Technical PanTherm Optimum-200/150, PanTherm PT68-200 PT75C G, PanAqua PA20, PanAqua PA25, PanAqua PA15 Instructions For Use Manual

...
1
Instructions for use
1. Installation guide
1.1. Chimney
The chimney must meet the criteria prescribed by currently effective standards:
ONLY a chimney inspected and approved by the competent
authority is accepted.
The apparatus is only allowed to be connected to a chimney
with identical or larger diameter compared to that of the smoke exit.
At the connection, the diameter of the chimney is not allowed
to be reduced in the direction of flue gas flow.
The chimney must be properly cleaned. NO solid fuel-fired apparatus is allowed to be connected to a
chimney with gas-fuelled equipment.
Only one appliance is allowed to be connected to a single
chimney.
The chimney must have an appropriate draught output.
2
1.2. Cover:
The firebox should always be installed and built in by a specialist, in compliance with the applicable requirements.
Fireboxes may only be operated with an appropriate cover in place. Even heat delivery must be ensured at installation (with an even air flow around the firebox): the air gap between the fireplace cover and the firebox should be at least 2-3 mm sideways at the door frame, then a minimum of 5 cm towards the wall. There should be a minimum of 5 mm at the top, between the firebox and the mantelpiece and a minimum of 5 cm between the firebox and the wall; a distance of at least 5 cm must be kept from the upper cone of the firebox; it should rather be 10 cm if allowed by the cover.
IMPORTANT: air flow must be ensured both at the bottom and at the top by an aperture or ventilation grid of appropriate size, the unobstructed dimensions of which should be minimum 30 cm2 per kW both at the bottom and the top. Their installation is a basic requirement.
ATTENTION: in case of LD fireboxes leave enough space for the maintenance of the lifting mechanism.
ATTENTION: even heat delivery must be ensured to avoid firebox
overload.
3
Figure 1.
Figure 2.
4
Figure 3.
An operating distance should be provided for firebox inlet controls: minimum 2 centimetres of free space must be ensured in addition to the space visibly required for their motion.
If the criteria listed are not met, the firebox may be seriously damaged and the guarantee is lost.
No flammable substances are allowed to be used or placed in the proximity of the apparatus. The smallest safety distance is 100cm; heat insulation is required for smaller distances.
5
1.3. Exhaust equipment effects:
If no sufficient ventilation is ensured, exhaust equipment in the same air space with the fireplace (including rooms behind a door provided with a ventilation grille or rooms with doors open) may disturb fireplace operation. Therefore exhaust devices must be provided with the air supply indispensable for their operation.
Important: if, for instance, outward air flow is only ensured for your vapour extraction device, it will not operate efficiently because it cannot take in air from anywhere. E.g. an exhaust device with a capacity of 600 cubic metres of air / hour will carry only 200 cubic metres of air. This reduces air pressure in your living space which is less than favourable to our general state of health. In certain cases, return flow can occur in case of not completely closed fireboxes (smoke gets into the living space) when out of service or when the door is opened. In case of inadequate ventilation, the firebox glass is also increasingly sooted.
1.4. Operation of a water jacket firebox
A firebox with a water jacket is only allowed to be operated if connected to a water system filled up with water, designed and installed by a heating engineer. The specialist makes sure to integrate the firebox into the system appropriately, connected to each of the 1­inch forward and return stubs diagonally, by plugging any unused stubs in order to prevent overcooling for adequate efficiency. The two half­inch stubs with external threading are the connection points for the cooling circuit (coilpipe) to prevent water from boiling and steam generation; they should not be plugged in case of an open system. It is recommended to fill the firebox with soft deionized water.
6
ATTENTION: the boiler protection circuit is required to be built in the central heating system to prevent overcooling and is a condition for guarantee provision. Precipitation of moisture and condensation water must be prevented as they highly corrode the metal and result in tar deposition, reduce efficiency and output, and these phenomena entail a loss of guarantee.
