Technibel MCAF78MR5I, MCAF248R5I, MCAF98MR5I, MCAF128MR5I, MCAF188R5I Technical & Service Manual

...
INDOOR UNIT : MCAF78MR5I
MCAF98MR5I MCAF128MR5I MCAF188R5I MCAF248R5I
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
FILE NO.
REFERENCE NO. SM700739
Indoor Model No.Capacity
2.20 kW
2.65 kW
3.50 kW
5.15 kW
7.10 kW
Product Code No.
< Applicable Multi-Outdoor Units >
GRF148MR5I (2-room multi unit) GRF198MR5I (2-room multi unit) GRF248MR5I (4-room multi unit) GRF318MR5I (4-room multi unit)
For details about the combinations, refer to "Unit Combination Table" in the
T. Service
Manual
for the Multi Outdoor Units.
NOTE
MCAF78MR5I
MCAF98MR5I
MCAF128MR5I
MCAF188R5I
MCAF248R5I
MCAF78MR5IAA
MCAF98MR5IAA
MCAF128MR5IAA
MCAF188R5IAA
MCAF248R5IAA
(1 852 349 58)
(1 852 349 59)
(1 852 349 60)
(1 852 349 61)
(1 852 349 62)
Wall Mounted Type Indoor Unit
RoHS
WARNING
This product does not contain any hazardous substances prohibited by the RoHS Directive.
• You are requested to use RoHS compliant parts for maintenance or repair.
• You are requested to use lead-free solder.
A
I
R
C
O
N
D
I
T
I
O
N
E
R
AIR CO
N
D
I
T
I
O
N
E
R
MCAF78MR5I MCAF98MR5I MCAF128MR5I
MCAF188R5I MCAF248R5I
Do not vent R410A into atmosphere : R410A is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975.
F-GAS REGULATION (EC) No 842 / 2006
TECHNICAL & SERVICE MANUAL
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
SPECIAL PRECAUTIONS
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
CAUTION
CAUTION
WARNING
WARNING
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. Install a protective leakage breaker depending on the installation location (especially a damp or humid location). If a leakage breaker is not installed, electric shock can occur.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
In a Room
Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. Check carefully for leaks before starting the test run.
When Servicing
Tu rn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
2
APPLICABLE MULTI-OUTDOOR UNITS
1. OPERATING RANGE
2. SPECIFICATIONS
2-1. Unit Specifications 2-2. Major Component Specifications 2-3. Other Component Specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
5. PERFORMANCE DATA
5-1. Air Throw Distance Charts
6. ELECTRICAL DATA
6-1. Electric Wiring Diagrams
7. FUNCTIONS
7-1. Operation Functions 7-2. Protective Functions
8. TROUBLESHOOTING
8-1. Precautions before Performing Inspection or Repair 8-2. Method of Self-Diagnostics 8-3. Checking the Indoor and Outdoor Units 8-4. Trouble Diagnosis of Fan Motor 8-5. Noise Malfunction and Electromagnetic Interference
APPENDIX A INSTRUCTION MANUAL
(MCAF78MR5I, MCAF98MR5I, MCAF128MR5I)
APPENDIX B INSTRUCTION MANUAL
(MCAF188R5I, MCAF248R5I)
APPENDIX C INSTALLATION INSTRUCTIONS
Table of Contents
4
5
6 11 16
17
19
20
25
27 29
30 30 32 33 34
A-1
A-2
A-3
.....................................................................................
...................................................................................................................
.............................................................................................................
.......................................................................................
.......................................................................................
.....................................................................................................................
...................................................................................................
.................................................................................................
....................................................................................................
...........................................................................................................
...........................................................................................................
...........................................................
.................................................................................................
..............................................................................
...........................................................................................
..........................................................
.....................................................
..................................................................................
.............................................................................
Page
3
APPLICABLE MULTI-OUTDOOR UNITS
MCAF78MR5I
Indoor Unit
Multi-Outdoor Unit
YES YES YES YES
MCAF98MR5I YES YES YES YES
MCAF128MR5I YES YES YES YES
MCAF188R5I NO YES YES YES
MCAF248R5I NO NO YES YES
2-Room 2-Room 4-Room 4-Room
GRF148MR5I GRF198MR5I GRF248MR5I GRF318MR5I
4
1. OPERATING RANGE
Maximum
Minimum
Maximum
Minimum
32 °C D.B. / 23 °C W.B.
19 °C D.B. / 14 °C W.B.
27 °C D.B.
16 °C D.B.
Temperature Indoor Air Intake Temp.
43 °C D.B.
19 °C D.B.
24 °C D.B. / 18 °C W.B.
D.B . / – 15 °C W.B.
Outdoor Air Intake Temp.
Cooling
Heating
5
2. SPECIFICATIONS
2-1. Unit Specifications
Indoor Unit MCAF78MR5I
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Vertical
dB-AIndoor : Hi/Me/Lo/Qt*
Air Filter
Refrigerant
0.11 25
0.11 25
2.2
7,500
2.5
8,500
Shipping Volume
Cooling Heating
410
1.3
Cooling Heating
Depth Net Shipping
Package Dimensions
Weight
Width Depth Height Width
mm
kg kg
m
3
mm mm mm mm
220 to 240V Single-Phase 50Hz
mm
460
-
198 to 264
Dimensions & Weight
(*Qt = Quiet mode) Refrigerant Tubing Connections
Unit Dimensions Height
Operation Sound
Electrical Rating
Air Circulation (High) Moisture Removal (High)
WPower Input
V A
Available Voltage Range Running Amperes
Refrigerant Tube Kit / Accessories
Narrow tube Wide tube
Refrigerant mm (in.)
Tube Diameter mm (in.)
350
9.0
11.0
0.08
825 189 255 900
Indoor Unit
285
6.35 (1/4)
9.52 (3/8)
Flare Type
33 / 30 / 27 /2333 / 30 / 27 / 23
R410A
Washable, Anti-Mold
Manual
Auto
Timer
Indoor Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Optional / Air Clean Filter
kW
Performance
Type
Power Source
Liters/h
BTU/h
Capacity
m
3
/h
Wall Mounted Type Indoor Unit
230VVoltage Rating
6
Indoor Unit MCAF98MR5I
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Vertical
dB-AIndoor : Hi/Me/Lo/Qt*
Air Filter
Refrigerant
0.15 35
0.15 35
2.65
9,000
3.6
12,300
Shipping Volume
Cooling Heating
440
1.6
Cooling Heating
Depth Net Shipping
Package Dimensions
Weight
Width Depth Height Width
mm
kg kg
m
3
mm mm mm mm
220 to 240V Single-Phase 50Hz
mm
480
-
198 to 264
Dimensions & Weight
(*Qt = Quiet mode) Refrigerant Tubing Connections
Unit Dimensions Height
Operation Sound
Electrical Rating
Air Circulation (High) Moisture Removal (High)
WPower Input
V A
Available Voltage Range Running Amperes
Refrigerant Tube Kit / Accessories
Narrow tube Wide tube
Refrigerant mm (in.)
Tube Diameter mm (in.)
350
9.0
11.0
0.08
825 189 255 900
Indoor Unit
285
6.35 (1/4)
9.52 (3/8)
Flare Type
34 / 31 / 28 / 2334 / 31 / 28 / 23
R410A
Washable, Anti-Mold
Manual
Auto
Timer
Indoor Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Optional / Air Clean Filter
kW
Performance
Type
Power Source
Liters/h
BTU/h
Capacity
m
3
/h
Wall Mounted Type Indoor Unit
230VVoltage Rating
7
Indoor Unit MCAF128MR5I
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Vertical
dB-AIndoor : Hi/Me/Lo/Qt*
Air Filter
Refrigerant
0.15 35
0.15 35
3.5
11,900
4.2
14,300
Shipping Volume
Cooling Heating
480
2.0
Cooling Heating
Depth Net Shipping
Package Dimensions
Weight
Width Depth Height Width
mm
kg kg
m
3
mm mm mm mm
220 to 240V Single-Phase 50Hz
mm
500
-
198 to 264
Dimensions & Weight
(*Qt = Quiet mode) Refrigerant Tubing Connections
Unit Dimensions Height
Operation Sound
Electrical Rating
Air Circulation (High) Moisture Removal (High)
WPower Input
V A
Available Voltage Range Running Amperes
Refrigerant Tube Kit / Accessories
Narrow tube Wide tube
Refrigerant mm (in.)
Tube Diameter mm (in.)
350
9.0
11.0
0.08
825 189 255 900
Indoor Unit
285
6.35 (1/4)
9.52 (3/8)
Flare Type
34 / 31 / 29 / 2536 / 33 / 29 / 25
R410A
Washable, Anti-Mold
Manual
Auto
Timer
Indoor Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Optional / Air Clean Filter
kW
Performance
Type
Power Source
Liters/h
BTU/h
Capacity
m
3
/h
Wall Mounted Type Indoor Unit
230VVoltage Rating
8
Indoor Unit MCAF188R5I
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Vertical
dB-AIndoor : Hi/Me/Lo/Qt*
Air Filter
Refrigerant
0.15 35
0.15 35
Shipping Volume
Cooling Heating
850
2.3
Cooling Heating
Depth Net Shipping
Package Dimensions
Weight
Width Depth Height Width
mm
kg kg
m
3
mm mm mm mm
220 to 240V Single-Phase 50Hz
mm
850
-
198 to 264
Dimensions & Weight
(*Qt = Quiet mode) Refrigerant Tubing Connections
Unit Dimensions Height
Operation Sound
Electrical Rating
Air Circulation (High) Moisture Removal (High)
WPower Input
V A
Available Voltage Range Running Amperes
Refrigerant Tube Kit / Accessories
Narrow tube Wide tube
Refrigerant mm (in.)
Tube Diameter mm (in.)
379
12.0
15.0
0.12
1,065
218 289
1,140
Indoor Unit
298
6.35 (1/4)
12.7 (1/2)
Flare Type
40 / 37 / 34 / 2841 / 38 / 34 / 28
R410A
Washable, Anti-Mold
Manual
Auto
Timer
Indoor Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Optional / Air Clean Filter
kW
Performance
Type
Power Source
Liters/h
BTU/h
Capacity
m
3
/h
Wall Mounted Type Indoor Unit
230VVoltage Rating
5.15
17,600
6.0
20,500
9
Indoor Unit MCAF248R5I
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Vertical
dB-AIndoor : Hi/Me/Lo/Qt*
Air Filter
Refrigerant
0.2 45
0.2 45
Shipping Volume
Cooling Heating
920
2.3
Cooling Heating
Depth Net Shipping
Package Dimensions
Weight
Width Depth Height Width
mm
kg kg
m
3
mm mm mm mm
220 to 240V Single-Phase 50Hz
mm
920
-
198 to 264
Dimensions & Weight
(*Qt = Quiet mode) Refrigerant Tubing Connections
Unit Dimensions Height
Operation Sound
Electrical Rating
Air Circulation (High) Moisture Removal (High)
WPower Input
V A
Available Voltage Range Running Amperes
Refrigerant Tube Kit / Accessories
Narrow tube Wide tube
Refrigerant mm (in.)
Tube Diameter mm (in.)
379
12.0
15.0
0.12
1,065
218 289
1,140
Indoor Unit
298
6.35 (1/4)
15.88 (5/8)
Flare Type
43 / 40 / 37 / 3044 / 41 / 38 / 30
R410A
Washable, Anti-Mold
Manual
Auto
Timer
Indoor Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Optional / Air Clean Filter
kW
Performance
Type
Power Source
Liters/h
BTU/h
Capacity
m
3
/h
Wall Mounted Type Indoor Unit
230VVoltage Rating
7.1
24,200
8.5
29,000
10
2-2. Major Component Specifications
2-2-1. Indoor Unit
Indoor Unit MCAF78MR5I
Flap Motor
Type Stepping Motor
Coil Resistance Ohm
(Ambient Temp. 25 °C)
Each Pair of Terminal : 400 +/- 7%
Aluminum Plate Fin / Copper Tube
2
1.3
0.188 Face Area
Coil
Rows
Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rating DC 12V
Model MP24Z3
Over-Heat Protection
Yes
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3.15A
CB-KMRV74EH
1 ... D94 / L634
RCS-4MHVPIN4E
Cross-Flow
DC Motor
SIC-39CVL-D847-4 ... 1
8
-
47
1,050 / 1,100
Internal Controller
Yes
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
mm
Fan Motor
Nominal Output Coil Resistance
Rough Measure RPM (Cool / Heat)
Type Model ... Q'ty No. of Poles
Safety Device
Type Over- Current Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
11
Indoor Unit MCAF98MR5I
Flap Motor
Type Stepping Motor
Coil Resistance Ohm
(Ambient Temp. 25 °C)
Each Pair of Terminal : 400 +/- 7%
Aluminum Plate Fin / Copper Tube
2
1.3
0.188 Face Area
Coil
Rows Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rating DC 12V
Model MP24Z3
Over-Heat Protection
Yes
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3.15A
CB-KMRV94EH
1 ... D94 / L634
RCS-4MHVPIN4E
Cross-Flow
DC Motor
SIC-39CVL-D847-4 ... 1
8
-
47
1,100 / 1,150
Internal Controller
Yes
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
mm
Fan Motor
Nominal Output Coil Resistance
Rough Measure RPM (Cool / Heat)
Type Model ... Q'ty No. of Poles
Safety Device
Type Over- Current Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
12
Indoor Unit MCAF128MR5I
Flap Motor
Type Stepping Motor
Coil Resistance Ohm
(Ambient Temp. 25 °C)
Each Pair of Terminal : 400 +/- 7%
Aluminum Plate Fin / Copper Tube
2
1.3
0.188 Face Area
Coil
Rows Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rating DC 12V
Model MP24Z3
Over-Heat Protection
Yes
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3.15A
CB-KMRV124EH
1 ... D94 / L634
RCS-4MHVPIN4E
Cross-Flow
DC Motor
SIC-39CVL-D847-4 ... 1
8
-
47
1,200 / 1,200
Internal Controller
Yes
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
mm
Fan Motor
Nominal Output Coil Resistance
Rough Measure RPM (Cool / Heat)
Type Model ... Q'ty No. of Poles
Safety Device
Type Over- Current Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
13
Indoor Unit MCAF188R5I
Flap Motor
Type Stepping Motor
Coil Resistance Ohm
(Ambient Temp. 25 °C)
Each Pair of Terminal : 400 +/- 7%
Aluminum Plate Fin / Copper Tube
2
1.3
0.285 Face Area
Coil
Rows Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rating DC 12V
Model MP24Z3
Over-Heat Protection
Yes
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3.15A
CB-KRV184EH
1 ... D94 / L845
RCS-4MHVPINW4E
Cross-Flow
DC Motor
SIC-39CVL-D847-2 ... 1
8
-
30
1,200 / 1,200
Internal Controller
Yes
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
mm
Fan Motor
Nominal Output Coil Resistance
Rough Measure RPM (Cool / Heat)
Type Model ... Q'ty No. of Poles
Safety Device
Type Over- Current Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
14
Indoor Unit MCAF248R5I
Flap Motor
Type Stepping Motor
Coil Resistance Ohm
(Ambient Temp. 25 °C)
Each Pair of Terminal : 400 +/- 7%
Aluminum Plate Fin / Copper Tube
2
1.3
0.285 Face Area
Coil
Rows
Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rating DC 12V
Model MP24Z3
Over-Heat Protection
Yes
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3.15A
CB-KRV244EH
1 ... D94 / L845
RCS-4MHVPINW4E
Cross-Flow
DC Motor
SIC-39CVL-D847-2 ... 1
8
-
30
1,300 / 1,300
Internal Controller
Yes
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
mm
Fan Motor
Nominal Output
Coil Resistance
Rough Measure RPM (Cool / Heat)
Type
Model ... Q'ty
No. of Poles
Safety Device
Type Over- Current Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
15
2-3. Other Component Specifications
10
1
2
3
4
5
6
7
8
9
10
15 20 25 30 35 40
Resistance (k ohm)
Temperature (°C)
0
0102030405060708090
40
60
80
100
120
140
160
180
200
20
Resistance (k ohm)
Temperature (°C)
Indoor air temp sensor
PTM-D51H­S3 TH2
Model No.
of sensor
Sensor Name
111
Quantity of Sensor
00
PTM-D51H­S3-2 TH2
00011
MCAF78MR5I MCAF98MR5I MCAF128MR5I
MCAF188R5I MCAF248R5I
Indoor heat exchanger sensor
PTM-D51H­S3 TH1
Model No.
