Voltage Type Board Terminal Block
1 DC KDC TB4 1 2 2 DC KDC TB4 3 4 3 DC KDC TB4 5 6 4 DC EAAI TB4 5 4 5 DC EAAI TB4 7 6 6 DC EAAI TB4 9 8 7 AC EAAI TB2 2 1 8 AC EAAI TB2 3 1
9 AC EAAI TB2 4 1 10 AC EAAI TB2 5 1 11 AC EAAI TB2 6 1
Terminal
Input (+)
Connections
Common (-)
12 AC BSE TB11 1 5 13 AC BSE TB11 2 5 14 AC BSE TB11 3 5 15 AC BSE TB11 4 5
Table 10. Digital Inputs
MN06135 Issue/Rev. 1.3 (6/17) 51
Page 58
Section IV – Diagrams
Out X-
Out X+
AccuLoad III KDC
DC Power
SupplyDevice
V+
V-
Receiving
Alarm,
Valve,
Etc.
Terminal Block TB5
Out X-
Out X+
AccuLoad III - EAAI
AC Power
SupplyDevice
V+
V-
Receiving
Alarm,
Valve,
Etc.
Terminal Blocks TB3 & TB7
Digital Outputs
The AccuLoa d III is c apable of prov iding el even DC digital ou tputs and twenty-seven AC digital o utputs ( standard) . The outputs can be pro gra mm ed as to f unctio n thr ough the conf igurati on direc tor y. Eight of the D C d igital ou tputs are bi-state and can be use d as either inputs or output s depen ding on h ow the y are progr amm ed and wir ed. (See Tables 9 and 10 for digital outputs terminal connections. For optional AICB outputs, see Table 19.)
Figure 41. DC Outputs
Figure 42. AC Outputs
MN06135 Issue/Rev. 1.3 (6/17) 52
Page 59
Section IV – Diagrams
Wiring Terminals, Digital Outputs
Output # Voltage Type Board Terminal Block
1 DC KDC TB5 1 2
2 DC KDC TB5 3 4
3 DC KDC TB5 5 6
4 AC EAAI TB3 1 2
5 AC EAAI TB3 3 4
6 AC EAAI TB3 5 6
7 AC EAAI TB3 7 8
8 AC EAAI TB3 9 10
9 AC EAAI TB3 11 12 10 AC EAAI TB7 1 2 11 AC EAAI TB7 3 4
Terminal
Output (+)
Connections
Common (-)
12 AC EAAI TB7 5 6 13 AC EAAI TB7 7 8 14 AC EAAI TB7 9 10 15 AC BSE TB10 1 2 16 AC BSE TB10 3 4 17 AC BSE TB10 5 6 18 AC BSE TB10 7 8 19 AC BSE TB10 9 10 20 AC BSE TB9 1 2 21 AC BSE TB9 3 4 22 AC BSE TB9 5 6 23 AC BSE TB9 7 8 24 AC BSE TB9 9 10 25 AC BSE TB9 11 12 26 AC BSE TB8 1 2 27 AC BSE TB8 3 4 28 AC BSE TB8 5 6 29 AC BSE TB8 7 8 30 AC BSE TB8 9 10
Table 11. Digital Outputs
MN06135 Issue/Rev. 1.3 (6/17) 53
Page 60
Input* Output*
Section IV – Diagrams
Voltage
Type
Board
Terminal
Block
Terminal Connections
16 31 DC BSE TB12 1 2 3 17 32 DC BSE TB12 4 5 6 18 33 DC BSE TB12 7 8 9 19 34 DC BSE TB12 10 11 12 20 35 DC BSE TB13 1 2 3 21 36 DC BSE TB13 4 5 6 22 37 DC BSE TB13 7 8 9 23 38 DC BSE TB13 10 11 12
Table 12. Bi-State Inputs/Outputs
*Note: Relay numbers for programming
Input + Common - Output +
MN06135 Issue/Rev. 1.3 (6/17) 54
Page 61
Section IV – Diagrams
Figure 43. KDC Typical Diagram
MN06135 Issue/Rev. 1.3 (6/17) 55
Page 62
Section IV – Diagrams
Figure 44. KDC Pulse Output 3, 4, and 5 Connections
Note: Maximum Frequency of these pulse outputs is 125 Hz. Pulse Output 3: Terminals 1 and 2 on TB4 and 1 and 2 on TB5. Pulse Output 4: Terminals 3 and 4 on TB4 and 3 and 4 on TB5. Pulse Output 5: Terminals 5 and 6 on TB4 and 5 and 6 on TB5.