ATTENTION: the 4 threaded ¾-inch studs on the firebox are to accommodate handles.
2. Firebox structure:
PanTherm fireboxes are made of cast iron. PanTech fireboxes are made of 4 and 5 mm thick, and PanAqua fireboxes of 5 mm thick steel plates, constituting the firebox together with up to 700oC heat-proof glass.
2.1. Firebox use:
Door: the firebox is not allowed to be lifted and tilted by taking hold of the door; it is prohibited to lean on and to clutch at the door during use as it cannot bear this load.
Glass: beware of the direct use of strong chemical cleaners on nero glasses.
Flame deflector: PanTherm fireboxes include a casting flame deflector for appropriate flame control, fitted into the u-shaped recess for this purpose on the back wall in various ways according to type.
Figure 4.
The firebox is not allowed to be operated without a flame deflector.
7
Grills: to ensure that the burning wood gets sufficient air through the ash box and that the ash gets into the ash box, so the grills should always be in the same position.
Heat-proof lining of the firebox: the vermiculite lining to protect metal plate fireboxes (PanTech firebox family, and optional for PanAqua fireboxes) decays when wet firewood (exceeding 15-20% moisture content) is used, therefore wet firewood is prohibited.
Convection cover: an optional metal sheet cover (available for PanTherm and PanTech firebox products) surrounding the firebox casing, where firebox operation is only allowed with parallel fan use (air flow around the firebox is slowed down by the convection cover, therefore little heat is lost; in some cases, flow is not even started so there is no appropriate heat delivery during operation leading to overload. Thereby efficiency is very low and the firebox also gets damaged, which is not a case for guarantee claims).
Overload seal: the piece part indicates with form-change or melt on the fire, that the firebox gets heavy by overload is permitted.
3. Lighting a fire:
Definition of overload: firing a quantity of firewood exceeding the
quantity corresponding to the output of the firebox on a pro-rata basis; and / or even heat delivery by the firebox is not ensured.
WARNING: firing a quantity of firewood exceeding the quantity corresponding to the output of the firebox on a pro-rata basis results in firebox overload, leading to serious firebox damage and injury to both the cover and the chimney.
8
Sudden heat shock: sudden excessive heat load in the heatup stage.
WARNING: Burning 1 kg of firewood yields about 3.65KW of heat
quantity. The maximum loadability of your firebox is yielded by dividing the output of the firebox with 3.65, the result being the quantity (in kg) of wood allowed to be used each hour.
E.g.: 15kW output / 3.65 = 4.1 wood / hour
Overload and sudden heat shock are prohibited, entailing a loss of guarantee.
Only hardwood should be used for firing, such as beech, oak, locust, ash, alder and wood from various fruit trees. The burning time of hardwoods is longer than that of soft wood; they produce less ash and their tar content is low. Soft wood can only be used for lighting fires. Soft wood types (birch, lime, pine, poplar and Lombardy poplar) burn quicker, yield large quantities of ash and their embers cool down quickly. As they flicker quickly, it is easy to overload the firebox with them. It is prohibited to use coniferous woods with resin content as they burn with intense and rapid flames, and resin crystals make them crackle and sizzle frequently with bursts of sparkles. In line with the known dimensions of the firebox of the fireplace, firewood should be cut into 30-60 cm long logs and stored at a place not exposed to precipitation.
Only dry wood should be used, with a moisture content below 15­20%, both in order to achieve best efficiency and to avoid excessive sooting and tarring of the flue pipe and the glass.
9
3.1. Procedure of lighting a fire:
- Remove any ash from previous fire; clean glass as required.
- Open the air control shutters at the bottom of the door.
- After replacing the ash tray / ash box, pile dry softwood cut into a
thumb’s width into the combustion chamber and put 3-4 kg
firewood on top of it.
- Then light a fire under the softwood using paper.
- Air for combustion must be supplied continuously through the
regulator for even heating.
