Technibel MCAV180C5VAA, MCAV220C5VAA, GR180C7TAA, KPAV180C5TAA, KPAV220C5TAA Technical Data & Service Manual

...
TECHNICAL DATA & SERVICE MANUAL
Indoor Unit Outdoor Unit
MCAV180/220C5VAA GR180C7TAA
KPAV180/220C5TAA GR220C7TAA
SPLIT SYSTEM AIR CONDITIONER
KPAV180/220C5TAA
MCAV180/220C5VAA
0.8180.166.0 02/2001
i
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the units weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
Table of Contents
Page
1 OPERATING RANGE 1 2 SPECIFICATIONS
2-1 Unit Specification 2 2-2 Major Components Specifications 6
2-3 Other Component Specifications 12 3 DIMENSIONAL DATA 16 4 REFRIGERANT FLOW DIAGRAM 20 5 PERFORMANCE DATA
5-1 Air Throw Distance Chart 21
5-2 Cooling Capacity 24 6 ELECTRICAL DATA
6-1 Electrical Characteristic 28
6-2 Electric Wiring Diagrams 30 7 INSTALLATION INSTRUCTION
7-1 Installation Site Selection 33 7-2 Remote Control Unit Installation Position 35 7-3 Recommended Wire Length and Diameter 36
8 FUNCTION
8-1 Room Temperature Control 37
8-2 Dry Operation 38
8-3 Freeze Prevention 38
9 TROUBLESHOOTING
9-1 Check before and after troubleshooting 39
9-2 Air Conditioner Does not operate 40 9-3 Some Parts of Air Conditioner does not operate 45 9-4 Air Conditioner operates, but abnormalities are observed 48 9-5 If a Sensor is defective 49
10 CHECKING ELECTRICAL COMPONENTS
10-1 Measure of insulation Resistance 50 10-2 Check Continuity of fuse on PCB Ass’y 51
10-3 Checking Motor Capacitor 51 11 DISASSEMBLY PROCEDURE FOR INDOOR UNIT
11-1 Removing air intake grille 52 11-2 Removing side panels 53 11-3 Access and removal of electrical component box 53 11-4 Removing flap motor 54 11-5 Removing evaporator 54 11-6 Removing fan and fan motor 56
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 46°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
2
2. SPECIFICATIONS
2-1. Unit Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Surce.......Voltage Rating 400V - 3N - 50Hz .. ....400 V
Control Circuit V 230 V 50 Hz
Cooling
Capacity
kW 4.9
BTU/h 17000
Air circulation (High) m
3
/h 760 Moisture removal (High) Liters/h 2.0 Available voltage range V 342 to 418 Running amperes A 4.0 Power input W 1960 Power factor % 80 C.O.P. W/W 2.5 Compressor locked rotor amperes A 21.5 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi,LO)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22/ 1405 Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 55 / 51 / 49
Outdoor – Hi dB-A 64 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 12.7 (1/2)
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 630
Width mm 995 830
Depth mm 206 305 Package dimensions Height mm 276 713
Width mm 1,070 994
Depth mm 363 413
Weight Net
kg 12.0 52
Shipping
kg 15.0 57
Shipping volume m
3
0.11 0.29
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit MCAV180C5VAA Outdoor Unit GR180C7TAA
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source..... Voltage Rating 400V - 3N - 50Hz........ 400 V
Control Circuit 230 V 50 Hz
Cooling
Capacity
kW 6.0
BTU/h 20500
Air circulation (High) m
3
/h 830 Moisture removal (High) Liters/h 3.2 Available voltage range V 342 to 418 Running amperes A 4.6 Power input W 2500 Power factor % 84 C.O.P. W/W 2.40 Compressor locked rotor amperes A 28 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 2380 Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 58 / 55 /52
Outdoor – Hi dB-A 67 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 15.88(5/8)
Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 835
Width mm 995 850
Depth mm 206 305 Package dimensions Height mm 276 913
Width mm 1,070 1000
Depth mm 363 400
Weight Net
kg 12.0 67.0
Shipping
kg 15.0 76.0
Shipping volume m
3
0.11 0.37
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit MCAV220C5VAA Outdoor Unit GR220C7TAA
Refrigerant tube kit/accessories Optional/Hanging wall bracket
4
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Surce.......Voltage Rating 400V - 3N - 50Hz .. ....400 V
Control Circuit 230 V 50Hz
Cooling
Capacity
kW 4.9
BTU/h 17000
Air circulation (High) m
3
/h 800 Moisture removal (High) Liters/h 2.0 Available voltage range V 342 to 418 Running amperes A 4.0 Power input W 1960 Power factor % 80 C.O.P. W/W 2.50 Compressor locked rotor amperes 21.5 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22/ 1405 Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 48 / 44 / 49
Outdoor – Hi dB-A 51 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 10
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 12.7 (1/2) Refrigerant tube kit Optional
Indoor Unit Outdoor Unit
Unit dimensions Height mm 680 630
Width mm 900 830
Depth mm 190 305 Package dimensions Height mm 813 713
Width mm 1011 994
Depth mm 296 413
Weight Net
kg 23.5 52.0
Shipping
kg 30.0 57.0
Shipping volume m
3
0.24 0.29
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit KPAV180C5TAA Outdoor Unit GR180C7TAA
5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Surce.......Voltage Rating 400V - 3N - 50Hz .. ....400 V
Control Circuit V 230 50Hz
Cooling
Capacity
kW 6.0
BTU/h 20500
Air circulation (High) m
3
/h 900 Moisture removal (High) Liters/h 3.3 Available voltage range V 342 to 418 Running amperes A 4.6 Power input W 2500 Power factor % 84 C.O.P. W/W 2.4 Compressor locked rotor amperes A 28 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto(Hi, Lo)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable,Anti - mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 2380 Refrigerant control Capillary tube
Noise Power Level
Indoor – Hi / Me / Lo dB-A 50 / 47 / 44
Outdoor – Hi dB-A 55 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 10
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 15.88 (5/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 680 835
Width mm 900 850
Depth mm 190 305 Package dimensions Height mm 813 913
Width mm 1011 1000
Depth mm 296 400
Weight Net
kg 23.5 67.0
Shipping
kg 30.0 76.0
Shipping volume m
3
0.24 0.37
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit KPAV220C5TAA Outdoor Unit GR220C7TAA
6
2-2. Major Component Specifications
2-2-1. Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K188E Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS–8PS3E
Type Cross-flow Q´ty ... Dia. and length mm 1 ... ø88 / L746 Fan motor model ... Q´ty UF2– 31A5PA–S ... 1 No. of poles ... rpm (High) 2 ... 1,305 Nominal output W 30 Coil resistance (Ambient temp. 20°C) WHT – BRN : 130.4
WHT – PNK : 169.8
– : – – : – – :
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440 Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 20°C) Each terminals (1–2, 1–3, 1–4, 1–5) 400 : ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m2 0.250
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit MCAV180C5VAA
7
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K228E Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS–8PS3E
Type Cross-flow Q´ty ... Dia. and length mm 1 ... ø88 / L746 Fan motor model ... Q´ty UF2– 31A5PA–S ... 1 No. of poles ... rpm (High) 2 ... 1,380 Nominal output W 30 Coil resistance (Ambient temp. 20°C) WHT – BRN : 130.4
WHT – PNK : 169.8
– : – – : – – :
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440 Type Stepping motor Model MP24GA2 Rating DC 12 V Coil resistance (Ambient temp. 20°C) Each terminals (1–2, 1–3, 1–4, 1–5) 400 : ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m2 0.250
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Circuit
Board
Ass´y
Indoor Unit MCAV220C5VAA
8
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K185GS–N Controls Microprocessor Control circuit fuse 250 V – 3 A
Remote Control Unit RCS – 5PN3E
Type Centrifugal Number ... Dia. and length mm 2 ... ø 130 / L 180 Fan motor model ... Number K48410–M01417 ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,140 Nominal output W 27 Coil resistance (Ambient temp. 20°C) GRY – WHT : 215 ± 7%
WHT – VLT : 87 ± 7%
VLT – YEL : 87 ± 7%
WHT – PNK : 273 ± 7%
Safety
Type Internal thermal fuse
devices
Operating temp.