MN06135 Issue/Rev. 1.3 (6/17) 56
Page 63
Section IV – Diagrams
Figure 45. KDC Pulse Output 3, 4, and 5 Connections to Smith Meter Ticket Printer
Note: Maximum Frequency of these pulse outputs is 125 Hz.
Pulse Output 3: Terminals 1 and 2 on TB4 and 1 and 2 on TB5. Pulse Output 4: Terminals 3 and 4 on TB4 and 3 and 4 on TB5. Pulse Output 5: Terminals 5 and 6 on TB4 and 5 and 6 on TB5.
MN06135 Issue/Rev. 1.3 (6/17) 57
Page 64
Section IV – Diagrams
Tx Rx
Gnd
AccuLoad III
Tx
Rx
Gnd
Tx Rx
Gnd
Tx
Rx
Gnd
Tx
Rx
Gnd
Shield
Communicating
Device
AccuLoad III
AccuLoad III
AccuLoad III
Figure 46. EIA-232 Multi-Drop Communications
The figure shows the typical wiring scheme for multi-drop com munications betwee n a c om munications device and multiple AccuLoad IIIs. R efer to the table below for pin numbers on each of the EIA-232 communication p orts. Note that the shield is to be terminated at the communication device.
Table 13. EIA 232 Communication Ports
Note: Communications Ports 1 and 2 can be either EIA-232 or EIA-485.
Comm Port Tx Rx Common Board Terminal Block
1 1 2 5 KDC TB1
2 1 2 3 KDC TB2
4 1 2 3 EAAI TB4
MN06135 Issue/Rev. 1.3 (6/17) 58
Page 65
Section IV – Diagrams
Figure 47. Network configuration for multiple AccuLoads connected via a hub then linked directly to the automation system and LAN.
Refer to the stan dards I EE E 802.X st ates f or wiring a nd using Ether net conn ecti vit y rules an d re gulat ions. Utili ze standard IT practices and protocol when connecting several AccuLoads to any type of hub, router, or switching device. There are various c onnec tivit y conf igura tions a nd the respons ibilit y of each confi gurati on is left t o eac h in dividu al. Distances, tr ansmission tim e, etc . wi ll a ll f oll ow t he s tan dard IE EE s pec rat ing. If th ere are an y ques ti ons r egar ding installation of multiple AccuLoads over Ethernet communications, please consult the factory.
Employ the standard CAT 5 Cable, used for connecting an AccuLoad to any router, switch, or hub.
MN06135 Issue/Rev. 1.3 (6/17) 59
Page 66
Section IV – Diagrams
AccuLoad III
Tx -
Rx +
Communicating
Device
Tx/485+
Rx/485-
Shield
Tx +
Rx -
Rx -
Rx +
Tx -
Tx +
Tx +
Tx -
Rx + Rx -
AccuLoad III
AccuLoad III
AccuLoad III
Rx -
Rx +
Tx -
Tx +
Tx/485-
Rx/485+
Figure 48. EIA-485 Multi-Drop Communications
The figure shows the typical wiring scheme for multi-drop com munications betwee n a c om munications device and multiple AccuLoad IIIs. R efer to the table below for pin numbers on each of the EIA-485 communication p orts. Note that the shield is to be terminated at the communication device.
Comm Port Tx + Tx - Rx + Rx - Board
1 6 7 8 9 KDC TB1 2 4 5 6 7 KDC TB2
Terminal
Block
3 1 2 3 4 KDC TB3
Table 14. EIA-485 Communication Ports
Note: Communications Ports 1 and 2 can be either EIA-485 or EIA-232.
