
08180012-2 03/2003
TECHNICAL DATA & SERVICE MANUAL
MODELS WITH R407C
SMDV

INDOOR UNIT COMPONENTS SPECIFICATION
OUTDOOR UNIT COMPONENTS SPECIFICATION
HEAT EXCHANGER FROSTING PREVENTION
ELECTRICAL CIRCUIT INTERRUPTED AFTER "ON" IS PRESSED
ELECTRIC CIRCUIT INTERRUPTED 3 MINUTES
FAN MOTOR DOES NOT WORK WHILE "ON" BUTTON
FAN MOTOR WORKS AT ONE SPEED ONLY (FMI) 11
POOR COOLING 11
FAN MOTOR WORKS NORMALLY BUT THE
COMPRESSOR DOES NOT OPERATE (FMI)
OUTDOOR UNIT FAN (FMO) DOES NOT OPERATE
THE FLASHING LED IS ON, AND THE UNIT NOT OPERATE
COMPRESSOR DOES NOT WORK BUT FAN MOTOR OPERATE NORMALLY
1;ADDED NEW ELECTRIC WIRING DIAGRAM FOR MODELS SMDV143C5

TECHNICAL DATA
UNIT SPECIFICATIONS
SMDV9XC5 SMDV11XC5 SMDV14XC5
Air flow rate (evaporator)
Air flow rate (condenser)
Moisture removal l/h 0,8 1 1,6
Coefficient of performance
Compressor locked rotor amperes A 20 23 35
FEATURES
Controls/Temperature controls
Refrigerant/standard charge at shipment
Refrigerant control
Noise level Lp (NOTE 3) INT.high/low dB(A) 44/40 44/40 47/45
Width mm 470
Depth mm 310
External unit Kg 8,5 9,5 13
Data can be changed without notice
NOTE 1: Rating conditions (ISO 5151):
Internal temperature: 27°C D.B. , 19°C W.B.
External temperature: 32°C D.B. , 24°C W.B.
NOTE 2: Operating limits: MINIMUM MAXIMUM
Internal temperature: 15°C D.B.,12°C W.B. 32°C D.B.,23°C W.B.
External temperature: 15°C D.B. 46°C D.B.
NOTE 3: Refering data :
Internal unit: room size 100m3 ; reverberation time 0,5sec.; distance 2m.
External unit: hemispheric radiance; distance 4m.
switches on the unit
two
Rotary (hermetic)
Capillary tube
Electronic/ I.C. thermostat
3

TECHNICAL DATA
INDOOR UNIT COMPONENTS SPECIFICATION
SMDV9XC5 SMDV11XC5 SMDV14XC5
Function selection and indicator lamps
Primary 220V
Secondaty 10,5V
Resistance
kΩ
-20°C 5846±5% ; 20°C 604±5%
-10°C 3159±5% ; 30°C 368±5%
0°C 1766±5% ; 40°C 230±5%
10°C 1018±5% ; 50°C 147±5%
10°C 1018±5% ; 30°C 368±5%
15°C 781±5% ; 35°C 290±5%
20°C 604±5% ; 40°C 230±5%
25°C 470±5% ; 50°C 147±5%
FAN & FAN MOTOR (FMI) M01582
Nominal input (230V) W 36
Electronic microprocessor
COOLING / FAN
HIGH/LOW speed
ALARM lamp
ON / OFF
4

FINDER OMRON FINDER OMRON OMRON OMRON
65.31 G4F 65.31 G4F G7L G4F
RY1 RY1.1 RY1 RY1.1 RY1 RY1.1
230V~50Hz 12Vdc 230V~50Hz 12Vdc 230V~50Hz 12Vdc
7.250±10% 158±10% 7.250±10% 158±10% 21.000±15% 158±10%
Contact rating
30A-250V 20A-250V 30A-250V 20A-250V 25A-250V 20A-250V
SAFETY DEVICE (OLR)
Operanting temperature Open
Operanting temperature
(OLR 1)
Close
Operanting temperature
(OLR 2)
Operanting temperature Open
RUN CAPACITOR (C3)
Capacity µF
POWER RELAY (RA) COMPRESSOR
HEAT EXCHANGER
Coils
Rows
Fin pitch mm
Face area m²
500
3,01±7%
550
1,92÷1,84±7%
5,28÷7,1±7%
MRA990003-9201 MST20ALU-9201
3,31±7%
7,82±7%7,35±7%
500
in 6÷16 sec.
135±5°C
69±11°C
19A
in 6÷16 sec.
140±5°C
22,5A
in 6÷16 sec.
CS-7C115
115±4°C
95±10°C
MST56ALU
80235245B
1290
COMPRESSOR
150±5°C
69±11°C
830 950
80225245B 80228245B
22,5
450
20
450
2 3 3
60÷120V~
690±5%
14
Alluminium fin / Copper tube
EVAPORATOR COIL
1,8
0,118
300V~50Hz
330
IF EQUIPED
13,150±2%
20A
185÷217V~
56
5