Open °C 145 ± 5 Close Automatic reclosing
Run capacitor
µF 2.0
VAC 440 Model M2LJ24ZE31 Rating AC 208 / 230 V, 50 / 60 Hz No. of poles ... rpm 8 ... 2.5 / 3.0 Nominal output W 3 / 2.5 Coil resistance (Ambient temp. 20°C) k 16.45 ± 15%
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area m
2
0.192
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit KPAV180C5TAA
9
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K185GS–N Controls Microprocessor Control circuit fuse 250 V – 3 A
Remote Control Unit RCS – 5PN3E
Type Centrifugal Number ... Dia. and length mm 2 ... ø 130 / L 180 Fan motor model ... Number K48410–M01418 ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,280 Nominal output W 41 Coil resistance (Ambient temp. 20°C) GRY – WHT : 95 ±7%
WHT – VLT : 73 ± 7%
VLT – YEL : 73 ± 7%
WHT – PNK : 207 ± 7%
Safety
Type Internal thermal fuse
devices
Operating temp.
Open °C 145 ± 5 Close Automatic reclosing
Run capacitor
µF 2.0
VAC 440 Model M2LJ24ZE31 Rating AC 208 / 230 V, 50 / 60 Hz No. of poles ... rpm 8 ... 2.5 / 3.0 Nominal output W 3 / 2.5 Coil resistance (Ambient temp. 20°C) k 16.45 ± 15%
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area m
2
0.192
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit KPAV220C5TAA
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW-C181BL
Control circuit fuse 250V – 5A Type Rotary (Hermetic) Compressor model C-2R173H8V- 80817C88D Source 380 – 400 V – 3N
~
50 Hz Nominal output W 1,700 Compressor oil ... Amount cc SUNISO 4GSD-T ... 800 Coil resistance (Ambient temp. 25°C) C – R : 6.369
C – S : 6.073 R – S : 6.217
Type Internal protector External protector
Safety
Overload relay HOE-10TB TH-5A
devices
Operating temp.
Open °C 125 ± 5 — Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C) — 5A
Run capacitor
µF
VAC — Crank case heater 240V 30W Type Propeller Q´ty ... Dia. mm 1 ... ø400 Fan motor model ... Q´ty SMEN 19 TFB6055 ... 1 Source 220 – 230 V
~
50 Hz No. of poles ... rpm (220 V, High) 6 ... 910 Nominal output W 43 Coil resistance (Ambient temp. 20°C) WHT – BRN : 77.7 WHT - YEL : 366
WHT – PNK : 211
Safety
Type Internal type
devices
Operating temp.
Open °C 130 ± 5 Close Automatic reclosing
Run capacitor
µF 2.0
VAC 400 Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area m
2
0.508
External Finish Acrylic baked-on enamel finish
Controller
PCB
Heat
Exch. Coil
Compressor
Fan & Fan Motor
10
Outdoor Unit GR180C7TAA
2-2-2. Outdoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. Johnson Control
Type Rotary (Hermetic) Compressor model C-R223H8S - 806187188B Source 380 – 400 V – 3N
~
50 Hz Nominal output W 2200 Compressor oil ... Amount cc SUNISO 4GSD-T ... 1350 Coil resistance (Ambient temp. 25°C) Ω C – R : 4.97
C – S : 4.64 R – S : 4.88
Type Internal protector External protector
Safety
Overload relay - HOE-10TB TH-7A
devices
Operating temp.
Open °C 125 ± 5 — Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C) - 7A
Run capacitor
µF
VAC — Crank case heater 240V 30W Type Propeller Q´ty ... Dia. mm 1 ... ø460 Fan motor model ... Q´ty SMEN 19TFB6064 ... 1 Source 220 – 230 V
~
50 Hz No. of poles ... rpm (220 V, High) 6 ... 840 Nominal output W 50 Coil resistance (Ambient temp. 20°C) WHT – BRN : 99.5 / WHT - YEL : 252
WHT – PNK : 63.2
Safety
Type Internal type
devices
Operating temp.