MN06135 Issue/Rev. 1.3 (6/17) 60
Page 67
Section IV – Diagrams
Figure 49. Lubrizol EIA-232 Communications
MN06135 Issue/Rev. 1.3 (6/17) 61
Page 68
Section IV – Diagrams
Rx
Tx
Additive Systems
Rx
Tx
+
­+
-
Rx
-
Tx
Rx
+
-
Tx+
Rx
Rx
-
Tx
Rx +
-
Tx
+
-
Tx
Rx +
Tx+
-
Rx
Rx
-
Tx
Rx +
-
Tx
+
-
+
Rx
Tx
Rx +
Tx
+
-
Rx
-
+
Tx Tx
-
Rx
-
Rx
Tx
+
-
Tx
+
Blend Pak
Figure 50. EIA-485 (Four-Wire) Additive Communication (Lubrizol Blend-Pak)
MN06135 Issue/Rev. 1.3 (6/17) 62
Page 69
Section IV – Diagrams
Tx
Rx
Additive Systems
Tx
Rx
+
­+
-
Tx
-
Rx
Tx+
-
Rx
+
Tx
Tx
-
Rx
Tx+
-
Rx +
-
Rx
Tx+
Rx +
-
Tx
Tx
-
Rx
Tx+
-
Rx
+
-
+
Tx
Rx
Tx
+
Rx
+
-
Tx
-
+Rx
Rx-
Tx
-
Tx
Rx
+
-
Rx +
Figure 51. EIA-485 (Four-Wire) Additive Communication (Titan Pa c3)
MN06135 Issue/Rev. 1.3 (6/17) 63
Page 70
Section IV – Diagrams
Parameter
AccuLoad III
Promass
Baud Rate
38400
38400
Parity
8/No Parity/2 Stop bits
No Parity, 2 stop bits
Modbus Endian
Big
Byte order 3-2-1-0
Sequence Number
1
Address 1
Mass Meter type
Promass
Timeout
0 Transmission Mode
RTU
Reply delay
10 mS
Figure 52. Promass Coriolis Meter Communications
Programming
MN06135 Issue/Rev. 1.3 (6/17) 64
Page 71
Section IV – Diagrams
Figure 53. Two-Arm Straight Product Loading as Configured Through AccuMate (AccuLoad III-S Hardware)
MN06135 Issue/Rev. 1.3 (6/17) 65
Page 72
Section IV – Diagrams
Figure 54. Six-Arm Straight Product Loading as Configured Through AccuMate (AccuLoad III-Q Hardware)
MN06135 Issue/Rev. 1.3 (6/17) 66
Page 73
Section IV – Diagrams
METERED INJECTOR
OR
PULSE TRANSMITTER
AICB
+V SIG COMM
V+ (SELECTABLE) SIG COMM
Monoblock Additive Meter
METERED INJECTOR
OR
PULSE TRANSMITTER
AICB
SIG COMM
Monoblock Additive Meter
Digital Inputs – AICB
Figure 55. Metered Injector / Pulse Transmitter Wiring Diagram
Figure 56. Metered Injector / Open Collector Wiring Diagram
MN06135 Issue/Rev. 1.3 (6/17) 67
Page 74
Section IV – Diagrams
METERED INJECTOR
OR
PULSE TRANSMITTER
AICB
SIG COMM
Monoblock Additive Meter
Figure 57. Metered Injector / Contact Closure Wiring Diagram
MN06135 Issue/Rev. 1.3 (6/17) 68
Page 75
Section IV – Diagrams
Optional AICB Board(s) (Additive Inputs/Outputs)
Terminal connections for the optional AICB board are shown in Figure 6. Metered Additive Pulses 1 and 2 (AccuLoad III-S) or Metered Additive Pulses 1 through 4 (AccuLoad III-Q)
are wired into the PIB board o n the EAAI bo ard. Mete red Additives 5 through 24 are w ired to the A ICB boar d(s). Connections are shown in the table below.
Meter Pulses (Optional AICB #1)
Injector # Metered Additive Pulses
ALIII-S
Hardware
5 5 TB5 1 2 3
6 6 TB5 4 5 6
7 7 TB5, TB4 7 (TB5) 8 (TB5) 1 (TB4)
8 8 TB4 2 3 4
9 9 TB4 5 6 7
10 10 TB4 8 9 10 11 11 TB3 1 2 3 12 12 TB3 4 5 6 13 13 TB3 7 8 9 14 14 TB3 10 11 12
N/A 15 TB5 1 2 3 N/A 16 TB5 4 5 6 N/A 17 TB5, TB4 7 (TB5) 8 (TB5) 1 (TB4) N/A 18 TB4 2 3 4
ALIII-Q
Hardware
Terminal Block + Voltage Signal Common
Meter Pulses (Optional AICB #2)
N/A 19 TB4 5 6 7 N/A 20 TB4 8 9 10 N/A 21 TB3 1 2 3 N/A 22 TB3 4 5 6 N/A 23 TB3 7 8 9 N/A 24 TB3 10 11 12
Table 15. Meter Pulses (Optional AICB #1 and #2)
MN06135 Issue/Rev. 1.3 (6/17) 69
Page 76
Section IV – Diagrams
Additive Pumps (Optional AICB #1)
Additive Pump #
ALIII-S Hardware
ALIII-Q Hardware
Terminal +V
Terminal Block
5 5 10
TB8 6 6 8 TB8 7 7 6 TB8 8 8 4 TB8 9 9 2 TB8
10
10
10
TB7
11
11
8
TB7
12
12
6
TB7
13
13
4
TB7
14
14
2
TB7
Additive Pumps (Optional AICB #2)
N/A
15
10
TB8
N/A
16
8
TB8
N/A
17
6
TB8
N/A
18
4
TB8
N/A
19
2
TB8
N/A
20
10
TB7
N/A
21
8
TB7
N/A
22
6
TB7
N/A
23
4
TB7
N/A
24
2
TB7
Additive Pumps 1 thr ough 4 are wired to the progr ammed term inals on the EAAI bo ard. Additi ve Pumps 3 t hrough 12 (AccuLoad III-S hardware) or Additive Pumps 5 through 24 (AccuLoad III-Q hardware) are w ire d per th e fol lowing table. Terminals are automatically assigned as additive pumps if metered injectors are programmed in the AccuLoad.
