Technibel KPA128R5TAA, GR79R5TBA, GR99R5TBA, MCAV127R5VAB, MCAV77R5TA Technical & Service Manual

...
MCAV77R5VAA - GR79R5TBA MCAV97R5VAA - GR99R5TBA MCAV127R5VAB - GR129R5TBA
7(&+1,&$/6(59,&(0$18$/
63/,76<67(0$,5&21',7,21(5
KPA128R5TAA - GR129R5TBA
Indoor Unit
MCAV77R5VAA MCAV97R5VAA MCAV127R5VAB
GR79R5TBA GR99R5TBA GR129R5TBA
Ceiling-Mounted
Floor-Mounted
KPA128R5TAA
0.8180.072.0 04/2001
i
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
Table of Contents
Page
1.OPERATING RANGE..............................................................................................................................1
2.SPECIFICATIONS
2-1.Unit Specifications..........................................................................................................................2
2-2.Major Component Specifications....................................................................................................6
2-3.Other Component Specifications....................................................................................................13
3.DIMENSIONAL DATA..............................................................................................................................14
4.REFRIGERANT FLOW DIAGRAM .........................................................................................................17
5.PERFORMANCE DATA
5-1.Performance charts .......................................................................................................................19
5-2.Air Throw Distance Chart ..............................................................................................................22
5-3. Heating Capacity ...........................................................................................................................26
6.ELECTRICAL DATA
6-1.Electrical Characteristics................................................................................................................27
6-2.Electric Wiring Diagram..................................................................................................................31
7.FUNCTION
7-1.Room Temperature Control ...........................................................................................................34
7-2.Dry Operation ................................................................................................................................36
7-3.Automatic Switching between Cooling and Heating ......................................................................36
7-4.Freeze Prevention .........................................................................................................................37
7-5.Overload Prevention ......................................................................................................................38
7-6.Cold Draft Prevention ....................................................................................................................39
7-7.Defrosting Operation .....................................................................................................................40
8.TROUBLESHOOTING
8-1.Check before and after troubleshooting ........................................................................................42
8-2.Air conditioner does not operate ....................................................................................................43
8-3.Some part of air conditioner does not operate ..............................................................................47
8-4.Air conditioner operates, but abnormalities are observed .............................................................49
8-5.If a sensor is defective ...................................................................................................................51
9.CHECKING ELECTRICAL COMPONENTS
9-1.Measurement of Insulation Resistance..........................................................................................52
9-2.Checking Continuity of Fuse on PCB Ass'y....................................................................................53
9-3.Checking Motor Capacitor .............................................................................................................53
ii
10. DISASSEMBLY PROCEDURE FOR INDOOR UNIT
10-1.Removing Air Intake Grille ...........................................................................................................54
10-2. Removing Side Panels ................................................................................................................55
10-3. Access and Removal of Electrical Component Box ....................................................................55
10-4. Removing Flap Motor ..................................................................................................................56
10-5. Removing Evaporator ..................................................................................................................56
10-6. Removing Fan and Fan Motor .....................................................................................................58
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
Heating
Maximum 27°C D.B. 24°C D.B. / 18°C W.B.
Minimum 16°C D.B. – 7°C D.B. / – 8°C W.B.
2
2.SPECIFICATIONS
2-1.Unit Specifications
Indoor Unit MCAV77R5VAA Outdoor Unit GR79R5TBA
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Heating
Capacity kW 2.30 2.70
BTU/h 7,843 9200
Air circulation (High) m
3
/h 430
Moisture removal (High) Liters/h 0.6 —
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 3.7 3.5 Power input W 790 750 Power factor % 93 96 C.O.P. W/W 2.9 3.6 Compressor locked rotor amperes A 20 20
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto /1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 /690 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 37 / 32 / 31 37 / 32 / 31
Outdoor : Hi dB-A 42 43 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 9.52(3/8) Accessories Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 35.0
Shipping kg 10.0 38.0 Shipping volume m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
3
Indoor Unit MCAV77R5VAA Outdoor Unit GR79R5TBA
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Heating
Capacity kW 2.60 3.45
BTU/h 8870 11760
Air circulation (High) m
3
/h 430
Moisture removal (High) Liters/h 0.8 —
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 4.4 4.2 Power input W 970 950 Power factor % 96 98 C.O.P. W/W 2.7 3.6 Compressor locked rotor amperes A 23 23
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto /1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 /770 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 37 / 32 / 31 37 / 32 / 31
Outdoor : Hi dB-A 42 43 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 9.52(3/8) Accessories Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 36.0
Shipping kg 10.0 39.0 Shipping volume m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B.
Outdoorairtemperature7°CD.B./6°CW.B.