Open °C 130 ± 5 Close Automatic reclosing
Run capacitor
µF 5.0
VAC 400 Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 2.0 Face area m
2
0.610
External Finish Acrylic baked-on enamel finish
Controller
PCB
Heat
Exch. Coil
Compressor
Fan & Fan Motor
11
Outdoor Unit GR220C7TAA
2-3. Other Component Specifications
12
Thermistor (Room sensor) DTN-TKS142B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit MCAV180C5VAA
MCAV220C5VAA
Indoor Unit KPAV180C5TAA
KPAV220C5TAA
13
Thermistor (Room sensor TH2) KTEC-35-S6
Resistance k 10°C 10.0 ± 4% 30°C 4.0 ± 4%
15°C 7.9 ± 4% 35°C 3.3 ± 4% 20°C 6.3 ± 4% 40°C 2.7 ± 4% 25°C 5.0 ± 4% 50°C 1.8 ± 4%
Thermistor (Coil sensor TH1) PBC-41E-S14
Resistance k –20°C 40.1 ± 5% 20°C 6.5 ± 5%
–10°C 24.4 ± 5% 30°C 4.4 ± 5%
0°C 15.3 ± 5% 40°C 3.0 ± 5%
10°C 9.9 ± 5% 50°C 2.1 ± 5%
Transformer (TR) ATR-H85
Rating Primary AC 230V, 50/60Hz
Secondary 11V, 0.727A Capacity 8VA
Coil resistance (at 21°C) Primary (WHT – WHT): 214 ± 10%
Secondary (BRN – BRN): 1.58 ± 10%
Thermal cut-off temp. 145°C, 2A, 250V
Outdoor Unit GR180C7TAA
Negative Phase Relay (47C) RDR-S400
Rating AC 415V, 3-phase 50Hz Contact rating AC 400V, 1A Operation Positive phase: ON
Negative phase: OFF
Electro Magnetic Contactor (MG) HOE-10TB TH-5A
Magnetic contactor
Coil rating AC 220–240V, 50Hz / AC 240–260V, 60Hz Coil resistance (at 25°C) 1,260 ± 10% Contact rating (Main) AC 440V, 8A
Thermal relay (Overcurrent relay)
Operating amperes 5A
14
MQT5S-27YZJ
Electro Magnetic Contactor (MG) HOE-10TB TH-7A
Magnetic Contactor
Coil rating AC 220–240V, 50Hz / AC 240–260V, 60Hz Coil resistance (at 25°C) 1,260 ± 10% Contact rating (Main) AC 440V, 8A
Thermal relay (Overcurrent relay)
Operating amperes 7A
Negative Phase Relay (47C) RDR-S400
Rating AC 415V, 3-phase 50Hz Contact rating AC 400V, 1A Operation Positive phase: ON
Negative phase: OFF
Thermostat (Fan Speed Control 23S)
YTB-S383
Switching temp. °C
high LOW 28.5°C ± 1 low HIGH31°C ±1
Outdoor Unit GR220C7TAA
15
16
3. DIMENSIONAL DATA
Indoor Unit MCAV180C5VAA
MCAV220C5VAA
28545
995
45
147.5 147.5
206 (3)
Remote control unit
Center of tubing hole (2 places)
Narrow tube ø6.35 (1/4")
Drain hose ø18
Wide tube ø12.7 (1/2") -------- - MCAV180 Wide tube ø15.88 (5/8") MCAV220
61
18.5
172.5
Unit : mm
Indoor Unit KPAV180C5TAA
KPAV220C5TAA
86
74 74
Center of tubing hole ø75 (4 places)
Wide tube ø12.7 (1/2")
Narrow tube ø6.35 (1/4")
Drain hose ø26
74 74
900
86
41
41
190
680
Wide tube ø15.88 (5/8")
KPAV180 KPAV220
Dimensions : mm
17
61
18.5
172.5
18
Outdoor Unit GR180C7TAA
Air discharge
Air intake
538 146
307
337
4 – ø12 holes
830
19
630
305
61 95
Wide tube service valve ø12.7 (1/2")
Narrow tube service valve ø6.35 (1/4")
Unit : mm
19
Outdoor Unit GR220C7TAA
Wide tube service valve ø15.88 (5/8")
Narrow tube service valve ø6.35 (1/4")
Check port ø6.35 (1/4")
86 88
155
57
7386
229
285
835
620130 100 55
20
20
325
850
250250
560
6 – ø3.1 holes
Air intake
Air discharge
Unit : mm
4. REFRIGERANT FLOW DIAGRAM
20
Indoor Unit MCAV180C5VAA
KPAV180C5TAA
Outdoor Unit GR180C7TAA
Compressor
Wide tube service valve
Wide tube
O.D. ø15.88 mm (5/8 ")
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Evaporator
Capillary for liquid injection
Indoor Unit Outdoor Unit
Muffler
Capillary tube
Condenser
Check port
Accumulator
Strainer
Indoor Unit MCAV220C5VAA
Outdoor Unit GR225C7VAA
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
IMPORTANT
CAUTION
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
KPAV220C5TAA
5-1. Air Throw Distance Chart
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
0
1
2
3
4
0 1 2 3 4 5 6 7 8 9
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
0
1
2
3
4
0 1 2 3 4 5 6 7 8 9
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
21
Indoor Unit MCAV180C5VAA
Indoor Unit MCAV220C5VAA
5. PERFORMANCE DATA
22
Indoor Unit KPAV180C5TAA
01234567
01234567
3
4
2
1
0
1
0
2
3
4
Horizontal distance (m)
Horizontal distance (m)
Axis air verocity (m/s)
Vertical distance (m)
Axis air verocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Axis air verocity
Flap angle
60°
45°
Axis air verocity
Flap angle
45°
30°
Floor mounted
Ceiling mounted
AIR FLOW CHART
23
Indoor Unit KPAV220C5TAA
01234567
01234567
3
4
2
1
0
1
0
2
3
4
Horizontal distance (m)
Horizontal distance (m)
Axis air verocity (m/s)
Vertical distance (m)
Axis air verocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Axis air verocity
Flap angle
60°
45°
Axis air verocity
Flap angle
45°
30°
Floor mounted
Ceiling mounted
RATING CAPACITY 4.9 kW AIR FLOW RATE 760 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 4.64 4.51 4.29 4.03 3.72
CM 1.61 1.72 1.85 2.03 2.21 21 SHC 3.18 3.12 3.01 2.89 2.74 23 SHC 3.61 3.54 3.43 3.30 3.15
15 25 SHC 4.02 3.94 3.83 3.71 3.56
27 SHC 4.45 4.36 4.25 4.03 3.72 29 SHC 4.64 4.51 4.29 4.03 3.72 31 SHC 4.64 4.51 4.29 4.03 3.72
TC 5.03 4.84 4.60 4.32 3.98
CM 1.65 1.77 1.90 2.09 2.27 21 SHC 2.78 2.71 2.60 2.47 2.31 23 SHC 3.20 3.11 3.00 2.88 2.73