- A burn-in smell may emanate from firebox inlets during the first use,
which is to discontinue after 7-8 hours of continuous firing. The
room should be aired in such a case as high concentrations of the
gases released can be injurious to health and can cause aesthetic
damage as well.
- External air supply must be ensured, especially in case of small air
space and perfectly sealed doors and windows.
Firewood (hardwood) moisture content (in %) according to
drying time on average
Fresh cut
75-78 %
1 year
35-36%
3 months
48-62%
1.5 years
18-27%
6 months
37-46%
2 years
16-24%
9 months
33-38%
2.5 years
15-24%
Freshly cut wood: 1750 Kcal/kg Dry wood: 3200 Kcal/kg
The maximum amount of firewood allowed to be placed in at the same time is triple the amount of quantity allowed to be fired per hour. It is permitted to be fired evenly in three hours or longer.
10
3.2. Draught demand: 10-15Pa
3.3. Specially prohibited fuels
- mineral, chimney fuels (all types of coal)
- garden and agricultural waste (e.g.: twigs, corn stalks, walnut
kernels, lacquered parquet broken up or painted lumber, etc.)
- pellet and other tableted wood fuel
- combustible mineral fluids (petrol, diesel oil, chemical solvents,
oils, etc.)
- alcohol to light a fire
- paper or cardboard (only to light a fire)
11
PanTherm Firebox Family
Type
Unit of
measure
PT80
PT71
PT68-
200
PT75C
G
PT68-
150
Optimum-
200/150
PT62 PT69
CG
Nominal output
kW
19
17
15
15
10
13
Flue gas temperature at nominal output
C
300
300
300
300
300
283
Efficiency at nominal output
%
77
77
77
77
73
77
CO emission according to MSZ EN 13229
%
0,28
0,28
0,28
0,28
0,29
0,28
Mass flow of flue gas at nominal output
g/s
19
17
15
15
11,3
14
Table 1.
Firebox overload can cause permanent damage to the entire system!
12
Overall dimensions
Unit of
measure
PT80
PT71
PT68 PT75
CG
PT68-
150
Opti
mum
-200
Opti
mum
-150
PT62
PT69C
G
Depth
mm
440
440
440
440
430
430
440
Width
mm
800
710
680
680
680
680
620
Height
mm
852
852
730
730
640
640
730
Size of filling aperture (firebox door)
Width
mm
760
670
640
640
640
640
580
Height
mm
480
480
430
430
430
430
430
Total
weight
kg
182
168
151
151
106
106
127
Recommen ded size of ventilation grids
cm2
570
510
450
450
300
300
390
Exhaust product nominal connection
mm
200
200
200
150
200
150
150
Actual exhaust product outlet diameter
mm
184
184
184
134
184
134
134
Required chimney draught
Pa
10,0-15,0
mbar
0,10-0,15
Table 2.
13
Fuel consumption at nominal output
Type
Unit
PT80
PT71
PT68
Optimum
PT62
Average fuel consumption
kg/h
6.5 -
7.5
5.7 -
6.8
5.1 - 6
3.4-3.8
4.4 – 5.2
Average length of logs
cm
45
40
35
35
30
Maximum fillup height
cm
30
30
25
25
25
Table 3.
Standards:
MSZ EN 13229:2001 Solid fuel-fired fireplace inlets,
including appliances under
MSZ EN 13229:2001/A1:2003 with an open fire chamber.
Requirements and
MSZ EN 13229:2001/A2:2005 testing methods. MSZ EN 1443:2003 Flue exhaust equipment. General
requirements.
MSZ EN 13384-1 Flue exhaust equipment. Thermal
and flow dimensioning procedure.
14
D
A
B
E
C
Main dimensions:
Figure 5.
Table 4.