4
Indoor Unit MCAV127R5VAB Outdoor Unit GR129R5TBA
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Heating
Capacity kW 3.40 4.10
BTU/h 11590 13980
Air circulation (High) m
3
/h 430
Moisture removal (High) Liters/h 1.3 —
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 5.8 6.4 Power input W 1270 1420 Power factor % 95 96 C.O.P. W/W 2.7 2.9 Compressor locked rotor amperes A 34 34
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto /1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 /1135 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 39 / 35 / 33 39 / 35 / 33
Outdoor : Hi dB-A 44 45 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Accessories Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 540
Width mm 805 700
Depth mm 177 265 Package dimensions Height mm 243 568
Width mm 855 815
Depth mm 332 343 Weight Net kg 8.0 38.0
Shipping kg 10.0 41.0 Shipping volume m
3
0.07 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Heating
Capacity kW 3.35 3.90
BTU/h 11,424 13,299
Air circulation (High)
m3/h 700
Moisture removal (High) Liters/h 1.3
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 5.6 6.1 Power input W 1,220 1,320 Power factor % 95 94 C.O.P. W/W 2.7 3.0 Compressor locked rotor amperes A 34 34
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1260 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 44 / 40 / 35 44 / 40 / 35
Outdoor : Hi dB-A 45 47 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Accessories Optional / Air Clean Filter
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 680 540
Width mm 900 700
Depth mm 190 265 Package dimensions Height mm 813 568
Width mm 1,011 815
Depth mm 296 343 Weight Net kg 23.5 38.0
Shipping kg 30.0 41.0 Shipping volume
m
3
0.24 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
Indoor Unit KPA128R5TAA Outdoor Unit GR129R5TBA
5
6
2-2.Major Component Specifications
2-2-1.Indoor Unit
Indoor Unit MCAV77R5VAA
Controller PCB
Part No. POW-K78EH(A), POW-K8EH(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8HPS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ...1,130 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT :561.8
VLT-WHT :197.4
VLT-ORG :63.4
YEL-ORG :155.7
YEL-PNK :115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close —
Run capacitor µF 0.6
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
7
Indoor Unit MCAV97R5VAA
Controller PCB
Part No. POW-K78EH(A), POW-K8EH(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8HPS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ...1,190 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT :561.8
VLT-WHT :197.4
VLT-ORG :63.4
YEL-ORG :155.7
YEL-PNK :115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close —
Run capacitor µF 0.8
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
8
Indoor Unit MCAV127R5VAB
Controller PCB
Part No. POW-K128EH(A), POW-K8EH(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-8HPS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ...1,230 Nominal output W 10 Coil resistance (Ambient temp. 20°C) BRN-WHT :561.8
VLT-WHT :197.4
VLT-ORG :63.4
YEL-ORG :155.7
YEL-PNK :115.9
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close —
Run capacitor µF 1.0
VAC 440
Flap Motor
Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.130
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Indoor Unit KPA128R5TAA
Controller PCB
Part No. POW-K126GHS-(C) Controls Microprocessor Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS-6HPS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 2 ... ø130 / L180 Fan motor model ... Q'ty K48407-M01596 ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,160 Nominal output W 20 Coil resistance (Ambient temp. 20°C) GRY-WHT : 314±7%
WHT-PNK : 444±7%
WHT-VLT : 98.9±7%
VLT-ORG : 98.9±7% ORG-YEL : 223±7%
Safety devices Type Internal protector
Operating temp. Open °C 145±5
Close Automatic reclosing
Run capacitor µF 1.5
VAC 440
Flap Motor
Model M2LJ24ZE31 Rating AC 208 / 230 V, 50 / 60 Hz No. of poles ... rpm 8 ... 2.5 / 3.0 Nominal output W 3 / 2.5 Coil resistance (Ambient temp. 20°C) k 16.45 ± 15%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area
m
2
0.192
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
10
2-2-2.Outdoor Unit
Outdoor Unit GR79R5TBA
Controller PCB POW-C96GH
Compressor
Type Rotary (Hermetic) Compressor model RH 145 VHAT Nominal output W 700 Compressor oil ... Amount cc DIAMOND MS56 ...300 Coil resistance (Ambient temp. 25°C) C–R :4.11±7%
C–S :6.04±7%
Safety devices Type Internal protector (K)
Operating temp. Open °C 150±5
Close °C 90±10
Operating amp.(Ambient temp. 25°C) Trip in 3 to 10 sec. at 22A
Run capacitor µF 25
VAC 400
Crank case heater —
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty K35610-M01723 ... 1 No. of poles ... rpm (230 V, High) 6 ...810 Nominal output W 22 Coil resistance (Ambient temp. 25°C) WHT-BRN :374±7%
BRN-PNK :484±7%
——
Safety devices Type Internal protector
Operating temp. Open °C 150±10
Close °C Automatic reclosing
Run capacitor µF 1.5
VAC 440
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area m
2
0.353
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
11
Outdoor Unit GR99R5TBA
Controller PCB POW-C96GH
Compressor
Type Rotary (Hermetic) Compressor model RH 174 VHAT Nominal output W 800 Compressor oil ... Amount cc DIAMOND MS56 ...300 Coil resistance (Ambient temp. 25°C) C–R :3.4±7%
C–S :6.13±7%
Safety devices Type Internal protector (K)
Operating temp. Open °C 150±5
Close °C 90±10
Operating amp.(Ambient temp. 25°C) Trip in 3 to 10 sec. at 28A
Run capacitor µF 25
VAC 400
Crank case heater —
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty K35610-M01723 ... 1 No. of poles ... rpm (230 V, High) 6 ...810 Nominal output W 22 Coil resistance (Ambient temp. 25°C) WHT-BRN :374±7%
BRN-PNK :484±7%
——
Safety devices Type Internal protector
Operating temp. Open °C 150±10
Close °C Automatic reclosing
Run capacitor µF 1.5
VAC 400
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.2 Face area m
2
0.353