17 25 SHC 3.63 3.53 3.42 3.29 3.13
27 SHC 4.05 3.93 3.82 3.70 3.55 29 SHC 4.47 4.35 4.24 4.11 3.95 31 SHC 4.89 4.75 4.60 4.32 3.98
TC 5.33 5.15 4.90 4.60 4.24
CM 1.73 1.83 1.96 2.15 2.33 21 SHC 2.33 2.26 2.15 2.02 1.87 23 SHC 2.74 2.67 2.57 2.44 2.29
19 25 SHC 3.14 3.08 2.97 2.85 2.70
27 SHC 3.55 3.49 3.39 3.26 3.11 29 SHC 3.94 3.90 3.79 3.68 3.52 31 SHC 4.36 4.31 4.21 4.08 3.93
TC 5.65 5.45 5.20 4.88 4.50
CM 1.77 1.88 2.02 2.21 2.40 23 SHC 2.30 2.23 2.12 1.99 1.84
21 25 SHC 2.70 2.63 2.54 2.41 2.26
27 SHC 3.11 3.05 2.94 2.82 2.66 29 SHC 3.50 3.45 3.36 3.23 3.08 31 SHC 3.91 3.87 3.76 3.64 3.49
TC 6.03 5.77 5.45 5.10 4.75
CM 1.80 1.92 2.07 2.26 2.46
23 25 SHC 2.26 2.16 2.05 1.92 1.79
27 SHC 2.65 2.57 2.45 2.32 2.19 29 SHC 3.04 2.98 2.87 2.74 2.61 31 SHC 3.48 3.40 3.27 3.14 3.03
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
24
5-2. Cooling Capacity
Indoor Unit MCAV180C5VAA Outdoor Unit GR180C7TAA
RATING CAPACITY 6 kW AIR FLOW RATE 830 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 5.69 5.52 5.26 4.93 4.55
CM 2.06 2.20 2.36 2.59 2.82 21 SHC 3.90 3.82 3.69 3.53 3.35 23 SHC 4.42 4.33 4.20 4.04 3.86
15 25 SHC 4.92 4.83 4.70 4.54 4.36
27 SHC 5.44 5.33 5.20 4.93 4.55 29 SHC 5.69 5.52 5.26 4.93 4.55 31 SHC 5.69 5.52 5.26 4.93 4.55
TC 6.16 5.92 5.63 5.30 4.88
CM 2.10 2.26 2.42 2.67 2.90 21 SHC 3.41 3.31 3.18 3.03 2.83 23 SHC 3.92 3.81 3.68 3.52 3.34
17 25 SHC 4.44 4.32 4.19 4.03 3.83
27 SHC 4.95 4.81 4.68 4.53 4.34 29 SHC 5.48 5.32 5.19 5.03 4.84 31 SHC 5.99 5.82 5.63 5.30 4.88
TC 6.52 6.30 6.00 5.63 5.19
CM 2.21 2.33 2.50 2.74 2.97 21 SHC 2.86 2.77 2.63 2.48 2.30 23 SHC 3.36 3.27 3.14 2.99 2.80
19 25 SHC 3.85 3.77 3.64 3.50 3.30
27 SHC 4.34 4.28 4.15 3.99 3.81 29 SHC 4.83 4.77 4.64 4.50 4.30 31 SHC 5.33 5.28 5.15 5.00 4.81
TC 6.91 6.68 6.37 5.97 5.50
CM 2.26 2.39 2.58 2.82 3.06 23 SHC 2.82 2.73 2.60 2.44 2.26
21 25 SHC 3.30 3.22 3.10 2.95 2.77
27 SHC 3.80 3.73 3.60 3.46 3.26 29 SHC 4.29 4.23 4.11 3.95 3.77 31 SHC 4.79 4.73 4.60 4.46 4.28
TC 7.38 7.07 6.68 6.25 5.82
CM 2.30 2.45 2.64 2.88 3.14
23 25 SHC 2.77 2.65 2.50 2.35 2.19
27 SHC 3.24 3.14 3.00 2.84 2.69 29 SHC 3.73 3.65 3.51 3.35 3.20 31 SHC 4.26 4.16 4.00 3.85 3.70
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
Indoor Unit MCAV220C5VAA
Outdoor Unit GR220C7TAA
25
RATING CAPACITY 4.9 kW AIR FLOW RATE 800 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 4.64 4.51 4.29 4.03 3.72
CM 1.61 1.72 1.85 2.03 2.21 21 SHC 3.18 3.12 3.01 2.89 2.74 23 SHC 3.61 3.54 3.43 3.30 3.15
15 25 SHC 4.02 3.94 3.83 3.71 3.56
27 SHC 4.45 4.36 4.25 4.03 3.72 29 SHC 4.64 4.51 4.29 4.03 3.72 31 SHC 4.64 4.51 4.29 4.03 3.72
TC 5.03 4.84 4.60 4.32 3.98
CM 1.65 1.77 1.90 2.09 2.27 21 SHC 2.78 2.71 2.60 2.47 2.31 23 SHC 3.20 3.11 3.00 2.88 2.73
17 25 SHC 3.63 3.53 3.42 3.29 3.13
27 SHC 4.05 3.93 3.82 3.70 3.55 29 SHC 4.47 4.35 4.24 4.11 3.95 31 SHC 4.89 4.75 4.60 4.32 3.98
TC 5.33 5.15 4.90 4.60 4.24
CM 1.73 1.83 1.96 2.15 2.33 21 SHC 2.33 2.26 2.15 2.02 1.87 23 SHC 2.74 2.67 2.57 2.44 2.29
19 25 SHC 3.14 3.08 2.97 2.85 2.70
27 SHC 3.55 3.49 3.39 3.26 3.11 29 SHC 3.94 3.90 3.79 3.68 3.52 31 SHC 4.36 4.31 4.21 4.08 3.93
TC 5.65 5.45 5.20 4.88 4.50
CM 1.77 1.88 2.02 2.21 2.40 23 SHC 2.30 2.23 2.12 1.99 1.84
21 25 SHC 2.70 2.63 2.54 2.41 2.26
27 SHC 3.11 3.05 2.94 2.82 2.66 29 SHC 3.50 3.45 3.36 3.23 3.08 31 SHC 3.91 3.87 3.76 3.64 3.49
TC 6.03 5.77 5.45 5.10 4.75
CM 1.80 1.92 2.07 2.26 2.46
23 25 SHC 2.26 2.16 2.05 1.92 1.79
27 SHC 2.65 2.57 2.45 2.32 2.19 29 SHC 3.04 2.98 2.87 2.74 2.61 31 SHC 3.48 3.40 3.27 3.14 3.03
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
Indoor Unit KPAV180C5TAA
Outdoor Unit GR180C7TAA
26
RATING CAPACITY 6 kW AIR FLOW RATE 900 m³/h
EVAPORATOR CONDENSER ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 5.69 5.52 5.26 4.93 4.55
CM 2.06 2.20 2.36 2.59 2.82 21 SHC 3.90 3.82 3.69 3.53 3.35 23 SHC 4.42 4.33 4.20 4.04 3.86
15 25 SHC 4.92 4.83 4.70 4.54 4.36
27 SHC 5.44 5.33 5.20 4.93 4.55 29 SHC 5.69 5.52 5.26 4.93 4.55 31 SHC 5.69 5.52 5.26 4.93 4.55
TC 6.16 5.92 5.63 5.30 4.88
CM 2.10 2.26 2.42 2.67 2.90 21 SHC 3.41 3.31 3.18 3.03 2.83 23 SHC 3.92 3.81 3.68 3.52 3.34
17 25 SHC 4.44 4.32 4.19 4.03 3.83
27 SHC 4.95 4.81 4.68 4.53 4.34 29 SHC 5.48 5.32 5.19 5.03 4.84 31 SHC 5.99 5.82 5.63 5.30 4.88
TC 6.52 6.30 6.00 5.63 5.19
CM 2.21 2.33 2.50 2.74 2.97 21 SHC 2.86 2.77 2.63 2.48 2.30 23 SHC 3.36 3.27 3.14 2.99 2.80
19 25 SHC 3.85 3.77 3.64 3.50 3.30
27 SHC 4.34 4.28 4.15 3.99 3.81 29 SHC 4.83 4.77 4.64 4.50 4.30 31 SHC 5.33 5.28 5.15 5.00 4.81
TC 6.91 6.68 6.37 5.97 5.50
CM 2.26 2.39 2.58 2.82 3.06 23 SHC 2.82 2.73 2.60 2.44 2.26
21 25 SHC 3.30 3.22 3.10 2.95 2.77
27 SHC 3.80 3.73 3.60 3.46 3.26 29 SHC 4.29 4.23 4.11 3.95 3.77 31 SHC 4.79 4.73 4.60 4.46 4.28
TC 7.38 7.07 6.68 6.25 5.82
CM 2.30 2.45 2.64 2.88 3.14
23 25 SHC 2.77 2.65 2.50 2.35 2.19
27 SHC 3.24 3.14 3.00 2.84 2.69 29 SHC 3.73 3.65 3.51 3.35 3.20 31 SHC 4.26 4.16 4.00 3.85 3.70