of sensor
Sensor Name
111
Quantity of Sensor
00
PTM-D51H­S3-2 TH1
00011
MCAF78MR5I MCAF98MR5I MCAF128MR5I
MCAF188R5I MCAF248R5I
16
3. DIMENSIONAL DATA
Indoor Unit MCAF78MR5I
MCAF98MR5I MCAF128MR5I
Unit: mm
17
Indoor Unit MCAF188R5I
MCAF248R5I
Unit: mm
18
Indoor heat exchanger
O.D. 9.52 mm (3/8")
O.D. 6.35 mm (1/4")
Cooling cycle
Heating cycle
Indoor unit
Indoor heat exchanger
O.D. 12.7 mm (1/2")
O.D. 6.35 mm (1/4")
Cooling cycle
Heating cycle
Indoor unit
Indoor heat exchanger
O.D. 15.88 mm (5/8")
O.D. 6.35 mm (1/4")
Cooling cycle
Heating cycle
Indoor unit
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
Indoor Unit MCAF78MR5I
MCAF98MR5I MCAF128MR5I
Indoor Unit MCAF188R5I
Indoor Unit MCAF248R5I
19
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
: Flap angle 0°, : Axis air velocity 0
°
: Flap angle 30°, : Axis air velocity 30
°
: Flap angle 45°, : Axis air velocity 45
°
: Flap angle 60°, : Axis air velocity 60
°
5. PERFORMANCE DATA
5-1. Air Throw Distance Charts
Indoor Unit MCAF78MR5I
20
0
1
2
3
4
012345678910
0
1
2
3
4
5
0123456789
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
: Flap angle 0°, : Axis air velocity 0
°
: Flap angle 30°, : Axis air velocity 30
°
: Flap angle 45°, : Axis air velocity 45
°
: Flap angle 60°, : Axis air velocity 60
°
Indoor Unit MCAF98MR5I
21
0
1
2
3
4
012345678910
0
1
2
3
4
5
0123456789
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
: Flap angle 0°, : Axis air velocity 0
°
: Flap angle 30°, : Axis air velocity 30
°
: Flap angle 45°, : Axis air velocity 45
°
: Flap angle 60°, : Axis air velocity 60
°
Indoor Unit MCAF128MR5I
22
0
1
2
3
4
012345678910
0
1
2
3
4
5
0123456789
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
: Flap angle 0°, : Axis air velocity 0
°
: Flap angle 30°, : Axis air velocity 30
°
: Flap angle 45°, : Axis air velocity 45
°
: Flap angle 60°, : Axis air velocity 60
°
Indoor Unit MCAF188R5I
23
0
1
2
3
4
012345678910
0
1
2
3
4
5
0123456789
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C Fan speed : High
Cooling
: Flap angle 0°, : Axis air velocity 0
°
: Flap angle 30°, : Axis air velocity 30
°
: Flap angle 45°, : Axis air velocity 45
°
: Flap angle 60°, : Axis air velocity 60
°
Indoor Unit MCAF248R5I
24
0
1
2
3
4
012345678910
0
1
2
3
4
5
0123456789
8FA-2-5257-72600-1
1 2 3 4 5 6
1 2 3 4
1 2 3 4
1 2 3 4
5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
6
1 2 3 4 5 6 7 8 9
10
1 2 3 4 5 6 7 8 9
10
1 2 3 4 5 6 7 8 9
10
1 2 3 4 5 6 7 8 9
10
FAN MOTOR
FLAP MOTOR
CONNECTOR
TERMINAL BASE
ROOM THERMISTOR
CONTROLLER
COIL THERMISTOR
CONNECTOR
ION ASSY
TO OUTDOOR UNIT
IND LAMP ASSY
EVAPORATOR
FM
FLAP
GRN/YEL
BLU
YEL
WHT
BLK
RED
RED PNK BLU BRN
YEL
RED
WHT
BLK
1
2
3
4
RED WHT WHT WHT WHT WHT WHT WHT WHT WHT
1 2 3
1
1 2 3 4
1 2 3 4 1 2 3 4
2 3
1 2 3
1 2 3
WHT RED
BLK
BLK BLK BLK BLK
AC1
FLAP 5P (WHT)
DCM 6P (BLU)
LAMP
10P (WHT)
ROOM/COIL
4P (WHT)
ION
3P (WHT)
HA
JEM-A
ION TERMINAL
4P (WHT)
SIAC2
BLK
BLK
BLK
RED
WHT
6. ELECTRICAL DATA
6-1. Electric Wiring Diagrams
Indoor Unit MCAF78MR5I
MCAF98MR5I MCAF128MR5I
WARNING
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
25
8FA-2-5257-68200-0
1 2 3 4 5 6
1 2 3 4
1 2 3 4
1 2 3 4
5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
6
1 2 3 4 5 6 7 8 9
10
1 2 3 4 5 6 7 8 9
10
1 2 3 4 5 6 7 8 9
10
1 2 3 4 5 6 7 8 9
10
FAN MOTOR
FLAP MOTOR
CONNECTOR
TERMINAL BASE
ROOM THERMISTOR
CONTROLLER
COIL THERMISTOR
ION ASSY
TO OUTDOOR UNIT
IND LAMP ASSY
EVAPORATOR
FM
FLAP
GRN/YEL
GRN/YEL
BLU
YEL
WHT
BLK
RED
RED PNK BLU BRN
YEL
RED
WHT
BLK
1
2
3
4
RED WHT WHT WHT WHT WHT WHT WHT WHT WHT
1 2 3
1
1 2 3 4
1 2 3 4 1 2 3 4
2 3
BLK BLK BLK BLK
AC1
FLAP 5P (WHT)
DCM 6P (BLU)
E
LAMP
10P (WHT)
ROOM/COIL
4P (WHT)
ION
3P (WHT)
HA
JEM-A
ION TERMINAL
4P (WHT)
SIAC2
BLK
BLK
BLK
RED
WHT
Indoor Unit MCAF188R5I
MCAF248R5I
WARNING
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
26
Emergency operation SENSOR DRY
AUTO cooling/heating operation
Selecting the operation mode
During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment.
SENSOR DRY operation
DRY operation is as shown in the figure below.
PAM- control
In order to further improve inverter performance, control is
switched between PWM control at low operation speeds, and PA M control at high operation speeds, making the most effective use of power.
The compressor operation frequency varies. The indoor fan operates with 1/f fluctuation.
The compressor operates at a low operating frequency. The indoor fan operates with 1/f fluctuation.
Monitoring operation takes place when the room temperature is below 15 °C, or more than 3 °C below the set temperature.
When the monitoring range is entered, the compressor stops, and the indoor fan operates with 1/f fluctuation.
DRY A
DRY B
Monitor
Conditions are monitored at all times when the room temperature is below 15 °C.
Load
COOL zone
A zone
B zone
Emergency operation is available when the remote controller malfunctions, has been lost, or otherwise cannot be used.
The set temperature is 2 °C below the detected room
temperature in the case of cooling operation, and 2 °C above the room temperature in the case of heating operation. The flap and fan speed settings are AUTO.
(GREEN) (RED) (Lamp Off)
COOL HEAT STOP
When AUTO mode is selected, the microprocessor calculates
the difference between the set temperature and the room temperature, and automatically switches to Cooling or Heating mode.
As shown by the example in the figure below, with AUTO cooling/heating operation, the mode changes between Heating and Cooling mode according to changes in the relationship between the current room temperature and the set temperature.
Room temp. Set temp. COOL Room temp. Set temp. HEAT
23
Zone A
Zone B
Zone C
Zone C
Zone B
Zone A
OFF OFF
Compressor
Operation mode
Room temp.
HeatingCooling Cooling
ON ON ON
More than
1 hour
Within
1 hour
Set temp.
Example Example of operation in AUTO mode with the set room temperature at 23 °C.
When multiple indoor units are used and units in other rooms are already operating, they will be set to the same mode of operation as the operating indoor units.
To operate the system, press the OPERATION button,
which is also used as the receiver, below the unit display.
Each time this button is pressed, the OPERATION lamp changes color to indicate the type of operation. Select the desired type of operation.
7. FUNCTIONS
7-1. Operation Functions
NOTE
27
When NIGHT SETBACK operation is set, the temperature and fan speed settings will be adjusted automatically to allow comfortable sleep.
When NIGHT SETBACK operation is set, " mark" appears on the remote controller. The main unit display lamp also becomes dimmer.
COOL and DRY modes
When the night setback mode is selected, the air conditioner automatically raises the temperature setting 1°C when 30 minutes have passed after the selection was made, and then another 1°C after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed.
HEAT mode
When the night setback mode is selected, the air conditioner automatically lowers the temperature setting 2°C when 30 minutes have passed after the selection was made, and then another 2°C after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle heating is needed.
HIGH POWER
NIGHT SETBACK
Lamp colors
Timer backup
This function acts to raise the power but keeps the AC system in the same operating mode. This function is set with the HIGH POWER button on the remote controller. (It can be set regardless of the temperature and fan speed settings.)
HIGH POWER operation from remote controller
The unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is 1 step above "High."
OPERATION lamp
When HIGH POWER operation ends, the unit operates at low
Hz for 5 minutes, regardless of the thermostat OFF conditions.
When in DRY mode, operation is in the cooling zone.
Operation stops if there are no operator controls for 25 hours or
longer after unit operation switched from OFF to ON by use of ON timer operation.
Frequency
MAX
0
Start End
Time
30 min. 5 min.
Setting temperature
Press the NIGHT SETBACK button
TIMER lamp Green
QUIET lamp Green
ION lamp Green
HEAT operation Red DRY operation Orange COOL operation Green DEFROSTING operation Red and Orange
alternately
NOTE
30 min. 30 min.
Time
1°C(2°F)
Setting temperature
Press the NIGHT SETBACK button
30 min. 30 min.
Time
1°C(2°F)
2°C(4°F)
2°C(4°F)
28
Overload prevention during heating
During HEAT operation, the temperature of the indoor heat exchanger is used to control the frequency and lessen the load on the compressor before the protective device is activated.
Cold-air prevention during heating
During heating, the fan speed is set to "LL" (very low) or stopped. As the temperature of the indoor heat exchanger rises, the fan speed is changed to the set speed.
Freeze prevention
During COOL or DRY operation, freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below.
1.
Freeze-prevention operation is engaged when the temperature of the indoor heat exchanger is below 6 °C.
2.
Restart after freeze-prevention operation occurs when the temperature of the indoor heat exchanger reaches 8 °C or above.
a.
Area: Automatic capacity control
b.
When Point A has been exceeded, the operation frequency is reduced by a certain proportion.
c.
Area: Frequency increase is prohibited.
d.
At Point B and below, overload prevention is ended and control is the same as in the
a
area.
a.
Area: Automatic capacity control
b.
When the temperature drops below Point A, the operation frequency is reduced by a certain proportion.
c.
Area: Frequency increase is prohibited.
d.
When the temperature reaches Point C or above, freezing prevention is ended and control is the same as in the
a
area.
* When the temperature drops to below 2 °C (continuously for 2
minutes or longer), the compressor stops. Once the freeze condition is detected, the air conditioner will work less than the maximum frequency until it is turned off.
Approx.
53
At stability of operation
At start of operation
A
High
LL
Stopped
A
*
B
C
B
Indoor heat exchanger A. Control start B. Control end
Set fan speed
25 30 Approx. 40
abc d
abcd
Indoor heat exchanger
temperature (°C)
Indoor heat exchanger
temperature (°C)
Indoor heat exchanger
temperature (°C)
Approx.
47
2
6
8
The fan speed is forcibly changed to "LL" beginning 30 seconds
after the thermostat turns OFF.
At stability of operation refers to operation when the room
temperature has approached the set temperature.
When HEAT operation starts, the indoor fan is stopped until the
temperature of the indoor heat exchanger reaches 20 °C or higher, or until the room temperature reaches 15 °C or higher.
NOTE
7-2. Protective Functions
29
1HR. TIMER button
ON/OFF operation button
ACL (Reset) button
ION button
8. TROUBLESHOOTING
8-1. Precautions before Performing Inspection or Repair
NOTE
After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.
High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the controller LED (red) turns OFF.
If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.
1: If the operation lamp blinks every 0.5 seconds immediately when the
power is turned ON, there is an external ROM (OTP data) failure on the indoor circuit board, or a ROM socket insertion problem, or the ROM has not been installed.
2: The failure mode is stored in memory even when the power is not ON.
Follow the procedure below to perform diagnostics.
8-2. Method of Self-Diagnostics
Follow the procedure below to perform detailed trouble diagnostics.
< Clock display >
Test run mode
Self-diagnostics mode
PROCEDURE
Step 1: Press and hold the remote controller ION button and 1 HR TIMER
button. Then, press and hold the ACL (reset) button with a pointed object such as the tip of a pen. After 5 seconds, release ACL button first, then release ION and 1 HR TIMER buttons, "oP-1" (test run) appears, blinking in the remote controller clock display area.
Step 2: Next, press the 1 HR TIMER button once to change the display
from "oP-1" to "oP-3" (self-diagnostics). (The display continues to blink.)
Step 3: Finally press the ON/OFF button to engage self-diagnostics mode.
• The self-diagnostics function utilizes the 3 indicator lamps on the main unit, in combinations of ON lamps, blinking lamps, and OFF lamps, to report the existence of sensor trouble or a protective operation. (The lamps blink or remain ON for 5 seconds, then turn OFF for 2 seconds.) Self-diagnostics is completed when the buzzer sounds 3 short beeps.
• A maximum of 3 self-diagnostics reports are displayed, for 5 seconds each, beginning with the most recent report. Following this display the lamps turn OFF. In order to view the self-diagnostics results again, press the ON/OFF button again.
• The 3 lamps remain OFF if no trouble has occurred.
<IMPORTANT> After self-diagnostics is completed, be sure to press the
ACL (reset) button to return to normal mode. The air conditioner will not operate if this is not done.
After turning on power to the air conditioner, use the remote controller and follow the steps below to execute self-diagnostics.
30
Since the indications cover various units, the corresponding parts listed below may not be present in some models.
REMOTE CONTROL receiver
(1) OPERATION lamp (2) TIMER lamp (3) QUIET lamp ION lamp
OPERATION button
INDOOR UNIT
(1) Self-diagnostics Lamps
Indication on indoor unit
....
OFF
Timer Operation
Code Diagnostics items Diagnostics contents
S01
Room temperature sensor failure
Indoor heat exchanger sensor failure
Humidity sensor failure
Compressor temperature sensor failure
Outdoor heat exchanger sensor failure
Outdoor air temperature sensor failure
Indoor/outdoor communications failure (serial communications)
Outdoor unit external ROM (OTP data) failure
Peak current cut-off
• HIC circuit failure
• Power Tr (transistor) circuit failure
PAM circuit failure Active circuit failure
Outdoor system communications failure OLR operation Outdoor power supply open phase Outdoor coil freezing
Compressor discharge overheat prevention activated.
Indoor fan operating failure
No-refrigerant protection
DC compressor drive circuit failure
Outdoor fan operating failure
Freeze-prevention operation activated.
4-way valve switching failure Indoor zero-cross failure
Outdoor electrical current detection failure
S02
S03
S04
S05
S06
S07
E01
E02
E03
E04
E05
E06
E07
E08
E09
E10
E11
E12
E13
....
Blinking
....
ON (Illuminated)
Quiet
(3) (2) (1)
(1) Sensor open circuit or short circuit (2) Contact failure at connector or open circuit at terminal crimping location
(short-circuit detection only for the humidity sensor)
(3) Indoor/outdoor PCboard failure
(1) Sensor open circuit or short circuit (2) Contact failure at connector or open circuit at terminal crimping location (3) Outdoor PCboard failure
Outdoor PCboard failure
(1) Mis-wiring (2) AC power failure (3) Blown fuse (4) Power Relay failure (5) Indoor or outdoor PCboard failure (6) Outdoor Fan Motor failure (7) Reactor failure (8) High-Pressure Switch failure (9) Overload Relay failure (10) Magnetic Coil failure * See detailed flowchart in this section.