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
12
Outdoor Unit GR129R5TBA
Controller PCB POW-C96GH
Compressor
Type Rotary (Hermetic) Compressor model RH 231 VHFT Nominal output W 1,100 Compressor oil ... Amount cc DIAMOND MS56 ...520 Coil resistance (Ambient temp. 25°C) C–R :2.17±7%
C–S :3.99±7%
Safety devices Type Internal protector (K)
Operating temp. Open °C 150±5
Close °C 90±10
Operating amp.(Ambient temp. 25°C) Trip in 3 to 10 sec. at 36A
Run capacitor µF 30
VAC 400
Crank case heater —
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty K35610-M01722 ... 1 No. of poles ... rpm (230 V, High) 6 ...830 Nominal output W 21 Coil resistance (Ambient temp. 25°C) WHT-BRN :269±7%
BRN-PNK :362±7%
Safety devices Type Internal protector
Operating temp. Open °C 150±10
Close °C Automatic reclosing
Run capacitor µF 1.5
VAC 400
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.333
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
2-3.Other Component Specifications
13
<Only for 7000 BTU/h class models>
<Only for 12000BTU/h class models>
<Only for 12,000BTU/h class models>
PTC Thermistor (TH) TDK 101YV
Resistance (at 25°C)
100 ±20%
4-way Valve (SC)
CHV01A (Coil), CHV0202 (Valve)
Coil rating
AC 220/240V, 50Hz, 6W
Coil resistance (at 20°C)
1402 ±7%
4-way Valve (SC)
LB64012 (Coil), VH7100C (Valve)
Coil rating
AC 220/240V, 50Hz, 6W
Coil resistance (at 20°C)1740 ±7%
Thermostat (Defrost thermo. 23D) TRS02-12MSR
Operating temp. °C ON 12 ±2
Diff. 8 deg. below
Power Relay (PR)
DFU24D1F
Coil rating
DC 24V Coil resistance (at 20°C) 650 ±10% Contact rating AC 250V, 20A
Outdoor Unit GR79R5TBA
GR99R5TBA GR129R5TBA
Thermistor (Room sensor) DTN-TKS134B
Resistance k 25°C 5.0 ±3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ±2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ±10%
Secondary (BRN – BRN): 2.0 ±10%
Thermal cut-off temp. 150°C
Indoor Unit MCAV77R5VAA
MCAV97R5VAA MCAV127R5VAB
4-way Valve (SC)
Coil rating
Coil resistance (at 20°C)
CHV-01A (Coil), CHV-0101 (Valve)
AC 220/240V, 50Hz, 6W
1402 ±7%
<Only for 9000BTU/h class models>
KPA128R5TAA
14
3.DIMENSIONAL DATA
Indoor Unit MCAV77R5VAA
MCAV97R5VAA MCAV127R5VAB
58.599.5
805 177
41.0
41.0 270
Narrow tube ø6.35 (1/4")
Wide tube ø9.52 (3/8") MCAV77/97 Wide tube ø12.7 (1/2") MCAV127
Center of tubing hole (2 places)
Drain hose ø18
Remote control unit
18.5
61
172.5
Unit : mm
Indoor Unit KPA128R5TAA
Remote control unit
86
74 74
Center of tubing hole ø75 (4 places)
Wide tube ø12.7 (1/2") Narrow tube ø6.35 (1/4")
Drain hose ø26
74 74
900
86
41
41
190
680
18.5
61
172.5
Unit : mm
15
16
Outdoor Unit GR79R5TBA
GR99R5TBA GR129R5TBA
700
540
15
255
Narrow tube service valve ø6.35 (1/4")
Wide tube service valve ø9.52 (3/8") ø12.7 (1/2")
170
103 57
470
4 – ø12 holes
116
320
294
Air intake
Air discharge
GR79/99 GR129
Unit : mm
4.REFRIGERANT FLOW DIAGRAM
17
Indoor Unit MCAV77R5VAA Outdoor Unit GR79R5TBA
Compressor
4-way valve
Accumulator
Wide tube service valve
Wide tube
O.D. ø9.52 mm (3/8 ")
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Heat exchanger
Heat exchanger
Muffler
Capillary tube
Capillary tube
Cooling cycle
Heating cycle
Strainer
Indoor unit Outdoor unit
Check
valve
Indoor Unit MCAV97R5VAA Outdoor Unit GR99R5TBA
Compressor
4-way valve
Accumulator
Wide tube service valve
Wide tube
O.D. ø9.52 mm (3/8 ")
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Heat exchanger
Heat exchanger
Muffler
Capillary tube
Cooling cycle
Heating cycle
Strainer
Indoor unit Outdoor unit
Check
valve
Strainer
Capillary
tube
Strainer
18
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulatedwith a proper insulation material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
IMPORTANT
CAUTION
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
Indoor Unit MCAV127R5VAB- KPA128R5TAA Outdoor Unit GR129R5TBA
Compressor
4-way valve
Accumulator
Wide tube service valve
Wide tube
O.D. ø12.7 mm (1/2 ")
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Heat exchanger
Heat exchanger
Muffler
Capillary
Cooling cycle
Heating cycle
Strainer
Indoor unit Outdoor unit
Check valve
Strainer
Capillary
tube
Accumulator
5.PERFORMANCE DATA
5-1.Performance charts
19
Indoor inlet air
D.B. temp. (°C)
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube service valve MPa (kgf/cm
2
G)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
Cooling Characteristics Heating Characteristics
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)
9 8 7 6 5 4 3 2 1
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
10
Indoor inlet air
D.B. temp. (°C)
8 7 6 5 4 3 2 1
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
9
10
7
32 27 19
27 20 15
2.95 (30)
2.85 (28)
2.65 (26)
2.46 (24)
2.26 (22)
2.06 (20)
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
High pressure at wide tube service valve MPa (kgf/cm
2
G)
1.87 (18)
1.67 (16)
1.47 (14)
25
7
1.28 (12)
1.08 (10)
32 27
19
27 20 15
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high in heating mode. (Refer to “7-5 Overload prevention”)
...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling:Indoor air temperature 27°C D.B./19°C W.B. Heating:Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
Indoor Unit MCAV77R5VAA Outdoor Unit GR79R5TBA
20
Indoor inlet air
D.B. temp. (°C)
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube service valve MPa (kgf/cm
2
G)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
Cooling Characteristics Heating Characteristics
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)
9 8 7 6 5 4 3 2 1
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
10
Indoor inlet air
D.B. temp. (°C)
8 7 6 5 4 3 2 1
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
9
10
7
2.95 (30)
2.85 (28)
2.65 (26)
2.46 (24)
2.26 (22)
2.06 (20)
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
High pressure at wide tube service valve MPa (kgf/cm
2
G)
1.87 (18)
1.67 (16)
1.47 (14)
25
7
1.28 (12)
1.08 (10)
32 27 19
27 20 15
32 27
19
27 20 15
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high in heating mode. (Refer to “7-5 Overload prevention”)