TECHNICAL DATA
OUTDOOR UNIT COMPONENTS SPECIFICATION
SMDV9XC5 SMDV11XC5 SMDV14XC5
Nominal input (230V) W 61 61 75
CLOSE
FAN ALTERNATIVE MOTOR (FMO) 40101243-L 40101243-L -
W7070-Coil resistance (20°C)
safety device Thermostat Thermostat -
Setting: OPEN °C 150±10 150±10 -
HEAT EXCHANGER
Coils
Rows
Automatic
Internal thermostat
230V~50Hz
CONDENSER COIL
6

TECHNICAL DATA
ROOM TEMPERATURE CONTROL
Room temperature control is obtained by cycling the compressor ON and OFF by means of room
temperature sensor TH
ON/OFF SWITCH
COMPRESSOR
SWITCH
COMPRESSOR
SET
TEMPERATURE +1°C
SET
TEMPERATURE
FAN
SET SPEED
NOTES:
1. If the compressor is turned off, the control circuit sets an automatic minimum 3 minutes delay to protect the
compressor from stalling out when trying to start against the high side refrigerant pressure.
2. If the room temperature is 1°C above the set temperature, the compressor starts working if this has been
OFF for at least 3 minutes.
3. If the room temperature is the same or under the set temperature the compressor stops working.
HEAT EXCHANGER FROSTING PREVENTION
The electronic control stops automatically the compressor each time the coil sensor TH reaches a
temperature of 1°C for 8 ÷ 10 minutes long, the compressor starts again automatically when the
temperature of heat exchanger reaches 8°C. The fan goes on working at the set speed.
minimum 10 minimum
minutes 3 minutes
ON/OFF SWITCH
COMPRESSOR
SWITCH
COMPRESSOR
HEAT EXCHANGER
TEMP.= 8 °C
HEAT EXCHANGER
TEMP.= 1 °C
FAN

TECHNICAL DATA
PERFORMANCE CHART
OPERATING CHARACTERISTICS WITH RELATIVE HUMIDITY AROUND 50%
SMDV117C5
3
3,5
4
4,5
5
5,5
20 25 30 35 40 45 50
EXTERNAL TEMPERATURE (°C)
OPERATING CURRENT (A)
21 °C
27 °C
32 °C
SMDV97C5
3
3,2
3,4
3,6
3,8
4
4,2
4,4
4,6
4,8
5
20 25 30 35 40 45 50
EXTERNAL TEMPERATURE (°C)
OPERANTING CURRENT (A)
21 °C
27 °C
32 °C
SMDV147C5
4
4,5
5
5,5
6
6,5
7
20 25 30 35 40 45 50
EXTERNAL TEMPERATURE (°C)

SERVICE MANUAL
THE UNIT DOES NOT WORK
Check the voltage. Are NO Check the unit YES Check the electrical
there 198 ÷ 264 volts ? electrical cable supply line
YES
(IF INSTALLED) If it is impossible to
Check if programmer NO close the contact,
contact is closed (black - replace the
brown cables). programmer.
YES
Check if the supplied NO Check if tank micro voltage on switch contacts are
the electric control (CE) closed.
(1 - 2 MS contacts)
YES
NO
Replace the electronic Check if the pilot NO Is the flickering alarm
control (CE) lamp is burnt. lamp on the control
Eventually replace panel not visible ?
it.
ELECTRIC CIRCUIT INTERRUPTED WHEN "ON" BUTTON IS PRESSED
Check the unit hardness NO Insulate the short
Is it insulated ? circuit cable
YES
Check if the fan motor is NO Replace the fan motor
working (FMI) (FMI)
YES
Check if the fan motor is NO Replace the fan motor
working (FMO) (FMO)
YES
Check the electronic NO Replace the electronic
control (CE) control (CE)
YES
Check the leds printed NO Replace the leds
circuit. printed circuit.
NO
(IF INSTALLED) Replace the
Check the motor YES