(1) HIC or power Tr failure (2) Outdoor fan does not turn. (3) Instantaneous power outage (4) Service valve not opened. (5) Outdoor fan blocked. (6) Continuous overload operation (7) Compressor failure (8) Outdoor PCboard failure
(1) External ROM data failure (2) Outdoor PCboard failure
(1) Instantaneous power outage (2) HIC or power transistor failure (3) Outdoor PCboard failure
(1) Outdoor PCboard failure (2) Outdoor power supply voltage failure
(1) Electric expansion valve failure (2) Capillaries choked (3) Shortage of refrigerant (4) Continuous overload operation (5) Outdoor fan does not rotate (6) Outdoor
PCboard
failure
(1) Fan motor failure (2) Contact failure at connector (3) Indoor PCboard failure
(1) 4-way valve failure (heat pump model only) (2) Outdoor PCboard failure
(1) Service valve not opened. (2) Shortage of refrigerant
(1) Open phase (2) Outdoor PCboard failure
(1) Fan motor failure (2) Contact failure at connector (3) Outdoor PCboard failure
(1) Mis-wiring (2) Blown fuse (3) Power Relay failure (4) Outdoor PCboard failure (5) Compressor failure * See detailed flowchart in this section.
(1) Indoor fan system failure (2) Shortage of refrigerant (3) Low-temperature operation
31
(2) If the self-diagnostics function fails to operate
8-3. Checking the Indoor and Outdoor Units
(1) Checking the indoor unit
(2) Checking the outdoor unit
(3) Checking the serial communications
Using the TEST/T-RUN terminals
Check the indoor unit.
Is the fuse blown?
ControlNo. Check items (unit operation)
Replace the controller.
Replace the circuit
board or the fuse.
No indicators illuminate and the indoor fan does not rotate.
Check the power voltage.
T-RUN : Test run (compressor and fan motor turn ON). TEST/MV : Compresses time to 1/60th (accelerates
operation by 60 times faster than normal).
Use the remote controller to operate the unit in "TEST run" mode. To determine whether the mode is currently in "TEST run" mode, check the 4 indicator lamps on the unit. If all 4 are blinking, the current mode is "TEST run."
If there are no problems with the above, then check the outdoor unit.
1
The rated voltage must be present between inter-unit wirings 1 and 2. Connect a 5 k ohm resistor between inter-unit wirings 2 and 3. When the voltage at both ends is measured, approximately 12 to 15V DC must be output and the multimeter pointer must bounce once every 8 seconds. Or instead of measuring the voltage, you can insert an LED jig and check that the LED flickers once every 8 seconds.
ControlNo. Check items (unit operation)
Apply the rated voltage between outdoor unit terminals L and N.
If there are no problems with the above, then check the indoor unit.
Tu rn the power OFF before performing short circuiting procedures.
Refer to the previous pages when performing system self-diagnostics.
So that the check can be made quickly, indicators blink at first communication after power ON.
Before performing the above checks, perform “TEST run” operation, and check that the rated voltage is output to terminals 1 and 2 on the outdoor unit. If it is not output, there is a failure related to the indoor unit power.
1 The control panel LED (red) must illuminate.
Short-circuit the outdoor unit COM terminal to the T-RUN terminal.
2 The compressor, fan motor, and 4-way valve must all turn on.
Normal
Blown
TEST/T-RUN terminals
(TEST)/MV T-RUN COM
For the "Test run" procedure, refer to 5. "HOW TO TEST RUN THE AIR CONDITIONER" on Appendix C.
Probable location of malfunction
Indoor unit circuit board failure
Outdoor unit circuit board failure
Failure (open circuit, contact failure, etc.) in the inter-unit wirings
Outdoor unit circuit board failure
Short-circuit terminals 2 and 3 on the outdoor unit terminal plate.
Short-circuit terminals 2 and 3 on the indoor unit terminal plate.
Initial self-diagnostics
Control 1 Control 2
....
OFF
....
Blinking
....
Illuminated
Quiet
( 3 )
Timer
( 2 )
Operation
( 1 )
Quiet
( 3 )
Timer
( 2 )
Operation
( 1 )
Quiet
( 3 )
Timer
( 2 )
Operation
( 1 )
32
8-4. Trouble Diagnosis of Fan Motor
8-4-1. Indoor Fan Motor
This indoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor. To perform diagnosis, operate the unit in cooling mode with indoor fan speed "High". Next, make sure that the indoor unit receive the signals from the remote controller when the ON/OFF operation button is pressed.
[Trouble symptom 1] The fan does not stop when the unit stops. Indoor unit controller trouble.
[Trouble symptom 2] The fan motor does not rotate when the unit is operating.
(Diagnostic procedure)
* Disconnect the motor connectors and measure the voltage at the DC motor connectors on the indoor
unit controller (3 locations).
(Diagnostic results)
All of the above measured values are normal. Fan motor trouble (Replace the motor.) Any one of the above measured values is not normal. Indoor unit controller trouble
(Replace the controller .)
(Reference) DC motor connector pin arrangement
Pin 1: Vm (red) Pin 2: Not used Pin 3: Gnd (black) Pin 4: Vcc (white) Pin 5: Vs (yellow) Pin 6: PG (blue)
[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the indoor unit
operates. (There is trouble in the system that provides feedback of motor rotation speed from the motor to the indoor unit controller.)
[Trouble symptom 4] Fan motor rotation speed does not change during indoor unit operation.
[Trouble symptom 5] Fan motor rotation speed varies excessively during indoor unit operation.
(Remedy for symptom 3 to 5)
It is not possible to identify whether the trouble is indoor unit controller trouble or motor trouble. Therefore, first replace the indoor unit controller, then (if necessary) replace the DC motor.
Important:
(A) Turn OFF the power before connecting or disconnecting the motor connectors. (B) When performing voltage measurement at the indoor controller connector for (3) in the table
below, the DC motor will trip and voltage output will stop approximately 1 minute after operation is started. For this reason, to measure the voltage again, turn OFF the unit once using the remote controller, and then start the air conditioner again.
(1) Vm-Gnd: Between pin 1 and pin 3 (2) Vcc-Gnd: Between pin 4 and pin 3 (3) Vs-Gnd: Between pin 5 and pin 3
Measurement location
DC 230V or more DC 14V or more Fluctuation between DC 1.7 to 6.1V
Normal value
33
8-5. Noise Malfunction and Electromagnetic Interference
An inverter A/C operates using pulse signal control and high frequencies. Therefore, it is susceptible to the effects of external noise, and is likely to cause electromagnetic interference with nearby wireless devices.
A noise filter is installed for ordinary use, preventing these problems. However, depending on the installation conditions, these effects may still occur. Please pay attention to the points listed below.
(1) Noise malfunction
This refers to the application of high-frequency noise to the signal wires, resulting in abnormal signal pulses and malfunction.
Locations most susceptible to noise
1. Locations near broadcast stations where there are strong electromagnetic waves
2. Locations near amateur radio (short wave) stations
3. Locations near electronic sewing machines and arc-welding machines
Correction
(The fundamental concept is to make the
system less susceptible to noise.)
- Insulate for noise or
distance from the noise source. -
1. Use shielded wires.
2. Move unit away from the noise source.
Trouble
Either of the following trouble may occur.
1. The unit may stop suddenly during operation.
2. Indicator lamps may flicker.
(2) Electromagnetic interference
This refers to noise generated by high-speed switching of the microcomputer and compressor. This noise radiates through space and returns to the electric wiring, affecting any wireless devices (televisions, radios, etc.) located nearby.
Locations most susceptible to noise
1. A television or radio is located near the A/C and A/C wiring.
2. The antenna cable for a television or radio is located close to the A/C and A/C wiring.
3. Locations where television and radio signals are weak.
Correction
1. Select a separate power source.
2. Keep the A/C and A/C wiring at least 1 meter away from wireless devices and antenna cables.
3. Change the wireless device’s antenna to a high­sensitivity antenna.
4. Change the antenna cable to a BS coaxial cable.
5. Use a noise filter (for the wireless device).
6. Use a signal booster.
Trouble
1. Noise appears in the television picture, or the picture is distorted.
2. Static occurs in the radio sound.
34
INSTRUCTION MANUAL
MCAF78MR5I MCAF98MR5I
MCAF128MR5I
(OI-852-6-4181-047-00-0)
APPENDIX A
A-1
OPERATING INSTRUCTIONS • INSTRUCCIONES DE USO
NOTICE D’UTILISATION • BEDIENUNGSANLEITUNG
ISTRUZIONI D’USO
This air conditioner uses the new refrigerant R410A
MCAF78MR5I MCAF98MR5I
MCAF128MR5I
Save These Instructions• Guardéis estas instrucciones
Conserver ce notice d’utilisation• Bewahren Sie bitte diese Bedienungsanleitung auf
Split air conditioner system • Acondicionador de aire de consola partida sistema split
Climatiseurs split • Split-klimagerät • Condizionatore d’aria split system
Pub. OI-85264181047000
Conservate queste istruzioni
12/2007
Features
This air conditioner is an inverter type unit that automatically adjusts capability as appropriate. Details on these functions are provided below; refer to these descriptions when using the air conditioner.
Microprocessor Controlled Operation
The interior compartment of the remote control unit contains several features to facilitate automatic operation, easy logically displayed for easy use.
Simple One-touch Wireless Remote Control
The remote control unit has several features to facilitate automatic operation.
24-Hour ON or OFF Timer
This timer can be set to automatically turn the unit on or off at any time within a 24 hour period.
1-Hour OFF Timer
This timer can be set to automatically turn off the unit at any time after one hour.
Night Setback
This function saves energy by controlling operation to provide a quieter operating sound than normal.
Automatic and 3-step Fan Speed
Auto/High/Medium/Low
Air Sweep Control
This function moves a flap up and down in the air outlet, directing air in a sweeping motion around the room and providing comfort in every corner.
Auto. Flap Control
This automatically sets the flap to the optimum position during heating, cooling, and drying operation.
Hot Start Heating System
Right from the start, the air is warm and comfortable. This system prevents any cold blasts at the beginning while the heat pump is warming up, or even defrosting.
Automatic Restart Function for Power Failure
Even when power failure occurs, preset programmed operation can be reactivated once power resumes.
High Power Operation
If not in Auto Operation, the unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is 1 step above “High”.
Quiet Operation
The fan rotates slower than the fan speed setting to provide a quieter operating sound.
ION Operation
While it is operating, the unit generates negative ions that freshen up the air in the room.
Anti-Mold Filter
This unit is equipped with an anti-mold filter that inhibits the growth of mold and bacteria.
Air Clean Filter
An air filter that eliminates unpleasant odors and cleans the air is available. Purchase a replacement filter at your local dealer. (model STK-FDXB)
2
OI-047-2-EG
Contents
Page
Features............................................................................................................ 2
Product Information........................................................................................... 3
Alert Symbols.................................................................................................... 3
Installation Location .......................................................................................... 4
Electrical Requirements .................................................................................... 4
Safety Instructions............................................................................................. 4
Names of Parts ................................................................................................. 5
Using the Remote Control Unit ....................................................................... 10
Operation with the Remote Control Unit ......................................................... 12
1. Automatic Operation .............................................................................. 12
2. Manual Operation .................................................................................. 13
3. Adjusting the Fan Speed........................................................................ 14
4. Night Setback Mode............................................................................... 15
5. QUIET Mode .......................................................................................... 16
6. HIGH POWER Mode ............................................................................. 16
7. ION Mode............................................................................................... 16
Special Remarks............................................................................................. 17
Setting the Timer............................................................................................. 18
Using the 1-Hour OFF Timer .......................................................................... 20
Tips for Energy Saving.................................................................................... 20
Adjusting the Airflow Direction ........................................................................ 21
Operation without the Remote Control Unit .................................................... 22
Care and Cleaning .......................................................................................... 22
Troubleshooting............................................................................................... 25
Operating Range............................................................................................. 25
Product Information
If you have problems or questions concerning your Air Conditioner, you will need the following information. Model and serial numbers are on the nameplate on the bottom of the cabinet.
Model No. ______________________ Serial No. ____________________ Date of purchase ________________________________________________ Dealer’s address ________________________________________________
Phone number ________________
DECLARATION OF CONFORMITY
This product is marked « » as it satisfies EEC Directive No. 89/336/ EEC, 73/ 23/EEC, 93/68/EEC and 92/31/EEC. This declaration will become void in case of mis-usage and/or from non observance though partial of Manufacturer’s installation and/or operating instructions.
Alert Symbols
The following symbols used in this manual, alert you to potentially dangerous conditions to users, service personnel or the appliance:
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
OI-047-3-EG
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
3
Installation Location
We recommend that this air conditioner be installed properly by
qualified installation technicians in accordance with the Installation Instructions provided with the unit.
Before installation, check that the voltage of the electric supply in your home
or office is the same as the voltage shown on the nameplate.
Do not install this air conditioner where there are fumes or flammable gases, or in an extremely humid space such as a greenhouse.
Do not install the air conditioner where excessively high heat­generating objects are placed.
Avoid: To protect the air conditioner from heavy corrosion, avoid installing the
outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa.
Electrical Requirements
1. All wiring must conform to the local electrical codes. Consult your dealer or a
qualified electrician for details.
2. Each unit must be properly grounded with a ground (or earth) wire or
through the supply wiring.
3. Wiring must be done by a qualified electrician.
CAUTION
Safety Instructions
Read this Instruction Manual carefully before using this air conditioner. If you still have any difficulties or problems, consult your dealer for help.
This air conditioner is designed to give you comfortable room conditions. Use this only for its intended purpose as described in this Instruction Manual.
Never use or store gasoline or other flammable vapor or liquid near the air conditioner — it is very dangerous.
This air conditioner has no ventilator for intaking fresh air from outdoors. You must open doors or windows frequently when you use gas or oil heating appliances in the same room, which consume a lot of oxygen from the air. Otherwise there is a risk of suffocation in an extreme case.
Do not turn the air conditioner on and off from the power mains switch. Use the ON/OFF operation button.
Do not stick anything into the air outlet of the outdoor unit. This is dangerous because the fan is rotating at high speed.
Do not let children play with the air conditioner.
Do not cool or heat the room too much if babies or invalids are present.
4
OI-047-4-EG
Names of Parts
Air intakes
Air outlet
Remote control unit
Refrigerant tubes
OUTDOOR UNIT
INDOOR UNIT
Drain hose
Air outlet
NOTE
Air Intake Air from the room is drawn into this section and passes through air filters
Air Outlet Conditioned air is blown out of the air conditioner through the air outlet.
Remote Control Unit The wireless remote control unit controls power ON/OFF, operation mode
Refrigerant Tubes The indoor and outdoor units are connected by copper tubes through which
Drain Hose Moisture in the room condenses and drains off through this hose.
Outdoor (Condensing) Unit The outdoor unit contains the compressor, fan motor, heat exchanger coil,
This illustration is based on the external view of a standard model. Consequently, the shape may differ from that of the air conditioner which you have selected.
This air conditioner consists of an indoor unit and an outdoor unit. You can control the air conditioner with the remote control unit.
which remove dust.
selection, temperature, fan speed, timer setting, and air sweeping.
refrigerant gas flows.
and other electrical components.
OI-047-5-EG
5
IMPORTANT
Avoid using radio equipment such as mobile phone near (within 1 m) the remote control receiver. Some radio equipment may cause malfunction of the unit.
If the trouble happens, disconnect power and restart the air conditioner after a few minutes.
Unit Display and Operation Button
INDOOR UNIT
OPERATION lamp TIMER lamp QUIET lamp
ION lamp
OPERATION button
REMOTE CONTROL receiver
REMOTE CONTROL receiver This section picks up infrared signals from the remote control unit
(transmitter).
OPERATION button When the remote control cannot be used, pressing this button enables
heating and cooling operation.
Each time this button is pressed, the type of operation conducted is indicated by the changing color of the OPERATION lamp. Press the button and select the lamp color that suits your preference for operation.
Cooling operation
(green)
Heating operation
(red)
Stop
(lamp off)
OPERATION lamp This lamp lights when the system is in the continuous AUTO (red or green),
HEAT (red), DRY (orange), and COOL (green) mode. The OPERATION lamp lights up red and orange alternately when the system is defrosting.
TIMER lamp This lamp lights when the system is being controlled by the timer.
QUIET lamp This lamp lights during operation in the QUIET mode.
ION lamp This lamp lights during operation in ION mode while the indoor unit is
operating.
NOTE
6
The unit’s display lamps are dimmed during operation in the NIGHT SETBACK mode.
OI-047-6-EG
Displayed when the
time display is set to
12-hour time.
Remote Control Unit (Display)
Displayed when transmitting data
Displayed when indoor unit sensor is in use Displayed when setting temperature
Displayed when temperature is shown
Displayed when setting timer
Symbols
(1) Operation mode
AUTO .....................................
HEAT ......................................
MILD DRY..............................
COOL.....................................
(2) Fan speed
Automatic operation ...............
HIGH .....................................