...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling:Indoor air temperature 27°C D.B./19°C W.B. Heating:Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
Indoor Unit MCAV99R5VAA Outdoor Unit GR99R5TBA
21
Indoor inlet air
D.B. temp. (°C)
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
25 30 35 40 45 50
Low pressure at wide tube service valve MPa (kgf/cm
2
G)
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
Cooling Characteristics Heating Characteristics
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)
11 10
9 8 7 6 5 4 3
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
12
Indoor inlet air
D.B. temp. (°C)
10
9 8 7 6 5 4 3
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
11
12
7
32
27
19
32 27
19
27 20 15
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
High pressure at wide tube service valve MPa (kgf/cm
2
G)
25
7
2.95 (30)
2.85 (28)
2.65 (26)
2.46 (24)
2.26 (22)
2.06 (20)
1.87 (18)
1.67 (16)
1.47 (14)
1.28 (12)
1.08 (10)
27 20
15
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high in heating mode. (Refer to “7-5 Overload prevention”)
...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling:Indoor air temperature 27°C D.B./19°C W.B. Heating:Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
Indoor Unit MCAV127R5VAB KPA128R5TAA Outdoor Unit GR129R5TBA
Outdoor inlet air D.B. temp. (°C)
22
5-2.Air Throw Distance Chart
Indoor Unit MCAV77R5VAA
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle
0°
30°
Room air temp.: 27°C Fan speed : High
Cooling
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle
45° 60°
Room air temp.: 20°C Fan speed : High
Heating
23
Indoor Unit MCAV97R5VAA
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle
45° 60°
Room air temp.: 20°C Fan speed : High
Heating
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle
0°
30°
Room air temp.: 27°C Fan speed : High
Cooling
24
Indoor Unit MCAV127R5VAB
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle
45° 60°
Room air temp.: 20°C Fan speed : High
Heating
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle
0°
30°
Room air temp.: 27°C Fan speed : High
Cooling
25
Indoor Unit KPA128R5TAA
Room air temp. : 27°C Fan speed : High
Cooling
Room air temp. : 20°C Fan speed : High
Heating
01234567
1
0
2
3
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air verocity
Flap angle
45°
30°
Ceiling mounted
01234567
1
0
2
3
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air verocity
Flap angle
60°
80°
5-3. Heating Capacity
–5 0 5
7
10 15
Outdoor temperature (°C DB)
0
10
20
30
40
50
60
70
80
90
100
110
120
Heating capacity ratio (%)
NOTE
1) … Point of Rating condition Black dot in the chart indicate the following rating condition.
Indoor : 20°C D.B. Outdoor : 7°C D.B. / 6°C W.B.
2) Above characteristics indicate instantaneous operation, which does not take into
consideration defrost operation.
3) Fan speed : High
4) Because this air conditioner heats a room by drawing in the heat of the outside
air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, use another heating appliance in conjunction with it.
–8
26
27
6.ELECTRICAL DATA
6-1.Electrical Characteristics
Indoor Unit MCAV77R5VAA Outdoor Unit GR79R5TBA
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.11 0.24 3.35 3.7
Power Input kW 0.025 0.055 0.710 0.790
Full Load ConditionsRunning Amps. A 0.11 0.24 4.05 4.4
Power Input kW 0.025 0.055 0.89 0.97
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.11 0.24 3.15 3.5
Power Input kW 0.025 0.055 0.671 0.75
Full Load ConditionsRunning Amps. A 0.11 0.24 3.2 3.55
Power Input kW 0.025 0.055 0.690 0.770
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions: Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
28
Indoor Unit MCAV97R5VAA Outdoor Unit GR99R5TBA
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.12 0.24 4.05 4.4
Power Input kW 0.027 0.055 0.888 0.97
Full Load ConditionsRunning Amps. A 0.12 0.24 4.74 5.1
Power Input kW 0.027 0.055 1.068 1.15
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.12 0.24 3.85 4.2
Power Input kW 0.027 0.055 0.868 0.95
Full Load ConditionsRunning Amps. A 0.12 0.24 4.19 4.55
Power Input kW 0.027 0.055 0.925 1.007
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions: Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
29
Indoor Unit MCAV127R5VAB Outdoor Unit GR129R5TBA
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.13 0.28 5.39 5.8
Power Input kW 0.031 0.062 1.177 1.27
Full Load ConditionsRunning Amps. A 0.13 0.28 6.79 7.2
Power Input kW 0.031 0.062 1.507 1.60
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.13 0.28 5.99 6.4
Power Input kW 0.031 0.062 1.327 1.42
Full Load ConditionsRunning Amps. A 0.13 0.28 7.09 7.5
Power Input kW 0.031 0.062 1.557 1.650
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions: Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
Indoor Unit KPA128R5TAA Outdoor Unit GR129R5TBA
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.29 0.28 5.03 5.6
Power Input kW 0.07 0.062 1.088 1.22
Full Load Conditions Running Amps. A 0.29 0.28 6.43 7.0
Power Input kW 0.07 0.062 1.388 1.52
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V 1-phase 50Hz Rating Conditions Running Amps. A 0.29 0.28 5.53 6.1
Power Input kW 0.07 0.062 1.188 1.32
Full Load Conditions Running Amps. A 0.29 0.28 7.43 8.0
Power Input kW 0.07 0.062 1.578 1.71
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.
30
31
6-2.Electric Wiring Diagrams
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
WARNING
Indoor Unit MCAV77R5VAA
MCAV97R5VAA MCAV127R5VAB
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
WARNING
Indoor Unit KPA128R5TAA
.
32
33
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
WARNING
Outdoor Unit GR79R5TBA
GR99R5TBA
GR129R5TBA
7.FUNCTION
7-1.Room Temperature Control
Cooling
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit.
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor operation.
Thermo. ON :When the room temperature is above T + 1°C (T°C is set temperature).