Table 16. Additive Pumps (Optional AICB #1 and #2)
MN06135 Issue/Rev. 1.3 (6/17) 70
Page 77
Section IV – Diagrams
Additive Solenoids 1 through 4 are wired to the programmed term inals on the EAAI board. Additive Solenoids 3 through 12 (AccuLoad III-S hardware) or Additive Solenoids 5 through 24 (Ac cuLoad III-Q hardware) are wired per the following table. T erminals are automatically assigned as ad ditive solenoids if metered injec tors are pro­grammed in the AccuLoad.
Additive Solenoids (Optional AICB #1)
Additive Solenoid #
ALIII-S Hardware ALIII-Q Hardware Terminal +V Terminal Block
5 5 9 TB8 6 6 7 TB8 7 7 5 TB8 8 8 3 TB8
9 9 1 TB8 10 10 9 TB7 11 11 7 TB7 12 12 5 TB7 13 13 3 TB7 14 14 1 TB7
Additive Solenoids (Optional AICB #2)
N/A 15 9 TB8 N/A 16 7 TB8 N/A 17 5 TB8 N/A 18 3 TB8 N/A 19 1 TB8 N/A 20 9 TB7 N/A 21 7 TB7 N/A 22 5 TB7 N/A 23 3 TB7 N/A 24 1 TB7
Table 17. Additive Solenoids (Optional AICB #1 and #2)
MN06135 Issue/Rev. 1.3 (6/17) 71
Page 78
Section IV – Diagrams
Communications (AICB Boards)
Type Function Terminal Jumpers
Communications
CN4 CN5
EIA - 232 TX TB2 (4) 1-2 Out EIA – 232 RX TB2 (2) EIA – 232 Com TB1 (2)
EIA - 485 RX+ TB2 (1) 1-2 Out
EIA - 485 RX- TB2 (2)
EIA - 485 TX+ TB2 (3)
EIA - 485 TX- TB2 (4)
Table 18. Communications (AICB Boards)
Jumper Locations
Transmitter Power
Designation Jumpers Description
CN2 1 – 2 24V – +V Out CN2 3 – 4 12V – +V Out CN2 5 – 6 5V – +V Out
3-4 Out
5-6 In
3-4 Out 5-6 Out
1-2 Out 3-4 Out
1-2 In 3-4 In
Communications
Designation Jumper Description
CN4 1 – 2 In Address 200, Out Address 100* CN4 3 – 4 In 9600 Baud, Out 38.4K Baud
CN4 5 – 6
Last Unit Only (Termination of Communications with AccuLoad)
Designation Jumper Description
CN5 1 – 2 In EIA 485, Out EIA 232 CN5 3 – 4 In EIA 485, Out EIA 232
Table 19. Jumper Locations
*Note: For ALIII-S hardware and Additives 5 through 14 on the ALIII-Q hardware, jumper must be out (Address 100). For Additives 15 through
24, the jumper must be installed (Address 200).
Note: Jumpers CN1 and CN3 for factory use only.