MEDIUM.................................
LOW.......................................
(4) Timer
24-hour clock with ON/OFF
program Timer........................
ON Timer................................
OFF Timer..............................
1-hour OFF Timer...................
(5) NIGHT SETBACK ..................
(6) Confirmation
of transmission .......................
(7) Auto. flap indication................
Flap angle indication ..............
(3) Temperature setting
16–30°C When set to 28 °C
temperature indication............
OI-047-7-EG
Sweep indication ....................
(8) High power operation .............
(9) Quiet operation.......................
(10) ION operation.......................
7
Remote Control Unit
Transmitter
ION button
QUIET button
FAN SPEED selector button
FLAP button
ON TIME
setting
buttons
Advance button
Return button
CANCEL button
SENSOR button
Display
Sensor
(Cover closed)
ON/OFF operation button
1 HR. TIMER button
Temperature setting buttons (TEMP.)
MODE selector button NIGHT SETBACK button
HIGH POWER button
Advance button
Return button
OFF TIME setting buttons
CLOCK button
Time display selector button
ADDRESS switch
ACL button
Temperature display
selector button
NOTE
The illustration above pictures the remote control unit after the cover has been opened.
Transmitter When you press the buttons on the remote control unit, the mark appears
in the display to transmit the setting changes to the receiver in the air conditioner.
Sensor A temperature sensor inside the remote control unit senses the room
temperature.
Display Information on the operating conditions is displayed while the remote control
unit is switched on. If the unit is turned off, FLAP setting and FAN SPEED setting are not displayed.
ION button : This button is for turning the negative ions generated during
operation on and off.
ON/OFF operation button This button is for turning the air conditioner on and off.
1 HR. TIMER button
(1-HOUR OFF TIMER)
: When you press this button, regardless of whether the unit is
operating or stopping, the unit operates for one hour and then shuts down.
8
OI-047-8-EG
Remote Control Unit (continued)
Temperature setting buttons
(TEMP.)
Press the button to increase the set temperature. Press the button to reduce the set temperature. The temperature setting changes by 1 °C or 2 °F each time one of the TEMP. buttons is pressed.
QUIET button : When you press this button, the fan rotates slower than the fan
speed setting to provide a quieter operating sound.
MODE selector button Use this button to select AUTO, HEAT, DRY or COOL mode.
(AUTO) : The air conditioner calculates the difference between the thermostat
setting and room temperature, and automatically selects ‘‘COOL’’ or ‘‘HEAT’’ mode as appropriate.
(HEAT) : The air conditioner makes the room warmer.
(DRY) : The air conditioner reduces the humidity in the room.
(COOL) : The air conditioner makes the room cooler.
NOTE
When multiple indoor units are used and units in other rooms are already operating, they will be set to the same mode of operation as the operating indoor units.
FAN SPEED selector button : The air conditioner automatically decides the fan speeds.
: High fan speed : Medium fan speed : Low fan speed
NIGHT SETBACK button For details, see “4. Night Setback Mode”. When you press this button in the
HEAT, DRY or COOL mode, the mark appears in the display, and the remote control unit will automatically adjust the set temperature to save energy.
FLAP button Press this button either to select the setting of the airflow direction to the
auto. flap in each mode or one of the six possible positions manually or to select the sweep function which moves the flap up and down automatically.
: Auto flap setting: If selected in a heating operation, the flap is set to
position (3) in the following chart. If selected in a cooling or dry
operation, the flap is set at position (7) in the following chart. : The airflow direction can be set manually. (six positions) : The flap moves up and down automatically.
NOTE
When you press the FLAP button, the air flow direction will be changed one by one as follows.
SWEEP
HIGH POWER button : If this button is pressed during HEAT, DRY or COOL operation, the
unit operates at maximum output for 30 minutes, regardless of the
desired temperature.
The fan speed is 1step above ‘‘HIGH’’.
ON TIME/OFF TIME setting
buttons
No display: The timer does not operate.
: The air conditioner starts at the set time. : The air conditioner stops at the set time.
: The air conditioner stops and starts, or starts and stops, at
the set times every day. For details, see “Setting the Timer”.
OI-047-9-EG
9
Remote Control Unit (continued)
SENSOR button When you press this button (use a small-tipped object such as a ballpoint
pen), the mark will appear at the display. And the room temperature is detected by the sensor which is built into the indoor unit and the air conditioner is controlled accordingly.
NOTE
Temperature Display Selector
button
Time Display Selector button This switches the time display between 24-hour time and 12-hour time.
ACL button (ALL CLEAR) Puts the remote control unit into pre-operation status. Always press this
ADDRESS switch The address switch changes to prevent mixing of signals from remote
NOTE
The remote control unit sends the temperature signal to the air conditioner regularly at five minute intervals. If the signal from the remote control unit stops for more than 15 minutes due to the loss of the remote control unit or other trouble, the air conditioner will switch to the temperature sensor which is built into the indoor unit and control the room temperature. In these cases, the temperature around the remote control unit may differ from the temperature detected at the air conditioner’s position.
If the remote control is located near a heat source, such as a space heater or in direct sunlight, press the SENSOR button to switch to the sensor on the indoor unit.
This switches the temperature display between °C and °F.
button after replacing the batteries.
control units when two air conditioners are installed next to each other. Normally, the address switch is set to A. For more information, please contact the dealer where you made the purchase.
Normally, the tabs on the remote control unit should not be bent.
Using the Remote Control Unit
How to Install Batteries
ACL button
NOTE
1. Slide the cover in the direction
indicated by the arrow and remove it.
2. Install two AAA alkaline batteries.
Make sure the batteries point in the direction marked in the battery compartment.
3. Use a thin object such as the tip of a
pen to press the ACL button.
The batteries last about six months, depending on how much you use the remote control unit. Replace the batteries when the remote control unit’s display fails to light, or when the remote control cannot be used to change the air conditioner’s settings.
Use two fresh leak-proof type-AAA alkaline batteries.
In replacing batteries, follow the instructions as mentioned in the sub-section “How to Install Batteries”.
If you do not use the remote control unit more than 1 month, take out the batteries.
10
OI-047-10-EG
Using the Remote Control Unit (continued)
How to Use the Remote
Control Unit
Remote Control Unit
Installation Position
DO NOT In direct sunlight
When using the remote control unit, always point the unit’s transmitter head directly at the air conditioner’s receiver.
Air conditioner (Indoor unit)
Receiver
Remote control
(Transmitter head)
unit
The remote control unit may be operated either from a non-fixed position or from a wall-mounted position. To ensure that the air conditioner operates correctly, DO NOT install the remote control unit in the following places:
Behind a curtain or other places where it is covered
More than 8 m away from the air conditioner
In the path of the air conditioner’s airstream
Where it may become extremely hot or cold
Where it may be subject to electrical or magnetic noise
Where there is an obstacle between the remote control unit and air conditioner (since a check signal is sent from the remote control unit every 5 minutes)
Mounting the Remote Control
Unit
Mounting screws
4 x 16 (included)
When Holding the Remote
Control Unit
Before mounting the remote control unit, press the ON/OFF operation button at the mounting location to make sure that the air conditioner operates from that location. The indoor unit should make a beeping sound to indicate that it has received the signal.
Remote control
Rear side
unit mount
Press
Set in place
Hole
To prevent loss of the remote control unit, you can connect the remote control unit to the mount by passing a string through the remote control unit and attachment hole.
To take out the remote control unit, pull it forward.
When using the remote control unit and during air conditioner operation, the transmitter on the remote control unit should be pointed toward the receiver on the indoor unit.
Make sure that there are no objects between the remote control unit and receiver which could block the signal.
OI-047-11-EG
11
Operation with the Remote Control Unit
1. Automatic Operation
The air conditioner calculates the difference between the thermostat setting and room temperature, and automatically selects ‘‘COOL’’ or ‘‘HEAT’’ mode as appropriate.
STEP 2
STEP 1
NOTE
NOTE
Check that the circuit breaker on the power panel is turned on.
Once mode is selected and the unit is preset by following the steps below, you can have the air conditioner automatically bring the room to the desired temperature simply by pressing the ON/OFF operation button.
STEP 1 Press the MODE selector button to .
STEP 2 Press the ON/OFF operation button.
To stop the air conditioner, press the ON/OFF operation button again.
To change the temperature setting; press the temperature setting buttons and change the setting to the desired temperature.
12
OI-047-12-EG
2. Manual Operation
Operation with the Remote Control Unit (continued)
STEP 2
STEP 3
STEP 1
STEP 4
NOTE
STEP 5
Check that the circuit breaker on the power panel is turned on.
If the automatic operation settings of the unit do not meet your needs, press the setting buttons as described below and change the settings as desired.
STEP 1 Press the MODE selector button and select the desired
mode.
For heating operation For dehumidifying operation For cooling operation
STEP 2 To start the air conditioner, press the ON/OFF operation
button.
STEP 3 Press the TEMP. setting buttons to change the temperature
setting to the desired temperature. Adjustable temperature range:
30 °C max.
16 °C min.
or 86 °F max.
60 °F min.
STEP 4 Set the FAN SPEED selector button to the setting you want.
STEP 5 Press the FLAP button and set the airflow direction as
desired. (Refer to “Adjusting the Airflow Direction” on page 21.)
NOTE
OI-047-13-EG
To stop the air conditioner, press the ON/OFF operation button again.
When multiple indoor units are used and units in other rooms are already operating, they will be set to the same mode of operation as the operating indoor units.
13
Operation with the Remote Control Unit (continued)
NOTE
Choose the best position in the room for the remote control unit, which also acts as the sensor for room comfort and transmits the operating instructions. Once you’ve found this best position, always keep the remote control unit there.
This appliance has a built-in 5-minute time delay circuit to ensure reliable operation. When the operation button is pressed, the compressor will start running within three minutes. In the event of power failure, the unit will stop.
3. Adjusting the Fan Speed
A. Automatic fan speed Simply set the FAN SPEED selector button to the position.
This automatically sets the best fan speed for the room temperature.
B. Manual fan speed If you want to adjust fan speed manually during operation, just set the FAN
SPEED selector button as desired. [ , , or ]
14
OI-047-14-EG
4. Night Setback Mode
Operation with the Remote Control Unit (continued)
Night Setback Mode is used for saving energy.
Press the NIGHT SETBACK button while operation. The mark appears in the display.
To release the night setback function, press the NIGHT SETBACK button again.
A. In Cooling and DRY
Mode: ( and )
B. In Heating Mode: ( )
When the night setback mode is selected, the air conditioner automatically raises the temperature setting 1 °C when 30 minutes have passed after the selection was made, and then another 1 °C after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed.
1°C (2°F)
Setting temperature
Press the NIGHT
1°C (2°F)
30 min.
30 min.
Time
SETBACK button
When the night setback mode is selected, the air conditioner automatically lowers the temperature setting 2 °C when 30 minutes have passed after the selection was made, and then another 2 °C after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle heating is needed.
OI-047-15-EG
Setting temperature
Press the NIGHT SETBACK button
30 min.
2°C (4°F)
30 min.
2°C (4°F)
Time
15
5. QUIET Mode
6. HIGH POWER Mode
Operation with the Remote Control Unit (continued)
QUIET Mode is used to reduce the fan sound of the indoor unit.
Press the QUIET button. The mark appears in the display.
To cancel, press QUIET button again.
In QUIET Mode, the fan rotates at a slower speed than the fan speed setting.
If the unit is already operating with a very low airflow, the fan sound may not change even if the QUIET button is pressed.
HIGH POWER mode can be used to increase the output of the indoor unit for all operation modes except automatic operation.
7. ION Mode
Press the HIGH POWER button. The mark appears in the display.
To cancel, press HIGH POWER button again.
When the HIGH POWER button is pressed, the unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is 1 step above “High”.
HIGH POWER Mode cannot be used when the operation mode is Automatic Operation.
QUIET Mode and HIGH POWER Mode cannot be used at the same time.
NOTE
When set to High fan speed during heating operation, the fan runs at High fan speed even though the mark is displayed.
Depending on the operating conditions, the fan speed may be increased by a small amount only.
The ION mode is used during operation to generate negative ions that freshen up the air in the room.
Press the ION button. The mark appears in the display.
To cancel, press ION button again.
16
The indoor unit’s ION lamp lights up while negative ions are being generated.
ION “on” is the remote control unit’s initial setting.
The negative ions are generated from the negative ion generator.
OI-047-16-EG
Special Remarks
‘‘DRY’’ ( ) Operation
How it works? Once the room temperature reaches the level that was set, the unit’s
operation frequency is changed automatically.
During DRY operation, the fan speed automatically runs at lower speed for providing a comfortable breeze.
‘‘DRY’’ operation is not possible if the indoor temperature is 15 °C or less.
Heating ( ) Operation
Heating performance Because this air conditioner heats a room by drawing in the heat of the
outside air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, use another heating appliance together with it.
Defrosting When the outdoor temperature is low, frost or ice may form on the heat
exchanger coil, reducing heating performance. When this happens, a microcomputer defrosting system operates. At the same time, the fan on the indoor unit stops and the OPERATION lamp lights red and orange alternately until defrosting is completed. Heating operation restarts after several minutes. (This interval will vary slightly depending upon the outdoor temperature and the way in which frost forms.)
Cold draft prevention For several minutes after the start of heating operation, the indoor fan runs
at a lower speed until the indoor heat exchanger coil has warmed up sufficiently. However, the fan may remain stopped when the room temperature is low. This is because the COLD DRAFT PREVENTION SYSTEM is in operation.
Power failure during
operation
Clicking Sound
Clicking sound is heard from
the air conditioner
Remote Control Unit
In the event of power failure, the unit will stop. When the power is resumed, the unit will restart automatically within 15 minutes by the remote control unit.
In heating or cooling operation, any plastic parts may expand or shrink due to a sudden temperature change. In this event, a clicking sound may occur. This is normal, and the sound will soon disappear.
The remote control unit sends the setting condition signals to the air conditioner regularly at five minute intervals.
OI-047-17-EG
17
Setting the Timer
NOTE
1. How to set the present time
In the descriptions below, the following settings are used for the temperature and time indicator selector button on the bottom front section of the remote control.
Temperature: °C
Time: AM, PM
(Example) To set to 10:30 pm.
Operation Indication
1. Press the CLOCK button once if
the time indicator is not flashing.
2. Press the Advance, Return ( ,
) button until PM 10:30 is
displayed.
3. Press the CLOCK button again. This completes the setting of the
The time indication alone flashes.
The time can be set in 1-minute increments. Holding down the button advances the time rapidly in 10-minute increments.
current time.
2. How to set the OFF time
18
(Example) To stop the air conditioner at 11:00 am.
1. Press the OFF TIME setting
button once.
The timer indication is displayed, and the present OFF time is shown.
2. Press the Advance, Return ( ,
) button until AM 11:00 is
displayed.
The timer indication blinks. The time can be set in 10-minute increments. Holding down the button advances the time rapidly in 10-minute increments.
3. Wait a few seconds, and then
the setting is complete.
The timer indication stops blinking and the present time is displayed.
OI-047-18-EG
Setting the Timer (continued)
3. How to set the ON time
4. How to set DAILY ON/OFF REPEAT timer
(Example) To start operation at 7:10 am.
Operation Indication
1. Press the ON TIME setting
button once.
The timer indication is displayed, and the present ON time is shown.
2. Press the Advance, Return ( ,
) button until AM 7:10 is
displayed.
The timer indication blinks. The time can be set in 10-minute increments. Holding down the button advances the time rapidly in 10-minute increments.
3. Wait a few seconds, and then
the setting is complete.
The timer indication stops blinking and the present time is displayed.
(Example) To start operation at 7:10 am. and stop the air conditioner at 11:00 am.
10:30 pm.
Present time
7:10 am.
ON
11:00 am.
OFF
1. Set the timer ON/OFF times as
shown in 2-1, 2, 3 and 3-1, 2, 3.
NOTE
The ON/OFF combination timer uses the current time as the reference, and it is activated starting from whichever set time comes first.
With the ON/OFF combination timer, the settings are repeated every day.
You can check the timer ON/OFF times after you have set them by pressing the ON TIME and OFF TIME setting buttons.
To cancel a timer program Press the CANCEL button.
When either an ON or OFF timer is to be canceled, press the button corresponding to the timer whose program is to be canceled, and then press the CANCEL button.
NOTE
The airflow direction, fan speed and temperature setting can be changed after a timer program has been set even when the unit is stopped. Even when operation is stopped during an ON timer program, the unit will start operating when the set time is reached provided that the program is not canceled.