Main dimensions (mm)
Sign
Description
Type
PT80
PT71
PT68
Optimum
PT62
A
width
800
710
680
680
620
B
depth
440
440
440
430
440
C
height
852
852
762
640
762
D
chimney connection
200
200
200
200
150
E
frame height
550
550
500
500
500
15
PanAqua Water Jacket Firebox Family
Table 5.
Type
Unit of
measure
PA15
PA20
PA25
PA75C
G
PA30
PA110
PA
Mini Nominal output
kW
15
20
25/24
30
30/40
12
Flue gas temperature
°C
230
230
230
230
250-
270
230
Efficiency
%
>80
>80
>80
>80
>80
>80
CO emission according to MSZ EN 13229
%
0,1
0,1
0,1
0,1
0,11
0,11
Mass flow of flue gas at nominal output
g/s
15
20
24
30
31
13
Maximum operating pressure
bar
1,5
1,5
1,5
1,5
1,5
1,5
16
Firebox overload can cause permanent damage to the entire system
Overall dimensions
Unit
PA15
PA20
PA25
PA75C
G
PA30
PA110
PA
Mini
Depth
mm
535
535
535
535
535
535
Width
mm
620
680
710/
750
800
1100
680
Height
mm
860
860
960
960
960
645
Size of filling aperture (firebox door)
Width
mm
580
640
670
760
1060
640
Height
mm
640
640
510
510
510
640
Total weight
kg
174
189
215/
209
238
310
141
Exhaust product nominal connection
mm
150
200
200
200
200/
250
150
Actual exhaust product outlet diameter
mm
137
187
187
187
187/
237
137
Required chimney draught
Pa
10,0-
15,0
10,0-
15,0
10,0-
15,0
10,0-
15,0
10,0-
15,0
10,0-
15,0
mbar
0,10-
0,15
0,10-
0,15
0,10-
0,15
0,10-
0,15
0,10-
0,15
0,10-
0,15
Table 6.
17
Standards:
MSZ EN 303-5:2000 Heating boilers. Solid fuel-fired heating
boilers with manual and automatic feed, having a maximum nominal heat output of 300 kW.
MSZ EN 14336:2005 Building heating systems. Installation and
putting into operation of water heating systems.
MSZ EN 1443:2003 Flue exhaust equipment. General
requirements.
MSZ EN 1457/ A1:2003 Flue exhaust equipment. Ceramic casing
tubes. Requirements and testing.
MSZ EN 13384-1 Flue exhaust equipment. Thermal and
flow dimensioning procedure.
MSZ EN 12953-3 Design of boilers with large water
chambers.
Decree 9/2001.(IV.5.) GM On EC design review under model B1 of
Directive 97/23 EC
18
Connection diagrams
Firebox overheating protection in case of excessive burning and / or
power supply interruption is ensured by a safety cooler circuit.
Figure 5.
Figure 6.
A higher-efficiency heating system can be produced by installing a buffer tank as shown in Figure 7.
Figure 7.
19
Safety heat exchanger connection diagram with the proposed safety
fittings
Thermal valve with a Honeywell TS type valve
Figure 8.
20
Main dimensions and connections
Figure 9.
7.
Table 7.
Main dimensions (mm)
Sign
Description
Type
PAII30Z
PAII25Z
PAII20Z
PAII15Z
A
width
800
710
680
620
B
depth
537
537
537
537
C
height
955
955
855
855
D
chimney connection
200
200
200
150
E
frame height
550
550
500
500
21
PanTech EVO Firebox Family
Type
Unit of
measure
PH 68
EVO
PH 68
EVO 2D
PH 80
EVO
PH 80
EVO 2D
PH 110
EVO
PH
110
EVO
2D
Nominal
output
KW
14
14
17
17
21
21
Flue gas
temperature
°C
260-
290
270-300
260-
290
270-300
260-
300
270-
310
Efficiency (h)
%
>80
>80
>80
>80
>80
>80
CO emission according to
MSZ EN 13229
%
0.09
0.1
0.09
0.1
0.09
0.1
Mass flow of
flue gas at
nominal output
g/s
15
15
18
18
21
21
Table 8.