Compressor ➞ON
Thermo. OFF :When the room temperature is equal to or below set temperature T°C.
Compressor ➞OFF
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes
3 minutes5 minutes
ON OFF ON OFF ON OFFCompressor
ON OFF ON OFF ON OFF
More than 5 minutes
Outdoor fan
Indoor fan
Set speed
T+1 °C
T °Cset temp.
Thermo. OFF
Thermo. OFF
Thermo. ON
Thermo. OFF
Thermo. ON
Thermo. ON
Thermo. ON
Room temp.
Signal from remote control unit
34
Heating
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit.
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 5 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor operation.
Thermo. ON : When the room temperature is below T – 1°C (T°C is set temperature).
Compressor ➞ON
Thermo. OFF : When the room temperature is equal to or above set temperature T°C.
Compressor ➞OFF
*1: Refer to "8-6 Cold Draft Prevention".
NOTE
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes
5 minutes 5 minutes
ON OFF ONOFFCompressor OFF
ON OFF ONOFFOutdoor fan OFF
Set speed
LL
LL
ON
OFF
OFF OFF ON OFF ON
*1
OFF
OFF
ON
ONReversing cycle
Thermo.ONThermo.
OFF
Thermo. ON
Thermo. OFF
More than 5 minutes
Signal from remote control unit
T °C T–1 °C T–2 °C
set temp.
Indoor fan
Standby lamp
Indoor heat exch. coil temp.
Tc °C
Solenoid coil
(4–way valve)
Operation button
Room temp.
*1
Set speed
30 seconds30 seconds
Max. 10minutes
OFF
35
7-2.Dry Operation (Dehumidification)
Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON and OFF automatically as shown in the chart below according to the room temperature.
Intermittent ventilation occurs by switching the indoor fan speed between L LL.
Dry operation does not occur when the room temperature is under 15°C, which is the monitor zone.
When the compressor stops, the indoor fan stops as well.
7-3.Automatic Switching between Cooling and Heating
When AUTO mode is selected, the microprocessor calculates the difference between the set temperature and the room temperature, and automatically switches to COOLING or HEATING mode to maintain the desired temperature.
Room temp. Set temp. COOL Room temp. < Set temp. HEAT
This means that if the room temperature is higher thanor equal tothe set temperature, COOLINGoperation begins. If the room temperature is lower thanthe set temperature, HEATINGoperation begins.
NOTE
Room temp.
Cooling operation
T+2 °C
Set temp.T °C
T–1 °C
Monitor zone Both the indoor and outdoor units stop.
Room temp. 15 °C
*Dry A zone
Compressor : FMI (indoor fan) :
Continuous operation L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
*Dry B zone
Compressor : FMI (indoor fan) :
Intermittent operation (ON for 3 minutes and OFF for 9 minutes) L (low speed) / LL (very low speed) intermittent ventilation
only while the compressor is ON.
36
7-4.Freeze Prevention (Cooling)
This function prevents freezing of the indoor heat exchange coil.
When the compressor has been running for 10 minutes
*1)
or more and the temperature of the indoor heat exchange coil falls below –1°C, the control circuit stops the compressor for at least 6 minutes. The compressor does not start again until the temperature rises above 8°C or 6 minutes has elapsed.
*1)Functionally, compressor running period, or time are of two types, 10 minutes and 6 minutes depending upon
production date.
NOTE
ON ON ON ON
OFFOFF
Set speed
More than
10 minutes
6 minutes
T+1 °C
Indoor heat exch. coil temp.
–1 °C
Compressor
Indoor fan
Room temp.
Thermo. OFF
Thermo. ON
Set temp.T °C
More than
10 minutes
More than
6 minutes
Set speed
*1) *1)
37
7-5.Overload Prevention (Heating)
This function prevents overheating of the indoor heat exchange coil.
When the temperature of the indoor heat exchange coil rises above B°C, and if the indoor fan is L (low speed), then the fan speed changes from L (low speed) to M (medium speed).
When the temperature of the indoor heat exchange coil rises above A°C, the outdoor fan stops.
The operation temperature shown as A, B, Cand Din the chart differ by models.
NOTE
ONON OFF
ON
H or M or L H H, M M, L M
A B
C D
Indoor heat exch. coil temp. °C
Outdoor fan
Indoor fan
Compressor
38
MCAV77R5VAA MCAV97R5VAA MCAV127R5VAB
A 50°C 54°C 58°C B 49°C 52°C 56°C C 42°C 45°C 50°C D 39°C 42°C 46°C
7-6.Cold Draft Prevention (Heating)
This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coil have sufficiently warmed up.
STANDBY lamp on front of the indoor unit lights up when this function is working.
when 10 minutes has elapsed,the fan speed is automatically switched to set speed regardless of indoor heat exchange coil temperature.
The operation temperature shown as Tcin the chart differ by models.
NOTE
OFF
ON
OFF
Set speed
Indoor fan
Standby lamp
Indoor heat exch.
coil temp. (°C)
Tc
Max. 10minutes
39
MCAV77R5VAA MCAV97R5VAAMCAV127R5VAB
Tc 32°C 33°C 34°C
7-7.Defrosting Operation (Heating)
Defrosting Flowchart
Compressor ON
Indoor heat exchanger coil temperature drops 0.8°C per 6 minutes and it repeats 3 times in succession.
Integrated operating time of compressor is more than 3 hours.
Defrosting begins.
Cold-draft prevention
Temperature of outdoor heat exchange coil is higher than 12°C.
Release of defrosting
Indoor fan runs at set speed when temperature of indoor heat exchanger reads Tc °C.
B
Defrosting time is over 12 minutes.
No LL fan operation during this period.
Compressor keeps running for at least 6 minutes.
Temperature of outdoor heat exchanger coil is below 9°C.
Integrated operating time of compressor is more than 1.5 hours.