When the ON timer and OFF timer are set to the same time, the timer operates as if it is turned off.
The present time 10:30 pm. and
are displayed.
OI-047-19-EG
19
Using the 1-Hour OFF Timer
1. 1-Hour OFF Timer This function causes the unit to operate for one hour and then stop, regardless of whether the unit is on or off when this button is pressed.
The indicator in the display indicates that this function is operating.
Setting procedure:
Regardless of whether the unit is operating or stopped, press the 1 HR. TIMER button.
appears in the display.
Cancellation procedure:
Press the ON/OFF operation button to turn the unit off, wait for the unit to stop operating, and then press the ON/OFF operation button again. The 1-Hour Timer function is now cancelled and the unit operates normally.
NOTE
2. Operation together with the DAILY ON/OFF REPEAT Timer
Do not Block the air intake and outlet of the unit. If they are obstructed, the
Do Always try to keep the air filter clean. (Refer to “Care and Cleaning”.) A
If, while the 1-Hour Timer function is operating, the 1HR. TIMER button is
pressed once to cancel the function and then again, the unit continues to operate for one hour from that point in time and then stops.
It is not possible to use the OFF Timer and 1-Hour OFF Timer together.
Whichever function is set last takes precedence. If the 1 HR. TIMER button is pressed while the TIMER OFF function operates, the OFF Timer is cancelled and the unit will stop operating one hour later.
The 1-Hour OFF Timer setting is given priority over the DAILY ON/OFF REPEAT setting.
Tips for Energy Saving
unit will not work well, and may be damaged.
Let direct sunlight into the room. Use sunshades, blinds or curtains. If the
walls and ceiling of the room are warmed by the sun, it will take longer to cool the room.
clogged filter will impair the performance of the unit.
To prevent conditioned air from escaping, keep windows, doors and any
other openings closed.
20
OI-047-20-EG
Adjusting the Airflow Direction
1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with your
hands to the left or right.
CAUTION
2. Vertical The vertical airflow can be adjusted by moving the flap with the remote
A. Sweep function
The flap starts moving up and down to deliver air over the sweep range.
C. Auto flap function
The flap is set to the recommended position.
When the humidity is high, the vertical vanes should be in the front position during the cooling or dehumidifying operation. If the vertical vanes are positioned all of the way to the right or left, condensation may begin to form around the air vent and drip down.
control unit. Do not move the flap with your hands. Confirm that the remote control unit has been turned on. Use the FLAP button to set either the sweep function or one of the six airflow direction settings.
SWEEP
COOL
DRY
B. Setting the airflow manually
Referring to the above illustration, use the FLAP button to set the airflow direction within the range used during the heating, cooling, or dehumidifying operation.
SWEEP
HEAT
NOTE
CAUTION
OI-047-21-EG
The flap automatically closes when the unit is off.
During the heating operation, the fan speed will be very low and the flap
will be in the horizontal position (position ) until the air being blown out of the unit begins to warm. Once the air warms up, the flap position and fan speed change to the settings specified with the remote control.
Use the FLAP button on the remote control to adjust the position of
the flap. If you move the flap by hand, the flap position according to the remote control and the actual flap position may no longer match. If this should happen, shut off the unit, wait for the flap to close, and then turn on the unit again; the flap position will now be normal again.
Do not have the flap pointed down during cooling operation.
Condensation may begin to form around the air vent and drip down.
21
Operation without the Remote Control Unit
INDOOR UNIT If you have lost the remote control unit or it has trouble, follow the steps
below.
When the air conditioner is not running
Each time the OPERATION button is pressed, the type of operation conducted is indicated by the changing color of the OPERATION lamp. Press the button and select the lamp color that suits your preference for operation.
OPERATION button
NOTE
Cooling operation
(green)
The temperature is set to the room temperature minus 2°C during the cooling operation and to the room temperature plus 2°C during the heating operation, and the fan speed and flap are set to Auto.
Heating operation
(red)
Stop
(lamp off)
Care and Cleaning
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.
2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
Casing and Grille (Indoor Unit) Clean the casing and grille of the indoor unit with a vacuum cleaner brush, or
wipe them with a clean, soft cloth.
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When cleaning the grille, be careful not to force the vanes out of place.
CAUTION
22
1. Never use solvents, or harsh chemicals when cleaning the indoor unit. Do not wipe the plastic casing using very hot water.
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts.
3. The internal coil and other components of the outdoor unit must be cleaned every year. Consult your dealer or service center.
OI-047-22-EG
Care and Cleaning (continued)
Anti-Mold Filter The anti-mold filter behind the air intake grille should be checked and cleaned
at least once every two weeks.
How to remove the anti-mold
filter
Cleaning Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter,
How to replace the anti-mold
filter
1. Grasp both ends of the air
Air intake grille
intake grille, and remove it by opening towards the front and pulling towards you.
2. Remove the anti-mold filter attached to the rear of the
Anti-mold filter
air intake grille.
wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.
1. With the FRONT mark of the anti-mold filter at the
Anti-mold filter
front, align the two indentions near the mark with the hooks at the rear of the air intake grille, and then mount the anti-mold filter.
FRONT mark
Hook
NOTE
OI-047-23-EG
2. Allow the edge of the air intake grille to slide into the top of the indoor unit, and then insert it all the way inside.
3. Press in the bottom right
Air intake grille
Groove
Pin
Air intake grille
and left corners of the air intake grille to attach the indoor unit.
Attach so that the round pins at the top right and left corners of the air intake grille are inserted into the grooves at the top right and left of the indoor unit.
23
Care and Cleaning (continued)
Air Clean Filter The air clean filter removes dust and dirt from the air, and reduces odors and
smoke from tobacco.
This air clean filter cannot remove harmful gases or vapors nor ventilate air in the room. You must open doors or windows frequently when you use gas or oil heating appliances. Otherwise there is a risk of suffocation in extreme cases.
How to install the air clean
filter
The air clean filter needs to be installed behind the air intake grille.
1. Remove the air intake grille.
2. Install the air clean filter in
the position shown in the figure.
3. Remount the air intake grille.
Air clean filter
How to clean the air clean filter In general, the filter should be sucked to remove dust in low fan speed of a
vacuum cleaner once every three months.
If there is heavily grime on the filter, soak the filter in lukewarm water with neutral detergent diluted 1:500 for 1 to 2 minutes then wash it.
Rinse the filter in clean water, then let it dry on the towel in room temperature.
NOTE
Do not bend nor give excessive force onto the air clean filter.
If the filter surface is heavily blocked with dirt or damaged, replace it with new one. Purchase a replacement filter at your local dealer. (model STK-FDXB)
Cleaning the main unit and
remote control unit
Wipe clean using a soft, dry cloth.
To remove stubborn dirt, moisten a cloth in warm water no hotter than 40 °C, wring thoroughly, and then wipe.
The air intake grille can be removed in order to wash it with water.
Removing and remounting the
air intake grille
Refer to “How to remove the anti-mold filter” and “How to replace the anti­mold filter” on page 23.
When using a footstool or the like, be careful not to let it tip over.
CAUTION
Washing the grille with water Clean the grille gently using a soft sponge, or the like. Then wipe away any
remaining moisture.
Neutral detergent may be used to remove stubborn dirt. Then rinse thoroughly with water and wipe away any remaining moisture.
Cleaning the negative ion
generator
Follow the steps below when the generator has become dirty.
For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.
Remove the dust on the negative ion generator.
Use a toothbrush, etc. to dust off the end.
Use a cotton swab, etc., to clean around the generator inside the plastic case,
Negative ion generator (metal electrodes inside plastic case)
taking care not to touch the electrodes.
NOTE
During use, the negative ion generator and other metal parts may become discolored: this is normal and not indicative of malfunctioning.
If the dirt on and around the negative ion generator is left to build up, a puffing or sputtering sound will eventually be heard. In this case, clean the generator immediately.
Do not apply excessive force while performing maintenance.
24
OI-047-24-EG
Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or service center.
Trouble Possible Cause Remedy
Air conditioner does not run at all. 1. Power failure. 1. Restore power.
2. Leakage circuit breaker tripped.
3. Line voltage is too low. 3. Consult your electrician or dealer.
2. Contact service center.
4. Batteries in remote control unit have run down.
OPERATION lamp blinks and air conditioner does not operate.
Compressor runs but soon stops. Obstruction in front of condenser coil. Remove obstruction.
Poor cooling (or heating) performance.
Clicking sound is heard from the air conditioner.
Trouble in system. Contact service center.
1. Dirty or clogged air filter. 1. Clean air filter to improve airflow.
2. Heat source or many people in room.
3. Doors and/or windows are open. 3. Shut them to keep the heat (or
4. Obstacle near air intake or air discharge port.
5. Thermostat is set too high for cooling (or too low for heating).
6. (Outdoor temperature is too low for heating.)
In heating or cooling operation, any plastic parts may expand or shrink due to a sudden temperature change. In this event, a clicking sound may occur.
4. Replace batteries.
2. Eliminate heat source if possible.
cold) out.
4. Remove it to ensure good airflow.
5. Set the temperature lower (or higher).
6. (Consult your dealer or try to use another heat appliance.)
This is normal, and the sound will soon disappear.
OPERATION lamp lights but outdoor unit will not run.
The use of cellular phones near the air conditioner may cause disturbance to its normal operation.
1. Turn off the power then restart the air conditioner after a while.
2. Consult your dealer.
Operating Range
The air conditioner is operable within the temperature ranges as listed below:
Temperature Indoor air temperature Outdoor air temperature
COOLING Max. 32 °C DB / 23 °C WB 43 °C DB
Min. 19 °C DB / 14 °C WB 19 °C DB
HEATING Max. 27 °C DB 24 °C DB / 18 °C WB
Min. 16 °C DB – DB/ –15 °C WB
OI-047-25-EG
25
INSTRUCTION MANUAL
MCAF188R5I MCAF248R5I
(OI-852-6-4181-048-00-0)
APPENDIX B
A-2
OPERATING INSTRUCTIONS • INSTRUCCIONES DE USO
NOTICE D’UTILISATION • BEDIENUNGSANLEITUNG
ISTRUZIONI D’USO
This air conditioner uses the new refrigerant R410A
MCAF188R5I MCAF248R5I
Save These Instructions• Guardéis estas instrucciones
Conserver ce notice d’utilisation• Bewahren Sie bitte diese Bedienungsanleitung auf
Split air conditioner system • Acondicionador de aire de consola partida sistema split
Climatiseurs split • Split-klimagerät • Condizionatore d’aria split system
Pub. OI-85264181048000
Conservate queste istruzioni
12/2007
Features
This air conditioner is an inverter type unit that automatically adjusts capability as appropriate. Details on these functions are provided below; refer to these descriptions when using the air conditioner.
Microprocessor Controlled Operation
The interior compartment of the remote control unit contains several features to facilitate automatic operation, easy logically displayed for easy use.
Simple One-touch Wireless Remote Control
The remote control unit has several features to facilitate automatic operation.
24-Hour ON or OFF Timer
This timer can be set to automatically turn the unit on or off at any time within a 24 hour period.
1-Hour OFF Timer
This timer can be set to automatically turn off the unit at any time after one hour.
Night Setback
This function saves energy by controlling operation to provide a quieter operating sound than normal.
Automatic and 3-step Fan Speed
Auto/High/Medium/Low
Air Sweep Control
This function moves a flap up and down in the air outlet, directing air in a sweeping motion around the room and providing comfort in every corner.
Auto. Flap Control
This automatically sets the flap to the optimum position during heating, cooling, and drying operation.
Automatic Switching between Cooling and Heating
When the remote control’s S/M switch is at the “S” (Single) position
This unit automatically switches between cooling operation and heating operation according to the difference between the room temperature and the temperature setting.
When the remote control’s S/M switch is at the “M” (Multiple) position
Unlike when the switch is at the “S” position as described above, the function for automatically switching between cooling and heating does not work.
Hot Start Heating System
Right from the start, the air is warm and comfortable. This system prevents any cold blasts at the beginning while the heat pump is warming up, or even defrosting.
Automatic Restart Function for Power Failure
Even when power failure occurs, preset programmed operation can be reactivated once power resumes.
High Power Operation
If not in Auto Operation, the unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is 1 step above “High”.
Quiet Operation
The fan rotates slower than the fan speed setting to provide a quieter operating sound.
ION Operation
While it is operating, the unit generates negative ions that freshen up the air in the room.
Anti-Mold Filter
This unit is equipped with an anti-mold filter that inhibits the growth of mold and bacteria.
Air Clean Filter
An air filter that eliminates unpleasant odors and cleans the air is available. Purchase a replacement filter at your local dealer. (model STK-FDXB)
IMPORTANT
“Single use” means that only one indoor unit is connected with one outdoor unit in a one-unit-to­one-unit configuration and that the remote control's S/M switch is at the “S” (Single) position.
“Multiple use” means that two or more indoor units are connected with one outdoor unit in a multiple-unit-to-one-unit configuration and that the remote control’s S/M switch is at the “M” (Multiple) position. (Refer to “Using the Remote Control Unit” on page 10.)
2
OI-048-2-EG
Contents
Page
Features............................................................................................................ 2
Product Information........................................................................................... 3
Alert Symbols.................................................................................................... 3
Installation Location .......................................................................................... 4
Electrical Requirements .................................................................................... 4
Safety Instructions............................................................................................. 4
Names of Parts ................................................................................................. 5
Using the Remote Control Unit ....................................................................... 10
Operation with the Remote Control Unit ......................................................... 12
1. Automatic Operation .............................................................................. 12
2. Manual Operation .................................................................................. 13
3. Adjusting the Fan Speed........................................................................ 14
4. Fan Only................................................................................................. 14
5. Night Setback Mode............................................................................... 15
6. QUIET Mode .......................................................................................... 16
7. HIGH POWER Mode ............................................................................. 16
8. ION Mode............................................................................................... 16
Special Remarks............................................................................................. 17
Setting the Timer............................................................................................. 18
Using the 1-Hour OFF Timer .......................................................................... 20
Tips for Energy Saving.................................................................................... 20
Adjusting the Airflow Direction ........................................................................ 21
Operation without the Remote Control Unit .................................................... 22
Care and Cleaning .......................................................................................... 22
Troubleshooting............................................................................................... 25
Operating Range............................................................................................. 25
Product Information
If you have problems or questions concerning your Air Conditioner, you will need the following information. Model and serial numbers are on the nameplate on the bottom of the cabinet.
Model No. ______________________ Serial No. ____________________ Date of purchase ________________________________________________ Dealer’s address ________________________________________________
Phone number ________________
DECLARATION OF CONFORMITY
This product is marked « » as it satisfies EEC Directive No. 89/336/ EEC, 73/ 23/EEC, 93/68/EEC and 92/31/EEC. This declaration will become void in case of mis-usage and/or from non observance though partial of Manufacturer’s installation and/or operating instructions.
Alert Symbols
The following symbols used in this manual, alert you to potentially dangerous conditions to users, service personnel or the appliance:
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
OI-048-3-EG
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
3
Installation Location
We recommend that this air conditioner be installed properly by
qualified installation technicians in accordance with the Installation Instructions provided with the unit.
Before installation, check that the voltage of the electric supply in your home
or office is the same as the voltage shown on the nameplate.
Do not install this air conditioner where there are fumes or flammable gases, or in an extremely humid space such as a greenhouse.
Do not install the air conditioner where excessively high heat­generating objects are placed.
Avoid: To protect the air conditioner from heavy corrosion, avoid installing the
outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa.
Electrical Requirements
1. All wiring must conform to the local electrical codes. Consult your dealer or a
qualified electrician for details.
2. Each unit must be properly grounded with a ground (or earth) wire or
through the supply wiring.
3. Wiring must be done by a qualified electrician.
CAUTION
Safety Instructions
Read this Instruction Manual carefully before using this air conditioner. If you still have any difficulties or problems, consult your dealer for help.
This air conditioner is designed to give you comfortable room conditions. Use this only for its intended purpose as described in this Instruction Manual.
Never use or store gasoline or other flammable vapor or liquid near the air conditioner — it is very dangerous.
This air conditioner has no ventilator for intaking fresh air from outdoors. You must open doors or windows frequently when you use gas or oil heating appliances in the same room, which consume a lot of oxygen from the air. Otherwise there is a risk of suffocation in an extreme case.
Do not turn the air conditioner on and off from the power mains switch. Use the ON/OFF operation button.
Do not stick anything into the air outlet of the outdoor unit. This is dangerous because the fan is rotating at high speed.