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
Indoor Unit KPAV220C5TAA
Outdoor Unit GR220C7TAA
27
28
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at
23O V 50 Hz 400 - 3N - 50Hz
Rating Conditions Running Amps. A 0.39 0.55 3.66 4.6
Power Input kW 0,075 0,120 2.305 2,5
Full Load Conditions Running Amps. A 0.39 0.55 4.46 5.4
Power Input kW 0,075 0,120 2.855 3,05
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit MCAV220C5VAA Outdoor Unit GR220C7TAA
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at
230 V 50 Hz 400 V - 3N - 50Hz
Rating Conditions Running Amps. A 0.37 0.50 3.13 4.0
Power Input kW 0,070 0,093 1,96 1.96
Full Load Conditions Running Amps. A 0.37 0.50 3.6 4.5
Power Input kW 0,070 0,093 2.16 2.33
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit MCAV180C5VAA Outdoor Unit GR180C7TAA
Indoor Unit KPAV180C5TAA
Outdoor Unit GR180C7TAA
Rating Conditions: Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions: Indoor Air Temperature 32°C DB / 23°C WB
Outdoor Air Temperature 43°C DB
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50Hz
Rating Conditions
Running Amps. A 0.33 0.40 3.27 4.0 Power Input kW 0.071 0.082 1.807 1.96
Full Load Conditions
Running Amps. A 0.33 0.40 3.77 4.5 Power Input kW 0.071 0.082 2.177 2.33
400 V – 3N ~ 50Hz
Rating Conditions: Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions: Indoor Air Temperature 32°C DB / 23°C WB
Outdoor Air Temperature 43°C DB
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50Hz
Rating Conditions
Running Amps. A 0.40 0.55 3.65 4.6 Power Input kW 0.083 0.120 2.297 2.50
Full Load Conditions
Running Amps. A 0.40 0.55 4.45 5.4 Power Input kW 0.083 0.120 2.847 3.05
400 V – 3N ~ 50Hz
Indoor Unit Outdoor Unit
KPAV220C5TAA GR220C7TAA
29
6-2 Electric Wiring Diagrams
Indoor Unit KPAV180C5TAA
WARNING
To avoid electrical shock hazard, be
sure to disconnect power before checking, servicing and/or cleaning any electrical parts
KPAV220C5TAA
30
Indoor Unit MCAV180C5VAA
MCAV220C5VAA
31
1 2
4
L1
L3
L2
N
TP2
GRN/YEL
FMO
CM
GRY GRY
GRN/YEL
7
UW
14
V
UW
MG
A
8
GRY
S13RT
B
YEL
RED
WHT
BLU
R
S
T
GRN/YEL
GRN/YEL
GRY
RED RED
RED GRY
WHT
BLU
RED
BLU
47C
S
A
C
TRB
BLK
WHT
BRN
CC
ORG
THERMO
C2
WHT
YEL
BRN
PNK
GRY
WHT
YEL
BRN
PNK
GRY
GRY
Indoor Unit GR180C7TAA
WARNING
To avoid electrical shock hazard, be
sure to disconnect power before checking, servicing and/or cleaning any electrical parts
GR220C7TAA
TO INDOOR UNIT
32
33
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection
To prevent abnormal heat generation and the possibility of fire, don’t place obstacles, enclosures and grills in front of or surrounding the air conditioner in a way that may block air flow.
AVOID:
direct sunlight.
nearby heat sources that may affect performance of the unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of the room can be uniformly air-conditioned. (High on a wall is best)
select a location that will hold the weight of the unit.
select a location where tubing and drain pipe have the shortest run to the outside.
allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 1)
install the unit within the maximum elevation difference (H) above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed Table 1 and Fig. 2a.
Indoor Unit
,
15 cm
min.
15 cm min.
15 cm min.
INDOOR UNIT
Front View
INDOOR UNIT
Tubing length (L)
OUTDOOR UNIT
Elevation difference (H)
Fig. 2
Fig. 2a
Fig.1
WARNING
Table 1
* If total tubing length becomes 7.5 to 20 m (max.), charge additional refrigerant (R22) by 25 g/m.
No additional charge of compressor oil is necessary.
Model
Max. Allowable
Tubing Length at
Shipment (m)
Limit of Tubing
Length (L)
(m)
Limit of Elevation
Difference (H)
(m)
Required Amount of
Additional Refrigerant
(g/m)*
MCAV180/KPAV180 20
Minimum height from floor level
1.5m
Indoor Unit
Wall
Floor level
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than
1.5m from floor level.
CAUTION
Fig. 2b
7.5 7 25
MCAV220/KPAV220 7.5 30
34
AVOID:
heat sources, exhaust fans, etc. (Fig. 3)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/exhaust and possible maintenance. (Figs. 4a to 4c)
provide a solid base (concrete block, 10 ✕40 cm beams or equal), a minimum of 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig.5a and 5b)
use lug bolts or equal to bolt down unit, reducing vibration and noise.
Outdoor Unit
Outdoor unit
Hot air
Heat source
Exhaust fan
Fig. 3
Air intake
Min. 10 cm
Air discharge
Min.
5 cm
Min. 40 cm
Valve side Min. 25 cm
Top View
Air intake
Concrete or equal
About 10 cm
Min. 10 cm
Anchor bolts (4 pcs.)
About 40 cm
Fig. 5 - A
Ground
Obstacle
Obstacle above
Air discharge
Min.
2 m
Min.
2 m
Side View
Fig. 4c
Required space around the unit.
Top View
Fig. 4a
Fig. 5a
Fig. 5 - B
Min. 10 cm
Anchor bolts (4 pcs.)
Fig. 5b
Min. 10 cm
Air discharge
Min.
10 cm
Min. 50 cm
Valve side Min. 60 cm
Air intake
Top View
Fig. 4b
GR180C7VAA mod.
GR220C7VAA mod.
GR180/220C7VAA mod.
GR180C7VAA mod.
GR220C7VAA mod.