SERVICE MANUAL
ELECTRICAL CIRCUIT INTERRUPTED 3 MINUTES AFTER "ON" BUTTON IS
COOLING
OPERATION
Check if compressor relay NO
connections are connections.
insulated.
YES
Check if compressor relay YES
circuit ? (PR)
NO
Check if compressor
circuited.
YES
Replace the
NO
(FMO) Check if
compressor(CM) outdoor fan motor
works
FAN MOTOR (FMI)DOES NOT WORK WHILE "ON" BUTTON IS PRESSED
Disconnect the unit from line. Check if the fan motor is well
fitted and if the blades can rotate
YES NO NO
Check hardness and Fit the fan motor Remove obstruction
various continuities properly or replace or replace fan motor
YES it assembly
Check the capacitor NO
Replace the capacitor
capacity (C)
YES
Check the fan motor INTERRUPTED Replace the fan motor
windings (FMI). assembly
YES
Replace the electronic
control (CE)
10

SERVICE MANUAL
FAN WORKS AT ONE SPEED ONLY(FMI)
Check electrical conec- NO Fit electrical connec tions. Is there continuity ? tions properly
YES
Check power supply NO Replace the electronic
on electronic control (CE)
control contacts (CE)
YES
Check fan motor winding
values (FMI))
YES
Replace fan motor (FMI)
POOR COOLING
Is the unit cooling capacity NO Suggest a more power suitable for the room ful unit
thermal loads ?
YES
Are both air filters and heat NO Clean filters and / or
exchanger cleaned ? heat exchanger
YES
Check if difference bet- YES
The unit works properly
ween room air
temperature and outlet air
delivered is up to 10 °C
gas charge
Proceed with
normal operations
foreseen for the
above points
11

SERVICE MANUAL
FAN MOTOR WORKS NORMALLY BUT THE COMPRESSOR DOES NOT OPERATE(FMI)
Check hardness
and continuity. Is the
relay compressor
coil (PR white cable)
power supplied ? YES
Replace the relay NO Check if relay YES Is the thermostat NO Adjust thermostat
(PR) contects are closed in the right posi - position
tion ?
YES YES
Replace klixon (ORL)
YES Check compressor Is room tempera - NO The unit cannot
klixon contacts(ORL) ture over 15 °C ? operate below
Are they open ?
15 °C
NO YES
Replace the NO Check the capaci - Check the sensor NO Replace the
capacitor (C) tor capacity (C) continuity (TH) sensor (TH)
on electronic
control (CE)
YES terminal blocks
YES
Replace the NO Check the com - Check electronic
compressor pressor winding control (CE)
continuity
OUTDOOR FAN(FMO) DOES NOT OPERATE.
Have 3 minutes time delay Wait for about 3 minutes
already elapsed since "on"
operation?
YES
Disconnect the unit from line Remove causes stopping
and manually rotate the
Check electrical connections Replace outdoor fan motor
and winding continuity on
Is the voltage in coil relay (RC)
Is the relay contact closed
Check electronic control (CE)
Check capacitor capacity.
Replace electronic control (CE)
12

SERVICE MANUAL
THE FLASHING LED IS ON, AND THE UNIT DOES NOT OPERATE
Check electrical connections
Check safety micro floating (MS)
Replace safety micro floating (MS)
Check condensate pump motor
Replace condensate pump motor
Replace safety relay (RS)
COMPRESSOR DOES NOT WORK BUT FAN MOTOR OPERATES NORMALLY.
Check hardness and continuities. Have 3 minutes time delay Wait for about 3 minutes
Is relay compressor coil power NO already elapsed since"on" NO
Is the thermostat properly
relay(RC) contact is closed set? thermostat position.
Is it properly fitted? It could
Is the rom temperature over
Check sensor continuity of
Check electronic control.(CE)

TECHNICAL DATA
ELECTRICAL WIRING DIAGRAM FOR MODELS WITH POWER RELAY 220V AND PCB RY1
ELECTRICAL WIRING DIAGRAM FOR MODELS WITH POWER RELAY 12V AND PCB RY1.1

TECHNICAL DATA
ELECTRICAL WIRING DIAGRAM FOR MODELS WITH POWER RELAY 12V AND PCB RY1.1