Do not let children play with the air conditioner.
Do not cool or heat the room too much if babies or invalids are present.
4
OI-048-4-EG
Names of Parts
Air intakes
Air outlet
Remote control unit
Refrigerant tubes
OUTDOOR UNIT
INDOOR UNIT
Drain hose
Air outlet
NOTE
Air Intake Air from the room is drawn into this section and passes through air filters
Air Outlet Conditioned air is blown out of the air conditioner through the air outlet.
Remote Control Unit The wireless remote control unit controls power ON/OFF, operation mode
Refrigerant Tubes The indoor and outdoor units are connected by copper tubes through which
Drain Hose Moisture in the room condenses and drains off through this hose.
Outdoor (Condensing) Unit The outdoor unit contains the compressor, fan motor, heat exchanger coil,
This illustration is based on the external view of a standard model. Consequently, the shape may differ from that of the air conditioner which you have selected.
This air conditioner consists of an indoor unit and an outdoor unit. You can control the air conditioner with the remote control unit.
which remove dust.
selection, temperature, fan speed, timer setting, and air sweeping.
refrigerant gas flows.
and other electrical components.
OI-048-5-EG
5
IMPORTANT
Avoid using radio equipment such as mobile phone near (within 1 m) the remote control receiver. Some radio equipment may cause malfunction of the unit.
If the trouble happens, disconnect power and restart the air conditioner after a few minutes.
Unit Display and Operation Button
INDOOR UNIT
OPERATION lamp TIMER lamp QUIET lamp
ION lamp
OPERATION button
REMOTE CONTROL receiver
REMOTE CONTROL receiver This section picks up infrared signals from the remote control unit
(transmitter).
OPERATION button When the remote control cannot be used, pressing this button enables
heating and cooling operation.
Each time this button is pressed, the type of operation conducted is indicated by the changing color of the OPERATION lamp. Press the button and select the lamp color that suits your preference for operation.
Cooling operation
(green)
Heating operation
(red)
Stop
(lamp off)
OPERATION lamp This lamp lights when the system is in the continuous AUTO (red or green),
HEAT (red), DRY (orange), COOL (green) and FAN (green) mode (but no FAN mode at M of the S/M switch on the remote control unit). The OPERATION lamp lights up red and orange alternately when the system is defrosting.
TIMER lamp This lamp lights when the system is being controlled by the timer.
QUIET lamp This lamp lights during operation in the QUIET mode.
ION lamp This lamp lights during operation in ION mode while the indoor unit is
operating.
NOTE
6
The unit’s display lamps are dimmed during operation in the NIGHT SETBACK mode.
OI-048-6-EG
Displayed when the
time display is set to
12-hour time.
Remote Control Unit (Display)
Displayed when transmitting data
Displayed when indoor unit sensor is in use Displayed when setting temperature
Displayed when temperature is shown
Displayed when setting timer
Symbols
(1) Operation mode
AUTO .....................................
HEAT ......................................
MILD DRY..............................
COOL.....................................
FAN ........................................
(2) Fan speed
Automatic operation ...............
HIGH .....................................
MEDIUM.................................
(4) Timer
24-hour clock with ON/OFF
program Timer........................
ON Timer................................
OFF Timer..............................
1-hour OFF Timer...................
(5) NIGHT SETBACK ..................
(6) Confirmation of transmission..
(7) Auto. flap indication................
Flap angle indication ..............
LOW.......................................
(3) Temperature setting
16–30°C When set to 28 °C
temperature indication............
OI-048-7-EG
Sweep indication ....................
(8) High power operation .............
(9) Quiet operation.......................
(10) ION operation.......................
7
Remote Control Unit
Transmitter
ION button
QUIET button
FAN SPEED selector button
FLAP button
ON TIME
setting
buttons
Advance button
Return button
CANCEL button
SENSOR button
Display
Sensor
(Cover closed)
ON/OFF operation button
1 HR. TIMER button
Temperature setting buttons (TEMP.)
MODE selector button NIGHT SETBACK button
HIGH POWER button
Advance button
Return button
OFF TIME setting buttons
CLOCK button Time display selector button
ADDRESS switch
ACL button
Temperature display
selector button
NOTE
The illustration above pictures the remote control unit after the cover has been opened.
Transmitter When you press the buttons on the remote control unit, the mark appears
in the display to transmit the setting changes to the receiver in the air conditioner.
Sensor A temperature sensor inside the remote control unit senses the room
temperature.
Display Information on the operating conditions is displayed while the remote control
unit is switched on. If the unit is turned off, FLAP setting and FAN SPEED setting are not displayed.
ION button : This button is for turning the negative ions generated during
operation on and off.
ON/OFF operation button This button is for turning the air conditioner on and off.
1 HR. TIMER button
(1-HOUR OFF TIMER)
: When you press this button, regardless of whether the unit is
operating or stopping, the unit operates for one hour and then shuts down.
8
OI-048-8-EG
Remote Control Unit (continued)
Temperature setting buttons
(TEMP.)
Press the button to increase the set temperature. Press the button to reduce the set temperature. The temperature setting changes by 1 °C or 2 °F each time one of the TEMP. buttons is pressed.
QUIET button : When you press this button, the fan rotates slower than the fan
speed setting to provide a quieter operating sound.
MODE selector button Use this button to select AUTO, HEAT, DRY, COOL or FAN mode.
(AUTO) : When this setting is selected, the air conditioner calculates the
difference between the thermostat setting and the room temperature and automatically switches to the ‘‘COOL’’ or ‘‘HEAT’’ mode as appropriate except at “M” of the Single/Multiple switch.
(HEAT) : The air conditioner makes the room warmer.
(DRY) : The air conditioner reduces the humidity in the room.
(COOL) : The air conditioner makes the room cooler.
(FAN) : The air conditioner works only as a circulation fan except at “M” of the
Single/Multiple switch.
FAN SPEED selector button : The air conditioner automatically decides the fan speeds.
: High fan speed : Medium fan speed : Low fan speed
NIGHT SETBACK button For details, see “5. Night Setback Mode”. When you press this button in the
HEAT, DRY or COOL mode, the mark appears in the display, and the remote control unit will automatically adjust the set temperature to save energy.
FLAP button Press this button either to select the setting of the airflow direction to the
auto. flap in each mode or one of the six possible positions manually or to select the sweep function which moves the flap up and down automatically.
: Auto flap setting: If selected in a heating operation, the flap is set to
position (3) in the following chart. If selected in a cooling or dry
operation, the flap is set at position (7) in the following chart. : The airflow direction can be set manually. (six positions) : The flap moves up and down automatically.
NOTE
When you press the FLAP button, the air flow direction will be changed one by one as follows.
SWEEP
HIGH POWER button : If this button is pressed during HEAT, DRY, COOL or FAN operation,
the unit operates at maximum output for 30 minutes, regardless of the
desired temperature.
The fan speed is 1step above ‘‘HIGH’’.
ON TIME/OFF TIME setting
buttons
No display: The timer does not operate.
: The air conditioner starts at the set time. : The air conditioner stops at the set time.
: The air conditioner stops and starts, or starts and stops, at
the set times every day. For details, see “Setting the Timer”.
OI-048-9-EG
9
Remote Control Unit (continued)
SENSOR button When you press this button (use a small-tipped object such as a ballpoint
pen), the mark will appear at the display. And the room temperature is detected by the sensor which is built into the indoor unit and the air conditioner is controlled accordingly.
NOTE
Temperature Display Selector button
Time Display Selector button This switches the time display between 24-hour time and 12-hour time.
ACL button (ALL CLEAR) Puts the remote control unit into pre-operation status. Always press this
ADDRESS switch The address switch changes to prevent mixing of signals from remote
S/M (Single/Multiple switch) Initially, the S/M switch is set to S (Single).
NOTE
NOTE
The remote control unit sends the temperature signal to the air conditioner regularly at five minute intervals. If the signal from the remote control unit stops for more than 15 minutes due to the loss of the remote control unit or other trouble, the air conditioner will switch to the temperature sensor which is built into the indoor unit and control the room temperature. In these cases, the temperature around the remote control unit may differ from the temperature detected at the air conditioner’s position.
If the remote control is located near a heat source, such as a space heater or in direct sunlight, press the SENSOR button to switch to the sensor on the indoor unit.
This switches the temperature display between °C and °F.
button after replacing the batteries and setting the S/M switch.
control units when two air conditioners are installed next to each other. Normally, the address switch is set to A. For more information, please contact the dealer where you made the purchase.
Normally, the tabs on the remote control unit should not be bent.
Set this switch to M (Multiple) for multiple operation.
Always press ACL button by a thin object such as the tip of a pen after setting the S/M switch.
When multiple indoor units are used and units in other rooms are already operating, they will be set to the same mode of operation as the operating indoor units.
How to Install Batteries
ACL button
NOTE
Using the Remote Control Unit
1. Slide the cover in the direction
indicated by the arrow and remove it.
2. Install two AAA alkaline batteries.
Make sure the batteries point in the direction marked in the battery compartment.
3. Use a thin object such as the tip of a
pen to press the ACL button.
The batteries last about six months, depending on how much you use the remote control unit. Replace the batteries when the remote control unit’s display fails to light, or when the remote control cannot be used to change the air conditioner’s settings.
Use two fresh leak-proof type-AAA alkaline batteries.
In replacing batteries, follow the instructions as mentioned in the sub-section “How to Install Batteries”.
If you do not use the remote control unit more than 1 month, take out the batteries.
10
OI-048-10-EG
Using the Remote Control Unit (continued)
How to Use the Remote
Control Unit
Remote Control Unit
Installation Position
DO NOT In direct sunlight
When using the remote control unit, always point the unit’s transmitter head directly at the air conditioner’s receiver.
Air conditioner (Indoor unit)
Receiver
Remote control
(Transmitter head)
unit
The remote control unit may be operated either from a non-fixed position or from a wall-mounted position. To ensure that the air conditioner operates correctly, DO NOT install the remote control unit in the following places:
Behind a curtain or other places where it is covered
More than 8 m away from the air conditioner
In the path of the air conditioner’s airstream
Where it may become extremely hot or cold
Where it may be subject to electrical or magnetic noise
Where there is an obstacle between the remote control unit and air conditioner (since a check signal is sent from the remote control unit every 5 minutes)
Mounting the Remote Control
Unit
Remote control
unit mount
Mounting screws
4 x 16 (included)
When Holding the Remote
Control Unit
Before mounting the remote control unit, press the ON/OFF operation button at the mounting location to make sure that the air conditioner operates from that location. The indoor unit should make a beeping sound to indicate that it has received the signal.
Rear side
Press
Set in place
Hole
To prevent loss of the remote control unit, you can connect the remote control unit to the mount by passing a string through the remote control unit and attachment hole.
To take out the remote control unit, pull it forward.
When using the remote control unit and during air conditioner operation, the transmitter on the remote control unit should be pointed toward the receiver on the indoor unit.
Make sure that there are no objects between the remote control unit and receiver which could block the signal.
OI-048-11-EG
11
Operation with the Remote Control Unit
1. Automatic Operation
When the remote control’s S/M switch is at the “S” (Single) position
This unit automatically switches between cooling operation and heating operation according to the difference between the room temperature and the temperature setting.
When the remote control’s S/M switch is at the “M” (Multiple) position
Unlike when the switch is at the “S” position as described above, the function for automatically switching between cooling and heating does not work.
STEP 2
NOTE
NOTE
STEP 1
Check that the circuit breaker on the power panel is turned on.
Once mode is selected and the unit is preset by following the steps below, you can have the air conditioner automatically bring the room to the desired temperature simply by pressing the ON/OFF operation button.
STEP 1 Press the MODE selector button to .
STEP 2 Press the ON/OFF operation button.
To stop the air conditioner, press the ON/OFF operation button again.
To change the temperature setting; press the temperature setting buttons and change the setting to the desired temperature.
12
OI-048-12-EG
2. Manual Operation
Operation with the Remote Control Unit (continued)
STEP 2
STEP 3
STEP 1
STEP 4
NOTE
STEP 5
Check that the circuit breaker on the power panel is turned on.
If the automatic operation settings of the unit do not meet your needs, press the setting buttons as described below and change the settings as desired.
STEP 1 Press the MODE selector button and select the desired
mode.
For heating operation For dehumidifying operation For cooling operation
For fan only operation (No FAN mode at M of the S/M switch on the remote control unit.)
STEP 2 To start the air conditioner, press the ON/OFF operation
button.
STEP 3 Press the TEMP. setting buttons to change the temperature
setting to the desired temperature. Adjustable temperature range:
30 °C max.
16 °C min.
or 86 °F max.
60 °F min.
OI-048-13-EG
STEP 4 Set the FAN SPEED selector button to the setting you want.
STEP 5 Press the FLAP button and set the airflow direction as
desired. (Refer to “Adjusting the Airflow Direction” on page 21.)
To stop the air conditioner, press the ON/OFF operation button again.
13
Operation with the Remote Control Unit (continued)
NOTE
Choose the best position in the room for the remote control unit, which also acts as the sensor for room comfort and transmits the operating instructions. Once you’ve found this best position, always keep the remote control unit there.
This appliance has a built-in 5-minute time delay circuit to ensure reliable operation. When the operation button is pressed, the compressor will start running within three minutes. In the event of power failure, the unit will stop.
3. Adjusting the Fan Speed
A. Automatic fan speed Simply set the FAN SPEED selector button to the position.
This automatically sets the best fan speed for the room temperature.
B. Manual fan speed If you want to adjust fan speed manually during operation, just set the FAN
SPEED selector button as desired. [ , , or ]
4. Fan Only
STEP 2
NOTE
STEP 1
STEP 3
If you want to circulate air without any temperature control, follow these steps:
STEP 1 Press the MODE selector button to switch to the fan mode
.
STEP 2 Press the ON/OFF operation button.
STEP 3 Press the FAN SPEED selector button to select the fan
speed of your choice ( , or ).
There is no FAN only function at M of the S/M switch on the remote control unit.
14
OI-048-14-EG
5. Night Setback Mode
Operation with the Remote Control Unit (continued)
Night Setback Mode is used for saving energy.
Press the NIGHT SETBACK button while operation. The mark appears in the display.
To release the night setback function, press the NIGHT SETBACK button again.
A. In Cooling and DRY
Mode: ( and )
B. In Heating Mode: ( )
When the night setback mode is selected, the air conditioner automatically raises the temperature setting 1 °C when 30 minutes have passed after the selection was made, and then another 1 °C after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed.
1°C (2°F)
Setting temperature
Press the NIGHT
1°C (2°F)
30 min.
30 min.
Time
SETBACK button
When the night setback mode is selected, the air conditioner automatically lowers the temperature setting 2 °C when 30 minutes have passed after the selection was made, and then another 2 °C after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle heating is needed.
OI-048-15-EG
Setting temperature
Press the NIGHT SETBACK button
30 min.
2°C (4°F)
30 min.
2°C (4°F)
Time
15
6. QUIET Mode
7. HIGH POWER Mode
Operation with the Remote Control Unit (continued)
QUIET Mode is used to reduce the fan sound of the indoor unit.
Press the QUIET button. The mark appears in the display.
To cancel, press QUIET button again.
In QUIET Mode, the fan rotates at a slower speed than the fan speed setting.
If the unit is already operating with a very low airflow, the fan sound may not change even if the QUIET button is pressed.
HIGH POWER mode can be used to increase the output of the indoor unit for all operation modes except automatic operation.
8. ION Mode
Press the HIGH POWER button. The mark appears in the display.
To cancel, press HIGH POWER button again.
When the HIGH POWER button is pressed, the unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is 1 step above “High”.
HIGH POWER Mode cannot be used when the operation mode is Automatic Operation.
QUIET Mode and HIGH POWER Mode cannot be used at the same time.
NOTE
When set to High fan speed during heating operation, the fan runs at High fan speed even though the mark is displayed.
Depending on the operating conditions, the fan speed may be increased by a small amount only.
The ION mode is used during operation to generate negative ions that freshen up the air in the room.
Press the ION button. The mark appears in the display.
To cancel, press ION button again.
16
The indoor unit’s ION lamp lights up while negative ions are being generated.
ION “on” is the remote control unit’s initial setting.
The negative ions are generated from the negative ion generator.
OI-048-16-EG
Special Remarks
‘‘DRY’’ ( ) Operation
How it works? Once the room temperature reaches the level that was set, the unit’s
operation frequency is changed automatically.
During DRY operation, the fan speed automatically runs at lower speed for providing a comfortable breeze.