Thermo. OFF. (Compressor OFF)
CD
Temperature of indoor heat exchanger coil is below
Ta°C.
Continuous operating time of compressor is more than 20 minutes.
Outdoor fan is either operated or stopped for more than 10 minutes.
A
Is outdoor fan continuously operating for more than 10 minutes?
Integrated operating time of compressor is more than 50 minutes.
Temperature of indoor heat exchanger coil is below
Ta+
13°C
. (See table below.)
Temp. of indoor heat exch. coil immediately before thermo goes off is either below Ta + 4°C or Tb + 4°C (when overload prevention works).
NO
NO
NO
YES
YES
YES
Overload
prevention works.
Does outdoor fan
stop?
Compressor keeps running for at least 6 minutes.
Release of overload prevention (Outdoor fan operates.)
Compressor keeps running for at least 6 minutes.
NOTE
NOTE
The values shown as Ta, Tb and Tc differ according to the models.
MCAV77R5VAA
Ta Tb Tc
*1 *2 *3
35 48 32
38 51 33
44 57 34
MCAV97R5VAA
MCAV129R5VAB
*1
*1
*3
*1 & *2
40
Defrosting Mode Timing Chart
41
ON
ON
ON ON ON
ON
ONON
Set speed
OFF
OFF
OFF
OFF
32 seconds 11 minutes 32 seconds
Start of defrosting
Release of defrosting
OFF
OFF
Release of
cold draft prevention
Compressor
Outdoor fan
Solenoid coil
(4–way valve)
Indoor fan
Standby lamp
Indoor heat exch. coil temp.   
ONON
Set speed
* 1
2 seconds 2 seconds
Tc°C
NOTE
*1: Refer to "8-6 Cold Draft Prevention".
8.TROUBLESHOOTING
8-1.Check before and after troubleshooting
8-1-1.Check power supply wiring.
Check that power supply wires are correctly connected to terminalsLand Non the terminal plate in the indoor unit.
8-1-2.Check inter-unit wiring.
Check that inter-unit wiring is correctly connected to the outdoor unit from the indoor unit.
8-1-3.Check power supply.
Check that voltage is in specified range (±10% of the rating).
Check that power is being supplied.
8-1-4.Check lead wires and connectors in indoor and outdoor units.
Check that coating of lead wires is not damaged.
Check that lead wires and connectors are firmly connected.
Check that wiring is correct.
Outdoor
unit
Indoor
unit
Power supply : Single phase 220–240V ~ 50Hz
Ground
Ground
Inter–unit power wiring
Power plug (Local supply)
Inter–unit control wiring
L
1 2 3 4
L
1 2 3 4
NN
42
WARNING
Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing.
8-2.Air conditioner does not operate.
8-2-1.Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 2Mor less, insulation is defective (“NO”).
NO
Measure insulation resistance of electrical parts in outdoor unit.
NO
Set circuit breaker to OFF.
*
Measure insulation resistance of electrical parts in indoor unit.
1
Remove inter-unit wires from terminal plate in outdoor unit.
Measure insulation resistance of outdoor unit.
2
Remove inter-unit wires from terminal plate in indoor unit. Then, pull the power plug out of the wall outlet
Measure insulation resistance of indoor unit.
Insulation of outdoor unit is defective.
Insulation of indoor unit is defective.
WARNING
LL
NN
1 2 3 4
1 2 3 4
Outdoor
unit
1
Indoor
unit
22
Inter–unit wiring
Circuit breaker
Ground
Ground
Power plug (Local supply)
Wall outlet (receptacle)
Single phase 220–240V ~ 50Hz
43
B. Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
8-2-2.Neither indoor nor outdoor unit runs.
A. Power is not supplied.
B. Check "OPERATION selector" switch in the indoor unit.
YES
NO
OPERATION selector switch is set in ON position.
Set OPERATION selector switch to ON.
Indoor PCB Ass'y is defective.
NO
Check power supply. Power is being supplied to the
indoor unit.
Circuit breaker is tripped.
Power failure
Reset breaker.
Wait for recovery or contact power company.
Replace with suitable one (larger capacity).
NO
Check capacity of circuit breaker. Capacity of circuit breaker is
suitable.
Measure resistance of outdoor fan motor winding.
Measure resistance of compressor motor winding.
Measure resistance of 4-way valve's winding.
In case of Heating operation :
44
C. Check remote control unit.
D. Check fuse on the indoor PCB Ass'y.
E. Check TIMER on the remote control unit.
Timer is turned ON. Check to see if or is displayed on remote control
YES
Cancel the timer mode.
ON
OK
OK
Check fuse on indoor PCB Ass'y for continuity. (F)
Check operation lamp to see if light is ON.
Light is OFF
Measure resistance of primary and secondary winding of transformer. (TR)
Indoor PCB Ass'y is defective.
OK
OK
Measure resistance of indoor and outdoor fan motor winding. (FM)
Measure resistance of compressor motor winding. (CM)
OK
Measure coil resistance of power relay in outdoor unit. (PR)
Replace the fuse.
If fuse has been blown,
OK
Try to run with another remote control unit.
First remote control unit is defective.
Check for residue buildup on transmitter of remote control unit.
Check for residue buildup on remote control receiver on front of indoor unit.
Clean transmitter.
Clean receiver.
45
8-2-3.Only outdoor unit does not run.
A. Check setting temperature.
B. Check PCB Ass'y in either indoor or outdoor unit.
8-2-4.Only Indoor unit does not run.
Indoor PCB Ass'y is defective.
Indoor PCB Ass'y is defective.
Check voltage between terminals No. 1(+) and No. 2 at the terminal plate. (DC 24V)
No voltage appears.
Outdoor PCB Ass'y is defective.
OK
OK
NO
Is room temperature too low ?
Try to lower setting temperature by temperature setting button ( button).
Outdoor unit still does not run.
Remote control unit is defective.