MN06135 Issue/Rev. 1.3 (6/17) 72
In 232 Communications,
Out 485 Communications
Page 79
Section IV – Diagrams
Optional AICB Board(s) (General Purpose Inputs/Outputs)
DC Inputs (Optional AICB #1)
Input # Terminal Block Signal Common
24 TB5 2 3 25 TB5 5 6 26 TB5/TB4 8 (TB5) 1 (TB4) 27 TB4 3 4 28 TB4 6 7 29 TB4 9 10 30 TB3 2 3 31 TB3 5 6 32 TB3 8 9 33 TB3 11 12
DC Inputs (Optional AICB #2) (Not Applicable to ALIII-S Hardware)
34 TB5 2 3 35 TB5 5 6 36 TB5/TB4 8 (TB5) 1 (TB4) 37 TB4 3 4 38 TB4 6 7 39 TB4 9 10 40 TB3 2 3 41 TB3 5 6 42 TB3 8 9 43 TB3 11 12
Table 20. Optional AICB DC Inputs
MN06135 Issue/Rev. 1.3 (6/17) 73
Page 80
Section IV – Diagrams
AC Outputs (Optional AICB #1)
Output #
Terminal +V
Terminal Block
39
10
TB8
40 9 TB8
41 8 TB8
42 7 TB8
43 6 TB7
44 5 TB7
45 4 TB7
46 3 TB7
47 2 TB7
48 1 TB7
49
10
TB7
50 9 TB7
51 8 TB7
52 7 TB7
53 6 TB7
54 5 TB7
55 4 TB7
56 3 TB7
57 2 TB7
58 1 TB7
AC Outputs (Optional AICB #2) (Not Applicable to ALIII-S Hardware)
59
10
TB8
60 9 TB8
61 8 TB8
62 7 TB8
63 6 TB8
64 5 TB8
65 4 TB8
66 3 TB8
67 2 TB8
68 1 TB8
69
10
TB7
70 9 TB7
71 8 TB7
72 7 TB7
73 6 TB7
74 5 TB7
75 4 TB7
76 3 TB7
77 2 TB7
78 1 TB7
Table 21. Optional AICB AC Outputs
MN06135 Issue/Rev. 1.3 (6/17) 74
Page 81
Section IV – Diagrams
Figure 58. Optional AICB Board(s)
MN06135 Issue/Rev. 1.3 (6/17) 75
Page 82
Section IV – Diagrams
Jumpers CN4
Jumpers CN5 Jumpers CN2
F
igure 59. AICB Jumper Locations
MN06135 Issue/Rev. 1.3 (6/17) 76
Page 83
Section IV – Diagrams
igure 60. AICB Communications and DC Power
F
MN06135 Issue/Rev. 1.3 (6/17) 77
Page 84
Section IV – Diagrams
Figure 61. AICB Communications and DC Power with Two AICB Boards (AccuLoad III-Q Hardware Only)
Note: Change Address to #2 via jumpers
MN06135 Issue/Rev. 1.3 (6/17) 78
Page 85
Section IV – Diagrams
Figure 62. AICB Communications (Two-wire RS-485)
MN06135 Issue/Rev. 1.3 (6/17) 79
Page 86
2
9
8
7
Add. Sol. 6
Add. Sol. 5
AC Output #2
AC Output #3
AC Output #4
CB2 CB2
TB9
TB7
TB8
TB6
AICB
Terminal Designations
AICB Connections
L1
L2 for 240V
N Or
Control
Add. Pump 6
AC Output #1
10
Add. Pump 5
AC Output #5
AC Output #8
AC Output #7
AC Output #6
4
3
5
6
Add. Sol. 8
Add. Pump 8
Add. Pump 7
Add. Sol. 7
AC Output #10
1
AC Output #9
2
Add. Sol. 9
Add. Pump 9
1
AC Output #20
AC Output #19
AC Output #18
1
2
3
AC Output #17
AC Output #16
AC Output #15
AC Output #14
AC Output #13
AC Output #12
AC Output #11
8
4
5
6
7
9
10
Add. Sol. 14
Add. Pump 14
Add. Sol. 13
Add. Pump 12
Add. Pump 13
Add. Sol. 11
Add. Sol. 12
Add. Pump 11
Add. Pump 10
Add. Sol. 10
2 1
CB1 CB1
Control
L2 for 240V
L1
N Or
Section IV – Diagrams
Figure 63. AICB Additive Outputs (Typical ALIII-S Hardware)
Note: 1. ALIII-Q Hardware Additive Pumps start at 5 and go through 14, as do the additive solenoids.
2. Optional AICB Board #2 Additive Pumps start at 15 and go through 24, as do the additive solenoids.
MN06135 Issue/Rev. 1.3 (6/17) 80
Page 87
Section IV – Diagrams
Optional ComFlash Mass Storage Expansion Board
The ComFlash Mas s Storage Expansion B oard is an opt ional hard ware feature t o the A3X that provides addi tional flash memory to store trans act ion data. The expa ns i on bo ar d comes with a 51 2M DS c ar d t ha t h as t he c a pa b i lity of storing approximately 10,000+ additional transactions per arm. The ComFlash operates on Com4 and uses RS2332 comm unications . The Com Flash also h as the c apabilit y of alarm ing if the de vice is not o perating c orrectl y. (The ComFlash Alarm will be invoked when the interf ace driver fails to receive a response within a reasonable amount of time.) The A3X also has the ability to operate (on C om4) both the mem ory expansion board an d the Smith Meter Card Reader simultaneously. This option can be chosen b y navigating through the s ystem director y and setting the Com4 function to: 20 Card Reader/ComFlash.
IMPORTANT: Must have EAAI board manufacture date year 2006 or newer AND have firmware Rev. 10.13 or higher.