‘‘DRY’’ operation is not possible if the indoor temperature is 15 °C or less.
Heating ( ) Operation
Heating performance Because this air conditioner heats a room by drawing in the heat of the
outside air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, use another heating appliance together with it.
Defrosting When the outdoor temperature is low, frost or ice may form on the heat
exchanger coil, reducing heating performance. When this happens, a microcomputer defrosting system operates. At the same time, the fan on the indoor unit stops and the OPERATION lamp lights red and orange alternately until defrosting is completed. Heating operation restarts after several minutes. (This interval will vary slightly depending upon the outdoor temperature and the way in which frost forms.)
Cold draft prevention For several minutes after the start of heating operation, the indoor fan runs
at a lower speed until the indoor heat exchanger coil has warmed up sufficiently. However, the fan may remain stopped when the room temperature is low. This is because the COLD DRAFT PREVENTION SYSTEM is in operation.
Cooling ( ) Operation
Power failure during
operation
Clicking Sound
Clicking sound is heard from
the air conditioner
Remote Control Unit
Sometimes the indoor unit may not get to the set fan speed such as LOW and QUIET under cool operation at very low outdoor temperatures due to the indoor unit being protected from ice or frost.
In the event of power failure, the unit will stop. When the power is resumed, the unit will restart automatically within 5 minutes or 15 minutes at M position of the S/M switch on AUTO mode by the remote control unit.
In heating or cooling operation, any plastic parts may expand or shrink due to a sudden temperature change. In this event, a clicking sound may occur. This is normal, and the sound will soon disappear.
The remote control unit sends the setting condition signals to the air conditioner regularly at five minute intervals.
OI-048-17-EG
17
Setting the Timer
NOTE
1. How to set the present time
In the descriptions below, the following settings are used for the temperature and time indicator selector button on the bottom front section of the remote control.
Temperature: °C
Time: AM, PM
(Example) To set to 10:30 pm.
Operation Indication
1. Press the CLOCK button once if
the time indicator is not flashing.
2. Press the Advance, Return ( ,
) button until PM 10:30 is
displayed.
3. Press the CLOCK button again. This completes the setting of the
The time indication alone flashes.
The time can be set in 1-minute increments. Holding down the button advances the time rapidly in 10-minute increments.
current time.
2. How to set the OFF time
18
(Example) To stop the air conditioner at 11:00 am.
1. Press the OFF TIME setting
button once.
The timer indication is displayed, and the present OFF time is shown.
2. Press the Advance, Return ( ,
) button until AM 11:00 is
displayed.
The timer indication blinks. The time can be set in 10-minute increments. Holding down the button advances the time rapidly in 10-minute increments.
3. Wait a few seconds, and then
the setting is complete.
The timer indication stops blinking and the present time is displayed.
OI-048-18-EG
Setting the Timer (continued)
3. How to set the ON time
4. How to set DAILY ON/OFF REPEAT timer
(Example) To start operation at 7:10 am.
Operation Indication
1. Press the ON TIME setting
button once.
The timer indication is displayed, and the present ON time is shown.
2. Press the Advance, Return ( ,
) button until AM 7:10 is
displayed.
The timer indication blinks. The time can be set in 10-minute increments. Holding down the button advances the time rapidly in 10-minute increments.
3. Wait a few seconds, and then
the setting is complete.
The timer indication stops blinking and the present time is displayed.
(Example) To start operation at 7:10 am. and stop the air conditioner at 11:00 am.
10:30 pm.
Present time
7:10 am.
ON
11:00 am.
OFF
1. Set the timer ON/OFF times as
shown in 2-1, 2, 3 and 3-1, 2, 3.
NOTE
The ON/OFF combination timer uses the current time as the reference, and it is activated starting from whichever set time comes first.
With the ON/OFF combination timer, the settings are repeated every day.
You can check the timer ON/OFF times after you have set them by pressing the ON TIME and OFF TIME setting buttons.
To cancel a timer program Press the CANCEL button.
When either an ON or OFF timer is to be canceled, press the button corresponding to the timer whose program is to be canceled, and then press the CANCEL button.
NOTE
The airflow direction, fan speed and temperature setting can be changed after a timer program has been set even when the unit is stopped. Even when operation is stopped during an ON timer program, the unit will start operating when the set time is reached provided that the program is not canceled.
When the ON timer and OFF timer are set to the same time, the timer operates as if it is turned off.
The present time 10:30 pm. and
are displayed.
OI-048-19-EG
19
Using the 1-Hour OFF Timer
1. 1-Hour OFF Timer This function causes the unit to operate for one hour and then stop, regardless of whether the unit is on or off when this button is pressed.
The indicator in the display indicates that this function is operating.
Setting procedure:
Regardless of whether the unit is operating or stopped, press the 1 HR. TIMER button.
appears in the display.
Cancellation procedure:
Press the ON/OFF operation button to turn the unit off, wait for the unit to stop operating, and then press the ON/OFF operation button again. The 1-Hour Timer function is now cancelled and the unit operates normally.
NOTE
2. Operation together with the DAILY ON/OFF REPEAT Timer
Do not Block the air intake and outlet of the unit. If they are obstructed, the
Do Always try to keep the air filter clean. (Refer to “Care and Cleaning”.) A
If, while the 1-Hour Timer function is operating, the 1HR. TIMER button is
pressed once to cancel the function and then again, the unit continues to operate for one hour from that point in time and then stops.
It is not possible to use the OFF Timer and 1-Hour OFF Timer together.
Whichever function is set last takes precedence. If the 1 HR. TIMER button is pressed while the TIMER OFF function operates, the OFF Timer is cancelled and the unit will stop operating one hour later.
The 1-Hour OFF Timer setting is given priority over the DAILY ON/OFF REPEAT setting.
Tips for Energy Saving
unit will not work well, and may be damaged.
Let direct sunlight into the room. Use sunshades, blinds or curtains. If the
walls and ceiling of the room are warmed by the sun, it will take longer to cool the room.
clogged filter will impair the performance of the unit.
To prevent conditioned air from escaping, keep windows, doors and any
other openings closed.
20
OI-048-20-EG
Adjusting the Airflow Direction
1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with your
hands to the left or right.
CAUTION
2. Vertical The vertical airflow can be adjusted by moving the flap with the remote
A. Sweep function
The flap starts moving up and down to deliver air over the sweep range.
C. Auto flap function
The flap is set to the recommended position.
When the humidity is high, the vertical vanes should be in the front position during the cooling or dehumidifying operation. If the vertical vanes are positioned all of the way to the right or left, condensation may begin to form around the air vent and drip down.
control unit. Do not move the flap with your hands. Confirm that the remote control unit has been turned on. Use the FLAP button to set either the sweep function or one of the six airflow direction settings.
COOL
DRY
FAN
B. Setting the airflow manually
Referring to the above illustration, use the FLAP button to set the airflow direction within the range used during the heating, cooling, or dehumidifying operation.
SWEEP
SWEEP
HEAT
NOTE
CAUTION
OI-048-21-EG
The flap automatically closes when the unit is off.
During the heating operation, the fan speed will be very low and the flap
will be in the horizontal position (position ) until the air being blown out of the unit begins to warm. Once the air warms up, the flap position and fan speed change to the settings specified with the remote control.
Use the FLAP button on the remote control to adjust the position of
the flap. If you move the flap by hand, the flap position according to the remote control and the actual flap position may no longer match. If this should happen, shut off the unit, wait for the flap to close, and then turn on the unit again; the flap position will now be normal again.
Do not have the flap pointed down during cooling operation.
Condensation may begin to form around the air vent and drip down.
21
Operation without the Remote Control Unit
INDOOR UNIT If you have lost the remote control unit or it has trouble, follow the steps
below.
When the air conditioner is not running
Each time the OPERATION button is pressed, the type of operation conducted is indicated by the changing color of the OPERATION lamp. Press the button and select the lamp color that suits your preference for operation.
OPERATION button
NOTE
Cooling operation
(green)
The temperature is set to the room temperature minus 2°C during the cooling operation and to the room temperature plus 2°C during the heating operation, and the fan speed and flap are set to Auto.
Heating operation
(red)
Stop
(lamp off)
Care and Cleaning
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.
2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
Casing and Grille (Indoor Unit) Clean the casing and grille of the indoor unit with a vacuum cleaner brush, or
wipe them with a clean, soft cloth.
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When cleaning the grille, be careful not to force the vanes out of place.
CAUTION
22
1. Never use solvents, or harsh chemicals when cleaning the indoor unit. Do not wipe the plastic casing using very hot water.
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts.
3. The internal coil and other components of the outdoor unit must be cleaned every year. Consult your dealer or service center.
OI-048-22-EG
Care and Cleaning (continued)
Anti-Mold Filter The anti-mold filter behind the air intake grille should be checked and cleaned
at least once every two weeks.
How to remove the anti-mold
filter
Cleaning Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter,
How to replace the anti-mold
filter
1. Grasp both ends of the air
Air intake grille
intake grille, and remove it by opening towards the front and pulling towards you.
2. Remove the anti-mold filter attached to the rear of the
Anti-mold filter
air intake grille.
wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.
1. With the FRONT mark of the anti-mold filter at the
Anti-mold filter
front, align the two indentions near the mark with the hooks at the rear of the air intake grille, and then mount the anti-mold filter.
FRONT mark
Hook
NOTE
OI-048-23-EG
2. Allow the edge of the air intake grille to slide into the top of the indoor unit, and then insert it all the way inside.
3. To attach the air intake
Air intake grille
Groove
Pin
Air intake grille
grille to the indoor unit, press its bottom right and left corners as well as its bottom center into place.
Attach so that the round pins at the top right and left corners of the air intake grille are inserted into the grooves at the top right and left of the indoor unit.
23
Care and Cleaning (continued)
Air Clean Filter The air clean filter removes dust and dirt from the air, and reduces odors and
smoke from tobacco.
This air clean filter cannot remove harmful gases or vapors nor ventilate air in the room. You must open doors or windows frequently when you use gas or oil heating appliances. Otherwise there is a risk of suffocation in extreme cases.
How to install the air clean
filter
The air clean filter needs to be installed behind the air intake grille.
1. Remove the air intake grille.
2. Install the air clean filter in
the position shown in the figure.
3. Remount the air intake grille.
Air clean filter
How to clean the air clean filter In general, the filter should be sucked to remove dust in low fan speed of a
vacuum cleaner once every three months.
If there is heavily grime on the filter, soak the filter in lukewarm water with neutral detergent diluted 1:500 for 1 to 2 minutes then wash it.
Rinse the filter in clean water, then let it dry on the towel in room temperature.
NOTE
Do not bend nor give excessive force onto the air clean filter.
If the filter surface is heavily blocked with dirt or damaged, replace it with new one. Purchase a replacement filter at your local dealer. (model STK-FDXB)
Cleaning the main unit and
remote control unit
Wipe clean using a soft, dry cloth.
To remove stubborn dirt, moisten a cloth in warm water no hotter than 40 °C, wring thoroughly, and then wipe.
The air intake grille can be removed in order to wash it with water.
Removing and remounting the
air intake grille
Refer to “How to remove the anti-mold filter” and “How to replace the anti­mold filter” on page 23.
When using a footstool or the like, be careful not to let it tip over.
CAUTION
Washing the grille with water Clean the grille gently using a soft sponge, or the like. Then wipe away any
remaining moisture.
Neutral detergent may be used to remove stubborn dirt. Then rinse thoroughly with water and wipe away any remaining moisture.
Cleaning the negative ion
generator
Follow the steps below when the generator has become dirty.
For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.
Remove the dust on the negative ion generator.
Use a toothbrush, etc. to dust off the end.
NOTE
Use a cotton swab, etc., to clean around the generator inside the plastic case, taking care not to touch the electrodes.
During use, the negative ion generator and other metal parts may become
Negative ion generator (metal electrodes inside plastic case)
discolored: this is normal and not indicative of malfunctioning.
If the dirt on and around the negative ion generator is left to build up, a puffing or sputtering sound will eventually be heard. In this case, clean the generator immediately.
Do not apply excessive force while performing maintenance.
24
OI-048-24-EG
Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or service center.
Trouble Possible Cause Remedy
Air conditioner does not run at all. 1. Power failure. 1. Restore power.
2. Leakage circuit breaker tripped.
3. Line voltage is too low. 3. Consult your electrician or dealer.
2. Contact service center.
4. Batteries in remote control unit have run down.
OPERATION lamp blinks and air conditioner does not operate.
Compressor runs but soon stops. Obstruction in front of condenser coil. Remove obstruction.
Poor cooling (or heating) performance.
Clicking sound is heard from the air conditioner.
Trouble in system. Contact service center.
1. Dirty or clogged air filter. 1. Clean air filter to improve airflow.
2. Heat source or many people in room.
3. Doors and/or windows are open. 3. Shut them to keep the heat (or
4. Obstacle near air intake or air discharge port.
5. Thermostat is set too high for cooling (or too low for heating).
6. (Outdoor temperature is too low for heating.)
In heating or cooling operation, any plastic parts may expand or shrink due to a sudden temperature change. In this event, a clicking sound may occur.
4. Replace batteries.
2. Eliminate heat source if possible.
cold) out.
4. Remove it to ensure good airflow.
5. Set the temperature lower (or higher).
6. (Consult your dealer or try to use another heat appliance.)
This is normal, and the sound will soon disappear.
OPERATION lamp lights but outdoor unit will not run.
The use of cellular phones near the air conditioner may cause disturbance to its normal operation.
1. Turn off the power then restart the air conditioner after a while.
2. Consult your dealer.
Operating Range
The air conditioner is operable within the temperature ranges as listed below:
Temperature Indoor air temperature Outdoor air temperature
COOLING Max. 32 °C DB / 23 °C WB 43 °C DB
Min. 19 °C DB / 14 °C WB For Single use –15 °C DB
For Multiple use 19 °C DB
HEATING Max. 27 °C DB 24 °C DB / 18 °C WB
Min. 16 °C DB – DB/ –15 °C WB
OI-048-25-EG
25
INSTALLATION INSTRUCTIONS
MCAF78MR5I MCAF98MR5I
MCAF128MR5I
MCAF188R5I MCAF248R5I
(II-852-6-4190-445-00-0)
APPENDIX C
A-3
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Unit Outdoor Unit
MCAF78MR5I GRF148MR5I MCAF98MR5I GRF198MR5I MCAF128MR5I GRF248MR5I MCAF188R5I GRF318MR5I MCAF248R5I
Power Source: 50 Hz, single-phase, 220 – 240 VAC
Combinations of indoor and outdoor units
Connect indoor and outdoor units only in the combinations listed in the catalog or installation manual.
Connecting any other model may result in operation failure and system damage.
Français
English
85264190445000 12/2007
Contents
Page
IMPORTANT!
Please Read Before Starting .................................. 2
1. GENERAL .......................................................... 3
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit 2-2. Embedding the Tubing and Wiring
3. HOW TO INSTALL THE INDOOR UNIT ............. 6
3-1. Remove the Rear Panel from the Unit 3-2. Make a Hole 3-3. Install the Rear Panel on the Wall 3-4. Remove the Grille to Install the Indoor Unit 3-5. Shape the Indoor Side Tubing 3-6. Wiring Instructions 3-7. Wiring Instructions for Inter-unit Connections 3-8. Mounting 3-9. Drain Hose
4. MULTIPLE SWITCH ON THE REMOTE CONTROL UNIT INDOOR UNIT TYPES
(MCAF188R5I, MCAF248R5I) ...........................15
5. HOW TO TEST RUN THE AIR CONDITIONER ... 16
6. REMOTE CONTROL UNIT INSTALLATION
POSITION ......................................................... 17
6-1. Mounting on a Wall
7. ADDRESS SWITCH.......................................... 18
7-1. Address Setting of the Remote
Control Unit
8. CONNECTING A HOME AUTOMATION
DEVICE.............................................................. 19
9. INSTALLATION CHECK SHEET ...................... 19
COOL/ DRY/ HEAT Model
Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A.
The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing.
For Indoor Unit
CAUTION
This air conditioner uses the new refrigerant R410A.
INSTALLATION INSTRUCTIONS
– Multi Split system air conditioner –
NOTE
2
English
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and oper­ating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
G
Carefully read this instruction booklet before beginning.
G
Follow each installation or repair step exactly as shown.
G
Observe all local, state, and national electrical codes.