22
Overall
dimensions
Unit of
measure
PH 68
EVO
PH 68
EVO
2D
PH 80
EVO
PH 80
EVO
2D
PH
110
EVO
PH
110
EVO
2D
Depth
mm
570
610
570
610
570
610
Width
mm
680
680
800
800
1100
1100
Height
mm
1070
1120
1070
1120
1170
1170
Size of filling aperture (firebox door) Width
mm
640
640
760
760
1060
1060
Height
mm
465
465
465
465
515
515
Total weight
kg
180
200
203
225
283
307
Recommended size of ventilation grids
cm²
420
420
510
510
630
630
Exhaust product nominal connection
mm
200
Actual exhaust product outlet diameter
mm
187
Chimney draught required
Pa
12.0-19.0
mbar
0.12-0.19
Table 9.
23
Table 10.
Standards
MSZ EN 13229:2001 Solid fuel-fired fireplace inlets,
including appliances under
MSZ EN 13229:2001/A1:2003 with an open fire chamber.
Requirements and
MSZ EN 13229:2001/A2:2005 testing methods. MSZ EN 1443:2003 Flue exhaust equipment. General
requirements.
MSZ EN 13384-1 Flue exhaust equipment. Thermal
and flow dimensioning procedure.
Fuel consumption at nominal output
Type
PH160
PH130
PH110
PH80
PH68
Average fuel consumption:
kg/h
5.8
5.8
5.8
4.7
3.8
Average length of logs:
cm
70
70
70
55
40
Maximum fillup length
cm
24
Main dimensions and connections
Figure 10.
e 11.
Table 11.
Main dimensions (mm)
Sign
Description
Type
PH110
PH80
PH68
A
width
1100
800
680
B
depth
569
571
567
C
height
1170­1265
1070­1170
1070­1170
D
chimney connection
200
200
200
E
frame height
550
500
500
25
Lift door version (LD)
Table 12.
Figure 11.
26
Table 12.
Before opening the door, ensure that the baffle valve is totally opened. Push the lift door slowly upwards and pull it steadily downwards for closing.
Cleaning the firebox: by releasing the spring-controlled latch above the door frame, the glass can be tipped out carefully until it stops. After applying a glass cleaner, place the glass carefully back into vertical position by gently putting it a bit downwards. Fasten in with the latch.
Main dimensions (mm)
Sign
Description
Type
PH200
LD
PH160
LD
PH130
LD
PH100
LD
A
width
1926
1526
1226
926
B
depth
646
595
595
595
C
height
1470-
1565
1470-
1565
1370-
1465
1270-
1365
D
chimney connection
300
200
200
200
E
frame width
1800
1400
1100
800
F
frame height
600
600
550
500
27
PanAqua EVO Firebox
Type
Unit of
measures
PA68E
PA80LD
PA80E
PA100LD
PA110E
PA130LD
Nominal output
kW
20
30
30
Flue gas temperature
°C
260-290
260-290
270-310
Efficiency (h)
%
>80
>80
>80
CO emisszion according to MSZ EN 13229
%
0,09
0,09
0,09
Mass flow of flue gas at nominal output
g/s
19
28
29
Maximum operating pressure
bar
1,5
1,5
1,5
Table 13.
Table 14.
Overall dimensions
Unit
PA68E
PA80LD
PA80E
PA100LD
PA110E
PA130LD
Depth
mm
555/620
555/620
555/620
Width
mm
680/810
800/930
1100/123
0
Height
mm
1100/1250
1100/1250
1150/135
0
Size of filling aperture (firebox door)
Width
mm
640
760
1060
Height
mm
465
465
515
Total weight
kg
222/276
260/318
341/414
Exhaust product nominal connection
mm
200
200
200
Actual exhaust product outlet diameter
mm
187
187
187
Chimney draught required
Pa
10,0-15,0
10,0-15,0
10,0-15,0
mbar
0,10-0,15
0,10-0,15
0,10-0,15
28
Main dimensions and connections
Figure 12.