Installation of the ComFlash Data Storage Device:
1. Make sure Power to the AccuLoad is turned OFF.
2. Open the cover of the AccuLoad so that the EAAI board is easily accessible.
3. The ComFlash will be mounted so the SD card is face up.
4. On the EAAI board you will notice CN1, CN2, and J4 & J5. The bottom of the SD Card should be positioned so that the female connectors will line up with all three of the male connectors (CN1, CN2, and J4 & J5).
5. Onc e the connect ors are lined up, simply pr ess the mem ory expansion board onto th e EAAI board until th
ale connectors a re seated fully into the female connectors. All CN1, CN2, and J4 & J5 should now be firmly
m secured and covered by the ComFlash board (no pins on any of these connectors should be exposed).
e
MN06135 Issue/Rev. 1.3 (6/17) 81
Page 88
Section IV – Diagrams
Figure 64. ComFlash Mass Storage Expansion Board
MN06135 Issue/Rev. 1.3 (6/17) 82
Page 89

Section V – Maintenance

Maintenance
Recommended backup battery replacement interval - 5 years
he following procedure applies to ALIII units with KDC.net boards.
T
he life of t he battery used for the backup RAM c an var y due to o perat ional c onditions , par ticular ly the amou nt o f
T time that the unit is left in a pow ered off state. It is suggested th e b ack up battery be replaced appr oximately every five years or during a reg ularly scheduled maintenance peri od. For applicatio ns that are under strict metrological control it may be convenie nt to replace the battery whenev er a W&M official will be on sit e since the cover seal will need to be broken and must then be reapplied.
F
ield replacement o f t he ba tter y is only possible with A cc uLoad III.net mo dels (firmware versions 11.00 and up); it is NOT possible t o fi eld up grade pre- .net Acc uLoad II I units (f irmware revisi ons less than 1 1.00) as the ba tter y is soldered directly to t he KDC board. To facilitate replacement of this battery, the KDC board must be removed from the unit to gain ac cess to the rear s ide of th e board to unsolder a nd replac e the batter y. Only qualified tec h­nical personnel that are familiar with print ed circuit bo ard de-solder ing / solder ing proced ures should attempt t his procedure. The KDC boar d should be returned to T echnipFMC for batt ery replacement or cons ider complete re­placement of the board assembly with an upgrade to the new KDC.net board.
C
aution: Any soldering w ork will need to be perfor med in a saf e (non-hazardous) area to preven t ignition o f haz-
ardous atmospheres. In addition, ESD contr ols should be e mployed to avoid da maging sensitiv e electronic com­ponents.
ote: The KDC.n et board utilizes a s pecial capacitor that was designed to maint ain power to the battery backed
N
up memory during th e t ime of ba tter y r ep lac em ent whe n the mains power is dis c o nnect e d. Ho wev er , as a pre c au­tionary measure, prior to replacing the battery , it recommended to download all parameter data, custom c onfig­ured print reports, Boolean equations, and or langu age translations fro m the AccuLoad via the AccuMate. These files should be save d to be used for the restorat ion of the AccuLoad in t he unlikely ev ent that the batt ery back ed up memory becomes corrupt during the battery exchange.
he case of a c omplete board replacement, f or example exchanging a KDC board for a KDC.net board , the
In t above procedure must be performed to create the files needed to restore the AccuLoad configuration.
I
n any case, transaction records should be downloaded for archival purposes if required by local agencies as these cannot be rel oaded back into th e AccuLoad. The AccuMate compan ion tool provid es a facility for transfer­ring the transaction log rec ords; the transaction log will be c onverted to a .CSV file and imported into an Exc el workbook when utilizing the AccuMate.
Battery replacement procedure:
1. R
etrieve all configuration information and data logs as detailed above using t he AccuMate program, s
MN
06136 for specific instructions on the use of AccuMate.
2. Power down the AccuLoad III.
3. B
reak the W&M seal wire on the two corner cover bolts.
4. Remove the AccuLoad III front cover bolts and open the front cover.
ee
emove the seven barrier screws and barrier plate (Figure 1) from the KDC.n et board located on the
5. R cover.
6. R
eplace battery with E NERGIZER P/N CR2032 (subst itutes not allowed), TechnipFMC P/ N 64458141
refer to Figure 1 of AB06071 for location of the battery on the KDC.net board).
(
MN06135 Issue/Rev. 1.3 (6/17) 83
8
Page 90
Section V – Maintenance
7. Replace the barrier plates, securing the screws removed earlier.
lose the front cover, taking care not to pinch any of the internal cables.