G
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
• Install a protective leakage breaker depending on the installation location (especially a damp or humid loca­tion). If a leakage breaker is not installed, electric shock can occur.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
When Connecting Refrigerant Tubing
• Do not add any refrigerant, air, or substance into the refrigeration circuit other than the designated refrigerant (R410A). Adding anything other than the specified refrigerant may cause the pressure to rise excessively in the refrigeration circuit, rupturing the circuit and causing injury or damage.
• Use all-new tubing and flare nuts to make the tubing connections. Using any previous parts (from R22-based systems) may result in damage to the equipment, and may lead to the refrigeration circuit rupturing, causing a serious accident.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
WARNING
WARNING
CAUTION
CAUTION
3
English
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Table 1
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or Air Conditioner workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2.
Cut each tube to the appropriate lengths +30 cm to 40 cm to dampen vibration between units.
2. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tub­ing. Wall thickness of the insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-6. Wiring Instructions for details.
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
Model
Narrow Tube Wide Tube
Outer Dia. Thickness Outer Dia. Thickness
MCAF78 6.35 mm 0.8 mm 9.52 mm 0.8 mm
MCAF98 6.35 mm 0.8 mm 9.52 mm 0.8 mm
MCAF128 6.35 mm 0.8 mm 9.52 mm 0.8 mm
MCAF188 6.35 mm 0.8 mm 12.70 mm 0.8 mm
MCAF248 6.35 mm 0.8 mm 15.88 mm 1.0 mm
Table 2
Parts Figure
Remote control unit
Remote control unit holder
AAA alkaline battery
Q’ty Q’ty Q’ty
1
1
2
Parts Figure
Tapping screw
Tapping screw
Truss-head Phillips 4 16 mm
Truss-head Phillips 4 30 mm
2
8
Parts Figure
Air clean filter
Clamp
Packed in the indoor unit.
2
1
4
English
1-5. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
AVOID:
G direct sunlight.
G nearby heat sources that may affect performance of the
unit.
G areas where leakage of flammable gas may be expected.
G placing or allowing any obstructions near the Air Condi-
tioner inlet or outlet.
G installing in rooms that contain instant-on (rapid-start)
fluorescent lamps. (These may prevent the Air Conditioner from receiving signals.)
G places where large amounts of oil mist exist. G installing in locations where there are devices that
generate high-frequency emissions.
DO:
G select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
G select a location that will hold the weight of the unit.
G select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
G allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2)
G install the unit within the maximum elevation difference
(H1, H2, H3, H4) above or below the outdoor unit and within a total tubing length (L1+L2, L1+L2+L3, L1+L2+L3+L4) from the outdoor unit as detailed in Table 3 and Fig. 3a.
Fig. 1
Fig. 2
INDOOR UNIT (1)
INDOOR UNIT (4)
INDOOR UNIT (3)
INDOOR UNIT (2)
Tubing length (L1)
L2
L3
L4
H2
H3
H4
OUTDOOR UNIT
Elevation difference (H1)
Fig. 3a
WARNING
To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow.
Indoor unit
Floor level
Wall
Minimum height from floor level
1.5 m
Fig. 3b
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 1.5 m from floor level.
CAUTION
5 cm
min.
Indoor unit
Outside drainage
Front View
15 cm min.
Drain hose
5 cm min.
5
English
G Install the indoor unit more than 1 meter away from
any antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.
G install in a sturdy manner to avoid increased operat-
ing noise.
Table 3
* If total tubing length becomes 45 to 60 m (max.) or 45 to 70 m (max.), charge additional refrigerant (R410A) by 20 g/m.
No additional charge of compressor oil is necessary.
Max. Allowable Max. Allowable Total Limit of Limit of Elevation Required Amount
Tubing Length Tubing Length Total Tubing Length Difference of Additional
Model per unit at shipment (L1+L2) or (L1+L2+L3) (H1, H2, H3, H4) Refrigerant
(m) (L1+L2) or (L1+L2+L3) or (L1+L2+L3+L4) (m) (g/m)*
or (L1+L2+L3+L4) (m)
(m)
GRF148 20 30 (L1+L2) 30 (L1+L2) 15
GRF198 25 45 (L1+L2) 45 (L1+L2) 15
GRF248 25 45 (L1+L2+L3+L4) 60 (L1+L2+L3+L4) 15 20
GRF318 30 45 (L1+L2+L3+L4) 70 (L1+L2+L3+L4) 15 20
2-2. Embedding the Tubing and Wiring
G Before beginning embedding installation work,
consult fully with agencies or offices related to the building’s foundation, construction, electricity, and water.
G Wait to make connections to the embedded portion.
Each connection step is described later in this manual.
G Securely cover the end of the embedded tubing to
prevent intrusion of dirt or moisture.
G If an embedded tube is to be left for a long time, fill
the tube with nitrogen and seal both ends securely. If a tube is left open for an extended time, moisture in the air inside the tubing may condense into water droplets, and lead to water contamination of the refrigerant circuit.
G In order to prevent insulation breakdown and ground
faults, do not allow wiring ends to come in contact with rainwater, or be subjected to condensation or dew.
G Apply sufficient thermal insulation to the refrigerant
tubing and drain pipes
6
English
Fig. 6
Fig. 7
Fig. 8
3. How to Install the Indoor Unit
3-1. Remove the Rear Panel from the Unit
(1) Remove and discard the set screw on the rear
panel. (Fig. 6)
(2) Press the 2 LL marks on the frame cover and dis-
engage the stationary tabs from the frame. (Fig. 7)
(3) Remove the rear panel.
Tubing can be extended in 5 directions as shown in Fig. 8. Select the direction you need providing the shortest run to the outside unit.
G When left tubing is to be done, switch the drain
hose and drain cap. (For details, refer to “Switching drain hose and drain cap” on page 14.)
3-2. Make a Hole
(1) Place the rear panel from the indoor unit on the
wall at the location selected. Make sure the panel is horizontal, using a carpenter’s level or tape mea­sure to measure down from the ceiling. Wait until after cutting the hole before attaching the rear panel to the wall.
(2) Determine which side of the unit you should make
the hole for tubing and wiring. (Fig. 9a or 9b)
In the case of left-rear tubing, use the measurement points from the edge of the rear panel for precise placement of the hose outlet. (Fig. 9a or 9b)
(3) Before making the hole, check carefully that no
studs or pipes are directly run behind the spot to be cut.
The above precautions are also applicable if tub­ing goes through the wall in any other location.
Fig. 9b
CAUTION
Also avoid areas where elec­trical wiring or conduits are located.
Fig. 9a
(MCAF78/98/128)
(MCAF188/248)
NOTE
Set screw only for transportation
NOTE
Left tubing
Left-rear tubing
Rear panel
marks
Right-rear tubing (recommended)
Right tubing
Downward tubing
70 mm
60 mm
7
English
Hole should be made at a slight downward slant to the outdoor side.
Fig. 10
Fig. 12
Fig. 11
(4) Using a sabre saw, key hole saw or hole-cutting
drill attachment, cut a hole in the wall. See Table 4 and Fig. 10.
Table 4
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a slight angle 6 mm shorter than the thickness of the wall. (Fig. 11)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert the pipe in the wall. (Fig. 12)
3-3. Install the Rear Panel on the Wall
Be sure to confirm that the wall is strong enough to suspend the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 8 screws
provided. (Fig. 13a or 13b)
If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use rawl plugs or toggle bolts to go through the holes on the panel or drill 5 mm dia. holes in the panel over the stud locations and then mount the rear panel.
(2) Double check with a carpenter’s level or tape mea-
sure that the panel is level. This is important to install the unit properly. (Fig. 14)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and vibration.
b) If Block, Brick, Concrete or Similar Type Wall
Make 4.8 mm dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 15)
Hole Dia. (mm)
MCAF78/98/128 MCAF188/248
65 80
Fig. 13b
Fig. 14
Fig. 15
Fig. 13a
(MCAF78/98/128)
(MCAF188/248)
NOTE
Indoor side
Outdoor side
PVC pipe (Locally purchased)
Cut at slight angle
INSIDE OUTSIDE
Wall
Plastic cover
(Locally purchased)
PVC pipe
Slight angle
4.8 mm dia. hole
Rawl plug (Locally purchased)
English
3-4. Remove the Grille to Install the Indoor Unit
3-4-1. Indoor unit types
(MCAF78/98/128)
Basically, these models can be installed and wired without removing the grille. If access to any internal part is needed, follow the steps as given below.
How to remove the grille
(1) Grasp both ends of the air intake grille, and remove it
by opening towards the front and pulling towards you.
(Fig. 16a) (2) Remove the 2 screws. (Fig. 16b) (3) Remove the screw on the right side cover plate and
open the cover. (Fig. 17a) (4) Take out the thermistor from the grille. (Fig. 17b) (5) Pull the lower part of the grille towards you to remove.
(Fig. 18a) (6) Use a standard screwdriver to push on the tabs to
remove the grille.
How to replace the grille
(1) Reinstall the grille into the lower part while aligning
its tabs on the upper part. (Fig. 18b) Insert the tabs in the slots and push the lower part of the grille back into position.
(2) Make sure that the grille and frame are firmly fitted
together by engaging the tabs. (3) Attach the thermistor on the grille. (Fig. 17a) (4) Close the cover and replace the screw. (Fig. 17a) (5) Affix the grille with the 2 previously removed screws.
(Fig. 16b) (6) Install the air intake grille.
(a) Allow the edge of the air intake grille to slide into
the top of the indoor unit, and then insert it all the way inside. (Fig. 19a)
(b) Press the bottom right and left corners of the air
intake grille to attach it to the indoor unit. (Fig. 19b)
Attach so that the round pins at the top right and left corners of the air intake grille are inserted into the grooves at the top right and left of the indoor unit.
Fig. 16a
Fig. 16b
Fig. 17a
Fig. 17b
Fig. 18a
Fig. 18b
Fig. 19b
Fig. 19a
CAUTION
Be sure to wear work gloves during installation to avoid being cut by the sharp aluminum fins of the heat exchanger.
8
Screw cover
Thermistor
Air intake grille
Cover
Grille
Thermistor
NOTE
Tab
*
*
Grille
Frame
Ta b
*
*
Grille
Frame
Ta b
Groove
Pin
9
English
3-4-2. Indoor unit types
(MCAF188/248)
Basically, these models can be installed and wired without removing the grille. If access to any internal part is needed, follow the steps as given below.
How to remove the grille
(1) Grasp both ends of the air intake grille, and
remove it by opening towards the front and pulling
towards you. (Fig. 16a-1) (2) Remove the 3 screws. (Fig. 16b-1) (3) Remove the screw on the right side cover plate
and open the cover. (Fig. 17a-1) (4) Take out the thermistor from the grille. (Fig. 17b-1) (5) Press the 3 tabs at the top of the grille and the 3
tabs on the front face to separate the grille from
the frame. (Fig. 18a-1) (6) Pull the grill towards you to remove it.
How to replace the grille
(1) When installing the grille, place the bottom of the
grille into the frame first. (Fig. 18b-1) Then insert the tabs on the top of the grille and on the front face into the frame.
(2) Make sure that the grille and frame are firmly fitted
together by engaging the tabs. (3) Attach the thermistor on the grille. (Fig. 17a-1) (4) Close the cover and replace the screw.
(Fig. 17a-1) (5) Affix the grille with the 3 previously removed
screws. (Fig. 16b-1) (6) Install the air intake grille.
(a) Allow the edge of the air intake grille to slide
into the top of the indoor unit, and then insert it all the way inside. (Fig. 19a-1)
(b) Press the bottom right and left corners and
center of the air intake grille to attach it to the indoor unit. (Fig. 19b-1)
Attach so that the round pins at the top right and left corners of the air intake grille are inserted into the grooves at the top right and left of the indoor unit.
Fig. 16a-1
Fig. 16b-1
Fig. 17a-1
Fig. 17b-1
Fig. 18a-1
Fig. 18b-1
Fig. 19b-1
Fig. 19a-1
Pin
Groove
Air intake grille
Grille
Thermistor
Cover
Thermistor
Ta b
NOTE
Ta b
10
English
3-5. Shape the Indoor Side Tubing
(1) Arrangement of tubing by directions
a) Right or left tubing
Cut out the corner of the right/left frame with a hacksaw or the like. (Figs. 20 and 21)
b) Right-rear or left-rear tubing
In this case, the corner of the frame need not be cut.
(2) To mount the indoor unit on the rear panel:
Hang the 2 mounting slots of the unit on the upper tabs of the rear panel. (Fig. 22)
3-6. Wiring Instructions
General precautions on wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, with a power supply disconnect and cir­cuit breaker for overcurrent protection provided in the exclusive line.
(3) To prevent possible hazard due to insulation fail-
ure, the unit must be grounded.
(4) Each wiring connection must be done tightly and in
accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can
be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
Fig. 21
Fig. 22
Fig. 20
Frame
Left tubing outlet
Frame
Right tubing outlet
11
English
3-7. Wiring Instructions for Inter-unit Connections
(1) Grasp both ends of the air intake grille, and
remove it by opening towards the front and pulling towards you.
(2) Remove the screw on the right side cover plate
and open the cover. (Fig. 24)
(3) Insert the inter-unit wiring into the through-the-wall
PVC pipe. Lead the power wiring into the room allowing approx. 25 cm to extend from the wall face. (Fig. 25)
(4) Route the inter-unit wiring from the back of the
indoor unit and pull it towards the front for connec­tion. (Fig. 26)
(5) Connect the inter unit wiring to the corresponding
terminals on the terminal plate (Fig. 26) while referring to the wiring diagram.
(6) Be sure to secure the wiring with the provided
clamp.
When closing the air intake grille, press the bottom right and left corners and center. (Fig. 27)
Please refer to “How to replace the grille” on page 8 or 9 for installing the air intake grille.
Fig. 25
Fig. 24
Fig. 26
Fig. 27
NOTE
Cover
Rear panel
Plastic cover
Wiring
25 cm
12
English
When connecting each power wire to the correspond­ing terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip
the insulation to expose the wire about 7 mm. See the label (Fig. 28) near the terminal plate.
(2) Using a screwdriver, loosen the terminal screw on
the terminal plate.
(3) Insert the wire and tighten the terminal screw
completely using a screwdriver.
b) For Outdoor Unit
I For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip
the insulation to expose the solid wire about 25 mm. (Fig. 29)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the ter-
minal plate and fix it securely with the removed terminal screw using a screwdriver.
I For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip
the insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends. (Figs. 30 and 31)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connec­tor. (Fig. 30)
(4) Place the ring connector wire, and replace and
tighten the removed terminal screw using a screw­driver. (Fig. 32)
Fig. 29
Fig. 28
Fig. 30
Fig. 32
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. There­fore, be sure all wiring is tightly connected.
Fig. 31
STRIP SIZE
7 mm (ACTUAL
SIZE)
Solid wire
Loop
Strip 25 mm
Insulation
Stranded wire
Ring connector
Strip 10 mm
Twist wire ends
Wire
Special washer
Screw
Ring connector
Te r mi nal plate
Wire
Screw and special washer
Ring connector
13
English
3-8. Mounting
(1) To install the indoor unit, mount the indoor unit
onto the 2 tabs on the upper part of the rear plate.
(2) Hold down the air discharge outlet and press the
lower part of the indoor unit until it clicks to securely fasten to the 2 tabs on the lower part of the rear plate. (Fig. 33)
For tubing, choose either the right or left tubing direc­tion and follow the steps below. This work can be made easier by placing padding material (such as styrofoam) at the rear right side of the indoor unit. (Fig. 34)
I Right-side tubing
(1) Shape the refrigerant tubing so that it can easily
go into the wall hole. (Fig. 35)
(2) Push the wiring, refrigerant tubing, and drain hose
through the hole in the wall. Adjust the indoor unit so it is securely seated on the rear panel. (Fig. 36)
(3) Carefully bend the tubing (if necessary) to run
along the wall in the direction of the outdoor unit and then tape as far as the fittings. (See Caution on page 15 in the outdoor unit installation manu­al.) The drain hose should come straight down the wall to a point where water runoff won’t stain the wall.
(4) Connect the refrigerant tubing to the outdoor unit.
(After performing a leak test on the connecting part, insulate it with the tubing insulation. (Fig. 37)) Also, refer to Section 3-6. Tubing connections in the outdoor unit installation manual.
(5) Assemble the refrigerant tubing, drain hose, and
inter-unit wiring as shown in Fig. 37.
Cover
Refrigerant tubing
Rear panel
Drain hose
Inter-unit wiring
Fig. 35
Fig. 36
Fig. 37
Fig. 33
Fig. 34
Insulation
NOTE
Push
Padding material