35
7-2. Remote Control Unit Installation
Position
The remote control unit can be operated from either a non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places:
In direct sunlight
Behind a curtain or other place where it is covered
More than 8 m away from the air conditioner
In the path of the air conditioner's airstream
Where it may become extremely hot or cold
Where it may be subject to electrical or magnetic interference
Mounting on a Wall
a) Removable mounting
1) Momentarily hold the remote control unit at the desired mounting position.
2) Confirm that the air conditioner responds correctly when you press keys on the remote control from that position.
3) After confirming correct operation, use a screwdriver to screw the supplied special mounting screw into the wall. (Fig.6a)
4) Hang the remote control unit from the mounting screw.
b) Non-removable mounting
1) Momentarily hold the remote control unit at the desired mounting position.
2) Confirm that the air conditioner responds correctly when you press keys on the remote control from that position.
3) After confirming correct operation, use a screwdriver to screw the supplied special mounting screw into the wall. (Fig.6a)
4) Remove the remote control cover by sliding it downward.
5) Remove the batteries of the remote control unit.
6) Use a screwdriver to screw the remote control unit securing screw into the wall through the hole in the battery compartment. (Fig.6b)
7) Replace the batteries.
8) Again confirm that the remote control unit operates correctly.
Wall
Special mounting screw
Screw
Wall
Fig.6b
Fig.6a
Removable mounting
Non-removable mounting
36
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation.
Table 2 lists recommended wire lengths and cross section area for power supply systems.
Refer to the WIRING SYSTEM DIAGRAM for the meaning of "A" and "B" in Table 2.
NOTE
Be sure to comply with local codes on running the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.).
Each wire must be firmly connected.
No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part.
To avoid the risk of electric shock, each air conditioner unit must be grounded.
Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit.
WARNING
WARNING
CAUTION
WIRING SYSTEM DIAGRAM
Power supply
220 – 240 V 50Hz
Ground
(A)
2
1
INDOOR
UNIT
OUTDOOR
UNIT
GR180C7VAA GR220C7VAA
L N
1 2
4 4
(B)
7-3. Recommended Wire Length and Size
Table 2
Cross-Sectional
Fuse or Circuit
Area (mm
2
)
2.5 2.5
Model
Breaker Capacity
GR180C7TAA
20 30
20 A22 20 A
GR220C7TAA
16
mm
2
mm
2
(A) Power Supply Wiring Length (m)
(B) Power Line
8. FUNCTION
8-1. Room Temperature Control
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit.
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor operation.
Thermo. ON : When the room temperature is above T + 1°C (T°C is set temperature).
Compressor ➞ON
Thermo. OFF : When the room temperature is equal to or below set temperature T°C.
Compressor ➞OFF
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes
3 minutes5 minutes
ON OFF ON OFF ON OFFCompressor
ON OFF ON OFF ON OFF
More than
5 minutes
Outdoor fan
Indoor fan
Set speed
T+1 °C
T °Cset temp.
Thermo. OFF
Thermo. OFF
Thermo. ON
Thermo. OFF
Thermo. ON
Thermo. ON
Thermo. ON
Room temp.
Signal from remote control unit
37
8-2. Dry Operation (Dehumidification)
Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON and OFF automatically as shown in the chart below according to the room temperature.
Intermittent ventilation occurs by switching the indoor fan speed between L LL.
Dry operation does not occur when the room temperature is under 15°C, which is the monitor zone.
When the compressor stops, the indoor fan stops as well.
8-3. Freeze Prevention
This function prevents freezing of the indoor heat exchange coil.
When the compressor has been running for 10 minutes or more and the temperature of the indoor heat exchange coil falls below –1°C, the control circuit stops the compressor for at least 6 minutes. The compressor does not start again until the temperature rises above 8°C or 6 minutes has elapsed.
ON ON ON ON
OFFOFF
Set speed
More than
10 minutes
6 minutes
T+1 °C
Indoor heat exch. coil temp.
–1 °C
Compressor
Indoor fan
Room temp.
Thermo. OFF
Thermo. ON
Set temp. T °C
More than
10 minutes
More than
6 minutes
Set speed
NOTE
Room temp.
Cooling operation
T+2 °C
Set temp. T °C
T–1 °C
Monitor zone Both the indoor and outdoor units stop.
Room temp. 15 °C
Dry A zone
Compressor : FMI (indoor fan) :
Continuous operation L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
Dry B zone
Compressor : FMI (indoor fan) :
Intermittent operation (ON for 3 minutes and OFF for 9 minutes) L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
38
9. TROUBLESHOOTING
9-1. Check before and after
troubleshooting
9-1-1. Check power supply wiring.
Check that power supply wires are correctly connected to terminals L and N on the terminal plate in the outdoor unit.
9-1-2. Check inter-unit wiring.
Check that inter-unit wiring is correctly connected to the indoor unit from the outdoor unit.
9-1-3. Check power supply.
Check that voltage is in specified range (±10% of the rating).
Check that power is being supplied.
9-1-4. Check lead wires and connectors in
indoor and outdoor units.
Check that coating of lead wires is not damaged.
Check that lead wires and connectors are firmly connected.
Check that wiring is correct.
39
WARNING
Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing.
1
Indoor
unit
Outdoor
unit
Inter-unit wiring
Power supply: 380 V – 400 V 3N ~ 50 Hz
N
2
L1 L2 L3
L1 L2
L3
N
Ground
Ground
1 2
4 4
Check that power supply wires are correctly connected to terminals L1, L2 , L3 and N on the terminal plate in the outdoor unit.
THREEPHASE MODELS
380V – (400V)
380V – (400V)
380V – (400V)
L1
L2
L3
N
220V – (230V)
THREEPHASE MODELS
40
9-2. Air conditioner does not operate.
9-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 2Mor less, insulation is defective (“NO”).
1
Indoor
unit
Ground
Outdoor
unit
21
2
4
2
4
11
N
L2
L1
L3
N
L2
L1
L3
Power supply
Power supply wiring
Inter-unit wiring
Circuit breaker
Measure insulation resistance of electrical parts in outdoor unit.
NO
NO
Set circuit breaker to OFF.
*
Measure insulation resistance of electrical parts in indoor unit.
1
Remove both power supply wires and inter-unit wires from terminal plate in outdoor unit.
Measure insulation resistance of outdoor unit.
2
Remove inter-unit wires from terminal plate in indoor unit.
Measure insulation resistance of indoor unit.
Insulation of outdoor unit is defective.
Insulation of indoor unit is defective.
41
9-2-2. Neither indoor nor outdoor unit runs.
A. Power is not supplied.
B. Check remote control unit.
C. Check "OPERATION selector" switch in the indoor unit.
D. Check transformer in indoor unit.
NO
Check power supply. Power is being supplied to the
outdoor unit.
Circuit breaker is tripped.
Power failure
Reset breaker.