8. C
9. F
ollow cover bolt re-torqueing instructions and flame path gap inspection from Section X. ower-up the AccuLoad III. The initializat ion test will ex ecute, followed by th e Ready Mode d isplay if the
10. P configuration data remained intact during the operation.
11. V
erify correctness of con figuration parameter data, custom figured print reports, Boolean eq uations, and
or language translations if used. If all is correct, proceed to Step 13.
12. I
f these files are corrupted, then configure and establish commun ication to the AccuMate program (see manual MN06136) a nd restore a ll param eter data, configura ble repor ts, languag e trans lation f iles, Boole­an equations, etc. as previously saved in Step 1.
13. O
nce the restoration is complete, re-seal t he unit via the two c orner cover bolts (may require local W&M
jurisdiction).
irmware updates
F
ote: When updati ng firmware al l transaction date is perman ently erased fro m memory, it is th e user’s respons i-
N
bility to archive all data utilizing the AccuMate prior to performing any firmware updates.
O
ptional ComFlash Mass Storage Expansion Board
or units equipped with the optional ComFlash Mass Storage Expansion Board (reference bulletin AB06066),
F transaction data can be downloaded via the AccuMate and saved to an excel transaction file (see bulletin AB06068). Please note that this process may take a significant amount of time depending on the configured communications channel and the amount of data stored on the card.
To save time during the firmware upgrade process it is recommended to replace t he SD card wit h a new car d, this will preserve the transac tion data for archival purpose s on the original card, the serial number of the unit Accu­Load in which the card was remov ed should be wr itten onto t he SD card for f uture referenc e, if data r etrieval ac­cess is required.
I
f for some reason the data stored on the SD card must be accessed outside of the AccuLoad consult the factory.
Enclosure Maintenance
Flame Path Inspection Criteria M
odels: ALIII-Q-XP or ALIII-S-XP
arning: T o prevent ig nition of hazar dous atmos pheres, discon nect from mains power sup ply before o pening the
W
cover.
I. I
nstallation/inspection/maintenance/repair /overhaul/reclamation of the AccuLoad in the European Union must be performed by qualified personnel in accordance with the applicable requirements of EN 60079-14, EN 60079-17, and EN 6007 9-19 in ad­dition to all local codes/regulations.
II. I
MN06135 Issue/Rev. 1.3 (6/17) 84
nstallation/inspection/maintenance/repair /overhaul/reclamation of AccuLoad’s relying upon the IECEx certification must be performed by qualified personnel in accord ance with the application requ irements of IEC 60079-14, IED 60 079-17, and IEC 60079-19 as required by local codes/regulations.
Page 91
Section V – Maintenance
III. Guidance for equipment ins pec t io n an d m ain te na nc e is pr o vi de d by EN/IEC 60079-17: “Electrical Appa-
ratus for expl osive gas atm ospheres, “Ins pection and maintenance of electrical i nstallations in hazard­ous areas” and should be utilized for the inspection / maintenance process.
V. W hen per form ing mai ntenanc e that r equ ires op ening of the encl osure c over, all f lame pat hs, w hich ar e
I
defined as th e machi ned fla nged s urface b etwe en the hous ing and t he cov er, sha ll be inspect ed to e n­sure that they are clean and undamaged, no scratches, nicks, corrosions, or other defects that would af­fect the inte grity of the flame path are allowed. If defects are detected the equi pment should not be placed back into service until the issues ar e resolved. Flame paths between window and cover an
eypad and cover s hould be inspec ted at an incr eased f requenc y for sig ns of corr osion when ins talled
k in special environments.
V. Ver ify that all tapped cover bo lt threaded locations i n the enclosure are clean an d intact with no miss-
ing/stripped threads.
. Verify that the cover bolts are the required M8 x 1.25-6g. Din 912, Steel Grade 12.9. Prior to reassembly
VI
apply a light coating of nickel based anti-seize such as TechnipFMC P/N (646002401) to all bolt threads.
VI
I. Verify that an y blind threaded cover bolt ho les do not have excessive grease / ant i-seize packed into
them as this could cause hydraulic fractures of the enclosure when the bolts are tightened.
III. Inspect to see tha t the envi ronmental O-ring is c orrectly i nstalled (s eated into the groove) and in go
V
ondition, no cr ack s, etc . if def ect ive r epl ace to m aint ain en vironmental prot ecti on. Greas e c over fla nge
c with petroleum jelly or Tec hnipFMC grease ( P/N 644886401) before reattachm ent of the cover to the housing.
od
d
. Follow cover bolt tor queing proced ure as outlined i n section 12, wh en complete, verify the flam e pat
IX
ps as per the procedure.
ga
Special Environments
n corrosive e nvir onm ents s uch as n ear sa lt water , is the us er’s res pons ibil it y to inc rease th e ins pect ion inter va ls f or
I verification of the flame path int egr ity. Inspectio n i nt erv al s will vary with local con di ti o ns an d is the user’s res po nsibil­ity to select appropriate intervals.