Try to run using another remote control unit.
COOL
OK
NO
Is room temperature too high ?
Try to raise setting temperature by temperature setting button ( button).
Outdoor unit still does not run.
Try to run using another remote control unit.
HEAT
Remote control unit is defective.
46
8-3.Some part of air conditioner does not operate.
8-3-1.Only indoor fan does not run.
8-3-2.Only flap motor does not run.
8-3-3.Only outdoor fan does not run.
Fan cannot be turned.
OK
Check fan rotation. Turn fan gently once or twice by hand.
Check fan casing foreign matter on inside.
Fan motor burnout or foreign matter in bearings.
Remove foreign matter or repair.
Repair or replace.
Measure resistance of outdoor fan motor winding.
Check fan motor capacitor.
Measure resistance of flap motor winding.
Fan cannot be turned.
OK
Check fan rotation. Turn fan gently once or twice by hand.
Check fan casing foreign matter on inside.
Fan motor burnout or foreign matter in bearings.
Remove foreign matter or repair.
Repair or replace.
Measure resistance of indoor fan motor winding.
Check fan motor capacitor.
47
8-3-4.Only compressor does not run.
Check compressor motor capacitor.
Measure resistance of compressor motor winding.
Measure resistance of power relay. (PR)
NO
YES
YES
Internal protector (K)
is working.
YES
Temperature of compressor is abnormally high.
Refrigerant gas shortage. Charge refrigerant gas (R22).
Rotor may be locked up.
(C1)
Measure Power supply voltage. The voltage is too low.
No
48
8-4.Air conditioner operates, but abnormalities are observed.
8-4-1.Operation does not switch from HEAT to COOL (or COOL to HEAT).
Indoor PCB Ass'y is defective.
Check voltage between terminals No. 1(+) and No. 3 at the terminal plate. (DC 24V)
No voltage appears.
Outdoor PCB Ass'y is defective.
OK
Remote control unit may be defective.
Measure resistance of 4–way valve's winding.
Receiver in lamp Ass'y may be defective.
COOL HEAT
Check voltage between terminals No. 1(+) and No. 3 at the terminal plate. (0V)
HEAT COOL
49
8-4-2.Poor cooling or heating.
8-4-3.Excessive cooling or heating.
NO
NO
Set temperature is suitable.
Set temperature to higher or lower value using temperature setting buttons of the remote control unit.
Remote control unit is placed where it can detect room temperature properly.
Change position of remote control unit.
Air filter is clogged.
NO
YES
Temperature difference is small.
YES
Temperature difference between suction and discharge air is large enough (approx. 10 deg. or more).
Possibility of gas shortage.
YES
Check position of remote control unit. Cool or warm air from air conditioner reaches position directly.
Change position of remote control unit.
Wide and narrow tubes between indoor unit and outdoor unit are insulated.
Insulate both wide and narrow tubes separately and then tape together.
Measure temperature of suction and discharge air of air conditioner.
Charge refrigerant gas (R22).
Check for clogging of air filter.
Fan speed is set to LOW.
Clean filter.
Set fan speed to either HIGH or MEDIUM.
Review cooling load estimate, if performance of air conditioner is normal.
Reduce cooling or heating load or replace the air conditioner with larger capacity.
50
8-5.If a sensor is defective.
8-5-1.Indoor coil temp. thermistor (TH1) is defective.
Alarm Signal (*)
Operation lamp on the front side of the indoor unit will flash on and off when the indoor coil thermistor is defective. At the same time the outdoor unit will stop. Indoor unit will operate only for ventilation.
8-5-2.Room temp. thermistor (TH2) is defective.
A. Open
When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect extremely low room temperature. a) In Cooling mode:The air conditioner soon stops and will not start again.
(Thermo.OFF) Neither outdoor fan nor compressor runs.
b) In Heating mode:The air conditioner continues to operate (Thermo.ON). Both
the outdoor fan and compressor do not stop. As a result, the room becomes too warm.
B. Short
When thermistor is short, the air conditioner will be in the following conditions as the controller tries to detect extremely high room temperature. a) In Cooling mode:The air conditioner continues to operate (Thermo.ON). Both
the outdoor fan and compressor do not stop. As a result, the room becomes too cold.
b) In Heating mode:The air conditioner soon stops and will not start again
(Thermo.OFF). Neither outdoor fan nor compressor runs.
Definition of Open or Short Circuit of Sensor (Thermistor)
Open ...A lead wire is broken or disconnected or the circuit inside the temperature sensor is open . Short ...The protective cover of a lead wire has been damaged, and the exposed wire is touching another metal
part, or both lead wires have become exposed and are touching each other. Alternatively, the circuit inside the temperature sensor is closed.
NOTE
NOTE
Operation lamp on front side of indoor unit is flashing on and off. (*)
YES
Replace thermistor.
Thermistor (TH1 ) is defective.
YES
51
Temperature sensor
Lead wires
Thermistor Structure
52
9-1.Measurement of Insulation
Resistance
The insulation is in good condition if the resistance exceeds 2M.
9-1-1.Power Supply Wires
Clamp the grounding terminal of the power plug with a lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the two power terminals. (Fig. 1)
Then, also measure the resistance between the grounding and other power terminals. (Fig. 1)
9-1-2.Indoor Unit
Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate. (Fig. 2)
9-1-3.Outdoor Unit
Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate. (Fig. 2) Note that the ground line terminal should be skipped for the check.
9-1-4.Measurement of Insulation
Resistance for Electrical Parts
Disconnect the lead wires of the desired electric part from terminal plate, capacitor, etc. Similarly disconnect the connector. Then measure the insulation resistance. (Figs. 3 and 4)
Refer to Electric Wiring Diagram. If the probe cannot enter the poles because the hole is
too narrow then use a probe with a thinner pin.