Wait for recovery or contact power company.
YES
NO
OPERATION selector switch is set in ON position.
Set OPERATION selector switch to ON.
Switch Ass'y or indoor PCB Ass'y is defective.
Refer to Step C below.
Clean transmitter.
OK
Try to run with another remote control unit.
First remote control unit is defective.
Check for residue buildup on transmitter of remote control unit.
Check for residue buildup on remote control receiver on front of indoor unit.
Clean receiver.
Does not run.
Measure resistance of primary and secondary winding. (TR2)
42
E. Check fuse on the indoor PCB Ass'y.
F. Check TIMER on the remote control unit.
OK
OK
OK
OK
OK
Check fuse on indoor PCB Ass'y for continuity. (F)
Check operation lamp to see if light is ON.
Light is OFF
Measure resistance of primary and secondary winding of transformer. (TR)
Indoor PCB Ass'y or switch Ass'y is defective.
OK
Measure resistance of indoor fan motor winding. (FMI )
Measure resistance of outdoor fan motor winding. (FMO)
OK
Measure resistance of flap motor winding. (FLP)
Measure resistance of either power relay or magnetic contactor. (MG)
If fuse has been blown,
Measure resistance of PTC thermistor. (PTC)
Replace the fuse.
Timer is turned ON. Check to see if "ON" is displayed on remote control
YES
Press TIMER SELECT button to select NORM. (NORM. is position when neither ON nor OFF appears on display.)
43
9-2-3. Only outdoor unit does not run.
A. Check MODE selector switch of remote control unit.
B. Check setting temperature.
C. Check power relay in outdoor unit.
D. Check magnetic contactor in outdoor unit.
OK
NO
Is room temperature too low ?
Try to lower setting temperature by temperature setting button cooler.
Outdoor unit still does not run.
Remote control unit is defective.
Try to run using another remote control unit.
OK
Measure coil resistance of power relay.
Check indoor PCB Ass'y.
(PR)
Check that MODE selector switch is not set at "FAN".
If it is set at FAN,
Set to "COOL".
Outdoor unit does not run when air conditioner is in following conditions.
During thermo OFF (when the room temperature is below the set temperature).
During freeze prevention (for at least 6 minutes).
NOTE
OK
Measure coil resistance of magnetic contactor.
Check indoor PCB Ass'y.
(MG)
44
E. Check negative phase relay.
F. Check magnetic contactor.
G. Check indoor PCB Ass'y.
H. Check compressor motor protector.
Check negative phase relay to see if it has operated.
Rewire power supply wires.
YES
(47C)
Check coil resistance of magnetic contactor.
• (MG)
YES
Check compressor motor internal protector.
• (49C)
Temperature of compressor is abnormally high.
Refrigerant gas shortage.
YES
YES
Charge refrigerant gas.
Check compressor. There is a possibility of locked rotor.
NO 90% or more of
rated voltage.
NO
It’s operated.
Check compressor motor overcurrent relay. (51C)
Clean heat exchanger or remove obstacles.
Check power supply voltage. Voltage is abnormally low.
Outdoor heat exchanger coil is dirty or there are obstacles near air suction inlet.
45
9-3. Some part of air conditioner does not operate.
9-3-1. Only indoor fan does not run.
9-3-2. Only outdoor fan does not run.
Fan cannot be turned.
OK
Check fan rotation. Turn fan gently once or twice by hand.
Check fan casing foreign matter on inside.
Fan motor burnout or foreign matter in bearings.
Remove foreign matter or repair.
Repair or replace.
Measure resistance of indoor fan motor winding.
Check fan motor capacitor.
Fan cannot be turned.
OK
Check fan rotation. Turn fan gently once or twice by hand.
Check fan casing foreign matter on inside.
Fan motor burnout or foreign matter in bearings.
Remove foreign matter or repair.
Repair or replace.
Measure resistance of indoor fan motor winding.
Check fan motor capacitor.
Measure coil resistance of relay. (1X)
(Only for models GR180C7VAA)
46
Check transformer in outdoor unit. (GR180C7TAA Only)
Check fuse on outdoor PCB Ass'y. (GR180C7TAA Only)
Measure resistance of primary and secondary winding. (TR2)
If fuse blows,
Check fuse on outdoor PCB Ass’y for continuity.
OK
Measure resistance of primary winding of transformer.
• (TR2)
OK
Measure resistance of outdoor fan motor winding.
Outdoor PCB Ass’y is defective.
(F)
9-3-3. Only compressor does not run.
Check solid state relay in outdoor unit.
(SSR)
( For GR180C7VAA)
Measure resistance of flap motor winding.
(FLP)
Measure resistance of compressor motor winding.
9-3-4. Only flap motor does not run
9-3-5. Function of outdoor fan speed control does not work properly.
47
48
9-4. Air conditioner operates, but abnormalities are observed.
9-4-1. Poor cooling.
9-4-2. Excessive cooling.
Air filter is clogged.
NO
YES
Temperature difference is small.
YES
Temperature difference between suction and discharge air is large enough (approx. 10 deg. or more).
Possibility of gas shortage.
YES
Check position of remote control unit. Cool air from air conditioner reaches position directly.
Change position of remote control unit.
Wide and narrow tubes between indoor unit and outdoor unit are insulated.
Insulate both wide and narrow tubes separately and then tape together.
Measure temperature of suction and discharge air of air conditioner.
Charge refrigerant gas (R22).
Check for clogging of air filter.
Fan speed is set to LOW.
Clean filter.
Set fan speed to either HIGH or MEDIUM.
Review cooling load estimate, if performance of air conditioner is normal.
Reduce cooling load or replace the air conditioner with larger capacity.
NO
NO
Set temperature is suitable.
Set temperature to higher or lower value using temperature setting buttons of the remote control unit.
Remote control unit is placed where it can detect room temperature properly.
Change position of remote control unit.
49
9-5. If a sensor is defective.
9-5-1. Indoor coil temp. thermistor (TH1) is defective.
A. Open
When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect extremely low indoor coil temperature.
In Cooling mode: Finction of freeze prevention continues to work. That is, the controller turns both
compressor and outdoor fan motor periodically ON and OFF for several minutes. (Refer to "5-2. Freeze Prevention")
B. Short
When thermistor is short, the air conditioner will be in the following conditions as the controller tries to detect extremely high indoor coil temperature.
In Cooling mode: Function of freeze prevention will not work even when the frost builds up on indoor heat
exchanger coil
9-5-2. Room temp. thermistor (TH2) is defective.
A. Open
When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect extremely low room temperature.
In Cooling mode: The air conditioner soon stops and will not start again.
(Thermo.OFF) Neither outdoor fan nor compressor runs.
B. Short
When thermistor is short, the air conditioner will be in the following conditions as the controller tries to detect extremely high room temperature.
In Cooling mode: The air conditioner continues to operate. (Thermo.ON)
Both the outdoor fan and compressor do not stop. As a result, the room becomes too cold.