Table 15.
Table 15.
Main dimensions (mm)
Sign
Description
Type
PA68E
PA80E
PA110E
A
width
680
800
1100
B
depth
575
575
575
C
height
1088-
1153
1088-
1153
1138-
1203
D
chimney connection
200
200
200
E
frame height
500
500
550
29
Lift door version (LD)
Figure 13.
Table 16.
Main dimensions (mm)
Sign
Description
Type
PA80LD
PA100LD
PA130LD
A
width
680
800
1100
B
depth
575
575
575
C
height
1088-
1153
1088-
1153
1138-
1203
D
chimney connection
200
200
200
E
frame height
500
500
550
Table 16.
30
ME
Warranty card
Manufacturer/Distributor: Technical Kft. 1103, Bp. Kőér utca 16.
Product .............................................................
Type ..................................................................
Duration of warranty is ........ year(s) on the firebox house.
Duration of 1 year on the following parts: grate, flame baffle, moving parts (hinges, handle, and fittings). No warranty coverage on glues, seals, ceramic glass, and fire-clay insert.
Venue of repairing work falls under this warranty: Technical Kft. 1103, Bp., Kőér u. 16. Tel: +3612602290 The mutation of seal and inappropriate use causes loss of warranty.
Date of purchase: 201 .......... year ... month .. day .....................
............................. Stamp & signature
Please stick the data label here found ont he glass of
the firebox door, the warranty card is valid only
together with that label!
31
Fireplace, the installation carried out by
Heating system assembled by
Contractor/company name:
Contractor/company name:
Address:
Address:
Licence number:
Licence number:
Tel:
Tel:
Date: 201……………….
Stamp
Date: 201………………
Stamp
Legible signature:
Legible signature
Warranty card for the period required by law
Warranty card for the period required by law
Date of report:
WARRANTY SLIP
Reported fault:
Type:
Reparation method:
Serial number:
Date of purchase: 201… year …….
month …….. day
Date: 201……………….
Stamp
Vendor:
Legible signature:
(Stamp & signature)
Date of report:
WARRANTY SLIP
Reported fault:
Type:
Reparation method:
Serial number:
Worksheet number:
Date of purchase: 201… year …….
month …….. day
Date: 201……………….
Stamp
Vendor:
Legible signature:
(Stamp & signature)
32
Important to know
. For any warranty claim the buyer must show this warranty card along with the invoice of purchasing thus those must be carefully retained.
2. We cannot replace lost warranty card.
3. Repair work falling under the scope of warranty is accepted only when presenting valid warranty card.
4. Any correction, deletion, or overwriting made on the warranty card or entering untrue data causes the warranty card become void.
5. It is the vendor’s responsibility to fulfil warranty claim if the warranty
card had been filled incorrectly. Unfilled or partially filled warranty card is void
6. The warranty card is valid if the fireplace erector engineer or heating engineer in case of water jacket type firebox has filled the relevant sections and the installation of the fireplace and, in case of water jacket type firebox, the heating system was assembled by professionals.
Commencement of the warranty period
The warranty period starts on the day when the unit is handed over to the buyer. If commissioning is carried out by Technical Kft. or our distributor, the period starts on the day the commissioning was finished. In case the commissioning does take place within 3 months from the date of purchase then the warranty period starts on the day of purchase.
The buyer’s rights emerging from the acts of warranty and guarantee:
The buyer has the rights listed in Sections 306-307 of Act IV of 1959 on the Civil Code, Section 6 (1) of Law-decree 2 of 1978 and Government Decree 117/1991. (IX.10.). Once the buyer reported his claim the repair work must commence within 30 days from the date of report and finished within the subsequent 30 days. I have received the user manual and accepted its content!
.........................................................Stamp & signature
Loading...