NOTE
9.CHECKING ELECTRICAL COMPONENTS
Ground
power plug (Local supply)
probe
Insulation tester
Terminal plate
Copper tube or metallic part
Clip
Insulation tester
Probe
Copper tube or metallic part
Clip
Insulation tester
Probe
Clip
Insulation tester
Probe
Metallic part
From fan motor, compressor and other parts
Fig. 1
Fig. 2
Fig. 3
Fig. 4
The shape of the power plug may differ from that of the air conditioner which you are servicing.
NOTE
53
9-2.Checking Continuity of Fuse
on PCB Ass'y
Remove the PCB Ass’y from the electrical component box. Then pull out the fuse from the PCB Ass’y. (Fig. 5)
Check for continuity using a multimeter as shown in Fig. 6.
9-3.Checking Motor Capacitor
Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 7. Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value.
The capacitor is “good” if the pointer bounces to a great extent and then gradually returns to its original position.
The range of deflection and deflection time differ according to the capacity of the capacitor.
Fuse
PCB Ass’y
Fuse
Compressor motor capacitor
Fan motor capacitor
Multimeter
Fig. 5
Fig. 6
Fig. 7
54
10-1. Removing Air Intake Grille
(1) Hold both ends and pull forward to open the
air intake grille. (Fig. 1)
(2) Remove the metal clips connecting the unit and the
grille. First, with a screwdriver, loosen the * marked screw a little at the right side clip (DO NOT loosen it too much, otherwise, the screw and small metal parts will fall off inside.), then press
on the stopper and pull off. (Fig. 2) (3) Do the same procedure for the left metal clip. (4) Unlatch the 2 tabs on the lower part of the grille to
take it off completely.
10. DISASSEMBLY PROCEDURE FOR INDOOR UNIT
IMPORTANT! Please Read Before Starting
Safety precautions for servicing the CEILING-MOUNTED indoor unit
Center latch
Air intake grille
Metal clip
*
Air intake grille
Unit
For Floor Installation
Fig.1
Fig.2
Before attempting to replace heavy and bulky parts such as the evaporator and fan motor, disconnect the indoor unit from the system and place it on the floor. Refer to the steps given below.
When checking or servicing the air intake grille, side panels, or electrical component box, first check that power is completely disconnected. Pay utmost care that your working platform is stable enough. Also, do not drop any replaced parts and tools on the floor.
55
10-2. Removing Side Panels
(1) Remove the 3 screws attaching the left side panel.
(Fig. 3) (2) Note the position of the hook on the inside of the
left side panel. To disengage the hook from the slot,
slide down the panel for removal. (Fig. 3) (3) Do the same procedure for the right side panel.
10-3. Access and Removal of
Electrical Component Box
(1) Remove the front screw with a screwdriver. (Fig. 4) (2) Slide the lid out and up. (Fig. 4) (3) Disconnect the wiring as necessary. (4) Remove the 4 screws, then pull out the electrical
component box. (Fig. 5)
Side panel
Tapping screws (4 × 10 mm)
Hook
Hook
Slot
Screw
Screw
Electrical component box
Screw
Connectors
Connectors
Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect the power or turn off circuit breaker before you start checking or servicing.
WARNING
Fig.3
Fig.4
Fig.5
56
10-4. Removing Flap Motor
(1) Remove the 3 screws used to mount the top panel.
(Fig. 6) (2) While unlatching the 2 tabs inside the back of the
top panel, lift the top panel diagonally in the
direction of the arrow.(Fig. 6) (3) Remove the 2 screws to pull off the flap motor.
The arm and cam come off together with the motor.
(Fig. 7)
10-5. Removing Evaporator (=Indoor Heat Exchange Coil)
(1) Remove the 7 screws used to mount the blades.
(Fig. 8) (2) Lift the blades in the direction of the arrow.(Fig. 8)
Top panel
Flap motor
Screw
Blade
Arm
Cam
Screw
Flap motor
Screw
Blades
Fig.6
Fig.7
Fig.8
57
(3) Remove the 6 screws of the front panel and pull it
toward you. (Fig. 9)
(4) Remove the 2 screws used to mount the
evaporator. (Fig. 10) (5) Remove the rubber cap to pull the thermistor out of
the evaporator. (Fig. 10) (6) Cut the plastic clamp securing the drain hose to the
front fan casing. (Fig. 10)
(7) The evaporator is built into the drain pan. Pull out
the drain pan together with the evaporator in the
direction of the arrow. (Fig. 10)
The foamed polystyrene drain pan is fragile: DO NOT apply excessive force when removing it.
(8) The evaporator can be removed by sliding it out
from the drain pan in the direction of the arrow.
(Fig. 11)
Front panel
Screw
Plastic clamp
Drain pan
Screw
Rubber cap
Thermistor
Drain hose
Front fan casing
Drain pan
Evaporator (Indoor coil)
Mounting plate
Mounting plate
Fig.9
Fig.10
Fig.11
IMPORTANT
58
10-6. Removing Fan and Fan Motor
(1) Unlatch the 2 hooks on each side to take off the
front fan casing. (Fig. 12)
(2) Remove the 2 screws attaching the rear fan casing
and then pull the fan casing out.
(3) Insert a hex wrench in the fan boss and turn it
counterclockwise to loosen the centrifugal fan.
The fan can be removed by sliding it to the left.
(Fig. 14)
(4) Remove the 4 bolts to remove the fan motor from
the frame. (Fig. 15)
Hook
Hook
Front fan casing
Rear fan casing
Hex wrench (3mm or 7/64")
Centrifugal fan
Bolts (M6)
Fan motor
Frame
Fig.12
Fig.13
Fig.14
Fig.15
S.A.C. - olgiate olona - printed in italy
R.D. 28 Reyrieux BP 131 - 01601 Trévoux CEDEX France
Tél. 04.74.00.92.92 - Fax 04.74.00.42.00
R.C.S. Bourg-en-Bresse B 759 200 728
Loading...