T
he most effective preven tive maintenance is per iodic wash downs of the enclos ure to remove th e salt buildu p on the outside s urf aces. It is r ec omm ended to us e a m ild s oap appl ied with a s pon ge or cl oth with a low press ure non­saline water rinse.
t is also ver y important t o maintain t he painted ext erior painte d finish of t he equipm ent, if exterior c orrosion is de-
I tected, the fi nish shou ld be cle aned, rem oval of a ny corros ion b y mechanical m eans an d prepare d for pain ting, th e affected area shall be repainted with a corrosion inhibiting paint. Factory paint is two-component polyurethane­acrylic enamel, Polane
I
t is required to apply a coating of petroleum jelly or TechnipFMC grease (P/N 644886401) to flanged metal surfaces to offer a protective barrier to reduce the effects due to exposur e to saline solution i.e. wet salt air, this surface should be clean e d an d n e w grease reapplied e v ery time the cover is o pe ne d for inspect ions or maintenance, t h is in­cludes the flame path between the window and cover and the keypad and cov e r.
®
T manufactured by Sherwin Williams, colors is “Precision Tan” and “Carbon Black”.
h
MN06135 Issue/Rev. 1.3 (6/17) 85
Page 92

Section VI – Completing the Installation

Completing the Installation
E
xplosion-proof housing closure
hen securing the front cover of the AccuLoad model or QT, use the following procedure to ensure the unit is
W properly sealed and is safe to operate in a Div. 1/Zone 1 environment:
nspect the door seal O-ring for dam age and replace i f damaged. The O-ring is not require d to maintain
1. I the explosion-proof rat ing, however, it is re quired to m aintain the IP 65 i ngress protecti on rating. Greas e cover flange with petro leu m jelly or T echnipFMC gre ase (P/N 644 886401) bef ore attac hm ent of t he cover to the housing.
2. Verify the mating areas bet w een th e f r ont c o ver an d the main hous ing ar e not s c ratc hed, c or rode d or oth­erwise damaged such that the surface contact between them would be compromised.
3. Close the cover and tighte n the cap screws around the per imeter of the front cover us ing the sequence shown below. The f inal torque should be 20 F T-LB / 240 IN-LB (27.1 Nm / 276.4 Kg.cm ). Be sure to note the locations for the two longer bolts used for the security seal wire.
4. Check that the enclos ure is prop erly sealed b y verif ying the cover to e nclosure j oint “gap” w ith a 0.0015 " (0.0381mm) feeler gau ge. The feeler gauge must not enter the joint for m ore than a ¼" (6mm) at any point around the perimeter of the cover to housing joint; see Figure 67 for example.
F
igure 65. Cover bolt torque pattern for AccuL oad III S
igure 66. Cover bolt torque pattern for AccuL oad III Q
F
MN06135 Issue/Rev. 1.3 (6/17) 86
Page 93
Section VI – Completing the Installation
Feeler gauge test of cover flame path joint, inspect joint around the complete
perimeter using a 0.0015" (0.0381 mm) feeler gauge. (ALIV-Q shown - use the same procedure for ALIV-S).
Figure 67. Flame path verification
Sealing
ach of the AccuLoad enclosures can be sealed using standard seal wires. On the AccuLoad S and Q models the
E seal wire is threaded through holes in two cover bolts as shown in the following figures.
MN06135 Issue/Rev. 1.3 (6/17) 87
Page 94

Section VIIRelated Publications

T
he following literature can be obtained from FMC Measurement Solutions Literature Fulfillment at
mailto:measurement.fulfillment@fmcti.com or online at www.fmctechnologies.com/measurementsolutions
W
hen requesting literature from Literature Fulfillment, please reference the appropriate bulletin number and title.
AccuMate for AccuLoad III
Specification .......................................................................................................................... Bulletin SS06032
Installation/Operation ............................................................................................................. Bulletin MN06136
A
ccuLoad III
Specification .......................................................................................................................... Bulletin SS06036
Operator Reference ............................................................................................................... Bulletin MN06129
Communications .................................................................................................................... Bulletin MN06130L
Modbus Communications ..................................................................................................... Bulletin MN06131L
isions included in MN06135 rev/issue 1.3 (6/17):
Rev
Page 1: Warning and Precautions added. Page 2: Weights and Measures Requirements added. Page 4: Environmental Considerations added. Page 6: General Requirements added. Page 7: Completing the Installation added. Page 88: Maintenance added.
MN06135 Issue/Rev. 1.3 (6/17) 88
Loading...