Definition of Open or Short Circuit of Sensor (Thermistor)
Open...A lead wire is broken or disconnected or the circuit inside the temperature sensor is open . Short...The protective cover of a lead wire has been damaged, and the exposed wire is touching another metal
part, or both lead wires have become exposed and are touching each other. Alternatively, the circuit inside the temperature sensor is closed.
NOTE
Temperature sensor
Lead wires
Thermistor Structure
50
10-1. Measurement of Insulation
Resistance
The insulation is in good condition if the resistance exceeds 2M.
10-1-1.Power Supply Wires
Clamp the ground wire of the power supply wires with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the power wires. (Fig. 1)
Then measure the resistance between the ground wire and the other power wire. (Fig. 1)
10-1-2.Indoor Unit
Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate. (Fig. 2) Note that the ground line terminal should be skipped for the check.
10-1-3.Outdoor Unit
Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate. (Fig. 2)
10-1-4.Measurement of Insulation
Resistance for Electrical Parts
Disconnect the lead wires of the desired electric part from terminal plate, capacitor, etc. Similarly disconnect the connector. Then measure the insulation resistance. (Figs. 3 and 4)
Refer to Electric Wiring Diagram. If the probe cannot enter the poles because the hole is
too narrow then use a probe with a thinner pin.
NOTE
10. CHECKING ELECTRICAL COMPONENTS
Insulation tester
Probe
Clip
Ground wire
Terminal plate
Copper tube or metallic part
Clip
Insulation tester
Probe
Copper tube or metallic part
Clip
Insulation tester
Probe
Clip
Insulation tester
Probe
Metallic part
From fan motor, compressor and other parts
Fig. 1
Fig. 2
Fig. 3
Fig. 4
51
10-2. Checking Continuity of Fuse
on PCB Ass'y
Remove the PCB Ass’y from the electrical component box. Then pull out the fuse from the PCB Ass’y. (Fig. 5)
Check for continuity using a multimeter as shown in Fig. 6.
10-3. Checking Motor Capacitor
Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 7. Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value.
The capacitor is “good” if the pointer bounces to a great extent and then gradually returns to its original position.
The range of deflection and deflection time differ according to the capacity of the capacitor.
Fuse
PCB Ass’y
Fuse
Compressor motor capacitor
Fan motor capacitor
Multimeter
Fig. 5
Fig. 6
Fig. 7
52
11-1. Removing Air Intake Grille
(1) Hold both ends and pull forward to open the
air intake grille. (Fig. 1)
(2) Remove the metal clips connecting the unit and the
grille. First, with a screwdriver, loosen the * marked screw a little at the right side clip (DO NOT loosen it too much, otherwise, the screw and small metal parts will fall off inside.), then press
on the stopper and pull off. (Fig. 2) (3) Do the same procedure for the left metal clip. (4) Unlatch the 2 tabs on the lower part of the grille to
take it off completely.
11. DISASSEMBLY PROCEDURE FOR INDOOR UNIT
IMPORTANT! Please Read Before Starting
Safety precautions for servicing the CEILING-MOUNTED indoor unit
Center latch
Air intake grille
Metal clip
*
Air intake grille
Unit
For Floor Installation
Fig.1
Fig.2
Before attempting to replace heavy and bulky parts such as the evaporator and fan motor, disconnect the indoor unit from the system and place it on the floor. Refer to the steps given below.
When checking or servicing the air intake grille, side panels, or electrical component box, first check that power is completely disconnected. Pay utmost care that your working platform is stable enough. Also, do not drop any replaced parts and tools on the floor.
53
11-2. Removing Side Panels
(1) Remove the 3 screws attaching the left side panel.
(Fig. 3) (2) Note the position of the hook on the inside of the
left side panel. To disengage the hook from the slot,
slide down the panel for removal. (Fig. 3) (3) Do the same procedure for the right side panel.
11-3. Access and Removal of
Electrical Component Box
(1) Remove the front screw with a screwdriver. (Fig. 4) (2) Slide the lid out and up. (Fig. 4) (3) Disconnect the wiring as necessary. (4) Remove the 4 screws, then pull out the electrical
component box. (Fig. 5)
Side panel
Tapping screws (4 × 10 mm)
Hook
Hook
Slot
Screw
Screw
Electrical component box
Screw
Connectors
Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect the power or turn off circuit breaker before you start checking or servicing.
WARNING
Fig.3
Fig.4
Fig.5
54
11-4. Removing Flap Motor
(1) Remove the 3 screws used to mount the top panel.
(Fig. 6) (2) While unlatching the 2 tabs inside the back of the
top panel, lift the top panel diagonally in the
direction of the arrow.(Fig. 6) (3) Remove the 2 screws to pull off the flap motor.
The arm and cam come off together with the motor.
(Fig. 7)
11-5. Removing Evaporator
(=Indoor Heat Exchange Coil)
(1) Remove the 7 screws used to mount the blades.
(Fig. 8) (2) Lift the blades in the direction of the arrow.(Fig. 8)
Top panel
Flap motor
Screw
Blade
Arm
Cam
Screw
Flap motor
Screw
Blades
Fig.6
Fig.7
Fig.8
55
(3) Remove the 6 screws of the front panel and pull it
toward you. (Fig. 9)
(4) Remove the 2 screws used to mount the
evaporator. (Fig. 10) (5) Remove the rubber cap to pull the thermistor out of
the evaporator. (Fig. 10) (6) Cut the plastic clamp securing the drain hose to the
front fan casing. (Fig. 10)
(7) The evaporator is built into the drain pan. Pull out
the drain pan together with the evaporator in the
direction of the arrow. (Fig. 10)
The foamed polystyrene drain pan is fragile: DO NOT apply excessive force when removing it.
(8) The evaporator can be removed by sliding it out
from the drain pan in the direction of the arrow.
(Fig. 11)
Front panel
Screw
Plastic clamp
Drain pan
Screw
Rubber cap
Thermistor
Drain hose
Front fan casing
Drain pan
Evaporator (Indoor coil)
Mounting plate
Mounting plate
Fig.9
Fig.10
Fig.11
IMPORTANT
56
11-6. Removing Fan and Fan Motor
(1) Unlatch the 2 hooks on each side to take off the
front fan casing. (Fig. 12)
(2) Remove the 2 screws attaching the rear fan casing
and then pull the fan casing out.
(3) Insert a hex wrench in the fan boss and turn it
counterclockwise to loosen the centrifugal fan.
The fan can be removed by sliding it to the left.
(Fig. 14)
(4) Remove the 4 bolts to remove the fan motor from
the frame. (Fig. 15)
Hook
Hook
Front fan casing
Rear fan casing
Hex wrench (3mm or 7/64")
Centrifugal fan
Bolts (M6)
Fan motor
Frame
Fig.12
Fig.13
Fig.14
Fig.15